egress - princeton university

35
Egress José L. Torero University College London United Kingdom Lecture – 2 Joelma fire, Sao Paulo, Brazil, Friday, February 1 st , 1974

Upload: others

Post on 16-Apr-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Egress - Princeton University

Egress

José L. ToreroUniversity College London

United Kingdom

Lecture – 2Joelma fire, Sao Paulo, Brazil, Friday, February 1st, 1974

Page 2: Egress - Princeton University

How do I get everyone out?

Page 3: Egress - Princeton University

Objectives

te<<<<tfte<<<<tSts→

Fire Safety Strategy

RSET<<<<ASET

Page 4: Egress - Princeton University

Prescriptive Design

o If codes are followed RSET <<<< ASET – by definition

Page 5: Egress - Princeton University

Performance Based Designo It has to be demonstrated: RSET <<<< ASET

Page 6: Egress - Princeton University

ASET

o A.S.E.T.: Available Safe Egress Time (tf)

Page 7: Egress - Princeton University
Page 8: Egress - Princeton University

o Models can be used for the definition of the evolution of the fire (tf)

Page 9: Egress - Princeton University

Or … Congregation Spaces (Theatres)

o Successful evacuationo Empire Palace Theatre

o9 May 1911oDisastrous fire on stageo3000 audience evacuated in 2.5 minuteso11 deaths backstageohttp://en.wikipedia.org/wiki/Edinburgh_Festival_Theatre

o Post‐war building studies reporto Fire grading of buildings, HMSO, 1952o2.5 minute clearing time for a space!

Page 10: Egress - Princeton University

The Great Lafayette and God Save the King

Page 11: Egress - Princeton University
Page 12: Egress - Princeton University

o We need to establish egress times(te)

o R.S.E.T. (te) –Required Safe Egress Time

RSET

Page 13: Egress - Princeton University

Egress Time (te)

te = tde + tpre+ tmov

o te – Egress timeo tde – Detection timeo tpre – Pre‐Movement timeo tmov – Displacement time

Page 14: Egress - Princeton University

Detection time (tde)

o Depends on the technology used but it is generally much smaller than all other times ( )

te = tpre+ tmov

Page 15: Egress - Princeton University

George

Page 16: Egress - Princeton University

Luna Club

Page 17: Egress - Princeton University

Rhode Island Night Club

Page 18: Egress - Princeton University

Choice of Materials

o The growth of the fire needs to be limited to enable egress to occur under ideal conditions

o If flames spread too fast then panic is inducedo Egress is unpredictable

o If flames spread too fast there is not enough time to evacuate before reaching tf

Page 19: Egress - Princeton University

Pre‐Movement Time (tpre)o Purely statistical – can be very long and brings great uncertainty

Page 20: Egress - Princeton University

Cinema School

Church

Page 21: Egress - Princeton University

Principles of Egresso Avoid panic behaviour

o Reduces uncertainty

o Guide people to behave like an ensembleo Signallingo Illumination

V [m/sec]

D [people/m2]

1 [m/sec]

Page 22: Egress - Princeton University

Corridor

Page 23: Egress - Princeton University

Displacement time (tmov)o Based on experiments

Page 24: Egress - Princeton University

Velocitieso Allow to calculate displacement times and times to flow through doors (tmov=d/Ve)

Stairs

Corridors

Page 25: Egress - Princeton University

Doors

Fixed Density

Variable Density

Page 26: Egress - Princeton University

CompatibilityWidth of stairso Time to fully evacuate a floor (tff)

o Time to displace down a floor (tdf)

tdf≈tff

Page 27: Egress - Princeton University

Egress Exercise

Page 28: Egress - Princeton University

Code Requirementso Untenable conditions (tf)o If the space is standardized then tf can be assumed constant

o te<tf

o.

o Maximum egress distances are defined so tmov can be neglected

≈0

dmax

Minimum width

Page 29: Egress - Princeton University

Hand Calculationso Hand calculation of displacement times tmovo Simple geometryo Precision is a function of available data and tpre

o Ideal application: tall buildings, train stations, stadia with limited egress options, no cross‐flows, etc.

Page 30: Egress - Princeton University

Software

o Commercial Codes: Simulex, Exodus, etc.

o Freeware: FDS‐(evac), etc.

Page 31: Egress - Princeton University

Software

o Computations of tmov

o Complex geometryo Precision also depends of available data and  tpre

o Ideal application: o Shopping centres, infrastructure with very large surface area and multiple egress paths, cross flow, etc.

Page 32: Egress - Princeton University

Example

o Very similar results

Hand calculations

Page 33: Egress - Princeton University

Egress Calculations

o Precision is given by the experimental data not by the complexity of the modelo Hand calculations for simple geometries

o Computations (software) for complex geometries

Page 34: Egress - Princeton University

Timeline

• 1st floor: 10 sec• 3 floors: 30 sec• 8 floors: 60 sec• 16 floors: 120 sec• 25 floors: 180 sec• Building: 240 sec

Page 35: Egress - Princeton University

How does this change egress?