electrical installation condition report:...

38
ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A. Details of the Person Ordering This Report Client PO Box 71462 London SE1P 4RW Address 18 Jul 2015 B. Reason for Producing This Report Date of Testing & Inspection Information requested by the Client in accordance with The Electricity at Work Regulations 1989 also to form part of the clients ongoing planned maintenance schedule. Purpose of this Report C. Details of the Installation which is Subject of this Report Whole of site Installation FSHC G68 0GA Occupier Carrickstone House Care Home 1 Ratho Drive Cumbernauld G68 0GA Address Domestic Description of Premises No Record of Installation Available N/A Records Held By 21 May 2010 Date of Previous Inspection 15 yrs Estimated Age of Wiring No Evidence of Alterations N/A yrs Estimated Age of Alterations D. Extent & Limitations Inspection & Testing Extent of Electrical Installation Covered by This Report Manager Agreed Limitations including the Reasons Refer to Appendix C Limitations Agreed With Operational Limitations including the Reasons Refer to Appendix D This inspection and testing detailed in this report and accompanying schedules have been carried out in accordance with BS7671:2008 (IET Wiring Regulations) as amended to July 2011. It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the building or underground, have NOT been inspected unless specifically agreed between the client and inspector prior to the inspection. F. Recommendations Where the overall assessment of the suitability of the installation for continued use above is stated as Unsatisfactory , I recommend that any observations classified as 'Danger present' (code C1) or 'Potentially dangerous (code C2) are acted upon as a matter of urgency. Investigation without delay is recommended for observations identified as 'further investigation required'. Observation classified as 'Improvement recommended' (code C3) should be given due consideration. Subject to the necessary remedial action being taken I recommend that the installation is further inspected and tested by 16/07/2020 G. Declaration I, being the person responsible for the inspection and testing of the electrical installation (as indicated by my signatures below) particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information in this report, including the observations & attached schedules, provides an accurate assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D of this report. Key Electrical Solutions Limited 218 Boughton Ind Est Boughton NG22 9LD England Trading Address n/a Branch Number 600616000 NIC EIC Number Inspected and Tested by: Lloyd Reilly Name Engineer Position Signature 18 Jul 2015 Date Authorised for Issue by: Martin Key Name Chief Engineer Position Signature 20 Jul 2015 Date H. Schedules The attached schedule(s) are part of this document and this report is valid only when they are attached to it. 9 Schedules of Test Results 9 Schedules of Inspection 100% testing and visual inspection to all aspects of the fixed wiring within the installation, including mains, sub-mains, distribution boards and final circuits within the limitations agreed with the client. E. Summary of the Condition of the Installation General Condition of the Installation (In terms of Electrical Safety) Refer to Appendix E UNSATISFACTORY Overall assessment of the installation *An unsatisfactory assessment indicates that dangerous (code C1) and/or potentially dangerous (code C2) conditions have been identified. Copyright. Key Electrical Solutions Limited. 2014 Page 1

Upload: others

Post on 04-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Mitie FSHC

A. Details of the Person Ordering This Report

ClientPO Box 71462LondonSE1P 4RW

Address

18 Jul 2015

B. Reason for Producing This Report

Date of Testing & Inspection

Information requested by the Client in accordance with The Electricity atWork Regulations 1989 also to form part of the clients ongoing plannedmaintenance schedule.

Purpose of this Report

C. Details of the Installation which is Subject of this Report

Whole of siteInstallationFSHC G68 0GAOccupierCarrickstone House Care Home1 Ratho DriveCumbernauldG68 0GA

Address

DomesticDescription of Premises

NoRecord of Installation AvailableN/ARecords Held By21 May 2010Date of Previous Inspection15 yrsEstimated Age of WiringNoEvidence of AlterationsN/A yrsEstimated Age of Alterations

D. Extent & Limitations Inspection & Testing

Extent of Electrical Installation Coveredby This Report

ManagerAgreed Limitations including the Reasons Refer to Appendix C Limitations Agreed WithOperational Limitations including the Reasons Refer to Appendix DThis inspection and testing detailed in this report and accompanying schedules have been carried out in accordance with BS7671:2008 (IET Wiring Regulations) asamended to July 2011. It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the buildingor underground, have NOT been inspected unless specifically agreed between the client and inspector prior to the inspection.

F. RecommendationsWhere the overall assessment of the suitability of the installation for continued use above is stated as Unsatisfactory , I recommend that any observations classified as'Danger present' (code C1) or 'Potentially dangerous (code C2) are acted upon as a matter of urgency. Investigation without delay is recommended for observationsidentified as 'further investigation required'. Observation classified as 'Improvement recommended' (code C3) should be given due consideration. Subject to thenecessary remedial action being taken I recommend that the installation is further inspected and tested by 16/07/2020

G. Declaration

I, being the person responsible for the inspection and testing of the electrical installation (as indicated by my signatures below) particulars of which are described above,having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information in this report, including the observations &attached schedules, provides an accurate assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D ofthis report.

Key Electrical Solutions Limited218 Boughton Ind EstBoughtonNG22 9LDEngland

TradingAddress

n/aBranch Number600616000NIC EIC Number

Inspected and Tested by: Lloyd ReillyName EngineerPosition Signature 18 Jul 2015DateAuthorised for Issue by: Martin KeyName Chief EngineerPosition Signature 20 Jul 2015Date

H. Schedules

The attached schedule(s) are part of this document and this report is valid only when they are attached to it.9Schedules of Test Results9Schedules of Inspection

100% testing and visual inspection to all aspects of the fixed wiringwithin the installation, including mains, sub-mains, distribution boardsand final circuits within the limitations agreed with the client.

E. Summary of the Condition of the Installation

General Condition of the Installation (In terms of Electrical Safety) Refer to Appendix E

UNSATISFACTORYOverall assessment of the installation*An unsatisfactory assessment indicates that dangerous (code C1) and/or potentially dangerous (code C2) conditions have been identified.

Copyright. Key Electrical Solutions Limited. 2014 Page 1

Page 2: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

K. Observations

Referring to the attached schedule(s) of Inspection and Test Results, and subject to the limitations specified at the Extent and Limitations of theInspection and testing section. There are a total of 7 Observations. One of the following codes, as appropriate, has been allocated to each of theobservations made, to indicate to the persons responsible for the installation, the degree of urgency for remedial action.

C1 - Danger present. Risk of Injury. Immediate Remedial Action Required: 0C2 - Potentially dangerous Urgent Remedial Action Required: 12C3 - Improvement Recommended: 0

Refer to Appendix F for full details of the observations

TN-C-S

I. Supply Characteristics & Earthing Arrangements

Earthing Arrangements

AC3 Phase ( 3 Wire )Three PhasePhase

Supply TypeType of Live Conductors

YesConfirmation of Polarity

400Nominal Voltage U (1)

230Nominal Voltage U O(1)

50Nominal Frequency f(1)

1.8Prospective Fault Current ipf(2)

0.09External Loop Impedance Ze(2)

1Number of Supplies

LIMBS(EN)LIMType

Nominal Current RatingLIMShort Circuit Capacity

Note: (1) by Enquiry, (2) by enquiry or bymeasurement

Number & Type of Live Conductors

Nature of Supply Parameters Supply Protective Device

Distributor's Facility

J. Particulars of Installation Referred to in this Report

Means of Earthing LocationN/AType of Earthing

N/A

N/AResistance to EarthMethod of Measurement N/A

Copper

Main Protective Conductors

Earthing Conductor 120csa Connection & Continuity Verified Yes

CopperMain Protective Bonding Conductors 35csa Connection & Continuity Verified Yes

Bonding of Incoming ServiceYesWater Gas Lightning

Oil Steel N/AOther

Maximum Demand Load100Amps

Protective Measures Against Shock ADS

Main Switch / Switch Fuse / Circuit Breaker / RCD

centre corridorcupboard

Location60947-2 Type BType BS(EN)

CopperSupply Conductor Material3 PolesNumber of Poles

120Supply Conductor csa

LIMCurrent Rating600Voltage Rating

N/ARated Residual Op.Current l∆n

N/ARated Time DelayN/AOperating Times at

l∆n

If RCD Main Switch

VV

HzkAΩ

kAA

Ω

Yes N/AN/A N/A

mm2

mm2

mm2

AV

mA

msms

Copyright. Key Electrical Solutions Limited. 2014 Page 2

Page 3: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Item Description OutcomeFurther

Investigation Comments

1.0 Distributor's Supply Intake Equipment

1.1 Service Cable Condition NoNo√1.2 Condition of Service Head NoNo√1.3 Condition of Tails - Distributor NoNo√1.4 Condition of Tails - Consumer NoNo√1.5 Condition of Metering Equipment NoNo√1.6 Condition of Isolator (where present) NoNoN/A

2.0 Presence of Adequate Arrangements for Other Sources such as Microgenerators

2.1 Presence of Adequate Arrangements for other sources such as Microgenerators (221.6,551.7) NoNoN/A

3.0 Earthing / Bonding Arrangements

3.1 Presence of distributor's earthing arrangement NoNo√3.2 Presence and condition of earth electrode connection where applicable NoNoN/A3.3 Provision of earthing / bonding labels at all appropriate locations NoNo√3.4 Confirmation of earthing conductor size NoNo√3.5 Accessibility and condition of earthing conductor at MET NoNo√3.6 Confirmation of main protective bonding conductor sizes (544.1) NoNo√3.7 Condition and accessibility of main protective bonding conductor connections (543.3.2; 544.1.2) NoNo√3.8 Accessibility and condition of all protective bonding connections (543.3.2) NoNo√

4.0 Consumer Unit / Distribution Board

4.1 Adequacy of working space / accessibility to consumer unit / distribution board (132.1.2; 513.1) NoNoN/A4.2 Security of fixing (134.1.1) NoNoN/A4.3 Condition of enclosure(s) in terms of IP rating etc (416.2) NoNoN/A4.4 Condition of enclosure(s) in terms of fire rating etc (526.5) NoNoN/A4.5 Enclosure not damaged/deteriorated so as to impair safety (621.2 (iii)) NoNoN/A4.6 Presence of linked main switch (as required by 537.1.4) NoNoN/A4.7 Operation of main switch (functional check) (612.13.2) NoNoN/A4.8 Manual operation of circuit-breakers and RCDs to prove disconnection (612.13.2) NoNoN/A4.9 Correct identification of circuit details and protective devices (514.8.1; 514.9.1) NoNoN/A4.1 Presence of RCD quarterly test notice at or near consumer unit / distribution board (514.12.2) NoNoN/A4.11 Presence of non-standard (mixed) cable colour warning notice at or near consumer unit / distribution

board (514.14)NoNoN/A

4.12 Presence of alternative supply warning notice at or near consumer unit / distribution board (514.15) NoNoN/A4.13 Presence of other required labelling (Please specify) (Section 514) NoNoN/A4.14 Examination of protective device(s) and base(s); correct type and rating (no signs of unacceptable

thermal damage, arcing and overheating (421.1.3)NoNoN/A

4.15 Single-pole protective devices in line conductor only (132.14.1; 530.3.2) NoNoN/A4.16 Protection against mechanical damage where cables enter consumer unit / distribution board

(522.8.1; 522.8.11)NoNoN/A

4.17 Protection against electromagnetic effects where cables enter consumer unit / distribution board /enclosures (521.5.1)

NoNoN/A

4.18 RCD(s) provided for fault protection – includes RCBOs (411.4.9; 411.5.2; 531.2) NoNoN/A4.19 RCD(s) provided for additional protection - includes RCBOs (411.3.3; 415.1) NoNoN/A

5.0 Final Circuits

5.1 Identification of conductors (514.3.1) NoNoN/A5.2 Cables correctly supported throughout their run (522.8.5) NoNoN/A5.3 Condition of insulation of live parts (416.1) NoNoN/A5.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking (521.10.1) NoNoN/A5.41 To include the integrity of conduit and trunking systems (metallic and plastic) NoNoN/A5.5 Adequacy of cables for current-carrying capacity with regard for the type and nature of installation

(523)NoNoN/A

Copyright. Key Electrical Solutions Limited. 2014 Page 3

Page 4: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Item Description OutcomeFurther

Investigation Comments

5.6 Co-ordination between conductors and overload protective devices (433.1; 533.2.1) NoNoN/A5.7 Adequacy of protective devices; type and rated current for fault protection (411.3) NoNoN/A5.8 Presence and adequacy of circuit protective conductors (411.3.1.1; 543.1) NoNoN/A5.9 Wiring system(s) appropriate for the type and nature of the installation and external influences (522) NoNoN/A5.1 Concealed cables installed in prescribed zones (see section D. extent and limitations) (522.6.101) NoNoN/A5.11 Concealed cables incorporating earthed armour or sheath, or run within earthed wiring system, or

otherwise protected against mechanical damage from nails, screws and the like (see section D. extentand limitations) (522.6.101; 522.6.103)

NoNoN/A

5.12 Provision of additional protection by RCD not exceeding 30mA NoNoN/A5.121 - for all socket-outlets of rating 20 A or less provided for use by ordinary persons unless exempt -

(411.3.3)NoNoN/A

5.122 - for supply to mobile equipment not exceeding 32 A rating for use outdoors (411.3.3) NoNoN/A5.123 - for cables concealed in walls or partitions (522.6.102; 522.6.103) NoNoN/A5.13 Provision of fire barriers, sealing arrangements and protection against thermal effects (527) NoNoN/A5.14 Band II Cables segregated / separated from Band I cables (528.1) NoNoN/A5.15 Cables segregated / separated from communications cabling (528.2) NoNoN/A5.16 Cables segregated / separated from non-electrical services (528.3) NoNoN/A5.17 Termination of cables at enclosures - indicate extent of sampling in Section D of the report (526) NoNoN/A5.171 - Connections soundly made and under no undue strain (526.6) NoNoN/A5.172 - No basic insulation of a conductor visible outside enclosure (526.8) NoNoN/A5.173 - Connections of live conductors adequately enclosed (526.5) NoNoN/A5.174 - Adequately connected at point of entry to enclosure (glands, bushes etc...) (522.8.5) NoNoN/A5.18 Condition of accessories including socket-outlets, switches and joint boxes (621.2 (iii)) NoNoN/A5.19 Suitability of accessories for external influences (512.2) NoNoN/A

6.0 Locations containing a Bath or Shower

6.1 Additional protection for all low voltage (LV) circuits by RCD not exceeding 30mA (701.411.3.3) NoNoN/A6.2 Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5) NoNoN/A6.3 Shaver sockets comply with BS EN 61558-2-5 formally BS 3535 (701.512.3) NoNoN/A6.4 Presence of supplementary bonding conductors, unless not required by BS 7671: 2008 (701.415.2) NoNoN/A6.5 Low Voltage (e.g.230 volts) socket outlets at least 3m from Zone 1 (701.512.3) NoNoN/A6.6 Suitability of equipment for external influences for installed location in terms of IP rating (701.512.2) NoNoN/A6.7 Suitability of equipment for installation in a particular zone (701.512.3) NoNoN/A6.8 Suitability of current-using equipment for particular position within the location (701.55) NoNoN/A

7.0 Other Part 7 Special Installations or Locations

7.1 List all other special installations or locations present, if any. (Record separately the results ofparticular inspections applied).

NoNoN/A

Inspected by

Lloyd ReillyName EngineerPosition Signature 18 Jul 2015Date

Copyright. Key Electrical Solutions Limited. 2014 Page 4

Page 5: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

centre corridorcupboard

Location

DB mainsDesignation

OriginSupply FromThree PhaseNo of Phases400Nominal Voltage

Overcurrent Protective DeviceLIMType BS(EN)

Rating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/TP 25 N/A .19DB eastfield wing G C 1 35 35 5.0 60947-2

B 200

2/TP 25 N/A .19DB hospital wing G C 1 35 35 5.0 60947-2

B 200

3/TP 25 N/A .19DB balloch wing G C 1 35 35 5.0 60947-2

B 200

4/TP 25 N/A .19DB dullatur wing G C 1 35 35 5.0 60947-2

B 200

5/L1 -Spare -

5/L2 -Spare -

5/L3 25 N/A .37DB external lightingvia contractor

D B 1 16 10 5.0 60947-2

B 100

6/TP 25 N/A .19DB kitchen & laundry G C 1 35 35 5.0 60947-2

B 200

7/TP 25 N/A .37DB extension A G C 1 25 35 5.0 60947-2

B 100

8/TP -Spare -

9/L1 -Spare -

9/L2 25 N/A 2.3nurse call system, TVsystem, door entry

A 100 4 1.5 1 0.4 60947-2

B 16

9/L3 -Spare -

10/L1 -Spare -

10/L2 25 N/A 2.3fire alarm equipment A 100 1 2.5 1.5 0.4 60947-2

B 16

10/L3 -Spare -

11/TP -Spare -

12/TP -Spare -

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 5

Page 6: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.09 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

1.75Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/TP Yes 0.10 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A Yes

2/TP Yes 0.13 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A Yes

3/TP Yes 0.05 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A Yes

4/TP Yes 0.09 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A Yes

5/L1 - - -- -- - - - - - - - - No

5/L2 - - -- -- - - - - - - - - No

5/L3 Yes 0.05 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A Yes

6/TP Yes 0.06 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A Yes

7/TP Yes 0.07 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A No

8/TP - - -- -- - - - - - - - - No

9/L1 - - -- -- - - - - - - - - No

9/L2 Yes 0.26 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A No

9/L3 - - -- -- - - - - - - - - No

10/L1 - - -- -- - - - - - - - - No

10/L2 Yes 0.19 N/AN/A LIMN/A N/A LIM N/A LIM LIM LIM N/A N/A No

10/L3 - - -- -- - - - - - - - - No

11/TP - - -- -- - - - - - - - - No

12/TP - - -- -- - - - - - - - - No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position18 Jul 2015Date of Testing Signature

Page 6

Page 7: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

centre corridorcupboard

Location

DB external lighting viacontractor

Designation

DB mains: 5/L3Supply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)100 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/L 6 N/A 3.68lights piazza at rearservice area

D B 3 2.5 1.5 0.4 60898 B 10

2/L 10 N/A 1.84bollards & designerlamp columns at

D B 7 2.5 1.5 0.4 60898 B 10

3/L 10 N/A 1.84lights floodlights atfront of premise

D B 3 2.5 1.5 0.4 60898 B 10

4/L 10 N/A 1.84lights floodlights atfront of premises

D B 1 2.5 1.5 0.4 60898 B 10

5/L 10 N/A 1.84bollards & floodlightson column on service

D B 3 2.5 1.5 0.4 60898 B 10

6/L 10 N/A 1.84bollards & wall lightsin open cupboard

D B 6 2.5 1.5 0.4 60898 B 10

7/L 6 N/A 3.68bollards in closedcourtyard

D B 2 2.5 1.5 0.4 60898 B 10

8/L 10 N/A 3.06lamps on pillars atmain front entrance

D B 2 1.5 1 0.4 60898 B 6

9/L -Spare -

10/L -Spare -

11/L -Spare -

12/L -Spare -

13/L -Spare -

14/L -Spare -

15/L -Spare -

16/L -Spare -

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 8

Page 8: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.05 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/L Yes LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

2/L Yes LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

3/L LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

5/L Yes LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

6/L Yes LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

7/L Yes LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

8/L Yes LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

9/L - - -- -- - - - - - - - - No

10/L - - -- -- - - - - - - - - No

11/L - - -- -- - - - - - - - - No

12/L - - -- -- - - - - - - - - No

13/L - - -- -- - - - - - - - - No

14/L - - -- -- - - - - - - - - No

15/L - - -- -- - - - - - - - - No

16/L - - -- -- - - - - - - - - No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position18 Jul 2015Date of Testing Signature

Page 9

Page 9: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

balloch wing sluiceroom 2

Location

DB balloch wingDesignation

DB mains: 3/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/L1 10 N/A .58heaters rm 30,31 &corridor

A 100 4 2.5 1.5 0.4 60898 B 32

1/L2 10 N/A 1.15heaters rm 33 &nurse station

A 100 3 2.5 1.5 0.4 60898 B 16

1/L3 10 N/A .58heaters rm 35,36,37& corridor

A 100 5 2.5 1.5 0.4 60898 B 32

2/L1 10 N/A .58heaters rm26,27,28,29 & linen

A 100 5 2.5 1.5 0.4 60898 B 32

2/L2 10 N/A .58heaters rm 34 &lounge

A 100 4 2.5 1.5 0.4 60898 B 32

2/L3 10 N/A .58heaters in dinning rm A 100 4 2.5 1.5 0.4 60898 B 32

3/L1 -Spare -

3/L2 10 N/A .58heaters rm 23,24,25,quite rm & utility rm

A 100 5 2.5 1.5 0.4 60898 B 32

3/L3 10 N/A .58heaters rm 21,22,bath 3, servery &

A 100 5 2.5 1.5 0.4 60898 B 32

4/L1 10 N/A .58heaters rm 32 & daylounge

A 100 4 2.5 1.5 0.4 60898 B 32

4/L2 -Spare -

4/L3 10 N/A .58heaters rm 38,39,40,bath 4 & store

A 100 5 2.5 1.5 0.4 60898 B 32

5/L1 -Spare -

5/L2 10 N/A .58ring sockets rm 33,34 & day rm

A 100 7 2.5 1.5 0.4 60898 B 32

5/L3 10 N/A .58ring sockets rm35,36,27& dinning rm

A 100 10 2.5 1.5 0.4 60898 B 32

6/L1 6 N/A 1.15ring sockets rm26,27,28,29,30,31,32,

A 100 21 2.5 1.5 0.4 60898 B 32

6/L2 6 N/A 1.15ring sockets rm23,24,25, utility rm,

A 100 12 2.5 1.5 0.4 60898 B 32

6/L3 6 N/A 1.15ring sockets rm21,22,28,29,40 &

A 100 12 2.5 1.5 0.4 60898 B 32

7/TP -Spare -

8/TP -Spare -

9/TP 10 N/A .58attic calorifier G C 1 6 SWA 0.4 60898 B 32

10/L1 -Spare -

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 11

Page 10: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

balloch wing sluiceroom 2

Location

DB balloch wingDesignation

DB mains: 3/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

10/L2 6 N/A 3.68lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

10/L3 -Spare -

11/TP -Spare -

12/L1 -Spare -

12/L2 10 N/A 1.84lights wall A 100 6 1.5 1 0.4 60898 B 10

12/L3 -Spare -

13/L1 -Spare -

13/L2 6 N/A 3.68lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

13/L3 10 N/A 3.06heating time clock A 100 1 1.5 1 0.4 60898 B 6

14/L1 -Spare -

14/L2 6 N/A 3.68lights rm 32, sittingrm & wc 6

A 100 7 1.5 1 0.4 60898 B 10

14/L3 10 N/A 3.06timer to de-stratification pumps

A 100 1 1.5 1 0.4 60898 B 6

15/L1 10 N/A 3.06lights rm26,27,28,29,30,31,

A 100 13 1.5 1 0.4 60898 B 6

15/L2 6 N/A 3.68lights rm 33,34, dayrm & nurse station

A 100 10 1.5 1 0.4 60898 B 10

15/L3 10 N/A 3.06lights rm 21,22, bath3, servery, dinning rm

A 100 9 1.5 1 0.4 60898 B 6

16/L1 10 N/A 3.06lights attic A 100 LIM 1.5 1 0.4 60898 B 6

16/L2 10 N/A 3.06lights rm 23,24,25,quite rm, sluice, utility

A 100 12 1.5 1 0.4 60898 B 6

16/L3 10 N/A 3.06lights rm35,36,37,38,39,40,

A 100 16 1.5 1 0.4 60898 B 6

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 12

Page 11: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.05 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/L1 Yes 0.36 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

1/L2 Yes 0.51 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

1/L3 Yes 0.29 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L1 Yes 0.33 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L2 Yes 0.41 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L3 Yes 0.24 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L1 - - -- -- - - - - - - - - No

3/L2 Yes 0.38 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L3 Yes 0.38 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

4/L1 Yes 0.29 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

4/L2 - - -- -- - - - - - - - - No

4/L3 Yes 0.30 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/L1 - - -- -- - - - - - - - - No

5/L2 Yes 0.36 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/L3 Yes 0.27 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L1 Yes 0.73 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L2 Yes 0.54 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L3 Yes 0.44 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/TP - - -- -- - - - - - - - - No

8/TP - - -- -- - - - - - - - - No

9/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L1 - - -- -- - - - - - - - - No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position18 Jul 2015Date of Testing Signature

Page 13

Page 12: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.05 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

10/L2 Yes 1.73 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L3 - - -- -- - - - - - - - - No

11/TP - - -- -- - - - - - - - - No

12/L1 - - -- -- - - - - - - - - No

12/L2 Yes 0.96 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

12/L3 - - -- -- - - - - - - - - No

13/L1 - - -- -- - - - - - - - - No

13/L2 Yes 1.73 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L3 Yes 0.25 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L1 - - -- -- - - - - - - - - No

14/L2 Yes 0.83 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L1 Yes 1.39 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L2 Yes 1.04 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L3 Yes 1.11 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L2 Yes 1.48 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L3 Yes 1.63 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position18 Jul 2015Date of Testing Signature

Page 14

Page 13: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

eastfield wing sluiceroom 1

Location

DB eastfield wingDesignation

DB mains: 1/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/L1 10 N/A .58heaters rm 7,8,9 & 16 A 100 4 2.5 1.5 0.4 60898 B 32

1/L2 10 N/A .58heaters rm 4,5,6,utility rm & nurse

A 100 5 2.5 1.5 0.4 60898 B 32

1/L3 10 N/A .58heaters rm10,11,12,13, linen

A 100 6 2.5 1.5 0.4 60898 B 32

2/L1 10 N/A .58heaters rm 14, bath 2& corridor

A 100 4 2.5 1.5 0.4 60898 B 32

2/L2 10 N/A .58heaters in day rm &lounge

A 100 5 2.5 1.5 0.4 60898 B 32

2/L3 10 N/A .58heaters rm 1,2,3 bath1

A 100 4 2.5 1.5 0.4 60898 B 32

3/L1 10 N/A 1.15heater rm 17 A 100 1 2.5 1.5 0.4 60898 B 16

3/L2 6 N/A 1.15ring sockets rm4,5,6,7,8, dinning rm,

A 100 18 2.5 1.5 0.4 60898 B 32

3/L3 10 N/A .58heater rm 20 A 100 1 2.5 1.5 0.4 60898 B 32

4/L1 10 N/A .58heaters in day rm &quite rm

A 100 6 2.5 1.5 0.4 60898 B 32

4/L2 10 N/A .58heaters rm 18 &dinning rm

A 100 5 2.5 1.5 0.4 60898 B 32

4/L3 10 N/A 1.15heater at rm 4corridor

A 100 5 2.5 1.5 0.4 60898 B 16

5/L1 10 N/A .58ring sockets rm7,8,9,16,17 & corridor

A 100 13 2.5 1.5 0.4 60898 B 32

5/L2 -Spare -

5/L3 -Spare -

6/L1 -Spare -

6/L2 10 N/A .58ring sockets day rm &lounge

A 100 7 2.5 1.5 0.4 60898 B 32

6/L3 6 N/A 1.15ring sockets rm1,2,3,19,20, servery &

A 100 17 2.5 1.5 0.4 60898 B 32

7/L1 10 N/A .58ring sockets rm14,15, day rm, sluice

A 100 11 2.5 1.5 0.4 60898 B 32

7/L2 -Spare -

7/L3 -Spare -

8/L1 -Spare -

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 16

Page 14: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

eastfield wing sluiceroom 1

Location

DB eastfield wingDesignation

DB mains: 1/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

8/L2 -Spare -

8/L3 10 N/A .58ring sockets rm10,11,12,13 & linen

A 100 10 2.5 1.5 0.4 60898 B 32

9/TP 10 N/A .58attic calorifier G C 1 6 SWA 0.4 60898 B 32

10/TP 10 N/A .58attic calorifier G C 1 6 SWA 0.4 60898 B 32

11/L1 -Spare -

11/L2 10 N/A 1.84lights wall A 100 8 1.5 1 0.4 60898 B 10

11/L3 -Spare -

12/L1 -Spare -

12/L2 10 N/A 1.84lights corridor & fireexit

A 100 LIM 1.5 1 0.4 60898 B 10

12/L3 -Spare -

13/L1 -Spare -

13/L2 10 N/A 1.84lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

13/L3 10 N/A 3.06lights rm 10,11,12,13& linen store

A 100 8 1.5 1 0.4 60898 B 6

14/L1 10 N/A 3.06timer for de-stratification pumps

A 100 1 1.5 1 0.4 60898 B 6

14/L2 10 N/A 1.84lights wall A 100 8 1.5 1 0.4 60898 B 10

14/L3 10 N/A 3.06lights attic A 100 LIM 1.5 1 0.4 60898 B 6

15/L1 10 N/A 1.84lights rm 14,15, dayrm, quite rm, wc7 &

A 100 12 1.5 1 0.4 60898 B 10

15/L2 10 N/A 1.84lights day rm, lounge& nurse station

A 100 12 1.5 1 0.4 60898 B 10

15/L3 10 N/A 3.06lights rm 1,2,3,9,20,servery, bath, wc3 &

A 100 10 1.5 1 0.4 60898 B 6

16/L1 10 N/A 1.84lights rm 7,8,9,17,19 A 100 9 1.5 1 0.4 60898 B 10

16/L2 10 N/A 1.84lights rm 4,5,6,8,dinning rm, utility,

A 100 14 1.5 1 0.4 60898 B 10

16/L3 10 N/A 3.06heating time clock A 100 1 1.5 1 0.4 60898 B 6

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 17

Page 15: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.10 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

1.75Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/L1 Yes 0.22 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

1/L2 Yes 0.27 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

1/L3 Yes 0.40 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L1 Yes 0.32 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L2 Yes 0.51 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L3 Yes 0.29 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L1 Yes 0.25 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

3/L2 Yes 0.69 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L3 Yes 0.19 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

4/L1 Yes 0.30 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

4/L2 Yes 0.37 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

4/L3 Yes 0.66 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

5/L1 Yes 0.52 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/L2 - - -- -- - - - - - - - - No

5/L3 - - -- -- - - - - - - - - No

6/L1 - - -- -- - - - - - - - - No

6/L2 Yes 0.39 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L3 Yes 0.83 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/L1 Yes 0.48 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/L2 - - -- -- - - - - - - - - No

7/L3 - - -- -- - - - - - - - - No

8/L1 - - -- -- - - - - - - - - No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position18 Jul 2015Date of Testing Signature

Page 18

Page 16: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.10 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

1.75Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

8/L2 - - -- -- - - - - - - - - No

8/L3 Yes 0.32 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

9/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

11/L1 - - -- -- - - - - - - - - No

11/L2 Yes 1.03 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

11/L3 - - -- -- - - - - - - - - No

12/L1 - - -- -- - - - - - - - - No

12/L2 Yes 1.55 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

12/L3 - - -- -- - - - - - - - - No

13/L1 - - -- -- - - - - - - - - No

13/L2 Yes 1.55 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L3 Yes 1.73 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L2 Yes 1.03 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L1 Yes 1.27 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L2 Yes 1.22 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L3 Yes 1.81 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L1 Yes 0.93 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L2 Yes 1.50 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L3 Yes 0.16 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position18 Jul 2015Date of Testing Signature

Page 19

Page 17: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

hospital wingcloakroom

Location

DB hospital wingDesignation

DB mains: 2/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/L1 10 N/A .58heaters in activity rm,adl rm & bathroom

A 100 4 2.5 1.5 0.4 60898 B 32

1/L2 10 N/A .58heater in activity rm A 100 1 2.5 1.5 0.4 60898 B 32

1/L3 10 N/A .58heaters dinning rm,servery & interview

A 100 5 2.5 1.5 0.4 60898 B 32

2/L1 10 N/A .58heaters in physio rm& office store

A 100 4 2.5 1.5 0.4 60898 B 32

2/L2 10 N/A .58heaters lounge,hairdressers & small

A 100 5 2.5 1.5 0.4 60898 B 32

2/L3 10 N/A .58heaters dinning rm,nurse rm & interview

A 100 5 2.5 1.5 0.4 60898 B 32

3/L1 10 N/A .58ring sockets activityrm & adl rm

A 100 6 2.5 1.5 0.4 60898 B 32

3/L2 6 N/A 1.15ring sockets activityrm, dsr, sluice,

A 100 11 2.5 1.5 0.4 60898 B 32

3/L3 -Spare -

4/L1 -Spare -

4/L2 10 N/A 1.15heaters equipmentrm, preparation &

A 100 4 2.5 1.5 0.4 60898 B 16

4/L3 6 N/A 1.15ring sockets dinningrm, servery, interview

A 100 14 2.5 1.5 0.4 60898 B 32

5/TP 10 N/A .58attic calorifier G C 1 6 SWA 0.4 60898 B 32

6/L1 6 N/A 1.15ring sockets lounge,equipment store,

A 100 13 2.5 1.5 0.4 60898 B 32

6/L2 10 30 .58ring sockets physiooffice & store

A 100 6 2.5 1.5 0.4 60898 B 32

6/L3 -Spare -

7/L1 10 N/A .46ADL cooker A 100 1 10 4 5.0 60898 B 40

7/L2 -Spare -

7/L3 -Spare -

8/TP -Spare -

9/TP -Spare -

10/TP -Spare -

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 21

Page 18: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

hospital wingcloakroom

Location

DB hospital wingDesignation

DB mains: 2/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

11/TP -Spare -

12/L1 -Spare -

12/L2 -Spare -

12/L3 10 N/A 1.84lights corridor A 100 15 1.5 1 0.4 60898 B 10

13/L1 10 N/A 3.06timer to de-stratification pump

A 100 1 1.5 1 0.4 60898 B 6

13/L2 10 N/A 3.06lights attic A 100 LIM 1.5 1 0.4 60898 B 6

13/L3 10 N/A 1.84lights wall A 100 8 1.5 1 0.4 60898 B 10

14/L1 -Spare -

14/L2 10 N/A 1.84lights activity rm A 100 4 1.5 1 0.4 60898 B 10

14/L3 10 N/A 1.84lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

15/L1 10 N/A 1.84lights physio officestore & emg external

A 100 12 1.5 1 0.4 60898 B 10

15/L2 10 N/A 3.06lights equipmentstore, cloakroom, wc,

A 100 6 1.5 1 0.4 60898 B 6

15/L3 10 N/A 3.06lights servery,interview rm, nurse

A 100 9 1.5 1 0.4 60898 B 6

16/L1 10 N/A 3.06lights ADL kitchen-bath-bedroom &

A 100 13 1.5 1 0.4 60898 B 6

16/L2 10 N/A 3.06lights refuse, DSR,hairdressers, lounge

A 100 15 1.5 1 0.4 60898 B 6

16/L3 10 N/A 1.84lights dinning rm A 100 10 1.5 1 0.4 60898 B 10

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 22

Page 19: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.13 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/L1 Yes 0.26 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

1/L2 Yes 0.26 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

1/L3 Yes 0.43 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L1 Yes 0.40 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L2 Yes 0.55 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L3 Yes 0.55 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L1 Yes 0.29 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L2 Yes 0.58 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L3 - - -- -- - - - - - - - - No

4/L1 - - -- -- - - - - - - - - No

4/L2 Yes 0.36 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L3 Yes 0.71 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/TP Yes LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

6/L1 Yes 0.52 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L2 Yes 0.47LIM N/ALIM LIM LIM N/A LIM >500 >500 LIM No

6/L3 - - -- -- - - - - - - - - No

7/L1 Yes 0.26 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

7/L2 - - -- -- - - - - - - - - No

7/L3 - - -- -- - - - - - - - - No

8/TP - - -- -- - - - - - - - - No

9/TP - - -- -- - - - - - - - - No

10/TP - - -- -- - - - - - - - - No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 23

Page 20: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.13 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

11/TP - - -- -- - - - - - - - - No

12/L1 - - -- -- - - - - - - - - No

12/L2 - - -- -- - - - - - - - - No

12/L3 Yes 1.36 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L2 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L3 Yes 1.14 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L1 - - -- -- - - - - - - - - No

14/L2 Yes 0.83 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L3 Yes 1.36 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L1 Yes 1.03 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L2 Yes 0.71 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L3 Yes 1.46 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L1 Yes 1.81 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L2 Yes 1.92 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L3 Yes 1.35 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 24

Page 21: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

laundry roomLocation

DB kitchen & laundryDesignation

DB mains: 6/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/TP 10 N/A .46washing machine D B 1 10 6 5.0 60898 B 40

2/TP 10 N/A .46washing machine D B 1 10 6 5.0 60898 B 40

3/L1 10 N/A .58heaters M/F & staffarea

A 100 5 2.5 1.5 0.4 60898 B 32

3/L2 10 N/A .58heaters managers,admin offices, centre

A 100 7 2.5 1.5 0.4 60898 B 32

3/L3 -Spare -

4/L1 10 30 .58heaters rm 32 & dayrm

A 100 4 2.5 1.5 0.4 60898 B 32

4/L2 6 N/A 1.15boiler kitchen A 100 1 6 2.5 0.4 60898 B 32

4/L3 6 N/A 1.15heaters store, laundrycorridor, visitors rm,

A 100 7 2.5 1.5 0.4 60898 B 32

5/L1 10 N/A .58ring sockets kitchensouth wall

A 100 4 2.5 1.5 0.4 60898 B 32

5/L2 -Spare -

5/L3 10 N/A .58ring sockets laundryrm

A 100 5 2.5 1.5 0.4 60898 B 32

6/L1 6 N/A 1.15ring sockets M/F staffarea, hand driers &

A 100 14 2.5 1.5 0.4 60898 B 32

6/L2 10 N/A .58ring sockets kitchennorth wall

A 100 6 2.5 1.5 0.4 60898 B 32

6/L3 -Spare -

7/L1 10 N/A .58ring sockets kitchenlaundry wall

A 100 3 2.5 1.5 0.4 60898 B 32

7/L2 10 N/A .58ring socketsmanagers, admin

A 100 7 2.5 1.5 0.4 60898 B 32

7/L3 10 N/A .58ring sockets store,small corridor,

A 100 6 2.5 1.5 0.4 60898 B 32

8/L1 10 N/A 1.15fan laundry rm A 100 1 2.5 1.5 0.4 60898 B 16

8/L2 10 N/A .58deep fat firer RHS A 100 1 10 4 0.4 60898 B 32

8/L3 10 N/A .58deep fat firer LHS A 100 1 10 4 0.4 60898 B 32

9/TP 10 N/A .58attic calorifier G C 1 6 SWA 0.4 60898 B 32

10/TP 10 N/A .58attic calorifier G C 1 6 SWA 0.4 60898 B 32

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 26

Page 22: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

laundry roomLocation

DB kitchen & laundryDesignation

DB mains: 6/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

11/TP 10 N/A .92dishwasher G C 1 4 SWA 0.4 60898 B 20

12/TP 10 N/A 1.15iron G C 1 4 SWA 0.4 60898 B 16

13/L1 -Spare -

13/L2 -Spare -

13/L3 10 N/A 3.06lights attic A 100 LIM 1.5 1 0.4 60898 B 6

14/L1 -Spare -

14/L2 -Spare -

14/L3 10 N/A 1.84lights entrancecorridor

A 100 12 1.5 1 0.4 60898 B 10

15/L1 6 N/A 3.68lights male & femalestaff area

A 100 8 1.5 1 0.4 60898 B 10

15/L2 6 N/A 3.68lights kitchen & store A 100 6 1.5 1 0.4 60898 B 10

15/L3 6 N/A 3.68lights visitors rm,waiting area,

A 100 20 1.5 1 0.4 60898 B 10

16/L1 10 N/A 3.06timer for de-stratification pump

A 100 LIM 1.5 1 0.4 60898 B 6

16/L2 6 N/A 3.68lights managers &admin offices

A 100 6 1.5 1 0.4 60898 B 10

16/L3 6 N/A 3.68lights laundry,corridor, wc, store

A 100 8 1.5 1 0.4 60898 B 10

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 27

Page 23: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.06 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

2/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

3/L1 Yes 0.31 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L2 Yes 0.47 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L3 - - -- -- - - - - - - - - No

4/L1 Yes 0.39LIM N/ALIM LIM LIM N/A LIM >500 >500 No

4/L2 Yes 0.26 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L3 Yes 0.64 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/L1 Yes 0.27 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/L2 - - -- -- - - - - - - - - No

5/L3 Yes 0.29 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L1 Yes 0.60 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L2 Yes 0.31 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L3 - - -- -- - - - - - - - - No

7/L1 Yes 0.19 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/L2 Yes 0.52 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/L3 Yes 0.40 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

8/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

8/L2 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

8/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

9/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 28

Page 24: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.06 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

11/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

12/TP Yes 0.22 N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L1 - - -- -- - - - - - - - - No

13/L2 - - -- -- - - - - - - - - No

13/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

14/L1 - - -- -- - - - - - - - - No

14/L2 - - -- -- - - - - - - - - No

14/L3 Yes 1.06 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L1 Yes 0.87 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L2 Yes 1.42 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

15/L3 Yes 1.52 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L2 Yes 1.48 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

16/L3 Yes 1.22 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 29

Page 25: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

dullatur wing sluiceroom 3

Location

DB dullatur wingDesignation

DB mains: 4/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/L1 10 N/A .58heaters rm 53,54,55,linen store & corridor

A 100 5 2.5 1.5 0.4 60898 B 32

1/L2 10 N/A .58heaters rm47,48,49,56 & nurse

A 100 5 2.5 1.5 0.4 60898 B 32

1/L3 10 N/A .58heaters rm 41,42,43& corridor

A 100 5 2.5 1.5 0.4 60898 B 32

2/L1 10 N/A .58heaters day room &quite rm

A 100 4 2.5 1.5 0.4 60898 B 32

2/L2 10 N/A .58heaters day room,nurse station & utility

A 100 5 2.5 1.5 0.4 60898 B 32

2/L3 10 N/A .58heaters rm 59,60,servery & bath 6

A 100 4 2.5 1.5 0.4 60898 B 32

3/L1 10 N/A .58ring sockets rm50,51,52,DSR &

A 100 12 2.5 1.5 0.4 60898 B 32

3/L2 10 N/A .58heaters rm 44,45,46& 58

A 100 5 2.5 1.5 0.4 60898 B 32

3/L3 10 N/A 1.15heaters corridor at rm44

A 100 3 2.5 1.5 0.4 60898 B 16

4/L1 10 N/A .58heaters rm 50,51,52& DSR

A 100 4 2.5 1.5 0.4 60898 B 32

4/L2 10 N/A 1.15heaters rm 57 A 100 1 2.5 1.5 0.4 60898 B 16

4/L3 10 N/A .58heaters dinning rm &bath 6

A 100 5 2.5 1.5 0.4 60898 B 32

5/L1 -Spare -

5/L2 10 N/A .58ring sockets rm 58,utility rm & corridor

A 100 9 2.5 1.5 0.4 60898 B 32

5/L3 10 N/A .58ring sockets dinningrm

A 100 6 2.5 1.5 0.4 60898 B 32

6/L1 6 N/A 1.15ring sockets rm53,54,55, quite rm,

A 100 12 2.5 1.5 0.4 60898 B 32

6/L2 10 N/A .58ring sockets rm47,48,49,56,57,

A 100 16 2.5 1.5 0.4 60898 B 32

6/L3 6 N/A 1.15ring sockets rm41,42,43,59,60,

A 100 12 2.5 1.5 0.4 60898 B 32

7/TP 10 N/A .58attic calorifier G C 1 6 SWA 0.4 60898 B 32

8/L1 -Spare -

8/L2 10 N/A .58ring sockets rm44,45,46 & day rm

A 100 12 2.5 1.5 0.4 60898 B 32

8/L3 10 N/A 3.06lights rm41,42,43,59,60,

A 100 13 1.5 1 0.4 60898 B 6

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 31

Page 26: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

dullatur wing sluiceroom 3

Location

DB dullatur wingDesignation

DB mains: 4/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)200 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

9/L1 10 N/A 1.84lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

9/L2 10 N/A 1.84lights sitting rm &quite rm

A 100 9 1.5 1 0.4 60898 B 10

9/L3 10 N/A 3.06lights dinning rm,bath 5 & small

A 100 11 1.5 1 0.4 60898 B 6

10/L1 10 N/A 1.84lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

10/L2 10 N/A 1.84lights corner day rm& nurse station

A 100 14 1.5 1 0.4 60898 B 10

10/L3 10 N/A 3.06attic lights A 100 LIM 1.5 1 0.4 60898 B 6

11/L1 10 N/A 3.06heating time clock A 100 1 1.5 1 0.4 60898 B 6

11/L2 10 N/A 3.06lights rm 44,45,46,58,wc 6, utility rm &

A 100 13 1.5 1 0.4 60898 B 6

11/L3 -Spare -

12/L1 10 N/A 3.06lights rm50,51,52,53,54,55,

A 100 15 1.5 1 0.4 60898 B 6

12/L2 10 N/A 3.06lights rm47,48,49,56,57

A 100 LIM 1.5 1 0.4 60898 B 6

12/L3 10 N/A 3.06timer to de-stratification pump

A 100 1 1.5 1 0.4 60898 B 6

13/L1 10 N/A 3.06lights wall A 100 8 1.5 1 0.4 60898 B 6

13/L2 -Spare -

13/L3 -Spare -

14/TP -Spare -

15/TP -Spare -

16/TP -Spare -

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 32

Page 27: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.09 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/L1 Yes 0.27 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

1/L2 Yes 0.29 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

1/L3 Yes 0.25 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L1 Yes 0.31 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L2 Yes 0.31 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

2/L3 Yes 0.33 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L1 Yes 0.26 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L2 Yes 0.40 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

3/L3 Yes 0.35 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L1 Yes 0.42 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

4/L2 Yes 0.63 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L3 Yes 0.32 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/L1 - - -- -- - - - - - - - - No

5/L2 Yes 0.51 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

5/L3 Yes 0.27 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L1 Yes 0.63 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L2 Yes 0.57 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L3 Yes 0.74 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/TP LIM LIM N/AN/A LIMN/A N/A LIM N/A LIM >500 >500 N/A N/A No

8/L1 - - -- -- - - - - - - - - No

8/L2 Yes 0.44 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

8/L3 Yes 1.65 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 33

Page 28: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.09 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

9/L1 Yes 1.53 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

9/L2 Yes 0.93 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

9/L3 Yes 1.30 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L1 Yes 1.53 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L2 Yes 1.22 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

11/L1 Yes 0.13 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

11/L2 Yes 1.47 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

11/L3 - - -- -- - - - - - - - - No

12/L1 Yes 1.81 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

12/L2 Yes 1.76 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

12/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L1 Yes 1.17 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

13/L2 - - -- -- - - - - - - - - No

13/L3 - - -- -- - - - - - - - - No

14/TP - - -- -- - - - - - - - - No

15/TP - - -- -- - - - - - - - - No

16/TP - - -- -- - - - - - - - - No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 34

Page 29: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

westerwood corridorcupboard

Location

DB extension ADesignation

DB mains: 7/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)100 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

1/L1 6 N/A 3.68lights lounge &dinning rm 2

A 100 14 1.5 1 0.4 60898 B 10

1/L2 6 N/A 3.68lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

1/L3 6 N/A 3.68lights rm 61,66,68 &assisted bath wc

A 100 11 1.5 1 0.4 60898 B 10

2/L1 6 N/A 3.68lights rm 64,65,67,69 A 100 8 1.5 1 0.4 60898 B 10

2/L2 6 N/A 3.68lights nurse station &corridor cupboard

A 100 9 1.5 1 0.4 60898 B 10

2/L3 6 N/A 3.68lights attic A 100 LIM 1.5 1 0.4 60898 B 10

3/L1 6 N/A 3.68lights rm 78,80, quiterm & treatment rm

A 100 14 1.5 1 0.4 60898 B 10

3/L2 6 N/A 3.68lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

3/L3 6 N/A 3.68lights rm 74,75,76,77 A 100 8 1.5 1 0.4 60898 B 10

4/L1 6 N/A 3.68lights corridor A 100 LIM 1.5 1 0.4 60898 B 10

4/L2 6 N/A 3.68lights rm 62,63 &lounge

A 100 12 1.5 1 0.4 60898 B 10

4/L3 6 N/A 3.68lights rm 79 & sluice A 100 3 1.5 1 0.4 60898 B 10

5/L1 6 N/A 3.68lights rm 70,71,72,73 A 100 8 1.5 1 0.4 60898 B 10

5/L2 6 N/A 3.68lights outside A 100 LIM 1.5 1 0.4 60898 B 10

5/L3 6 N/A 1.15ring sockets rm74,75,76,77, lounge

A 100 16 2.5 1.5 0.4 60898 B 32

6/L1 6 N/A 1.15ring sockets corridor A 100 LIM 2.5 1.5 0.4 60898 B 32

6/L2 6 N/A 1.15ring sockets rm61,62,63,66,68

A 100 10 2.5 1.5 0.4 60898 B 32

6/L3 6 N/A 1.15ring sockets rm64,65,67 & lounge

A 100 12 2.5 1.5 0.4 60898 B 32

7/L1 6 N/A 1.15ring sockets rm69,70,71,72,73

A 100 10 2.5 1.5 0.4 60898 B 32

7/L2 6 N/A 1.15ring sockets rm 79 &nurse station

A 100 6 2.5 1.5 0.4 60898 B 32

7/L3 6 N/A 1.15ring sockets rm78,80, treatment,

A 100 12 2.5 1.5 0.4 60898 B 32

8/L1 6 N/A 1.15sockets attic A 100 LIM 2.5 1.5 0.4 60898 B 32

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 36

Page 30: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Distribution Board Details

westerwood corridorcupboard

Location

DB extension ADesignation

DB mains: 7/TPSupply FromNo of Phases

230Nominal VoltageOvercurrent Protective Device

60947-2Type BS(EN)100 ARating

Associated RCD (if any)N/ABS(EN)N/ANo of PolesN/ARating

CircuitNumber& Phase

Circuit Designation Type ofWiring

ReferenceMethod

No ofPointsServed Live

mm2cpcmm2

MaxPermittedDisconnec

tionTimesSecs

BS(EN) TypeNo

Rating ShortCircuit

Capacity

OpCurrent

MaxPermitted

Zs

Overcurrent Protective Device RCDCircuit Conductors CSA

A kA l∆n Ω

mA

Circuit Details

V

A

8/L2 6 N/A 2.3TV amp A 100 1 2.5 1.5 0.4 60898 B 16

8/L3 6 N/A 1.84sluice A 100 1 2.5 1.5 0.4 60898 B 20

9/L1 6 N/A 1.84sprinkler pump A 100 LIM 2.5 1.5 0.4 60898 B 20

9/L2 6 N/A 3.68fire alarm A 100 1 2.5 1.5 0.4 60898 B 10

9/L3 6 N/A 3.68door holders A 100 1 2.5 1.5 0.4 60898 B 10

10/L1 6 N/A 3.68keypad access A 100 1 2.5 1.5 0.4 60898 B 10

10/L2 6 N/A 3.68door closers A 100 1 2.5 1.5 0.4 60898 B 10

10/L3 6 30 1.84arjo bath far end A 100 1 2.5 1.5 0.4 60898 B 20

11/L1 6 30 1.84arjo bath this end A 100 1 2.5 1.5 0.4 60898 B 20

11/L2 6 N/A 1.84sockets plant rm A 100 3 2.5 1.5 0.4 60898 B 20

11/L3 6 N/A 3.68nurse call A 100 1 2.5 1.5 0.4 60898 B 10

12/L1 6 N/A 1.84sewerage plant G C 1 4 4 0.4 60898 B 20

12/L2 -Spare -

12/L3 -Spare -

Copyright. Key Electrical Solutions Limited. 2014

Wiring Codes

A

PVC / PVCCables

B

PVC Cables inMetallic Conduit

C

PVC Cables inNon-Metallic

Conduit

D

PVC Cables inMetallicTrunking

E

PVC Cables inNon-Metallic

Trunking

F

PVC / SWACables

G

XLPE / SWACables

H

MineralInsulatedCables

O

Other

Page 37

Page 31: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.07 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

1/L1 Yes 2.13 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

1/L2 Yes 2.33 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

1/L3 Yes 1.91 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

2/L1 Yes 1.88 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

2/L2 Yes 1.51 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

2/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

3/L1 Yes 1.37 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

3/L2 Yes 2.13 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

3/L3 Yes 1.44 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L1 Yes 2.13 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L2 Yes 1.53 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

4/L3 Yes 1.11 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

5/L1 Yes 1.29 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

5/L2 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

5/L3 Yes 0.95 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L1 Yes 0.81 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L2 Yes 0.71 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

6/L3 Yes 0.59 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/L1 Yes 0.78 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/L2 Yes 0.55 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

7/L3 Yes 0.46 N/ALIM N/ALIM LIM LIM N/A LIM >500 >500 N/A N/A No

8/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A Yes

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 38

Page 32: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

0.07 Ω

Distribution Board Tests

Max MeasuredLoop Impedance Zs

Prospective FaultCurrent ipf

CircuitNumber& Phase

r1 (Line)

Final Ring CircuitsMeasured (end to end)

SupplyPolarity

Confirmed

YesConfirmation ofSupply Polarity

101330570Insulation Resistance101330570Continuity101330570RCD101330570Multi-Function

Circuit Impedances Ω

rn (Neutral) r2 (cpc)

All Circuits(At Least 1 column to

be completed)

(R1 + R2) (R2)

MaximumMeasuredEarth Fault

LoopImpedance

Atl ∆ n

Insulation Resistance

Ω

Live /Live

Live /Neutral

Live /Earth

Earth /Neutral

MΩ MΩ MΩ MΩ ms

TestButton

Operation

ms

At5l ∆ n

RemarksRCD Operating Times

Circuit Tests

101330570Loop Impedance

Test Instruments Used (Serial Numbers)

Other

Operating Times of Assocaited RCD (if any)N/AAt l ∆ nN/AAt 5l ∆ n

msms

8/L2 Yes 0.16 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

8/L3 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

9/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

9/L2 Yes 0.31 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

9/L3 Yes 0.16 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L1 Yes 0.17 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L2 Yes 0.16 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

10/L3 LIM LIMN/A N/AN/A N/A LIM N/A LIM >500 >500 LIM No

11/L1 LIM LIMN/A N/AN/A N/A LIM N/A LIM >500 >500 LIM No

11/L2 Yes 0.16 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

11/L3 Yes 0.16 N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

12/L1 LIM LIM N/AN/A N/AN/A N/A LIM N/A LIM >500 >500 N/A N/A No

12/L2 - - -- -- - - - - - - - - No

12/L3 - - -- -- - - - - - - - - No

Copyright. Key Electrical Solutions Limited. 2014

Lloyd ReillyName

Tested by

Engineer

Position19 Jul 2015Date of Testing Signature

Page 39

Page 33: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Appendix C - Agreed Limitations

Item Limitation including the Reason

1 As the main protective devices were sealed during the inspection they could not be verified.

2 As the main earth conductor could not be disconnected it was not possible to measure the Ze for the installation. An installation Zs and PFChave therefore been measured at the nearest possible point to the origin of the installation.

3 All insulation resistance tests to lighting and unverified circuits have been carried out using regulation 612.3.3 to ensure no damage tosensitive or electronic equipment and lighting.

4 All high level and in-accessible termination points have been tested to the furthest possible available point.

Copyright. Key Electrical Solutions Limited. 2014 Page 41

Page 34: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Appendix K - Photographic Record (Faults)

No RCD present for socket likely to supplyequipment outdoors

6297/DB extension A - C2

No RCD present for socket likely to supplyequipment outdoors

6297/DB balloch wing - C2

No RCD present for socket likely to supplyequipment outdoors

6297/DB eastfield wing - C2

No RCD present for socket likely to supplyequipment outdoors

6297/DB eastfield wing - C2

No RCD present for socket likely to supplyequipment outdoors

6297/DB kitchen & laundry - C2

Copyright. Key Electrical Solutions Limited. 2014 Page 44

Page 35: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Appendix G - Observations

DB extension A: 8/L1 Code

C2Overrated Cable6297/DB extension A:8/L1 (A)DB mains: 1/TP Code

C2Overrated Cable6297/DB mains: 1/TP (A)

DB mains: 2/TP Code

C2Overrated Cable6297/DB mains: 2/TP (A)

DB mains: 3/TP Code

C2Overrated Cable6297/DB mains: 3/TP (A)

DB mains: 4/TP Code

C2Overrated Cable6297/DB mains: 4/TP (A)

DB mains: 5/L3 Code

C2Overrated Cable6297/DB mains: 5/L3 (A)

DB mains: 6/TP Code

C2Overrated Cable6297/DB mains: 6/TP (A)

Copyright. Key Electrical Solutions Limited. 2014 Page 44

Page 36: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Appendix H - Photographic Record (Distribution Boards)

6297/DB balloch wing 6297/DB balloch wingNormal Thermal

6297/DB dullatur wing 6297/DB dullatur wingNormal Thermal

6297/DB eastfield wing 6297/DB eastfield wingNormal Thermal

6297/DB extension A 6297/DB extension ANormal Thermal

Copyright. Key Electrical Solutions Limited. 2014 Page 45

Page 37: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

Appendix H - Photographic Record (Distribution Boards)

6297/DB external lighting via contractor 6297/DB external lighting via contractorNormal Thermal

6297/DB hospital wing 6297/DB hospital wingNormal Thermal

6297/DB kitchen & laundry 6297/DB kitchen & laundryNormal Thermal

6297/DB mains 6297/DB mainsNormal Thermal

Copyright. Key Electrical Solutions Limited. 2014 Page 46

Page 38: ELECTRICAL INSTALLATION CONDITION REPORT: 6297upload.directaudits.com/UploadedDocs/141/5343/5343... · 2015-08-19 · ELECTRICAL INSTALLATION CONDITION REPORT: 6297 Mitie FSHC A

ELECTRICAL INSTALLATIONCONDITION REPORT: 6297

CONDITION REPORT: Guidance Notes for Recipients

This report is an important and valuable document which should be retained for future reference.

1. The purpose of this Condition Report is to confirm, so far as reasonably practicable, whether or not the electrical installation is in asatisfactory condition for continued service (see Section E). The Report should identify any damage, deterioration, defects and/orconditions which may give rise to danger (see Section K).

2. The person ordering the Report should have received the original Report and the inspector should have retained a duplicate.

3. The original Report should be retained in a safe place and be made available to any person inspecting or undertaking work on theelectrical installation in the future. If the property is vacated, this Report will provide the new owner /occupier with details of thecondition of the electrical installation at the time the Report was issued.

4. Where the installation incorporates residual current devices (RCD) there should be a notice at or near the device stating that it shouldbe tested quarterly. For safety reasons it is important that this instruction is followed.

5. Section D (Extent and Limitations) should identify fully the extent of the installation covered by this Report and any limitations on theinspection and testing. The inspector should have agreed these aspects with the person ordering the Report and with other interestedparties (licensing authority, insurance company, mortgage provider and the like) before the inspection was carried out.

6. Some operational limitations such as such as inability to gain access to parts of the installation or an item of equipment may have beenencountered during the inspection. The inspector should have noted these in Section D.

7. For items classified in Section K as C1 (“Danger Present”), the safety of those using the installation is at risk, and it is recommendedthat a competent person undertakes the necessary remedial work immediately.

8. For items classified in Section K as C2 (“Potentially Dangerous”), the safety of those using the installation may be at risk and it isrecommended that a competent person undertakes the necessary remedial work as a matter of urgency.

9. Where it has been stated in Section K that an observation requires further investigation the inspection has revealed an apparentdeficiency which could not, due to the extent or limitations of this inspection, be fully identified. Such observations should beinvestigated as soon as possible. A further examination of the installation will be necessary, to determine the nature and extent of theapparent deficiency (see Section F).

10. For safety reasons, the electrical installation should be re-inspected at appropriate intervals by a competent person. The recommendeddate by which the next inspection is due is stated in Section F of the Report under ‘Recommendations’ and on a label at or near to theconsumer unit / distribution board.

Copyright. Key Electrical Solutions Limited. 2014 Page 48