electrical and chemical diagnostics of transformer insulation abstrac1
TRANSCRIPT
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
1/36
ABSTRACT
This paper describes the application of two relatively new diagnostic
techniques for the determination of insulation condition in aged transformers. The
techniques are (a) measurements of interfacial polarization spectra by a DC method
and (b) measurements of molecular weight and its distribution by gel permeation
chromatography. Several other electrical properties of the cellulose polymer were
also investigated. Samples were obtained from a retired power transformer and
they were analysed by the developed techniques. Six distribution transformers
were also tested with the interfacial polarization spectra measurement technique,
and the molecular weight of paper/pressboard samples from these transformers
were also measured by the gel permeation chromatography. The variation of the
results through different locations in a power transformer is discussed in this paper.
The possible correlation between different measured properties was investigated
and discussed in this paper.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
2/36
1. INTRODUCTION
The main function of a power system is to supply electrical energy to its
customers with an acceptable degree of reliability and quality. Among many other
things, the reliability of a power system depends on trouble free transformer
operation. Now, in the electricity utilities around the world, a significant number of
power transformers are operating beyond their design life. Most of these
transformers are operating without evidence of distress. The same situation is
evident in Australia. In PowaaerLink Queensland (PLQ), 25% of the power
transformers were more than 25 years old in 1991. So priority attention should be
directed to research into improved diagnostic techniques for determining the
condition of the insulation in aged transformers.
The insulation system in a power transformer consists of cellulosic
materials (paper, pressboard and transformerboard) and processed mineral oil. The
cellulosic materials and oil insulation used in transformer degrade with time. The
degradation depends on thermal, oxidative, hydrolytic, electrical and mechanical
conditions which the transformer experienced during its lifetime.
The condition of the paper and pressboard insulation has been monitored by
(a) bulk measurements (dissolved gas analysis (DGA) insulation resistance (IR),
tan and furans and (b) measurements on samples removed from the transformer
(degree of polymerization (DP) tensile strength). At the interface between the
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
3/36
paper and oil in the transformer, interfacial polarization may occur, resulting in an
increase in the loss tangent and dielectric loss. A DC method was developed for
measuring the interfacial polarization spectrum for the determination of insulation
condition in aged transformers.
This paper makes contributions to the determination of the insulation
condition of transformers by bulk measurements and measurements on samples
removed from the transformer. It is based on a University of Queensland research
project conducted with cooperation from the PLQ and the GEC-Alsthom.
Most of the currently used techniques have some drawbacks. Dissolved gas
analysis requires a data bank based on experimental results from failed
transformers for predicting the fault type. When transformer oil is rep or
refurbished, the analysis of furans in the refurbished oil may not show any trace of
degradation, although the cellulose may have degraded significantly. DP
estimation is based on a single-point viscosity measurement. Molecular weight
studies by single-point viscosity measurements are of limited value when dealing
with a complex polymer blend, such as Kraft paper, particularly in cases where the
molecular weight distribution of the paper changes significantly as the degradation
proceeds. In these instances, a new technique, gel permeation chromatography
(GPC), is likely to be more useful than the viscosity method, because it provides
information about the change in molecular weight and molecular weight
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
4/36
distribution. Investigation of the GPO technique has been included in this research
to assess its effectiveness in determining the condition of insulation.
Conventional electrical properties (dissipation factor and breakdown
strengths) of cellulosic materials are not significantly affected by ageing .so very
little recent research has been directed to electrical diagnostic techniques, in this
research project, thorough investigations were also undertaken of the conventional
electrical properties, along with interfacial polarization parameters of the cellulosic
insulation materials. The interfacial phenomena are strongly influenced by
insulation degradation products, such as polar functionalities, water etc. The
condition of the dielectric and its degradation due to ageing can be monitored by
studying the rate and process of polarization and can be studied using a DC field.
Furthermore, this is a non-destructive diagnostic test.
A retired power transformer (25 MVA, l1/132 kV) and several distribution
transformers were used for the experimental work. The results from these
transformers will be presented and an attempt will be made to correlate the
electrical and chemical test results. The variation of the results through the
different locations in a power transformer will be discussed with reference to their
thermal stress distribution. Accelerated ageing experiments were conducted to
predict the long term insulation behaviour and the results are presented in the
accompanying paper.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
5/36
2. EXPERIMENTAL TECHNIQUES
Experimental techniques used for the assessment of insulation condition in
aged transformers are described in the following section.
2.1 Conventional Electrical Tests
The dissipation factor and capacitance were measured at 50 Hz using a
Schering bridge. The partial discharge inception voltage was measured by a partial
discharge detector using a circuit with an input unit in series with the test sample.
Power frequency breakdown strength was measured by using the step by step
method. The standard wave shape of l. was used for determining the negative
lightning impulse breakdown strength. The electrical tests were carried out in
accordance with relevant ASTM standards.
2.2 Interfacial Polarization Spectra (IPS) Measurements
When a direct voltage is applied to a dielectric for a long period of time,
and it is then short circuited for a short period, after opening the short circuit, the
charge bounded by the polarization will turn into free charges i.e, a voltage will
build up between the electrodes on the dielectric. This phenomena is called the
return voltage. After applying the field for a time t, the polarization is expressed by
P(t) = P0 F(t), where P0 = E is the steady state value of the polarization, a is a
proportionality factor between the polarization and the field strength (E), called the
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
6/36
polarizabiity, F(t) is the relaxation function of the polarization describing the
development of polarization in time and P is the bound charge density.
After opening the short circuit, the charge bound by the polarization will
turn into free charge, and a voltage will build up. So an increase in the polarization
due to bound charges will increase the voltage build up. Again, polarizabiity will
increase when polarization increases. So the maximum return voltage can be
correlated with the polarizability of the material.
With the development of polarization, the charge bounded on the electrodes
tends to grow. In the external circuit maintaining the field, this growth will cause
an absorption current given by Ja(t) = P(t) = d/dt P (t). With polarization
approaching a steady state value, the current decays in time to zero. As for
polarization, the absorption current is proportional to the field strength. So the
initial value can be written as Ja (0) = E, where is the proportionality factor
between absorption cur rent and field strength, and is called polarization
conductivity. It can be shown that the initial slope of the return voltage is
proportional to the polarization conductivity [10]. When the return voltage
approaches its maximum value quickly, the initial slope of the return voltage is
larger. Another parameter termed as central time constant, i.e. the time at which
the return voltage is maximum, is also dependent on the polarization conductivity.
Hence the fundamental characteristics of the dielectric can be measured by return
voltage measurements.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
7/36
Figure 1: A typical return voltage wave shape of a specimen from the retired
transformer
An experimental set up with an IBM PC and a programmable electrometer
(Keithley 617 model) was developed and implemented to measure the return
voltage of a two terminal dielectric system. The charging voltage was 100 volt DC
for the retired transformer insulation samples. The developed software was used to
control the electrometer. Adsorbed moisture and temperature of the oil-paper
insulation adversely affects the re turn voltage measurement. So the return voltage
measurement was always conducted at a known and low oil-paper moisture content
and at ambient environmental conditions (20 25 C).
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
8/36
A typical return voltage wave shape of a specimen from the retired
transformer is shown in Fig. 1. The relevant parameters (maximum return voltage,
initial slope and central time constant) are identified in Fig. 1. Initial slope is the
slope of the return voltage graph (with linear approximation) for first few seconds.
As interfacial polarization is predominant at longer time constants, the spectrum of
the return voltage was investigated by changing the charging and discharging time
over a range of times greater than 1 second until the peak value of the maximum
return voltage was obtained The ratio of charging and discharging time was
two.then the spectra of maximum return voltage and initial slope were plotted
versus the central time constant (the time at which the return voltage is maximum).
The peak value of the maximum return voltage (from the return voltage spectrum)
and the corresponding initial slope (from the initial slope spectrum), along With
central time constant (from either of the spectrum), are the parameters used to
assess the insulation condition from the return voltage measurements.
2.3 GPC Analysis
Gel permeation chromatography provides a detailed molecular weight
distribution of the polymer. GPC is a chromatographic technique which uses
highly porous, non-ionic gel beads for the separation of polydispersed polymers in
solution. GPC separates polymer molecules on the basis of their hydrodynamic
volume. Detailed information of GPC technique is presented elsewhere [7].
Cellulose is not soluble in any common GPC solvents. Hence, for GPC
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
9/36
measurements the cellulosic materials had to be derivatized to enhance their
solubility in these solvents. For this purpose, a cellulose tricarbanilate derivative
was prepared by the method of Evans et al. .
The molecular weight distribution of the cellulose tricarbanilate was
measured using a Waters Chromatograph equipped with a variable wavelength
tunable absorbance detector. Four ultrastyragel columns were used in series in the
Chromatograph, with tetrahydrofuran (THF) as the eluent. Detection was carried
out using the absorbance at 236 nm and the elution profile was acquired by
interfacing to an IBM computer. The elution profiles were converted to molecular
weight distributions using a calibration based upon narrow molecular weight
distribution polystyrene standards.
3. RESULTS AND DISCUSSIONS
Paper wrapped insulated conductor specimens 200 mm long and pressboard
samples of dimension 80*80 mm were collected from an aged power transformer.
Several distribution transformers were also tested.
3.1 Case Study 1: Kareeya Transformer
A 25 year old, 25 MVA, 132/11 kV transformer from Kareeya power
station, North Queensland, had been gassing for some years. This transformer was
dismantled and was used to investigate the quality of the insulation using electrical
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
10/36
and chemical testing techniques, Since the aged transformer had been exposed to
air after dismantling, the samples had to be processed. The moisture content of
processed samples varied in the range 0.5 to 1.3%.
From our discussions with the experts from the GEC-Alsthom, it was
revealed that the top coils are subjected to higher thermal stress than the bottom
ones. To examine the differences that exist between the high stress and low stress
insulation samples, the samples were collected from top, middle and bottom coils
of low voltage and high voltage windings of the transformer. The schematic
diagram of a low voltage winding is shown in Fig. 2.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
11/36
Figure 2: Schematic diagram of one phase of LV winding of 25 MVA Kareeya
transformer
There were 90 coils/phase and 18 turns or layers of conductor/coil in the
low voltage winding. There were 10 conductors in parallel in the low voltage
winding. There were 60 coils/phase and 19 turns or layers of conductors/coil in the
high voltage winding. The HV and LV conductors were of rectangular cross
section 13.9 and 12 mm wide respectively and 2.6 mm thick with rounded corners.
The test specimens for insulated conductor samples were made up by placing two
samples side by side in a Perspex assembly, so that they overlapped each other for
a length of 100 mm. With two insulated conductors placed side by side to form the
specimen, the thickness of paper insulation between them was 1.0 mm and 0.8 mm
for the HV and LV specimens respectively. Pressboard (of 0.2 mm thickness)
samples were collected from the main bulk insulation between the high voltage and
low voltage windings.
Table 1: Results of conventional electrical tests on samples from LV A phase
winding of Kareeya transformer
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
12/36
3.1.1 Conventional Electrical Test Results
To obtain an understanding of the effects of varying stresses along complete
windings, samples were taken from various locations of the LV A and HV B phase
windings and were tested. Two sizes of new (unaged) paper wrapped conductors
(New1 and New2) and new pressboard samples of similar composition and
thickness were obtained from the transformer manufacturer GEC-Alsthom.
Conventional electrical test results on paper wrapped insulated conductor
specimens from the LV A phase and HV B phase windings are presented in Tables
1 and 2 respectively.
In LV A phase, coils 1,2/44,45/89,90 are from top/middle/ bottom locations
respectively and layers 1,2/18 are from outer and inner locations. For each of the
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
13/36
samples at least two samples were tested and average was taken. The partial
discharge inception stresses were usually very close to the power frequency
dielectric strength, and hence these results are not presented. In HV B phase, coils
1/29,30/59,60 are the top/middle /bottom locations and layers 1/12/19 are the
outer/medium/ inner locations.
The following comparison can be made between the results of the aged
insulation samples and those of the new insulation.
1. The average dissipation factor of LV A phase samples is 0.017 and that of
the New1 (similar to LVA phase) sample is 0.008. The average dissipation
factor of HV B phase samples is 0.015 and that of the New2 (similar to HV B
phase) sample is 0.009. The dissipation factor of aged samples is significantly
different from that of new insulation.
2. The average power frequency dielectric strength of the LVA phase samples
is 48.4 kVp/mm (with a SD= 3.16) and that of the New1 sample is 50.0
kVp/mm. The average power frequency dielectric strength of the HV B phase
samples is 41.6 kVp/mm (with a SD=3.5) and that of the New2 samples is 45.0
kVp/mm. The difference between the average value of the power frequency
breakdown strength of the LV A phase and the new samples is not significant,
whereas the variation of the HV B phase samples is 7.5% lower than the
corresponding new samples.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
14/36
3. The average lightning impulse breakdown strength of the LV A phase
samples is 77.0 kVp/mm (with a SD=7) and that of the New! samples is 81
kVp/mm. The average lightning impulse strength of the HV B phase is 68.5
kV/mm (with a SD=8.1) and that of the New2 samples is 84 kVp/mm. Again
the variation is not very significant for the LV A phase samples. The LI
strength of HV B phase sample is about 18% lower than the corresponding new
sample strength.
Table 2: Results of conventional electrical tests on samples from HV B phase of
Kareeya transformer.
3.1.2 Interfacial Polarization Spectra Results
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
15/36
The same aged insulation specimens from LV A and HV B phase and
unaged insulation samples (New1and New2) were tested using interfacial
polarization spectra (IPS) measurements. The results from the IPS measurements
are presented in Tables 3 and 4.
In Table 3 all the samples from the aged transformer show large peak
maximum voltages, short central time constants and large initial slopes by
comparison with the values for new samples. There are significant variations
between the aged samples from different locations. For example, we see the
maximum return voltage of top coil 1-1 (1st coil from top, 1st outside layer)
reached its peak at 31 s, whereas 89-1 reached its peak value at 75 s, which is more
than twice the time constant of 1-1. The dissipation factor for sample 1-1 is fifty
percent larger than the 89-1 sample (Table 1). It is also observed that 45-1, 45-18,
90-2 and 90-18 samples have maximum return voltages at very small (low) central
time constants and large values of initial slope and dissipation factor. The variation
of insulation status between top, middle and bottom coils of LV A phase, observed
from the conventional tests is consistent with the data from IPS measurements. It
suggests that degradation due to ageing is characterised by higher dissipation factor
and consistent changes in IPS e.g. higher return voltage and initial slope, and low
central time constant.
Table 3: Results of IPS measurements on samples from LV A phase winding of
Kareeya transformer
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
16/36
Table 4: Results of IPS measurements on samples from HV B phase winding of
Kareeya transformer
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
17/36
In Table 4 for HV B phase, the peak maximum values of return voltage are
somewhat lower than for the LV A phase. The variation of the peak maximum
return voltage for the HV B phase is not as significant as LV A phase by
comparison with the corresponding new samples. For example, the mean of the
peak maximum return voltage of LV A phase is 3.2 volt and that for the
New1sample is 1.6 volt, whereas, the mean of the peak maximum return voltage of
HV B phase is 2.0 volt and that for the New2 sample is 1.8 volt. There are large
variations in central time constant. Again, all but one (29-12) of the samples from
the aged transformer show lower central time constant and larger initial slope by
comparison with the new samples. The maximum return voltage of 1-12 reached
its peak value at 43 s, where as 1-1 and 1-19 reached their peak values at 94 s. The
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
18/36
dissipation factor for sample 1-12 is at least fifty percent larger than that for the 1-1
and 1-19 samples. This again illustrates consistency between dissipation factor and
IPS characteristics. Also, for HV B phase samples, it was found that the condition
of the insulation varies even between the layers. It is generally correct to say that
whenever samples have peak values of maximum return voltage with a fast (low)
central time constant, the associated values of the initial slope and dissipation
factor are large. This is illustrated by the examples of samples 60-1, 60-12, 60-19
and samples 29-1, 29-12, 29-19 (29-12 has already been mentioned as an
exception, but even this sample demonstrates the link between better dissipation
factor and better IPS characteristics). Although there are significant differences
of insulation characteristics between top, middle and bottom coils, it is not possible
to draw any conclusion about the trend of variation of insulation status between the
coil locations.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
19/36
3.1.3 GPC Test Results
Figure 3: GPC chromatogram of insulating paper samples obtained from new stock
and aged transformer
The GPC chromatograms of typical new and aged (from Kareeya
transformer insulation papers) cellulose are shown in Fig.3. The chromatogram of
new paper shows the presence of two components. The major component at lower
elution volume, high molecular weight, is due to cellulose, while the smaller, lower
molecular weight component is due to hemi-cellulose. The peak molecular weight
of the cellulose is 1.5 * 106 g/mol, while that of the hemi-cellulose is 5.8 * 104
g/mol.
The chromatogram of the cellulose paper taken from the aged transformer
shows that the molecular weight of the cellulose component has decreased
significantly, with the peak molecular weight falling to approximately 2 * 10
5
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
20/36
g/mol. The molecular weight distribution of the cellulose has also broadened
considerably, and the peak due to the hemi-cellulose has become barely
discernible, suggesting that the hemi-cellulose component of the paper may have
been largely degraded.
In order to obtain an understanding of the nature of the reduction in the
molecular weight of the paper, separate studies were made on the effects of
accelerated ageing on paper and cotton linter (which only contains cellulose).the
results enabled the chromatograms of the new and aged insulation samples to be
simulated by combinations of components.
The simulated chromatograms of the new paper are shown in Fig. 4. The x
axis and y axis of Fig. 4 are in elution volume (ml) and in absorbance respectively
(similar to fig.3). This profile can be simulated reasonably well by a combination
of three components with three peaks, using the computer program peakfit and
an exponential Gaussian function to simulate the peak shape. Of the three
components used, two may be attributed to the cellulose component of the paper,
and the third may be attributed to the hemi-cellulose component. The molecular
weight at the peaks were calculated by employing the universal calibration
procedure to correct the polystyrene calibration curve. Similar simulations were
made for the transformer aged insulations, and the results of some selected samples
have been summarised in Tables 5 and 6.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
21/36
Table 5: Results from GPC analysis on samples from LV A phase of Kareeya
transformer
Figure 4: The simulation chromatogram of the new insulating paper
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
22/36
In Tables 5 and 6, the molecular weights of the peaks P1 and P2 of the
insulating paper in the LV A phase and in the HV B phase of the transformer fall to
about one half to one third of the molecular weights at the corresponding peaks for
P1 and P2 of new insulating paper. A comparison between the LV A phase and the
HV B phase papers indicates that the largest change in molecular weight occurs in
the outermost layers (1-1,45-1,89-1) of the LV A phase conductors. The paper near
the top of the transformer, where the temperature is greatest, shows the greatest
decrease in molecular weight.
3.1.4 Results From Pressboard Samples
The conventional electrical test results of new pressboard and pressboard
collected from Kareeya transformer are presented in Table 7. Unequal electrodes
(ASTM D 149) were used for these tests.
The results show that the dissipation factor of aged transformer pressboard
is much higher than that for new pressboard samples. The power frequency
breakdown strength for aged transformer pressboard is reduced by 29.7% from that
of new unaged pressboard. The lightning impulse breakdown strength of aged
pressboard is reduced by 14.3 %.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
23/36
Table 6: Results from GPC analysis on samples from HV B phase of Kareeya
transformer
Table 7: Results obtained from aged and new press board: Unequal Electrodes
(ASTM D 149)
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
24/36
The IPS results are shown in Table 8. The maximum return voltage of aged
pressboard from the Kareeya transformer reached its peak value at 21 s, whereas
the new pressboard sample reached its peak value after 360 s. The value of the
peak maximum return voltage and initial slope of aged pressboard are also much
larger than those of the new pressboard. Again, these findings are consistent with
those presented earlier for pa per insulation. So, from both the conventional
electrical tests and IPS measurements, it can be concluded that, the degradation of
pressboard in the Kareeya transformer was much more severe than for the paper
insulation.
The GPC technique was applied to new pressboard samples and samples
from the Kareeya transformer. The chromatograms were analysed in a similar way
to that described previously. The results are summarised in Table 9. The reduction
in the molecular weights of peak I and 2 for old pressboard relative to that of new
pressboard shows the deterioration in the condition of the insulation. However, in
contrast to what was observed for paper insulation, there was little change in the
molecular weight of peak 3 (P3) for pressboard.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
25/36
Table 8: Results of IPS measurements on new and aged pressboard samples
Table 9: GPC Results obtained from aged and new pressboard Sample
Figure 5: Peak molecular weight versus the central time constants for different
samples of Kareeya transformer
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
26/36
3.1.6 Correlation Between Methods
Attention has already been drawn to the consistency in changes to electrical
(dissipation factor and IPS data) and chemical(peak molecular weight data)
properties caused by ageing induced degradation. The results are now re-examined
more closely to determine the level of consistency between the electrical and
chemical test methods. Coil 1-1from LV A phase(Table 3 ) shows that the peak
maximum return voltage is attained with a fast (short) central time constant, it has
a large initial slope and its peak molecular weights P1 and P2 (Table 5) are both
very low. So the same conclusion can be drawn from both the tests; that the
insulation has been severely degraded by ageing, and sample 1-1 is one of the most
degraded samples. Similar conclusions can be drawn for the samples 45-1 and 45-
18. Sample 44-18 shows peak maximum return voltage at a larger central time
constant, and as expected this is associated with a larger molecular weight. To
examine the extent of correlation between the electrical and chemical properties,
peak molecular weights P1 of the LV A phase and HV B phase specimens are
plotted against central time constants and initial slopes of the return voltages.
Although there were a few outlying points in both the graphs, Fig. 5 shows that the
decrease in the peak molecular weight corresponds to a decrease (fast) in the
central time constant and Fig. 6 shows that a decrease in the peak molecular weight
corresponds to an increase in the initial slopes.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
27/36
To test the statistical independence of the measured parameters, rank
correlation coefficients [4] were calculated for both the cases (with all data points
and with outlying omitted data points). These values are shown in Table 10.
Critical values of the rank correlation coefficients for two sided test with
significance level = 0.05 [4] are also shown in the Table 10. If the observed
value of the rank correlation coefficient is greater than the critical rank correlation
coefficient, then the statistical independence between the tested parameter is
rejected. With omitted outlying data points both graphs show good linear
correlations (with correlation coefficients greater than 0.9). At the same time their
rank correlation coefficients are also greater than the corresponding critical
correlation coefficients. When all the data points are considered, Fig. 6 show linear
correlation with correlation coefficients greater than 0.5. With all the data points,
the observed rank correlation coefficient is greater than the critical rank correlation
coefficient for the data points in Fig. 6. Although the test programme was
necessarily limited, a good trend has been emerged between the IPS parameters
and the chemical test results.
Table 10: Results of correlation coefficients from the correlation Figs. 5 and 6
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
28/36
Figure 6: Peak molecular weight versus the initial slopes for different samples of
Kareeya transformer
3.2 case study 2:distribution transformers
3.2.1 Conventional E1ectrical Tests Results
Six distribution transformers were provided by electricity distribution
authorities. The dissipation factors of these transformers were measured by the
Schering bridge. For a single phase transformer, the shorted low voltage winding
was connected to the lower voltage arm of the Schering bridge, and shorted high
voltage winding was connected to the high voltage supply. For a three phase
transformer, three phases in the LV winding were short circuited and connected to
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
29/36
the lower voltage arm of the Schering bridge and three phases in the HV winding
were short circuited and connected to the high voltage supply. Dissipation factors
were measured at two different voltages and the average was determined. This
arrangement measures the dissipation factor of the bulk insulation (insulation
between HV and LV windings) of the transformers. Results from the Schering
bridge measurements are shown in Table 11. Dissipation factors varied from 0.003
to 0.067 for single phase transformers and 0.006 to 0.081 for three phase
transformers. Transformers TI, T3 and T6 show high dissipation factors compared
to the other transformers.
3.2.2 Interfacial Polarization Test Results
All the six distribution transformers were tested for IPS measurements. The
charging voltage was 1000 volt DC and the procedure was similar to that followed
for the specimens made
Table 11: Results of Dissipation factors and capacitances of distribution
transformers
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
30/36
Table 12: Results of IPS measurements of the single phase distribution
transformers
with two paper wrapped insulated conductors. The connection arrangements
of the transformers (two terminal dielectric) were the same as those used for
dissipation factor measurements. In this case, the bulk insulation between HV and
LV was tested.
From Tables 12 and 13, it is observed that the initial slopes and central time
constants vary significantly between the trans formers. The variation of the peak
maximum return voltage did not follow any specific trend. Some form of
normalisation may be necessary to compare different peak maximum values, when
the transformers are of different insulation resistances and capacitances. In general,
higher initial slopes are associated with shorter central time constants, and this is
consistent with previously presented results. Transformers with these
characteristics also tend to have large dissipation factors. For example, transformer
T1 and T3 show larger dissipation factors and higher initial slopes and lower
central time constants than the transformer T2. The oldest transformer of the three
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
31/36
phase trans formers, T6 shows high dissipation factor, high initial slope and low
central time constant compared to the corresponding values for the transformers T4
and T5. Thus, a good correlation exists between initial slope, central time constant
and dissipation factor.
3.2.3 GPC Test Results
Several paper and pressboard samples were taken from the distribution
transformers (T1, T2, T3 and T5) for the GPC analysis. The results are shown in
Table 14. From the Tables 11 and
Table 13: Results of IPS measurements of the three phase distribution transformers
Table 14: GPC Results of cellulose samples from distribution transformers
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
32/36
13, it is observed that the transformer T5 has a very low dissipation factor
with a low peak maximum return voltage, initial slope and large central time
constant. From Table 14, both paper and pressboard samples from T5 show high
peak molecular weight P1, close to that of new paper. From both the electrical and
chemical tests, it is evident that insulation of T5 is in very good condition. Both
paper and pressboard samples from T1 and T3 show a large reduction in peak
molecular weights compared to new ones. From Tables 11 and 12, it is observed
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
33/36
that the transformer T1 and T3 have high dissipation factors with large initial
slopes and low central time constants compared to the transformer T2. A good
correlation is observed between the IPS parameters, dissipation factor and the GPC
results from the limited number of samples analysed from the distribution
transformers. The important point is that this finding is consistent with similar
findings for the aged power transformer, and as can be seen in the adjunct paper
with the results for artificially aged paper [12].
4 CONCLUSIONS
Conventional electrical tests and IPS measurements were applied to
insulated conductors and pressboard samples collected from a retired power
transformer. The molecular weights of the samples were also studied by GPC
analysis. Significant differences in the condition of the insulation have been ob
served throughout different locations within the Kareeya transformer. The
electrical test results (in particular dissipation factor and the IPS parameters) on the
Kareeya transformer insulation specimens were found to be consistent with the
GPC results. A good correlation has been observed between the electrical test
results and GPC analysis for detecting changes in the properties of the insulation
samples. The condition of aged pressboard from the Kareeya transformer has been
found to be significantly deteriorated compared to new pressboard. This was also
evident from both the electrical and chemical teat results.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
34/36
Several distribution transformers were also studied, Dissipation factors and
IPS measurements showed a good consistency in explaining the condition of
insulation in distribution transformers. GPC results from the distribution
transformers also correlated well with the dissipation factor and IPS parameters.
5 REFERENCES
AISN Software, Peakfit, vol. 2.0.
A. Bognar and et al., Diagnostic Test Method of Solid/Liquid Electrical
Insulations Using Polarization Spectrum in the Range of Long Time Constants,
7th International Symposium on High Voltage Engineering, pp. , Dresden,
Germany, 1991.
P. J. Burton and et al, Applications of Liquid Chromatography to the Analysis of
Electrical Insulating Materials, International Conference on Large High Voltage
Electric Sys tem, CIGRE Proceedings of the 1988 Session , Paper 15-08,
pp. , Paris, France, 28 August-3 September, 1988.
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
35/36
K. V. Bury, Statistical Models in Applied Science, USA, John Wiley and Sons,
1975.
R. Evans, R. H. Wearne and A. F. A. Wallis, Molecular Weight Distribution of
Cellulose as Its Tricarbanilate by High Performance Size Exclusion
Chromatography., Journal of Applied Polymer Science, Vol.37, pp. , 1989.
D. J. T. Hill, P. T. Le, M. Darveniza, T. K. Saha and B. Williams, Gel Permeation
Chromatography of the Thermal Degradation of Cellulose Insulation Paper in
Aged Power Transformer, Materials Forum, Vol.16, pp. , 1992.
D. J. T. Hill, T. T. Le, M. Darveniza and T. K. Saha, Degradation of Cellulosic
Insulation Materials in a Power Transformer-
Part 1: Molecular Weight Study of Cellulose Insulation Pa per, Polymer
Degradation and Stability, Vol.48, no. 1, pp. 1995.
LEO, LEG 599-78, Interpretation of the Analysis of Gases in Transformers and
Other Oil-filled Electrical Equipment, iii Operation, 1978.
H. P. Moser and et al., Application of Cellulosic and Non cellulosic Materials in
Power Transformers, International Conference on Large High Voltage Electric
-
7/31/2019 Electrical and Chemical Diagnostics of Transformer Insulation Abstrac1
36/36
System, CIGRE Proceedings of the 31st Session (Paper 12-12), Vol.1,27 August 4
September, 1986.
B. Nemeth, Proposed Fundamental Characteristics Describ ing Dielectric
Processes in Dielectrics, Periodica Polytechnica, Electrical Engineering,, Vol.15,
no. 4, 1971.
T. V. Oomen and L. N. Arnold, Cellulose Insulation Materials Evaluated by
Degree of Polymerization Measurements, Proceedings of the 15th
Electrical/Electronics Insulation Conference, pp. , Chicago, IL, USA 19-22 Oct.
1981.
T. K. Saha, M. Darveniza, D. J. T. H.ill and T. T. Le, Electrical and Chemical
Diagnostics of Transformers Insulation-Part B: Accelerated Aged Insulation
Samples, Accompany ing Paper.
D. H. Shroff and A. W. Stannett, A Review of Papi Aging in Power
Transformers, lEE Proc. , Vol. 132, pt.c, no. 6, pp. , Nov. 1985.
J. Unsworth and F. Mitchell, Degradation Of Electrical Insulating Paper
Monitored With High Performance Liquid Chromatography, IEEE Transaction on
Electrical Insulation, Vol.25, no. 24, pp. , August 1990.