electric machines i - philadelphia university › academics › fobeidat...8 •transformer vector...

41
Electric Machines I Three Phase Transformers 1 Dr. Firas Obeidat

Upload: others

Post on 02-Feb-2021

37 views

Category:

Documents


3 download

TRANSCRIPT

  • Electric Machines I Three Phase Transformers

    1

    Dr. Firas Obeidat

  • 2

    Table of contents

    1 • Introduction

    2 • Wye-Wye Connection

    3 • Wye-Delta Connection

    4 • Delta-Wye Connection

    5 • Delta-Delta Connection

    6 • Polarity of a Transformer

    7

    • Parallel Operation of Transformers

    8 • Transformer Vector Group

    Dr. Firas Obeidat Faculty of Engineering Philadelphia University

  • 3 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Introduction

    A three-phase power transformer is used at the

    power generating station to step-up the voltage.

    Whereas in the power distribution substation,

    the three-phase voltage is again stepped down

    through a three-phase distribution transformer.

    A three-phase transformer can be made either

    by three windings wound on a common core or

    by three single-phase transformer connected

    together in a three-phase bank.

    The first approach is a cheaper one that results

    in a transformer with smaller size and less

    weight. The main disadvantage of the first

    approach is that if one phase becomes defective,

    then the whole transformer needs to be

    replaced. Whereas in the second approach, if

    one of the transformers becomes defective then

    the system can be given power by an open delta

    at a reduced capacity. In this case, the defective

    transformer is normally replaced by a new one.

  • 4 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Introduction

    The primary and secondary windings of the transformer may be connected

    in either by wye (Y) or delta (Δ).

    Three-phase transformer connections

    Y-Y

    (Wye-Wye)

    Y-Δ

    (Wye-Delta)

    Δ-Y

    (Delta-Wye)

    Δ-Δ

    (Delta-Delta)

  • 5 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Wye-Wye Connection

    At the primary side, the phase voltage can be written as,

    At the secondary side, the phase voltage can be written as,

    The ratio of the primary

    line voltage to the

    secondary line voltage of

    this connection is,

  • 6 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Wye-Wye Connection

    The Y- Y connection has two very serious problems

    1) If loads on the transformer circuit are unbalanced, then the voltages on

    the phases of the transformer can become severely unbalanced.

    2) Third-harmonic voltages can be large.

    If a three-phase set of voltages is applied to a Y- Y transformer, the voltages

    in any phase will be 120o apart from the voltages in any other phase.

    However, the third-harmonic components of each of the three phases will be

    in phase with each other. There are always some third-harmonic components

    in a transformer because of the nonlinearity of the core, and these

    components add up. The result is a very large third-harmonic component of

    voltage on top of the 50-ar 60-Hz fundamental voltage. This third-harmonic

    voltage can be larger than the fundamental voltage itself.

    This type of connection of a three-phase transformer is rarely used for large

    amount of power transmission.

  • 7 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Wye-Wye Connection

    Unbalance problem and the third-harmonic problem can be solved by:

    • Solidly ground the neutrals of the transformers, especially the primary winding's neutral. This connection permits the additive third-harmonic components to cause a current flow in the neutral instead of building up large voltages. The neutral also provides a return path for any current imbalances in the load.

    • Add a third (tertiary) winding connected in Δ to the transformer bank. If a third Δ-connected winding is added to the transformer. then the third-harmonic components of voltage in the Δ will add up, causing a circulating current flow within the winding. This suppresses the third-harmonic components of voltage in the same manner as grounding the transformer neutrals. The Δ-connected tertiary windings need not even be brought out of the transformer case, but they often are used to supply lights and auxiliary power within the substation where it is located. The tertiary windings must be large enough to handle the circulating currents, so they are usually made about one-third the power rating of the two main windings.

  • 8 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Wye-Wye Connection

    Advantages Disadvantages

    Magnetizing current of transformer has 3rd harmonic component

    The third harmonic present in the alternator voltage may appear on the secondary side. This causes distortion in the secondary phase voltages

    If the load on the secondary side unbalanced then the shifting of neutral point is possible

    Less dielectric strength in insulating materials

    phase voltage is less

    Cross section of winding is large i.e. stronger to bear stress during short circuit

    Line current is equal to phase current

    Requires less turns per winding ie cheaper

    Phase voltage is 1/√3 times of line voltage

  • 9 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Wye-Delta Connection

    The expression of the primary line voltage is

    At the secondary side, the line voltage is

    The ratio of primary phase voltage to secondary phase voltage is

    The ratio of primary line voltage to secondary line voltage is

    The primary phase current is

    The turns ratio is

  • 10 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Wye-Delta Connection

    The expression of the secondary phase current is

    The secondary line current is

    This connection does have one problem; Because of the connection, the

    secondary voltage is shifted 30° relative to the primary voltage of the

    transformer. The fact that a phase shift has occurred can cause problems in

    paralleling the secondaries of two transformer banks together. The phase

    angles of transformer secondaries must be equal if they are to be paralleled,

    which means that attention must be paid to the direction of the 30o phase

    shift occurring in each transformer bank to be paralleled together.

    The connection will cause the secondary voltage to be lagging if the system

    phase sequence is abc. If the system phase sequence is acb, then the

    connection will cause the secondary voltage to be leading the primary voltage

    by 30o.

  • 11 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Wye-Delta Connection

    Advantages Disadvantages

  • 12 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Delta-Wye Connection

    The expression of the primary line voltage is

    The line voltage at the secondary side is

    The ratio of primary line voltage to secondary line voltage is

    The phase current at the primary side is

    For this connection, the turns ratio is

    In this case, the secondary phase

    current is

    The secondary line current is

  • 13 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Delta-Wye Connection

    Advantages Disadvantages

  • 14 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Delta-Delta Connection

    The expression of the primary line voltage is

    The line voltage at the secondary side is

    The ratio of primary line voltage to secondary line voltage is

    The secondary line current is

    The output capacity in delta-delta

    connection can be expressed as

    and

    𝑆 = 3𝑉𝐿𝐼𝐿 = 3𝑉𝑝𝐼𝑝

    𝑝 = 3𝑉𝐿𝐼𝐿𝑐𝑜𝑠θ = 3𝑉𝑝𝐼𝑝𝑐𝑜𝑠θ

  • 15 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Delta-Delta Connection

    Advantages Disadvantages

  • 16 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Three Phase Transformers

    Primary winding Secondary winding

    Primary winding Secondary winding

    Primary winding Secondary winding

    Primary winding Secondary winding

    √3V

    I

    V

    aI

    V/a√3V/a

    I

    V√3V

    √3aI

    V/aaI

    √3I

    IV

    aI

    V/a√3V/a

    √3I

    IV

    √3aI

    V/aaI

    The relations between three phase current/voltage and single phase current/voltage

  • 17 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Three Phase Transformers

    Example: A three-phase transformer is connected to an 11 kV supply and

    draws 6 A current. Determine

    (i) line voltage at the secondary side,

    (ii) the line current in the secondary coil.

    Consider the turns ratio of the transformer is 11.

    Also, consider delta-wye and wye-delta connections.

    1- For delta-wye connection

    𝐼𝑝1 =𝐼𝐿1

    3=

    6

    3= 3.46 𝐴

  • 18 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Three Phase Transformers

    2- For wye-delta connection

    𝐼𝐿2 = 𝐼𝑝2 = 𝑎𝐼𝑝1 = 11 × 3.46 = 38 𝐴

  • 19 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Polarity of a Transformer

    Polarity of a transformer is defined as the relative directions of induced

    voltages between the high voltage and low voltage terminals.

    The polarity of a transformer is very

    important to construct three-phase

    transformer bank, parallel connection of

    transformer, connection of current

    transformer (CT) and potential transformer

    (PT) power with metering device.

    Two polarities namely additive and

    subtractive are used in the transformer.

    A polarity of a transformer is said to be an

    additive if the measured voltage between the

    high voltage and the low voltage terminals is

    greater than the supply voltage at the high

    voltage terminals.

    A polarity is said to be a subtractive if the

    measured voltage between the high voltage

    and the low voltage terminals is lower than the

    supply voltage at the high voltage terminals. Subtractive polarity

    Additive polarity

  • 20 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Polarity of a Transformer

    Consider a 220/110V single-phase

    transformer with the high voltage

    and the low voltage terminals for

    testing polarities. The high voltage

    terminal H1 is connected to the low

    voltage terminal X1 by a cable. The

    voltmeter is connected between H2

    and X2. In this case, the turns ratio

    of the transformer is,

    V1/V2=220/110=2.

    A voltage of 110 V is applied to the

    primary side. In this case, a voltage

    of 55 V (110/2) will appear at the

    secondary terminals. If the meter

    read out the voltage of 165 V (110 +

    55) then the transformer is said to

    be in additive polarity.

    If the voltmeter reads the voltage of

    55V (110−55) then the transformer

    is said to be in subtractive polarity.

    Testing for additive polarity

    Testing for subtractive polarity

  • 21 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    For supplying a load in excess of the rating

    of an existing transformer, two or more

    transformers may be connected in parallel

    with the existing transformer.

    The transformers are connected in

    parallel when load on one of the

    transformers is more than its capacity.

    The reliability is increased with parallel

    operation than to have single larger unit.

    The cost associated with maintaining the

    spares is less when two transformers are

    connected in parallel.

    It is usually economical to install another transformer in parallel instead of

    replacing the existing transformer by a single larger unit. The cost of a spare

    unit in the case of two parallel transformers (of equal rating) is also lower

    than that of a single large transformer. In addition, it is preferable to have a

    parallel transformer for the reason of reliability. With this at least half the

    load can be supplied with one transformer out of service.

  • 22 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Advantages Disadvantages

    the parallel transformers may have very low impedance, which creates

    the high short circuit currents

    The bus ratings could be too high

    The risk of circulating currents running from one transformer to

    another Transformer

    Increasing short-circuit currents that increase necessary breaker

    capacity

    Maximize electrical system flexibility

    Maximize power system reliability

    Maximize electrical system availability

    Maximize electrical system efficiency

  • 23 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Condition for Parallel Operation of Transformer:

    1- The voltage rating of both primaries and secondaries should be identical,

    i.e. the transformers should have the same turn ratio.

    If the transformers connected in parallel have slightly different voltage ratios, then due to the inequality of induced emfs in the secondary windings, a circulating current will flow in the loop formed by the secondary windings under the no-load condition, which may be much greater than the normal no-load current.

    The current will be quite high as the leakage impedance is low. When the secondary windings are loaded, this circulating current will tend to produce unequal loading on the two transformers, and it may not be possible to take the full load from this group of two parallel transformers (one of the transformers may get overloaded).

    A small voltage difference may cause sufficiently high circulating current causing unnecessary extra I2R loss.

  • 24 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Condition for Parallel Operation of Transformer:

    2- The percentage impedances should be equal in magnitude and have same

    X/R ratio in order to avoid circulating currents and operation in different

    power factor.

    If this condition is not satisfied then the impedance triangles are not

    identical in shape and size, parallel operation will still be possible, but the

    power factor at which the two transformers operate will be different (one

    transformer will operate with higher power factor and the other with

    lower power factor) from the power factor of the common load. In this

    case the two transformers will not share the load in proportion to their

    KVA ratings.

  • 25 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Condition for Parallel Operation of Transformer:

    3- The polarity of the two transformers should be the same.

    Polarity of transformer means the instantaneous direction of induced emf

    in secondary. If the instantaneous directions of induced secondary emf in

    two transformers are opposite to each other when same input power is fed

    to the both of the transformers, the transformers are said to be in opposite

    polarity.

    The transformers should be properly connected with regard to their

    polarity. If they are connected with incorrect polarities then the two emfs,

    induced in the secondary windings which are in parallel, will act together

    in the local secondary circuit and produce a short circuit.

    Polarity of all transformers run in parallel should be same otherwise huge

    circulating current flows in the transformer but no load will be fed from

    these transformers.

    If the instantaneous directions of induced secondary emf in two

    transformers are same when same input power is fed to the both of the

    transformers, the transformers are said to be in same polarity. Inside the

    loop formed by the two secondaries the resulting voltage must be zero.

  • 26 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Condition for Parallel Operation of Transformer:

    3- The polarity of the two transformers should be the same.

    4- Phase sequences and phase angle shifts must be the same (for three-phase

    transformer).

    The transformer windings cab be connected in variety of ways which

    produce different magnitudes and phase displacement of secondary voltages

  • 27 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Overall summary of different connection types of parallel transformers

    Transformer

    Parallel

    Connection Types

    Equal

    Loading

    Unequal

    Loading

    Overloading

    Concerns

    Circulating

    Currents

    Recommended

    Connection

    Equal impedances—

    Equal ratios— Same kVA Yes No No No Yes

    Equal impedances—

    Equal ratios— Different

    kVA

    No Yes No No Yes

    Unequal impedances—

    Equal ratios— Same kVA No Yes Yes No No

    Unequal impedances—

    Equal ratios— Different

    kVA

    No Yes Yes No No

    Unequal impedances—

    Unequal ratios— Same

    kVA

    Yes No Yes Yes No

    Unequal impedances—

    Unequal ratios—

    Different kVA

    No Yes Yes Yes No

  • 28 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Case I: Equal Impedances-Equal Ratios-Same kVA

    𝐼 = 𝐼𝐴 + 𝐼𝐵

    𝐼𝐴 =𝑍𝐵

    𝑍𝐴 + 𝑍𝐵𝐼

    𝐼𝐵 =𝑍𝐴

    𝑍𝐴 + 𝑍𝐵𝐼

    𝑉2 = 𝐸 − 𝐼𝐴 𝑍𝐴 = 𝐸 − 𝐼𝐵𝑍𝐵 = 𝐸 − 𝐼𝑍𝐴𝐵

    𝐼𝐴 𝑍𝐴 = 𝐼𝐵𝑍𝐵

    𝐼𝐴𝐼𝐵

    =𝑍𝐵𝑍𝐴

    Case II: Equal Impedances-Equal Ratios-Different kVA

  • 29 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Case I: Equal Impedances-Equal Ratios-Same kVA

    𝐼𝐴 =𝐾𝑉𝐴𝐴/%𝑍𝐴

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐼

    𝐼𝐵 =𝐾𝑉𝐴𝐵/%𝑍𝐵

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐼

    𝐾𝑉𝐴𝐴 =𝐾𝑉𝐴𝐴/%𝑍𝐴

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    𝐾𝑉𝐴𝐵 =𝐾𝑉𝐴𝐵/%𝑍𝐵

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    %𝑍𝑇 =𝑍𝑇𝐼𝑇

    𝑉𝑇× 100 =

    𝑍𝑇

    𝑉𝑇2 𝑆𝑇 × 100

    Where:

    IA = load current from transformer A

    IB = load current from transformer B

    % ZA = % impedance of transformer A

    % ZB = % impedance of transformer B

    kVAA = kVA rating of transformer A

    kVAB = kVA rating of transformer B

    % ZT = % impedance of any transformer

    IT = rated current of any transformer

    VT = rated voltage of any transformer

    ST = KVA rating of any transformer

    Case II: Equal Impedances-Equal Ratios-Different kVA

  • 30 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Case III: Unequal Impedances-Equal Ratios-Same kVA

    Case IV: Unequal Impedances-Equal Ratios-Different kVA

    The equations for case III

    and Case IV are the same

    equations for case I and

    case II.

  • 31 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Example: Connecting two 2000 kVA, 5.75% impedance transformers in

    parallel, each with the same turn ratios to a 4000 kVA load. What is the

    loading on the transformers?

    𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐵 =𝐾𝑉𝐴𝐴/%𝑍𝐴

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐵 =2000/5.75

    2000/5.75+2000/5.75× 4000 =

    348

    348+348× 4000 = 2000 𝐾𝑉𝐴

    Example: Connecting 3000 kVA and 1000 kVA transformers in parallel, each

    with 5.75% impedance, each with the same turn ratios, connected to a

    common 4000 kVA load. What is the loading on each transformer?

    𝐾𝑉𝐴𝐴 =𝐾𝑉𝐴𝐴/%𝑍𝐴

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    =3000/5.75

    3000/5.75+1000/5.75× 4000 = 3000 𝐾𝑉𝐴

  • 32 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    𝐾𝑉𝐴𝐵 =𝐾𝑉𝐴𝐵/%𝑍𝐵

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    =1000/5.75

    3000/5.75+1000/5.75× 4000 = 1000 𝐾𝑉𝐴

    Example: Connecting two 2000 kVA transformers in parallel, one with 5.75%

    impedance and the other with 4% impedance, each with the same turn ratios,

    connected to a common 3500 kVA load. What is the loading on each

    transformer?

    𝐾𝑉𝐴𝐴 =𝐾𝑉𝐴𝐴/%𝑍𝐴

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    =2000/5.75

    2000/5.75+2000/4× 3500 = 1436 𝐾𝑉𝐴

    𝐾𝑉𝐴𝐵 =𝐾𝑉𝐴𝐵/%𝑍𝐵

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    =2000/4

    2000/5.75+2000/4× 3500 = 2064 𝐾𝑉𝐴

    The 4% impedance

    transformer is overloaded

    by 3.2%, while the 5.75%

    impedance transformer is

    loaded by 72%.

  • 33 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Parallel Operation of Transformers

    Example: Connecting two transformers in parallel with one 3000 kVA with

    5.75% impedance, and the other a 1000 kVA with 4% impedance, each with

    the same turn ratios, connected to a common 3500 kVA load. What is the

    loading on each transformer?

    𝐾𝑉𝐴𝐴 =𝐾𝑉𝐴𝐴/%𝑍𝐴

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    =3000/5.75

    2000/5.75+2000/4× 3500 = 2366 𝐾𝑉𝐴

    𝐾𝑉𝐴𝐵 =𝐾𝑉𝐴𝐵/%𝑍𝐵

    𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵𝐾𝑉𝐴𝐿𝑜𝑎𝑑

    =1000/4

    2000/5.75+2000/4× 3500 = 1134 𝐾𝑉𝐴

    The 4% impedance transformer is overloaded

    by 13.4%, while the 5.75% impedance

    transformer is loaded by 78.8%.

  • 34 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Transformer Vector Group

    The primary and secondary windings of a three-phase transformer are

    connected either in the same (delta-delta or star-star), or different (delta-

    star or star-delta) configuration-pair.

    The secondary voltage waveforms of a three-phase transformer are in

    phase with the primary waveforms when the primary and secondary

    windings are connected in the same configuration. This condition is known

    as ‘no phase shift’ condition.

    If the primary and secondary windings are connected in different

    configuration pair then the secondary voltage waveforms will differ from

    the corresponding primary voltage waveforms by 30 electrical degrees.

    This condition is called a ‘30° phase shift’ condition.

    The windings and their position to each other are usually marked by

    vector group. The vector group is used to identify the phase shift between

    the primary and secondary windings. In the vector group, the secondary

    voltage may have the phase shift of 30° lagging or leading, 0° i.e., no phase

    shift or 180° reversal with respect to the primary voltage.

  • 35 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Transformer Vector Group

    The transformer vector group is

    labeled by capital and small letters

    plus numbers from 1 to 12 in a

    typical clock-like diagram.

    The capital letter indicates primary

    winding and small letter represents

    secondary winding.

    In the clock diagram, the minute

    hand represents the primary line to

    neutral line voltage, and its place is

    always in the 12. The hour hand

    represents the secondary line to

    neutral voltage and its position in

    the clock changes based on the

    phase shift

  • 36 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Vector Groups Used in the Three Phase Transformer Connection

    Group I

    0 o’clock, zero phase displacement

    Yy0

    Dd0

    Dz0

    Group II

    6 o’clock, 180° phase displacement

    Yy6

    Dd6

    Dz6

    Group III

    1 o’clock, -30° lag phase displacement

    Dy1

    Yd1

    Yz1

    Group IV

    11 o’clock, 30° lead phase displacement

    Dy11

    Yd11

    Yz11

    Transformer Vector Group

  • 37 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Transformer Vector Group

  • 38 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Transformer Vector Group

  • 39 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Transformer Vector Group

  • 40 Dr. Firas Obeidat Faculty of Engineering Philadelphia University

    Transformer Vector Group

  • 41