Electrical Failure

InvestigationsPresented byPresented by

Ashley HarknessAshley Harkness

Page 2: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Forensics, the Mystery

• Our Forensics Work

• Project Examples

Page 3: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Why Do Things Fail?

Page 4: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Because of...• Installation

• Application

• Operation

• Maintenance

Page 5: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

What we will look at...

• When the installer does it wrong…

• When the unexpected happens...

• When the design has problems...

• When People get involved…

Page 6: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Poor Installation...

First:

Page 7: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

A High Voltage Bushing

• 27 KV bushing installed on a commuter train system.

• Steamed and Smoked when energized.

• Client wanted to know: What happened.

Page 8: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Manufacturer’s Information

• Cut the Cable• Strip off insulation• Strip away insulation

shield• Wrap tape stress cone• Attach top connector• Assemble components• Fill with sealant

Page 9: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The first step: X-ray the Sample

Page 10: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

What the X-ray revealed:

• The connector had not been properly soldered.

• The conductor strands were clearly visible.

Page 11: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 12: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

How bad was the connection?

Page 13: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

It was not the only problem!

• Question: Where did the steam come from?

• Further investigation showed a second problem.

Page 14: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The cable seal was improper.

The seal is in the wrong place.

Page 15: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Correct Seal Position

The seal is against the outer jacket material.

Page 16: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Report:

• The poor connection caused heat and steam.• The improper seal allowed water to

penetrate the bushing.• This was caused by poor workmanship.

Page 17: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Next Example:

Contractor: “It’s bad equipment!”

Manufacturer: “Poor workmanship!”

Owner: “Help!”

Page 18: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 19: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Arcing between phases

Page 20: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Mfg. Limits:

Page 21: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Conclusion:

• Improper installation

Page 22: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

“Well, we had a limited budget…”

Let’s take another example..

Page 23: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 24: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 25: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 26: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 27: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 28: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Conclusion:

• Mismatch of equipment• Poor installation

Page 29: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Something “Off the Wall”...

Weird ones:

Page 30: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

An Airport Maintenance Facility in Texas

Page 31: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Problem:

• Blow-outs between A Phase and Ground• Several in the first months of installation.• No previous history of such faults.• Was it bad product?• Was it bad installation?• What was the cause?

Page 32: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Power Bus Duct

• Reduced impedance.

• Reduced cost.• Increased inherent

strength.• Manufacturing

simplicity.• Reliable.

Page 33: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Buss Duct End View

Page 34: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Fault Tree

Page 35: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Insulation Porosity

Page 36: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Report:

• Rain water entered the product.• Insulation porosity was present.• The installation was correct.• The product was properly produced.• The transportation was incorrect.

Page 37: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

A defective product.

Undetected, until suspicions were aroused

Another weird one:

Page 38: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Problem:

• The installing splicersdid not like the cable.

• Client wanted it tested to Specifications.

Page 39: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

5 KV Cable Sample

Page 40: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Suspicious gaps in the strand shield system.

Page 41: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Close-up of the defect.

• The strand shield had separated during extrusion.

• The mark did not follow the strands.

• A longitudinal impression was present.

Page 42: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Culprit

• A cut-off knife caused the gash in the conductor stranding.

Page 43: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Report:

• A manufacturing defect was found.• The life of the cable had been shortened. • The manufacturer offered the client an

extended warranty.

Page 44: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

There was no fault!

–A Different Type of Case:–A Critical Area—EDP–The Fuse Blew!–The mystery…

Page 45: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 46: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 47: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Melted element

Page 48: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Intact Elements

Page 49: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Mechanical Fractures

Page 50: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Hey, wait a minute...

• Earlier testing records noted this fuse--

• One fuse had high resistance

• Replacement had not been done

Page 51: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Conclusion:

• Work hardened elements fractured• Fuse opened on less than full load

• Operation and Maintenance Issue• Preventable Outage

Page 52: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

TIME OUT!

How do you know that?

Page 53: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Forensic Process...

• Things we know:

• Arc Behavior• Fire Directions • Expected Performance

• Things we Learn:

• Circuit Loading• Environmental Factor• Discovery

– Inspection– Testing

Page 54: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Fault Tree

• Initiating Event• Failure Mechanism• Findings

– Test, inspections, measurements• Conclusion:

– Not Likely Cause– Most Probable Cause

Page 55: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 56: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

A Design Problem:

•“Well, I’m not sure what the load is...”

Page 57: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Why did it fail?

Better question:

What is it?

Page 58: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 59: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Conclusion:

• Bus Overload– 4000 Amp Bus– 5000 Amp Load!

– Application

Page 60: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Human Factor...

And then:

Page 61: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

What People will do...

• Working “Hot”

Page 62: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

“I don’t need no stinking safety procedures.”

“Hey, loan me your wiggie.”

Page 63: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 64: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 65: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 66: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 67: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 68: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Conclusion:

• Defective meter initiated fault• Poor Work Practices• Lack of Protective Equipment

Page 69: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

But we paid extra to

keep the power on !

(Human Factor)

Page 70: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

The Attorney's

Office

Page 71: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

480 Volt Generator

Page 72: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 73: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

208 Volt Generator

Page 74: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 75: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Conclusion:

• Improper wiring of generator– No connected neutral or ground

– Metal Oxide Varistor could not withstand the voltage.

– Fire was result

Page 76: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

When maintenance goes wrong…”

“What’s this green wire for?”

“It’s only a street light!”

Page 77: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 78: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 79: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone
Page 80: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

Conclusion:

• Poor Installation and Maintenance:– Water Damage– Pinched Wire– Not Grounded

• Child’s death:– She touched the energized light pole and a

grounded fence.

Page 81: Electrical Failure Investigations · 2007-04-24 · Manufacturer’s Information • Cut the Cable • Strip off insulation • Strip away insulation shield • Wrap tape stress cone

In Summary:

• Forensics finds the strangest things.– Poor Workmanship– Defective Product– Off-the-Wall Problems