DESCRIPTION SYMBOL POWER DEVICES DESCRIPTION SYMBOL DISTRIBUTION & EQUIPMENT DESCRIPTION SYMBOL LIGHTING DESCRIPTION SYMBOL SWITCHING CONTROLS DESCRIPTION SYMBOL DIAGRAMS DESCRIPTION SYMBOL SIGNAL DEVICES DESCRIPTION SYMBOL REFERENCE SYMBOLS DESCRIPTION SYMBOL WIRING DESCRIPTION SYMBOL SECURITY SYSTEM DESCRIPTION SYMBOL FIRE ALARM SYSTEM DESCRIPTION SYMBOL GROUNDING SYSTEM ABBREVIATIONS ELECTRICAL DESIGN CRITERIA ELECTRICAL DRAWING LIST ELECTRICAL EQUIPMENT NAMING CONVENTION LEGEND ELECTRICAL LEGEND ELECTRICAL BASIS OF DESIGN ELECTRICAL ADD ALTERNATES P 15 30 15 15 R/C,F,R P,B,R,C D DETAILS APPLY TO ALL APPLICABLE SITUATIONS, UON. NOT ALL DETAIL REFERENCES ARE SHOWN. ALL REFER TO DETAIL NO. ON DRAWING INDICATED MECHANICAL EQUIPMENT IDENTIFICATION TAG TYPE; REFER TO BRANCH CIRCUIT AND FEEDER SHEET NOTE REFERENCE ELEVATION TAG: REFER TO ELEVATION NUMBER ON DRAWING INDICATED DRAWING INDICATED SECTION TAG: REFER TO SECTION NUMBER ON KITCHEN EQUIPMENT REFERENCE, REFER TO KITCHEN EQUIPMENT SCHEDULE BRANCH CIRCUIT OR FEEDER NOMINAL AMPACITY & SCHEDULES FOR WIRE AND CONDUIT SIZES & QTY. EQUIPMENT BY OTHERS IDENTIFICATION TAG INCLUDES ALL PIPING BY DIV. 16. EARLY WARNING SMOKE DETECTION SYSTEM - HORN - CEILING, WALL MOUNTED FLAME DETECTOR (FLICKER DETECTOR) LIGHT (LAMP, SIGNAL LIGHT, INDICATOR LAMP, STROBE) FIREMAN'S PHONE JACK, WALL MOUNTED END OF LINE RESISTOR (NOT SHOWN ON PLANS) ADDRESSABLE MONITOR MODULE ADDRESSABLE CONTROL MODULE RISE AND FIXED TEMPERATURE TYPE, UON. SPRINKLER VALVE TAMPER SWITCH CONNECTION (# = CANDELA RATING) STROBE LIGHT - WALL, CEILING MOUNTED SPEAKER - WALL, CEILING MOUNTED ALARM BELL OR GONG WALL MOUNTED FIRE ALARM SYSTEM ANNUNCIATOR COMBINATION SPEAKER/STROBE, WALL MOUNTED FIRE ALARM SYSTEM MANUAL PULL STATION, (# = CANDELA RATING) SPRINKLER FLOW SWITCH CONNECTION RECEIVER, BT=BEAM TRANSMITTER) WIDTH SAMPLING TUBES. PHOTOELECTRIC TYPE LIGHT BEAM TYPE SMOKE DETECTOR (BR=BEAM HEAT DETECTOR, CEILING MOUNTED. RATE OF FIREMAN'S PHONE HANDSET, WALL MOUNTED FIRE ALARM OUTPUT OR RELEASE ABORT PUSHBUTTON, REFER TO SPECIFICATIONS AND COMPONENTS. PROVIDE 120V POWER AS REQUIRED FIRE ALARM CONTROL PANEL AND ASSOCIATED OR AS INDICATED. SMOKE DETECTOR, DUCT MOUNTED, WITH FULL MINI HORN - WALL, CEILING MOUNTED DETAILS. UON. SMOKE DETECTOR, LOW AIR VELOCITY IN DUCT MOUNTED PHOTOELECTRIC TYPE U.O.N. SMOKE DETECTOR MOUNTED BELOW RAISED FLOOR DATA LOOP ISOLATION MODULE COMBINATION HORN/STROBE - WALL, CEILING MOUNTED (# = CANDELA RATING) COMBINATION MINI HORN/STROBE - WALL, CEILING MOUNTED (# = CANDELA RATING) HEAT DETECTOR (R/C=RATE OF COMBUSTION, F=FIXED TEMP. ONLY, R=RATE OF RISE ONLY) AGENT RELEASE INITIATING VALVE BELL SILENCE SWITCH AGENT DISCHARGE SWITCH ELECTROMAGNETIC DOOR HOLDER - WALL, FLOOR, DOOR CLOSURE MOUNTED. PROVIDED BY DIV. 8 UON. SMOKE DETECTOR - WALL, CEILING MOUNTED (P=PLENUM MOUNTED, B=W/RELAY BASE, R=ELEVATOR RECALL, C=INTEGRAL TO DOOR CLOSURE) FIRE/SMOKE DAMPER BY DIV 15. WIDTH OF SYMBOL WILL VARY WITH DUCT WIDTH. PROVIDE POWER AND MONITORING AS INDICATED. GROUND ROD LOCATION 24" GROUND BAR LIGHTNING PROTECTION CONDUCTOR ROUTED DOWN 60" GROUND BAR LIGHTNING PROTECTION BIMETAL CONNECTION LIGHTNING PROTECTION BOND PLATE GROUND GRID BOND POINT LIGHTNING PROTECTION AIR TERMINAL GROUND ROD IN TEST WELL GROUND GRID BOND POINT - MECHANICAL CONNECTION GROUND GRID BOND POINT - EXOTHERMIC WELD CONNECTION LIGHTNING PROTECTION PARAPET MOUNTED AIR TERMINAL LIGHTNING PROTECTION MID ROOF MOUNTED AIR TERMINAL BARE GROUNDING GRID OR CONDUCTORS, UON. GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZED CONDUIT, UON. WW DIRECTION WW DIRECTION A 1 L H XFR- A 1 H M MCC- DP- U L D 1 A A 1 SN H M SWBD- EXAMPLES / LEGEND EQUIPMENT TYPE POWER SYSTEM PNL- E H K 2 B NOT ALL SYMBOLS, ABBREV., ETC. ARE NECESSARILY USED ON THIS PROJECT REFER TO DETAILS FOR MOUNTING HEIGHTS OF DEVICES BUSWAY RISER DAMPER MOTOR MAGNETIC MOTOR STARTER (CONTROLLER) WITH CODE CLEARANCES SHOWN SHOWN SIZE PER CONNECTED MOTOR SIZE AND CONNECTION TO MOTOR PROVIDED BY OTHERS SERVICE AND/OR DISTRIBUTION EQUIPMENT TRANSFORMER WITH CODE CLEARANCES SHOWN SHOWN, DASHED EQUIP. = FUTURE BRANCH CIRCUIT PANELBOARDS, SURFACE AND MOTOR CONTROL CENTER W/ CODE CLEARANCES BUILDING GROUND BUS, SEE DETAILS FUSE PER MANUFACTURER'S RECOMMENDATIONS SURFACE AND RECESS MOUNTED EQUIPMENT OR TERMINAL ENCLOSURE AS NOTED, FREQUENCY DRIVE WITH INTEGRAL DISCONNECT FUSED DISCONNECT SWITCH, SIZE AS NOTED. SIZE RECESS MOUNTED (CONTROLLER) OR CONTACTOR. SIZE PER ENCLOSED CIRCUIT BREAKER DISCONNECT SWITCH, TRIP SIZE AS NOTED. DISCONNECT SWITCH, SIZE AS NOTED OR IF NOT MOTOR DISCONNECT SCHEDULE CONNECTION TO DIV. 15 FURNISHED VARIABLE DIV. 16 TO INSTALL VFD EQUIPMENT INTEGRAL DISCONNECT THAT IS PROVIDED BY DIV. 16 CONNECTION TO EQUIPMENT PROVIDED BY OTHERS. SHADED = ON ALT. POWER SOURCE NOTED DIV. 16 CONNECTION TO EQUIPMENT WITH BUSWAY STAB-IN TYPE CIRCUIT BREAKER OR FUSE DISCONNECT. SIZE AS NOTED. OTHERS. SHADED = ON ALT. POWER SOURCE NOTED DISCONNECT W/ MAGNETIC MOTOR STARTER LOAD SERVED. NEMA SIZE #1 MINIMUM. OR CONTACTOR. SIZE PER LOAD SERVED. NEMA SIZE #1 MINIMUM. "ON ALT." AB STANDBY, UPS, ETC.) PER CIRCUITING INDICATED SHADED RECEPTACLES NOTED "ON ALT." ABOVE ARE IN RAISED FLOOR - SEE ARCH DWGS; WITH SIMPLEX RECEPTACLE - WALL, CEILING, ON ALT. DUPLEX RECEPTACLE - WALL, CEILING, ON ALT. DOUBLE DUPLEX RECEPTACLE - WALL, CLG, ON ALT. DUPLEX RECEPTACLE - WALL - HALF SWITCHED ON ALT. POWER; NEMA CONFIGURATION AS NOTED FLUSH FLOOR BOX DEVICE - DEVICE TYPE PER SYMBOLS ABOVE PEDESTAL FLOOR DEVICE - DEVICE TYPE PER SYMBOLS ABOVE TELE/POWER POLE, POWER POLE RECEPTACLE TYPE SHOWN -WALL -ABOVE COUNTER BACKSPLASH. SEE ARCHITECTURAL DRAWINGS. FLUSH, PEDESTAL MOUNTED. NEUTRAL, 1 ISOLATED GROUND) NEUTRALS POKE THRU UNIT WITH DUPLEX RECEPTACLE - ELECTRIFIED FURNITURE. PROVIDE 8 WIRES (4 HOTS, 1 DEDICATED NEUTRAL, 1 COMMON RECEPT. TYPE SHOWN AT SPECIAL HEIGHT +42" CLOCK HANGER RECEPTACLE TWO-PIECE SURFACE METAL RACEWAY WITH RECEPTACLES AS NOTED, LENGTH AS FITTINGS AS REQUIRED. CONNECTED TO ALTERNATE POWER SOURCE (EMERG., L5-15R COMBINATION SWITCH/DUPLEX RECEPTACLE GFI DUPLEX RECEPTACLE - WALL - WITH INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER WP RECEPT. TYPE SHOWN W/ WEATHERPROOF COVER SPECIAL PURPOSE RECEPTACLE -WALL, CEILING WALL MOUNTED ELECTRICAL CONNECTION TO TO BE #10 AWG. USE LIQUID-TIGHT FLEX. INDICATED ON THE DRAWINGS AND WITH ALL INDICATED, LENGTH AS INDICATED ON THE DRAWINGS. PROVIDE ALL FITTINGS AS RACEWAY WITH RECEPTACLES AND OUTLETS AS TWO OR THREE COMPARTMENT SURFACE METAL REQUIRED. POKE THRU UNIT WITH DOUBLE DUPLEX RECEPTACLE - FLUSH, PEDESTAL MOUNTED. POKE THRU UNIT WITH JUNCTION BOX. RACEWAY COMPONENTS RC-700 SERIES. COMBO POKE THRU UNIT WITH DUPLEX RECEPTACLE AND TELEPHONE OUTLET - FLUSH, MULTI-SERVICE FLOOR BOX CAST IN CONC. OR RECEPTACLES & SIGNAL OUTLETS AS NOTED. PEDESTAL MOUNTED. TELE/POWER POLE WITH WHIP CONNECTION TO ELECTRIFIED FURNITURE AND INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER CCTV SECURITY PAN/TILT/ZOOM CAMERA CCTV SECURITY INDOOR DOME CAMERA CARD READER- WALL MOUNTED/MULLION MOUNTED REQUEST TO EXIT DEVICE WALL,MULLION MOUNTED M INTELLIGENT CARD READER INTERFACE ROLL-UP DOOR MOTOR CONTROL OUTPUT LOCAL DOOR MONITOR WARNING NOISE DEVICE DURESS PUSHBUTTON STATION DOOR POSITION MONITOR SWITCH ELECTRIC STRIKE ELECTRIC LOCK/LATCH ELECTRIC BOLT SECURITY ELECTRONIC MOTION SENSOR CCTV SECURITY FIXED CAMERA - WALL,CEILING EMERGENCY DOOR RELEASE BREAK-GLASS STATION M = MASTER STATION INTERCOM STATION - WALL, DESK MOUNTED. MAGNETIC LOCK ELECTRIC POWER TRANSFER HINGE GLASS BREAK SENSOR SWBD - SWITCHBOARD U - UNINTERRUPTIBLE POWER (UPS) UTX - UTILITY MAIN TRANSFORMER BIATS - BYPASS ISOLATION ATS MCC - MOTOR CONTROL CENTER XFR - TRANSFORMER DSW - NON-FUSED DISCONNECT SW. MTS - MANUAL TRANSFER SWITCH CB - ENCLOSED CIRCUIT BREAKER FSW - FUSED DISCONNECT SWITCH TYPE PNL - BRANCH PANEL DP - DISTRIBUTION PANEL SUB - UNIT SUBSTATION C - CRITICAL POWER (Hospital) M - MAIN UTILITY SERVICE EM - EMERGENCY POWER (Life Safety) S - STANDBY POWER LETTERS SEQ. EQUIP. DESIG. SYSTEM POWER SYSTEM VOLTAGE DESIG. ADDN'L FLOOR Q - EQUIPMENT POWER (Hospital) S - LIFE SAFETY POWER (Hospital) BLANK - NORMAL LOADS ATS - AUTOMATIC TRANSFER SWITCH SWGR - SWITCHGEAR D INTEGRAL AMMETER DISPLAY CONNECTION TO DIV. 15 CHILLER CAPACITOR, POWER FACTOR CORRECTION, SIZE KEY INTERLOCK MONITORING COMMUNICATION MODULE SHUNT TRIP UNIT, 120VAC OR VOLTAGE AS NOTED GROUND FAULT TRIP UNIT DRAWOUT CIRCUIT BREAKER INDIVIDUALLY MOUNTED CIRCUIT BREAKER FUSED SWITCH, WITH FUSE AND SWITCH AMPERE RATING CIRCUIT BREAKER, WITH TRIP & FRAME AMPERE GROUNDED WYE CONNECTION DELTA CONNECTION LED INDICATOR LIGHT, PUSH TO TEST, R=RED TERMINAL FOR FIELD CONNECT, SIZE & TYPE CURRENT TRANSFORMER SHORTING TERMINAL BLOCK. INSTALLED. SQUARE = REMOTE MOUNTED UTILITY CO. APPROVED SOCKET WITH METER METER: KILOWATT HOUR METER: POWER FACTOR FUSED VOLTAGE SENSE LEADS NORMALLY CLOSED PUSH BUTTON CURRENT TRANSFORMER CLASS I = INTERMEDIATE CLASS CONTACTOR COIL PIPE GROUND BATTERY GENERAL CONTACTS OVERLOADS TO DESTINATION SHOWN, U.O.N. HAND/OFF/AUTO SWITCH BUS DUCT IN KVAR MECHANICAL INTERLOCK TRANSIENT VOLTAGE SURGE SUPPRESSOR DIGITAL METER UNIT. REFER FUSE, HOLDER & PULLER 10 CIRCUIT BREAKER, MEDIUM VOLTAGE, DRAWOUT SOLENOID 400AS 225AF G= GREEN, B= BLUE, Y= YELLOW, W= WHITE SUITABLE FOR CONDUCTOR INSTALLED. 225AF 100AT POTENTIAL TRANSFORMER BELL ALARM TRIP MODULE CONTACTS BUS BAR LIGHTNING SURGE ARRESTOR D= DISTRIBUTION RELAY COIL GENERATOR NORMALLY OPEN CONTACTOR OR RELAY CONTACTS RATING NORMALLY OPEN PUSH BUTTON CONNECTION TO GROUND TO SPECIFICATIONS. FIELD INSTALLED CONTROL CIRCUIT WIRING SWITCH RESISTOR CONNECTOR, FEMALE AND MALE RESPECTIVELY NORMALLY CLOSED CONTACTOR OR RELAY IN PANEL AND BRANCH CIRCUIT SCHEDULES TO STROKES INDICATE QUANTITY OF #12 AWG. 20A BRANCH CIRCUITS ARE NOT SHOWN ON PROVIDE REQUIRED CIRCUITING. CONDUCTORS, UON. NOTE: WIRING STROKES FOR DRAWINGS. CONTRACTOR SHALL USE INFORMATION G T MV MEDIUM VOLTAGE CONDUIT BARE GROUNDING GRID OR CONDUCTORS, UON. TELEPHONE SYSTEM CONDUIT GC GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZED CONDUIT, UON. SHADED= ON ALT. POWER SOURCE (EMERG,UPS,ETC.) WIRE IN EXPOSED OR "HARD" CEILING AREAS. JUNCTION BOXES, WALL, CEILING AND FLUSH FLOOR BRANCH CIRCUIT SCHEDULES. HOME RUN WIRING TO INDICATED DESTINATION, HD1A SCHEDULES AND INFORMATION IN THE FEEDER AND SHALL USE CIRCUIT SIZES NOTED IN RESPECTIVE INSTALLER(S) PRIOR TO ROUGH-IN. SIDES. TERMINATE WITH BUSHINGS. (1) 1.25" CO PULL BOX, MIN. SIZE PER NEC., UON. NEUTRAL CONDUIT RUN TURNED UP THROUGH FLOOR OR CEILING. CORE & FIREPROOF AS REQUIRED. CONDUIT STUBBED OUT AT LOCATION SHOWN. PROVIDE INSULATED BUSHING & PULLROPE. TELEPHONE/DATA SLEEVE THROUGH WALL, ABOVE UON. COORDINATE LOCATIONS WITH CABLE WIRING EXTENSION POINT - CONDUIT TO MC CABLE UNDERFLOOR RACEWAY FLEXIBLE CONDUIT CONNECTION GROUND HOT CEILING. CORE & FIREPROOF AS REQUIRED. CONDUIT RUN TURNED DOWN THROUGH FLOOR OR CEILING. EXTEND TO ACCESSIBLE TILE CLG. BOTH OR MANUFACTURED WIRING SYSTEM J-BOX ABOVE MOUNTED. 4" SQ. BOX MIN., LARGER IF REQUIRED ACCESSIBLE CEILINGS AREAS, OR EXTEND CONDUIT & POWER CONNECTION TO DIV 15 FIRE/SMOKE DAMPER. REFER TO FSD CONNECTION DETAIL IF NOT SHOWN L1A-1,3 3/4"C. MIN. OR AS OTHERWISE NOTED. CONTRACTOR ASSISTIVE LISTENING INFRARED TRANSMITTER PANEL, AV INPUT OUTLET, 1"C WITH 3-GANG BOX. CONDUIT SURFACE, RECESSED MOUNTED SIGNAL SYSTEM EQUIPMENT ENCLOSURES AS NOTED- ACCESSIBLE TILE CEILING. 1"C WITH 2-GANG BOX. CONDUIT STUBBED ABOVE STUBBED ABOVE ACCESSIBLE TILE CEILING. MOUNTING HEIGHT PER MOUNTING HT. DETAIL TELEPHONE OUTLET - WALL, W = USE HIGHER W SHOWN, FIRE TREATED. TERMINAL/MOUNTING BOARD, 8' HIGH X WIDTH AS CHIME BUZZER BELL COMBO TELEPHONE/DATA OUTLET - WALL DATA OUTLET - WALL DUAL COIL SPEAKER - SURFACE CEILING, PAGING SYSTEM HORN (OUTDOOR) SPEAKER - WALL, CEILING VOLUME CONTROL - WALL SYSTEM CLOCK - WALL , CEILING SYMBOLS ABOVE PEDESTAL FLOOR DEVICE - DEVICE TYPE PER SYMBOLS ABOVE FLUSH FLOOR DEVICE - DEVICE TYPE PER RECESSED CEILING. PAGING OR PAGING/SOUND MASKING SPEAKER, MOUNTED ABOVE ACOUSTIC TILE CEILING. INDICATED. SEE RISER DIAGRAM. PROVIDE 120V POWER AS REQUIRED OR AS RF COAX CABLE DISTRIBUTION AMPLIFIER. PUSHBUTTON OR PUSHBUTTONS RF COAX CABLE OUTLET (TV, VCR, ETC.) RF COAX CABLE SIGNAL SPLITTER INTERCOM STATION - WALL, DESK M = MASTER STATION M MICROPHONE JACK - WALL, FLOOR COMBINATION RF COAX CABLE AND DATA OUTLET MOUNTED CORRIDOR/AISLE OCCUPANCY SENSOR - CEILING 360 DEGREE OCCUPANCY SENSOR - CEILING MTD. 180 DEGREE OCCUPANCY SENSOR - CEILING MTD. OCCUPANCY SENSOR - WALL MOUNTED PUSHBUTTON OR PUSHBUTTONS, BY DIV. 16 REMOTE MOUNTED LINE TO LOW-VOLTAGE FUSED TRANSFORMER. CONCEAL FROM VIEW. COMPONENTS. PROVIDE 120V OR 277V CONTROL POWER AS REQUIRED OR AS INDICATED. LIGHTING CONTROL PANEL AND ASSOCIATED SINGLE POLE SWITCH (SUPERSCRIPT DENOTES SIMILARLY MARKED LUMINAIRES CONTROLLED TOGETHER) TWO POLE SWITCH PHOTOCELL TIME CLOCK PROVIDED WITH EQUIPMENT, INSTALLED AND THERMOSTAT - WALL, CEILING. PROVIDED BY DIV. 15, INSTALLED AND WIRED BY DIV. 16 EQUIPMENT OPERATOR PUSH BUTTON STATION. CONNECTED BY DIV. 16, UON. EMERGENCY POWER OFF, HEAVY-DUTY, OIL-TIGHT RED MUSHROOM-HEAD PUSHBUTTON W/ GUARD. LIGHTING CONTROL OVERIDE SWITCH, SEQ. NUMBER LINE VOLTAGE, VARIABLE SPEED FAN CONTROL DIMMER SWITCH. NUMBER INDICATES WATTAGE RATING. IF NOT SHOWN THEN EQUAL TO LOAD. SWITCH, PROVIDED BY DIV. 15, INSTALLED BY DIV. 16. LOCATE ADJACENT TO ADJACENT SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN MOTOR-RATED THERMAL OVERLOAD SWITCH EXPLOSION PROOF SWITCH SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN DIMMER SWITCH UNDER SEPARATE COVERPLATE SWITCH IS "OFF"). TO LIGHT SWITCHES. WEATHERPROOF SWITCH TIMER SWITCH SWITCH IS "ON"). KEY OPERATED SWITCH FOUR WAY SWITCH THREE WAY SWITCH LOW VOLTAGE MOMENTARY CONTACT SWITCH, UPPER CASE LETTER SUPERSCRIPT INDICATES CONNECTION TO LOW VOLTAGE RELAY CONTROLLING SIMILARLY MARKED LUMINAIRES. BASKET TYPE CABLE TRAY WITH 90 DEGREE ELBOW SHOWN LADDER TYPE CABLE TRAY WITH 90 DEGREE ELBOW SHOWN G GC 1. OREGON ELECTRICAL SPECIALTY CODE (OREGON AMENDED VERSION OF 2014 NATIONAL ELECTRIC CODE) . 2. FIRE/LIFE SAFETY CODE: 2007 IFC WITH OREGON AMMENDMENTS . 3. 2010 STATE OF OREGON STRUCTURAL SPECIALTY CODE: OREGON AMMENDED VERSION OF 2009 IBC . 4. AMERICANS WITH DISABILITIES ACT, (ADA) . COMBINATION OCCUPANCY SENSOR & SWITCH GANGED UNDER A COMMON COVER PLATE. OCCUPANY SENSOR TO CONTROL ALL LUMINAIRES IN ROOM WITH 1/2 LIGHT REDUCTION CONTROLLED BY SWITCH, DESIGNATED BY LETTER. 2-GANG BOX WITH SINGLE-GANG MUDRING, UON SPECIFIED 3c 3A RECESSED 2X4 LUMINAIRE SURFACE MOUNTED 2X4 LUMINAIRE RECESSED 1X4 LUMINAIRE SURFACE MOUNTED 1X4 LUMINAIRE RECESSED 2X2 LUMINAIRE SURFACE MOUNTED 2X2 LUMINAIRE SHADING OF ANY LUMINAIRE INDICATES CONNECTION TO ALTERNATE POWER SOURCE (EMERGENCY, UPS, STANDBY, ETC.) PER CIRCUITING INDICATED SUSPENDED LINEAR LUMINAIRE (SIZE VARIES) WALL MOUNTED LINEAR LUMINAIRE (SIZE VARIES) SUSPENDED PENDANT LUMINAIRE (SIZE VARIES) RECESSED DOWNLIGHT, CEILING MOUNTED SURFACE DOWNLIGHT, CEILING MOUNTED RECESSED WALLWASH SURFACE WALLWASH RECESSED LINEAR WALLWASH SURFACE LINEAR WALLWASH RECESSED WALL MOUNTED LUMINAIRE TRACK LIGHTING WITH HEADS AS INDICATED. RECESSED CEILING ADJUSTABLE POINT SOURCE SURFACE CEILING ADJUSTABLE POINT SOURCE WALL MOUNTED LUMINAIRE WALL MOUNTED DIRECTIONAL (SIZE VARIES) FLUORESCENT STRIPLIGHT - POWER FEED SECTION, FEED THROUGH SECTION. LENGTH AS SHOWN. WALL MOUNTED FLUORESCENT STRIPLIGHT UNDERCABINET FLUORESCENT STRIPLIGHT CONTINUOUS LINEAR SOURCE (LED, COLD CATHODE, NEON, FIBER OPTIC, ETC...) BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEE LUMINAIRE SCHEDULE FOR QUANTITY OF HEADS) - WALL, CEILING MOUNTED. ILLUMINATED EXIT SIGN, SHADED QUADRANT INDICATES FACES, ARROWS AS SHOWN BOLLARD POLE MOUNTED LUMINAIRE- SINGLE OR DUAL HEAD INDICATES ROTATED OPTICS POST TOP MOUNTED LUMINAIRE IN-GRADE POINT SOURCE GARAGE LIGHTING LUMINAIRE WITH CUTOFF LOUVERS LUMINAIRE MARKING CONVENTION LEGEND: HA = LUMINAIRE TYPE IDENTIFICATION. SEE LUMINAIRE SCHEDULE. 3c = CIRCUIT NUMBER VIA LOCAL SWITCH (LOWERCASE LETTER) THAT SERVES THE LUMINIARE. 3A = CIRCUIT NUMBER/UPPERCASE LETTER COMBINATION INDICATES LOW VOLTAGE RELAY OR LIGHTING CONTACTOR THAT SERVES THE LUMINAIRE F C C DM VFD F J S J J J J J J J PTZ CR I I RX RX MRIB DS CR ER EB ML GB ES EL H D N MO TVSS R C K 52 DMU KWH PF BA ST CM C AM M GF M PB J J J D PA D V S C C S S S S S B AV IR M M I I LCP ? a b OS OS OS OS OS T T TC EPO PC TX REFER TO FSD CONNECTION DETAIL. S S S S S S S S S S S S D D S S S S C 12 125.4 1 E4.1 2 E4.1 3 E4.1 K112 CH 1 EQUIP NAME STB 3 2 a 4 K P PL TS 5A 5C 5A,5B XP WP V T OR1 D (E) (F) (R) (RL) AB ACU AC A, AMP AF AFF AFG AIC AL ALC AS AT ATS AUTO AUX AWG BAT BG BRKR C CAB CB CFM CKT CLG CO CPT CT CU DC DISC DIA DIV DP DPDT DPST DWG E,EMERG EF EMT ENCL EO EOL EWC EWH FA FAA FBO FC FF FLA FLEX FPB FSD FW FU GEN GFI GND GRAP GRC HLO HP HPF HTR HZ IES IBC ID IG IMC KCMIL KO KW KVA LTG LCP MAX MCA MFR MIN MISC MLO MO MTD MTR -N- NC NEC -,NEG NEMA NL NO NTS NP OC OD OFCI OFOI OS P PB PH, Ø PNL +,POS PRI REQD RNC RS RST S.A.D. SEC SN SOL SPDT SPST SUB SWBD SWGR TB TDC TDO TEL TYP UL UON UPS UTX V VA VFD W W/ W/O WP XFR XP Z ", IN ', FT Ø > < > EXISTING TO REMAIN FUTURE EXISTING TO BE REMOVED EXISTING TO BE RELOCATED ABOVE COUNTER BACKSPLASH AIR CONDITIONING UNIT ALTERNATING CURRENT AMPERES AMPERE (RATED) FUSE OR CB FRAME ABOVE FINISHED FLOOR ABOVE FINISHED GRADE EQUIPMENT SHORT CIRCUIT INTERRUPT RATING (RMS SYM. AMPS) ALUMINUM (ALLOY) AUTOMATIC LIGHTING CONTROL AMPERE (RATED) SWITCH CIRCUIT BRKR TRIP SETTING (AMPS) AUTOMATIC TRANSFER SWITCH AUTOMATIC AUXILIARY AMERICAN WIRE GAUGE BATTERY BELOW GRADE CIRCUIT BREAKER CONDUIT (CIRCULAR RACEWAY) CABINET CIRCUIT BREAKER CUBIC FEET PER MINUTE CIRCUIT CEILING CONDUIT ONLY CONTROL POWER TRANSFORMER CURRENT TRANSFORMER COPPER DIRECT CURRENT DISCONNECT DIAMETER DIVISION DISTRIBUTION PANEL DOUBLE POLE DOUBLE THROW DOUBLE POLE SINGLE THROW DRAWING EMERGENCY EXHAUST FAN ELECTRICAL METALLIC TUBING ENCLOSURE ELECTRICALLY OPERATED END OF LINE ELECTRIC WATER COOLER ELECTRIC WATER HEATER FIRE ALARM FIRE ALARM ANNUNCIATOR FURNISHED BY OTHERS FOOT CANDLES FLUSH FLOOR MOUNTED FULL LOAD AMPERES FLEXIBLE FAN POWERED BOX FIRE/SMOKE DAMPER FLUSH WALL MOUNTED FUSE GENERATOR GROUND FAULT CIRCUIT INTERRUPTER GROUND GENERATOR REMOTE ANNUNCIATOR PNL GALVANIZED RIGID STEEL CONDUIT HANDLE LOCK-ON(OFF) HORSEPOWER HIGH POWER FACTOR HEATER HERTZ (CYCLES PER SECOND) ILLUMINATING ENGINEERING SOCIETY INDIVIDUAL BRANCH CIRCUIT INSIDE DIAMETER ISOLATED GROUND INTERMEDIATE METAL CONDUIT THOUSAND CIRCULAR MILS KNOCK OUT KILOWATTS KILOVOLT-AMPERES LIGHTING LIGHTING CONTROL PANEL MAXIMUM MINIMUM CIRCUIT AMPERES MANUFACTURER MINIMUM MISCELLANEOUS MAIN LUGS ONLY MANUAL OPERATOR MOUNTED MOTOR NEUTRAL (GROUNDED CONDUCTOR) NORMALLY CLOSED NATIONAL ELECTRICAL CODE NEGATIVE NATIONAL ELECTRICAL MFGR'S ASSOC. NIGHT LIGHT (UNSWITCHED) NORMALLY OPEN NOT TO SCALE NAMEPLATE ON CENTER OUTSIDE DIAMETER OWNER FURNISHED CONTRACTOR INSTALLED OWNER FURNISHED, OWNER INSTALLED OCCUPANCY SENSOR POLE PUSHBUTTON PHASE PANEL POSITIVE PRIMARY REQUIRED RIGID NON-METALLIC CONDUIT (PVC) RAPID START REMOTE STATION TRANSMITTER SEE ARCHITECTURAL DRAWINGS SECONDARY SHEET NOTE SOLENOID SINGLE POLE DOUBLE THROW SINGLE POLE SINGLE THROW SUBSTATION SWITCHBOARD SWITCHGEAR TERMINAL BOARD TIME DELAY CLOSING TIME DELAY OPENING TELEPHONE TYPICAL UNDERWRITERS LAB UNLESS OTHERWISE NOTED UNINTERRUPTIBLE POWER SUPPLY UTILITY TRANSFORMER VOLTS VOLT-AMPERES VARIABLE FREQUENCY DRIVE WATT WITH WITHOUT WEATHERPROOF, SEE RECEPT. SYMBOL TRANSFORMER EXPLOSION PROOF ZONE INCHES FEET PHASE GREATER THAN LESS THAN GREATER THAN OR EQUAL TO (E) (D) (F) NEW WORK WIRING CONCEALED IN FLOOR OR UNDER GRADE OR ROUTED IN CEILING SPACE OF FLOOR BELOW. EXISTING WORK TO REMAIN EXISTING WORK TO BE REMOVED FUTURE WORK 1. THE EXISTING OLD GENERATOR, LOCATED IN THE PENTHOUSE AND SERVING THE BUILDING'S ELEVATORS, WAS REMOVED. THIS PROJECT IS TO RECONNECT THE EXISTING ATS SERVING THE ELEVATORS TO THE RECENTLY ADDED GENERATOR LOCATED IN THE SUB-BASEMENT. . 2. DUE TO SELECTIVE COORDINATION REQUIRMENTS OF THE 2014 NATIONAL ELECTRIC CODE, THE EXISTING PENTHOUSE EMERGENCY PANEL EM2 WAS REPLACED WITH A FUSED PANELBOARD AND ONLY ONE ELEVATOR CAN BE OPERATED WHILE OPERATING ON THE GENERATOR. . 3. PSU HAS CONFIRMED THAT THE ELEVATOR CONTROLLER IS LAREADY PROGRAMMED TO ALLOW ONLY ONE ELEVATOR TO OPERATE AT ONE TIME WHILE ON EMERGENCY POWER. . 4. SOME WALLS WILL NEED TO BE REMOVED TO ALLOW ACCESS TO THE EXISTING CONDUIT RISER THAT IS PART OF THIS PROJECT. THE OWNER WILL PROVIDE DEMO AND PATCHING OF THOSE WALLS. FIRE AND WATER PROOFING OF ANY NEW FLOOR OR FIRE RATED WALL PENETRATIONS ARE PART OF THE ELECTRICAL CONTRACTORS SCOPE OF WORK. . 5. SHORT CIRCUIT FAULT CURRENT CALCULATIONS AND A COORDINATION STUDY OF BREAKERS AND FUSES WERE PERFORMED. 1. ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO REPLACE AND RECONNECT EXISTING PANEL EM2 INI THE PENTHOUSE PER THE NOTE ON THE SINGLE-LINE DIAGRAM. . 2. ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO PROVIDE A NEW 400A, 4P, 208Y,120V ATS IN PLACE OF THE EXISTING ONE. T M e n g i n e e r s f o r a s u s t a i n a b l e f u t u r e 2014 - GLUMAC ALL RIGHTS RESERVED THESE DRAWINGS ARE THE PROPERTY OF GLUMAC ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER, WITHOUT PRIOR WRITTEN PERMISSION SHEET JOB NO. SHEET TITLE: CHECKED BY: DRAWN BY: Project © Client Job No.: Contact: www.glumac.com 900 SW Fifth Ave., Suite 1600 Portland, OR 97204-2640 T. 503.227.5280 F. 503.274.7674 7/30/2014 11:19:18 AM 12" = 1'-0" E0.1 LEGENDS, ABBREVIATIONA AND DRAWING LIST Author LRH PSU ELEVATOR RECONNECTION TO GENERATOR PORTLAND STATE UNIVERSITY 02.14.00651 7/30/14 100% CD'S/ PERMIT SET 02.14.00651 LRH E0.1 LEGENDS, ABBREVIATIONA AND DRAWING LIST E3.1 PARTIAL FLOOR PLANS - POWER PLAN E5.1 ELECTRICAL SINGLE-LINE DIAGRAM E9.1 ELECTRICAL DETAILS Revisions # Description Date

Upload: others

Post on 01-Jan-2020

59 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: ELECTRICAL LEGEND ABBREVIATIONS ELECTRICAL DESIGN …...not all symbols, abbrev., etc. are necessarily used on this project refer to details for mounting heights of devices ... connection

DESCRIPTIONSYMBOL

POWER DEVICESDESCRIPTIONSYMBOL

DISTRIBUTION & EQUIPMENTDESCRIPTIONSYMBOL

LIGHTING

DESCRIPTIONSYMBOL

SWITCHING CONTROLS

DESCRIPTIONSYMBOL

DIAGRAMS

DESCRIPTIONSYMBOL

SIGNAL DEVICES

DESCRIPTIONSYMBOL

REFERENCE SYMBOLS

DESCRIPTIONSYMBOL

WIRING

DESCRIPTIONSYMBOL

SECURITY SYSTEM

DESCRIPTIONSYMBOL

FIRE ALARM SYSTEM

DESCRIPTIONSYMBOL

GROUNDING SYSTEM

ABBREVIATIONS ELECTRICAL DESIGN CRITERIA

ELECTRICAL DRAWING LIST

ELECTRICAL EQUIPMENT NAMING CONVENTION LEGEND

ELECTRICAL LEGEND

ELECTRICAL BASIS OF DESIGN

ELECTRICAL ADD ALTERNATES

P

15

30

15

15

R/C,F,R

P,B,R,C

D

DETAILS APPLY TO ALL APPLICABLE SITUATIONS, UON.NOT ALL DETAIL REFERENCES ARE SHOWN. ALLREFER TO DETAIL NO. ON DRAWING INDICATED

MECHANICAL EQUIPMENT IDENTIFICATION TAG

TYPE; REFER TO BRANCH CIRCUIT AND FEEDER

SHEET NOTE REFERENCE

ELEVATION TAG: REFER TO ELEVATION NUMBER ONDRAWING INDICATED

DRAWING INDICATEDSECTION TAG: REFER TO SECTION NUMBER ON

KITCHEN EQUIPMENT REFERENCE, REFER TO KITCHENEQUIPMENT SCHEDULE

BRANCH CIRCUIT OR FEEDER NOMINAL AMPACITY &

SCHEDULES FOR WIRE AND CONDUIT SIZES & QTY.

EQUIPMENT BY OTHERS IDENTIFICATION TAG

INCLUDES ALL PIPING BY DIV. 16.EARLY WARNING SMOKE DETECTION SYSTEM -

HORN - CEILING, WALL MOUNTED

FLAME DETECTOR (FLICKER DETECTOR)

LIGHT (LAMP, SIGNAL LIGHT,INDICATOR LAMP, STROBE)

FIREMAN'S PHONE JACK, WALL MOUNTED

END OF LINE RESISTOR (NOT SHOWN ON PLANS)

ADDRESSABLE MONITOR MODULE

ADDRESSABLE CONTROL MODULE

RISE AND FIXED TEMPERATURE TYPE, UON.

SPRINKLER VALVE TAMPER SWITCH CONNECTION

(# = CANDELA RATING)

STROBE LIGHT - WALL, CEILING MOUNTED

SPEAKER - WALL, CEILING MOUNTED

ALARM BELL OR GONG

WALL MOUNTED

FIRE ALARM SYSTEM ANNUNCIATOR

COMBINATION SPEAKER/STROBE, WALL MOUNTED

FIRE ALARM SYSTEM MANUAL PULL STATION,

(# = CANDELA RATING)

SPRINKLER FLOW SWITCH CONNECTION

RECEIVER, BT=BEAM TRANSMITTER)

WIDTH SAMPLING TUBES. PHOTOELECTRIC TYPE

LIGHT BEAM TYPE SMOKE DETECTOR (BR=BEAM

HEAT DETECTOR, CEILING MOUNTED. RATE OF

FIREMAN'S PHONE HANDSET, WALL MOUNTED

FIRE ALARM OUTPUT OR RELEASE ABORTPUSHBUTTON, REFER TO SPECIFICATIONS AND

COMPONENTS. PROVIDE 120V POWER AS REQUIREDFIRE ALARM CONTROL PANEL AND ASSOCIATED

OR AS INDICATED.

SMOKE DETECTOR, DUCT MOUNTED, WITH FULL

MINI HORN - WALL, CEILING MOUNTED

DETAILS.

UON.

SMOKE DETECTOR, LOW AIR VELOCITY IN DUCTMOUNTED PHOTOELECTRIC TYPE U.O.N.

SMOKE DETECTOR MOUNTED BELOW RAISED FLOOR

DATA LOOP ISOLATION MODULE

COMBINATION HORN/STROBE - WALL, CEILINGMOUNTED (# = CANDELA RATING)

COMBINATION MINI HORN/STROBE - WALL, CEILINGMOUNTED (# = CANDELA RATING)

HEAT DETECTOR (R/C=RATE OF COMBUSTION,F=FIXED TEMP. ONLY, R=RATE OF RISE ONLY)

AGENT RELEASE INITIATING VALVE

BELL SILENCE SWITCH

AGENT DISCHARGE SWITCH

ELECTROMAGNETIC DOOR HOLDER - WALL, FLOOR,DOOR CLOSURE MOUNTED. PROVIDED BY DIV. 8UON.

SMOKE DETECTOR - WALL, CEILING MOUNTED(P=PLENUM MOUNTED, B=W/RELAY BASE,R=ELEVATOR RECALL, C=INTEGRAL TO DOORCLOSURE)

FIRE/SMOKE DAMPER BY DIV 15. WIDTH OFSYMBOL WILL VARY WITH DUCT WIDTH. PROVIDEPOWER AND MONITORING AS INDICATED.

GROUND ROD LOCATION

24" GROUND BAR

LIGHTNING PROTECTION CONDUCTOR ROUTED DOWN

60" GROUND BAR

LIGHTNING PROTECTION BIMETAL CONNECTION

LIGHTNING PROTECTION BOND PLATE

GROUND GRID BOND POINT

LIGHTNING PROTECTION AIR TERMINAL

GROUND ROD IN TEST WELL

GROUND GRID BOND POINT - MECHANICALCONNECTION

GROUND GRID BOND POINT - EXOTHERMICWELD CONNECTION

LIGHTNING PROTECTION PARAPET MOUNTED AIRTERMINAL

LIGHTNING PROTECTION MID ROOF MOUNTEDAIR TERMINAL

BARE GROUNDING GRID OR CONDUCTORS, UON.

GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZEDCONDUIT, UON.

WW DIRECTION

WW DIRECTION

A1LHXFR-

A1H MMCC-

DP- U L D 1 A

A1SNHMSWBD-

EXAMPLES / LEGEND EQUIPMENT TYPE POWER SYSTEM

PNL- E H K 2 B

NOT ALL SYMBOLS, ABBREV., ETC. ARE NECESSARILY USED ON THIS PROJECT

REFER TO DETAILS FOR MOUNTING HEIGHTS OF DEVICES

BUSWAY RISER

DAMPER MOTOR

MAGNETIC MOTOR STARTER (CONTROLLER)

WITH CODE CLEARANCES SHOWN

SHOWN SIZE PER CONNECTED MOTOR SIZE AND

CONNECTION TO MOTOR PROVIDED BY OTHERS

SERVICE AND/OR DISTRIBUTION EQUIPMENT

TRANSFORMER WITH CODE CLEARANCES SHOWN

SHOWN, DASHED EQUIP. = FUTURE

BRANCH CIRCUIT PANELBOARDS, SURFACE AND

MOTOR CONTROL CENTER W/ CODE CLEARANCES

BUILDING GROUND BUS, SEE DETAILS

FUSE PER MANUFACTURER'S RECOMMENDATIONS

SURFACE AND RECESS MOUNTEDEQUIPMENT OR TERMINAL ENCLOSURE AS NOTED,

FREQUENCY DRIVE WITH INTEGRAL DISCONNECT

FUSED DISCONNECT SWITCH, SIZE AS NOTED. SIZE

RECESS MOUNTED

(CONTROLLER) OR CONTACTOR. SIZE PER

ENCLOSED CIRCUIT BREAKER DISCONNECTSWITCH, TRIP SIZE AS NOTED.

DISCONNECT SWITCH, SIZE AS NOTED OR IF NOT

MOTOR DISCONNECT SCHEDULE

CONNECTION TO DIV. 15 FURNISHED VARIABLE

DIV. 16 TO INSTALL VFD EQUIPMENT

INTEGRAL DISCONNECT THAT IS PROVIDED BY

DIV. 16 CONNECTION TO EQUIPMENT PROVIDED BYOTHERS. SHADED = ON ALT. POWER SOURCE NOTED

DIV. 16 CONNECTION TO EQUIPMENT WITH

BUSWAY STAB-IN TYPE CIRCUIT BREAKEROR FUSE DISCONNECT. SIZE AS NOTED.

OTHERS. SHADED = ON ALT. POWER SOURCE NOTED

DISCONNECT W/ MAGNETIC MOTOR STARTER

LOAD SERVED. NEMA SIZE #1 MINIMUM.

OR CONTACTOR. SIZE PER LOAD SERVED.NEMA SIZE #1 MINIMUM.

"ON ALT."

AB

STANDBY, UPS, ETC.) PER CIRCUITING INDICATED

SHADED RECEPTACLES NOTED "ON ALT." ABOVE ARE

IN RAISED FLOOR - SEE ARCH DWGS; WITH

SIMPLEX RECEPTACLE - WALL, CEILING, ON ALT.

DUPLEX RECEPTACLE - WALL, CEILING, ON ALT.

DOUBLE DUPLEX RECEPTACLE - WALL, CLG, ON ALT.

DUPLEX RECEPTACLE - WALL - HALF SWITCHED

ON ALT. POWER; NEMA CONFIGURATION AS NOTED

FLUSH FLOOR BOX DEVICE - DEVICE TYPE PERSYMBOLS ABOVE

PEDESTAL FLOOR DEVICE - DEVICE TYPE PERSYMBOLS ABOVE

TELE/POWER POLE, POWER POLE

RECEPTACLE TYPE SHOWN -WALL -ABOVE COUNTERBACKSPLASH. SEE ARCHITECTURAL DRAWINGS.

FLUSH, PEDESTAL MOUNTED.

NEUTRAL, 1 ISOLATED GROUND) NEUTRALS

POKE THRU UNIT WITH DUPLEX RECEPTACLE -

ELECTRIFIED FURNITURE. PROVIDE 8 WIRES

(4 HOTS, 1 DEDICATED NEUTRAL, 1 COMMON

RECEPT. TYPE SHOWN AT SPECIAL HEIGHT+42"

CLOCK HANGER RECEPTACLE

TWO-PIECE SURFACE METAL RACEWAY WITHRECEPTACLES AS NOTED, LENGTH AS

FITTINGS AS REQUIRED.

CONNECTED TO ALTERNATE POWER SOURCE (EMERG.,

L5-15R

COMBINATION SWITCH/DUPLEX RECEPTACLE

GFIDUPLEX RECEPTACLE - WALL - WITH INTEGRALGROUND FAULT CIRCUIT INTERRUPTER

WP RECEPT. TYPE SHOWN W/ WEATHERPROOF COVER

SPECIAL PURPOSE RECEPTACLE -WALL, CEILING

WALL MOUNTED ELECTRICAL CONNECTION TO

TO BE #10 AWG. USE LIQUID-TIGHT FLEX.

INDICATED ON THE DRAWINGS AND WITH ALL

INDICATED, LENGTH AS INDICATED ON THEDRAWINGS. PROVIDE ALL FITTINGS AS

RACEWAY WITH RECEPTACLES AND OUTLETS ASTWO OR THREE COMPARTMENT SURFACE METAL

REQUIRED.

POKE THRU UNIT WITH DOUBLE DUPLEXRECEPTACLE - FLUSH, PEDESTAL MOUNTED.

POKE THRU UNIT WITH JUNCTION BOX.RACEWAY COMPONENTS RC-700 SERIES.

COMBO POKE THRU UNIT WITH DUPLEXRECEPTACLE AND TELEPHONE OUTLET - FLUSH,

MULTI-SERVICE FLOOR BOX CAST IN CONC. OR

RECEPTACLES & SIGNAL OUTLETS AS NOTED.

PEDESTAL MOUNTED.

TELE/POWER POLE WITH WHIP CONNECTION TOELECTRIFIED FURNITURE

AND INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER

CCTV SECURITY PAN/TILT/ZOOM CAMERA

CCTV SECURITY INDOOR DOME CAMERA

CARD READER- WALL MOUNTED/MULLION MOUNTED

REQUEST TO EXIT DEVICE WALL,MULLION MOUNTED

M

INTELLIGENT CARD READER INTERFACE

ROLL-UP DOOR MOTOR CONTROL OUTPUT

LOCAL DOOR MONITOR WARNING NOISE DEVICE

DURESS PUSHBUTTON STATION

DOOR POSITION MONITOR SWITCH

ELECTRIC STRIKE

ELECTRIC LOCK/LATCH

ELECTRIC BOLT

SECURITY ELECTRONIC MOTION SENSOR

CCTV SECURITY FIXED CAMERA - WALL,CEILING

EMERGENCY DOOR RELEASE BREAK-GLASS STATION

M = MASTER STATIONINTERCOM STATION - WALL, DESK MOUNTED.

MAGNETIC LOCK

ELECTRIC POWER TRANSFER HINGE

GLASS BREAK SENSOR

SWBD - SWITCHBOARD

U - UNINTERRUPTIBLE POWER (UPS)

UTX - UTILITY MAIN TRANSFORMER

BIATS - BYPASS ISOLATION ATS

MCC - MOTOR CONTROL CENTER

XFR - TRANSFORMER

DSW - NON-FUSED DISCONNECT SW.

MTS - MANUAL TRANSFER SWITCH

CB - ENCLOSED CIRCUIT BREAKER

FSW - FUSED DISCONNECT SWITCHTYPE

PNL - BRANCH PANEL

DP - DISTRIBUTION PANEL

SUB - UNIT SUBSTATION

C - CRITICAL POWER (Hospital)

M - MAIN UTILITY SERVICE

EM - EMERGENCY POWER (Life Safety)

S - STANDBY POWER

LETTERSSEQ.

EQUIP.DESIG.

SYSTEMPOWER

SYSTEMVOLTAGE

DESIG.ADDN'L

FLOOR

Q - EQUIPMENT POWER (Hospital)

S - LIFE SAFETY POWER (Hospital)

BLANK - NORMAL LOADS

ATS - AUTOMATIC TRANSFER SWITCH

SWGR - SWITCHGEAR

D

INTEGRAL AMMETER DISPLAY

CONNECTION TO DIV. 15 CHILLER

CAPACITOR, POWER FACTOR CORRECTION, SIZE

KEY INTERLOCK

MONITORING COMMUNICATION MODULE

SHUNT TRIP UNIT, 120VAC OR VOLTAGE AS NOTED

GROUND FAULT TRIP UNIT

DRAWOUT CIRCUIT BREAKER

INDIVIDUALLY MOUNTED CIRCUIT BREAKER

FUSED SWITCH, WITH FUSE AND SWITCH AMPERE

RATINGCIRCUIT BREAKER, WITH TRIP & FRAME AMPERE

GROUNDED WYE CONNECTION

DELTA CONNECTION

LED INDICATOR LIGHT, PUSH TO TEST, R=RED

TERMINAL FOR FIELD CONNECT, SIZE & TYPE

CURRENT TRANSFORMER SHORTING TERMINAL BLOCK.

INSTALLED. SQUARE = REMOTE MOUNTEDUTILITY CO. APPROVED SOCKET WITH METER

METER: KILOWATT HOUR

METER: POWER FACTOR

FUSED VOLTAGE SENSE LEADS

NORMALLY CLOSED PUSH BUTTON

CURRENT TRANSFORMER

CLASS I = INTERMEDIATE CLASS

CONTACTOR COIL

PIPE GROUND

BATTERY GENERAL

CONTACTS

OVERLOADS

TO DESTINATION SHOWN, U.O.N.

HAND/OFF/AUTO SWITCH

BUS DUCT

IN KVAR

MECHANICAL INTERLOCK

TRANSIENT VOLTAGE SURGE SUPPRESSOR

DIGITAL METER UNIT. REFER

FUSE, HOLDER & PULLER

10

CIRCUIT BREAKER, MEDIUM VOLTAGE, DRAWOUT

SOLENOID

400AS225AF

G= GREEN, B= BLUE, Y= YELLOW, W= WHITE

SUITABLE FOR CONDUCTOR INSTALLED.

225AF100AT

POTENTIAL TRANSFORMER

BELL ALARM TRIP MODULE CONTACTS

BUS BAR

LIGHTNING SURGE ARRESTOR D= DISTRIBUTION

RELAY COIL

GENERATOR

NORMALLY OPEN CONTACTOR OR RELAY CONTACTS

RATING

NORMALLY OPEN PUSH BUTTON

CONNECTION TO GROUND

TO SPECIFICATIONS.

FIELD INSTALLED CONTROL CIRCUIT WIRING

SWITCH

RESISTOR

CONNECTOR, FEMALE AND MALE RESPECTIVELY

NORMALLY CLOSED CONTACTOR OR RELAY

IN PANEL AND BRANCH CIRCUIT SCHEDULES TO

STROKES INDICATE QUANTITY OF #12 AWG.

20A BRANCH CIRCUITS ARE NOT SHOWN ON

PROVIDE REQUIRED CIRCUITING.

CONDUCTORS, UON. NOTE: WIRING STROKES FOR

DRAWINGS. CONTRACTOR SHALL USE INFORMATION

G

T

MV MEDIUM VOLTAGE CONDUIT

BARE GROUNDING GRID OR CONDUCTORS, UON.

TELEPHONE SYSTEM CONDUIT

GC GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZEDCONDUIT, UON.

SHADED= ON ALT. POWER SOURCE (EMERG,UPS,ETC.)WIRE IN EXPOSED OR "HARD" CEILING AREAS.

JUNCTION BOXES, WALL, CEILING AND FLUSH FLOOR

BRANCH CIRCUIT SCHEDULES.

HOME RUN WIRING TO INDICATED DESTINATION,

HD1ASCHEDULES AND INFORMATION IN THE FEEDER ANDSHALL USE CIRCUIT SIZES NOTED IN RESPECTIVE

INSTALLER(S) PRIOR TO ROUGH-IN.

SIDES. TERMINATE WITH BUSHINGS. (1) 1.25" CO

PULL BOX, MIN. SIZE PER NEC., UON.

NEUTRAL

CONDUIT RUN TURNED UP THROUGH FLOOR ORCEILING. CORE & FIREPROOF AS REQUIRED.

CONDUIT STUBBED OUT AT LOCATION SHOWN.PROVIDE INSULATED BUSHING & PULLROPE.

TELEPHONE/DATA SLEEVE THROUGH WALL, ABOVE

UON. COORDINATE LOCATIONS WITH CABLE

WIRING EXTENSION POINT - CONDUIT TO MC CABLE

UNDERFLOOR RACEWAY

FLEXIBLE CONDUIT CONNECTION

GROUND

HOT

CEILING. CORE & FIREPROOF AS REQUIRED.CONDUIT RUN TURNED DOWN THROUGH FLOOR OR

CEILING. EXTEND TO ACCESSIBLE TILE CLG. BOTH

OR MANUFACTURED WIRING SYSTEM J-BOX ABOVE

MOUNTED. 4" SQ. BOX MIN., LARGER IF REQUIRED

ACCESSIBLE CEILINGS AREAS, OR EXTEND CONDUIT &

POWER CONNECTION TO DIV 15 FIRE/SMOKE DAMPER.REFER TO FSD CONNECTION DETAIL IF NOT SHOWN

L1A-1,33/4"C. MIN. OR AS OTHERWISE NOTED. CONTRACTOR

ASSISTIVE LISTENING INFRARED TRANSMITTER PANEL,

AV INPUT OUTLET, 1"C WITH 3-GANG BOX. CONDUIT

SURFACE, RECESSED MOUNTEDSIGNAL SYSTEM EQUIPMENT ENCLOSURES AS NOTED-

ACCESSIBLE TILE CEILING.1"C WITH 2-GANG BOX. CONDUIT STUBBED ABOVE

STUBBED ABOVE ACCESSIBLE TILE CEILING.

MOUNTING HEIGHT PER MOUNTING HT. DETAILTELEPHONE OUTLET - WALL, W = USE HIGHER

W

SHOWN, FIRE TREATED.TERMINAL/MOUNTING BOARD, 8' HIGH X WIDTH AS

CHIME

BUZZER

BELL

COMBO TELEPHONE/DATA OUTLET - WALL

DATA OUTLET - WALL

DUAL COIL SPEAKER - SURFACE CEILING,

PAGING SYSTEM HORN (OUTDOOR)

SPEAKER - WALL, CEILING

VOLUME CONTROL - WALL

SYSTEM CLOCK - WALL , CEILING

SYMBOLS ABOVEPEDESTAL FLOOR DEVICE - DEVICE TYPE PER

SYMBOLS ABOVEFLUSH FLOOR DEVICE - DEVICE TYPE PER

RECESSED CEILING.

PAGING OR PAGING/SOUND MASKING SPEAKER,MOUNTED ABOVE ACOUSTIC TILE CEILING.

INDICATED. SEE RISER DIAGRAM.PROVIDE 120V POWER AS REQUIRED OR ASRF COAX CABLE DISTRIBUTION AMPLIFIER.

PUSHBUTTON OR PUSHBUTTONS

RF COAX CABLE OUTLET (TV, VCR, ETC.)

RF COAX CABLE SIGNAL SPLITTER

INTERCOM STATION - WALL, DESKM = MASTER STATIONM

MICROPHONE JACK - WALL, FLOOR

COMBINATION RF COAX CABLE AND DATA OUTLET

MOUNTEDCORRIDOR/AISLE OCCUPANCY SENSOR - CEILING

360 DEGREE OCCUPANCY SENSOR - CEILING MTD.

180 DEGREE OCCUPANCY SENSOR - CEILING MTD.

OCCUPANCY SENSOR - WALL MOUNTED

PUSHBUTTON OR PUSHBUTTONS, BY DIV. 16

REMOTE MOUNTED LINE TO LOW-VOLTAGE FUSEDTRANSFORMER. CONCEAL FROM VIEW.

COMPONENTS. PROVIDE 120V OR 277V CONTROLPOWER AS REQUIRED OR AS INDICATED.

LIGHTING CONTROL PANEL AND ASSOCIATED

SINGLE POLE SWITCH (SUPERSCRIPT DENOTESSIMILARLY MARKED LUMINAIRES CONTROLLEDTOGETHER)

TWO POLE SWITCH

PHOTOCELL

TIME CLOCK

PROVIDED WITH EQUIPMENT, INSTALLED AND

THERMOSTAT - WALL, CEILING. PROVIDED BY DIV.15, INSTALLED AND WIRED BY DIV. 16

EQUIPMENT OPERATOR PUSH BUTTON STATION.

CONNECTED BY DIV. 16, UON.

EMERGENCY POWER OFF, HEAVY-DUTY, OIL-TIGHTRED MUSHROOM-HEAD PUSHBUTTON W/ GUARD.

LIGHTING CONTROL OVERIDE SWITCH, SEQ. NUMBER

LINE VOLTAGE, VARIABLE SPEED FAN CONTROL

DIMMER SWITCH. NUMBER INDICATES WATTAGERATING. IF NOT SHOWN THEN EQUAL TO LOAD.

SWITCH, PROVIDED BY DIV. 15, INSTALLEDBY DIV. 16. LOCATE ADJACENT TO ADJACENT

SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN

MOTOR-RATED THERMAL OVERLOAD SWITCH

EXPLOSION PROOF SWITCH

SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN

DIMMER SWITCH UNDER SEPARATE COVERPLATE

SWITCH IS "OFF").

TO LIGHT SWITCHES.

WEATHERPROOF SWITCH

TIMER SWITCH

SWITCH IS "ON").

KEY OPERATED SWITCH

FOUR WAY SWITCH

THREE WAY SWITCH

LOW VOLTAGE MOMENTARY CONTACT SWITCH,UPPER CASE LETTER SUPERSCRIPT INDICATESCONNECTION TO LOW VOLTAGE RELAYCONTROLLING SIMILARLY MARKED LUMINAIRES.

BASKET TYPE CABLE TRAY WITH 90 DEGREE ELBOWSHOWN

LADDER TYPE CABLE TRAY WITH 90 DEGREE ELBOWSHOWN

G

GC

1. OREGON ELECTRICAL SPECIALTY CODE (OREGON AMENDED VERSION OF 2014 NATIONALELECTRIC CODE).

2. FIRE/LIFE SAFETY CODE: 2007 IFC WITH OREGON AMMENDMENTS.

3. 2010 STATE OF OREGON STRUCTURAL SPECIALTY CODE: OREGON AMMENDED VERSION OF2009 IBC.

4. AMERICANS WITH DISABILITIES ACT, (ADA).

COMBINATION OCCUPANCY SENSOR & SWITCHGANGED UNDER A COMMON COVER PLATE.OCCUPANY SENSOR TO CONTROL ALL LUMINAIRES INROOM WITH 1/2 LIGHT REDUCTION CONTROLLED BYSWITCH, DESIGNATED BY LETTER. 2-GANG BOX WITHSINGLE-GANG MUDRING, UON SPECIFIED

3c

3A

RECESSED 2X4 LUMINAIRE

SURFACE MOUNTED 2X4 LUMINAIRE

RECESSED 1X4 LUMINAIRE

SURFACE MOUNTED 1X4 LUMINAIRE

RECESSED 2X2 LUMINAIRE

SURFACE MOUNTED 2X2 LUMINAIRE

SHADING OF ANY LUMINAIRE INDICATES CONNECTIONTO ALTERNATE POWER SOURCE (EMERGENCY, UPS,STANDBY, ETC.) PER CIRCUITING INDICATED

SUSPENDED LINEAR LUMINAIRE (SIZE VARIES)

WALL MOUNTED LINEAR LUMINAIRE (SIZE VARIES)

SUSPENDED PENDANT LUMINAIRE (SIZE VARIES)

RECESSED DOWNLIGHT, CEILING MOUNTED

SURFACE DOWNLIGHT, CEILING MOUNTED

RECESSED WALLWASH

SURFACE WALLWASH

RECESSED LINEAR WALLWASH

SURFACE LINEAR WALLWASH

RECESSED WALL MOUNTED LUMINAIRE

TRACK LIGHTING WITH HEADS AS INDICATED.

RECESSED CEILING ADJUSTABLE POINT SOURCE

SURFACE CEILING ADJUSTABLE POINT SOURCE

WALL MOUNTED LUMINAIRE

WALL MOUNTED DIRECTIONAL (SIZE VARIES)

FLUORESCENT STRIPLIGHT - POWER FEED SECTION,FEED THROUGH SECTION. LENGTH AS SHOWN.

WALL MOUNTED FLUORESCENT STRIPLIGHT

UNDERCABINET FLUORESCENT STRIPLIGHT

CONTINUOUS LINEAR SOURCE (LED, COLD CATHODE,NEON, FIBER OPTIC, ETC...)

BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEELUMINAIRE SCHEDULE FOR QUANTITY OF HEADS) -WALL, CEILING MOUNTED.

ILLUMINATED EXIT SIGN, SHADED QUADRANTINDICATES FACES, ARROWS AS SHOWN

BOLLARD

POLE MOUNTED LUMINAIRE- SINGLE OR DUAL HEAD

INDICATES ROTATED OPTICS

POST TOP MOUNTED LUMINAIRE

IN-GRADE POINT SOURCE

GARAGE LIGHTING LUMINAIRE WITH CUTOFF LOUVERS

LUMINAIRE MARKING CONVENTION LEGEND: HA = LUMINAIRE TYPE IDENTIFICATION. SEE LUMINAIRE SCHEDULE. 3c = CIRCUIT NUMBER VIA LOCAL SWITCH (LOWERCASE LETTER) THAT SERVES THE LUMINIARE. 3A = CIRCUIT NUMBER/UPPERCASE LETTER COMBINATION INDICATES LOW VOLTAGE RELAY OR LIGHTING CONTACTOR THAT SERVES THE LUMINAIRE

FC

C

DM

VFD

F

J

S

J

J

J

J

JJ

J

PTZ

CR

II

RXRX

MRIB

DS

CR

ER

EB

ML

GB

ES

EL

H

D

N

MO

TVSS

R

C

K

52

DMU

KWH

PF

BA

ST

CM

C

AM

M

GF

M

PB

JJ J

D

PA

D

V

S

CC

S

SS

S

S

B

AV

IR

M M

I I

LCP ?

ab OS

OS

OS

OS

OS

T T

TC

EPO

PC

TX

REFER TO FSD CONNECTION DETAIL.

S

S

S

S

S

S

S

S

S

S

S

S

D

D

S

S

S

S

C

12

125.4

1

E4.1

2

E4.1

3

E4.1

K112

CH

1

EQUIP NAME

STB

3

2

a

4

K

P

PL

TS

5A

5C5A,5B

XP

WP

V

T

OR1

D

(E)(F)(R)(RL)ABACUACA, AMPAFAFFAFGAIC

ALALCASATATSAUTOAUXAWGBATBGBRKRCCABCBCFMCKTCLGCOCPTCTCUDCDISCDIADIVDPDPDTDPSTDWGE,EMERGEFEMTENCLEOEOLEWCEWHFAFAAFBOFCFFFLAFLEXFPBFSDFWFUGENGFIGNDGRAPGRCHLOHPHPFHTRHZIESIBCIDIGIMCKCMILKOKWKVALTGLCPMAXMCAMFRMINMISCMLOMOMTDMTR-N-NCNEC-,NEGNEMANLNONTSNPOCODOFCI

OFOIOSPPBPH, ØPNL+,POSPRIREQDRNCRSRSTS.A.D.SECSNSOLSPDTSPSTSUBSWBDSWGRTBTDCTDOTELTYPULUONUPSUTXVVAVFDWW/W/OWPXFRXPZ", IN', FTØ><>

EXISTING TO REMAINFUTUREEXISTING TO BE REMOVEDEXISTING TO BE RELOCATEDABOVE COUNTER BACKSPLASHAIR CONDITIONING UNITALTERNATING CURRENTAMPERESAMPERE (RATED) FUSE OR CB FRAMEABOVE FINISHED FLOORABOVE FINISHED GRADEEQUIPMENT SHORT CIRCUIT INTERRUPTRATING (RMS SYM. AMPS)ALUMINUM (ALLOY)AUTOMATIC LIGHTING CONTROLAMPERE (RATED) SWITCHCIRCUIT BRKR TRIP SETTING (AMPS)AUTOMATIC TRANSFER SWITCHAUTOMATICAUXILIARYAMERICAN WIRE GAUGEBATTERYBELOW GRADECIRCUIT BREAKERCONDUIT (CIRCULAR RACEWAY)CABINETCIRCUIT BREAKERCUBIC FEET PER MINUTECIRCUITCEILINGCONDUIT ONLYCONTROL POWER TRANSFORMERCURRENT TRANSFORMERCOPPERDIRECT CURRENTDISCONNECTDIAMETERDIVISIONDISTRIBUTION PANELDOUBLE POLE DOUBLE THROWDOUBLE POLE SINGLE THROWDRAWINGEMERGENCYEXHAUST FANELECTRICAL METALLIC TUBINGENCLOSUREELECTRICALLY OPERATEDEND OF LINEELECTRIC WATER COOLERELECTRIC WATER HEATERFIRE ALARMFIRE ALARM ANNUNCIATORFURNISHED BY OTHERSFOOT CANDLESFLUSH FLOOR MOUNTEDFULL LOAD AMPERESFLEXIBLEFAN POWERED BOXFIRE/SMOKE DAMPERFLUSH WALL MOUNTEDFUSEGENERATORGROUND FAULT CIRCUIT INTERRUPTERGROUNDGENERATOR REMOTE ANNUNCIATOR PNLGALVANIZED RIGID STEEL CONDUITHANDLE LOCK-ON(OFF)HORSEPOWERHIGH POWER FACTORHEATERHERTZ (CYCLES PER SECOND)ILLUMINATING ENGINEERING SOCIETYINDIVIDUAL BRANCH CIRCUITINSIDE DIAMETERISOLATED GROUNDINTERMEDIATE METAL CONDUITTHOUSAND CIRCULAR MILSKNOCK OUTKILOWATTSKILOVOLT-AMPERESLIGHTINGLIGHTING CONTROL PANELMAXIMUMMINIMUM CIRCUIT AMPERESMANUFACTURERMINIMUMMISCELLANEOUSMAIN LUGS ONLYMANUAL OPERATORMOUNTEDMOTORNEUTRAL (GROUNDED CONDUCTOR)NORMALLY CLOSEDNATIONAL ELECTRICAL CODENEGATIVENATIONAL ELECTRICAL MFGR'S ASSOC.NIGHT LIGHT (UNSWITCHED)NORMALLY OPENNOT TO SCALENAMEPLATEON CENTEROUTSIDE DIAMETEROWNER FURNISHED CONTRACTORINSTALLEDOWNER FURNISHED, OWNER INSTALLEDOCCUPANCY SENSORPOLEPUSHBUTTONPHASEPANELPOSITIVEPRIMARYREQUIREDRIGID NON-METALLIC CONDUIT (PVC)RAPID STARTREMOTE STATION TRANSMITTERSEE ARCHITECTURAL DRAWINGSSECONDARYSHEET NOTESOLENOIDSINGLE POLE DOUBLE THROWSINGLE POLE SINGLE THROWSUBSTATIONSWITCHBOARDSWITCHGEARTERMINAL BOARDTIME DELAY CLOSINGTIME DELAY OPENINGTELEPHONETYPICALUNDERWRITERS LABUNLESS OTHERWISE NOTEDUNINTERRUPTIBLE POWER SUPPLYUTILITY TRANSFORMERVOLTSVOLT-AMPERESVARIABLE FREQUENCY DRIVEWATTWITHWITHOUTWEATHERPROOF, SEE RECEPT. SYMBOLTRANSFORMEREXPLOSION PROOFZONEINCHESFEETPHASEGREATER THANLESS THANGREATER THAN OR EQUAL TO

(E)

(D)

(F)

NEW WORK

WIRING CONCEALED IN FLOOR OR UNDER GRADEOR ROUTED IN CEILING SPACE OF FLOOR BELOW.

EXISTING WORK TO REMAIN

EXISTING WORK TO BE REMOVED

FUTURE WORK

1. THE EXISTING OLD GENERATOR, LOCATED IN THE PENTHOUSE AND SERVING THEBUILDING'S ELEVATORS, WAS REMOVED. THIS PROJECT IS TO RECONNECT THEEXISTING ATS SERVING THE ELEVATORS TO THE RECENTLY ADDED GENERATORLOCATED IN THE SUB-BASEMENT..

2. DUE TO SELECTIVE COORDINATION REQUIRMENTS OF THE 2014 NATIONAL ELECTRICCODE, THE EXISTING PENTHOUSE EMERGENCY PANEL EM2 WAS REPLACED WITH AFUSED PANELBOARD AND ONLY ONE ELEVATOR CAN BE OPERATED WHILE OPERATINGON THE GENERATOR..

3. PSU HAS CONFIRMED THAT THE ELEVATOR CONTROLLER IS LAREADY PROGRAMMEDTO ALLOW ONLY ONE ELEVATOR TO OPERATE AT ONE TIME WHILE ON EMERGENCYPOWER. .

4. SOME WALLS WILL NEED TO BE REMOVED TO ALLOW ACCESS TO THE EXISTINGCONDUIT RISER THAT IS PART OF THIS PROJECT. THE OWNER WILL PROVIDE DEMOAND PATCHING OF THOSE WALLS. FIRE AND WATER PROOFING OF ANY NEW FLOOR ORFIRE RATED WALL PENETRATIONS ARE PART OF THE ELECTRICAL CONTRACTORSSCOPE OF WORK..

5. SHORT CIRCUIT FAULT CURRENT CALCULATIONS AND A COORDINATION STUDY OFBREAKERS AND FUSES WERE PERFORMED.

1. ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO REPLACE ANDRECONNECT EXISTING PANEL EM2 INI THE PENTHOUSE PER THE NOTE ON THESINGLE-LINE DIAGRAM..

2. ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO PROVIDE A NEW 400A, 4P,208Y,120V ATS IN PLACE OF THE EXISTING ONE.

TM

en

gin

ee

rsfo

ra

su

sta

ina

ble

futu

re

2014 - GLUMAC ALL RIGHTS RESERVEDTHESE DRAWINGS ARE THE PROPERTY OF

GLUMAC ARE NOT TO BEUSED OR REPRODUCED IN ANY MANNER,WITHOUT PRIOR WRITTEN PERMISSION

SHEET

JOB NO.

SHEET TITLE:

CHECKED BY:

DRAWN BY:

Project

©

Client

Job N

o.:

Conta

ct:

ww

w.g

lum

ac.c

om

900 S

W F

ifth

Ave.

, S

uit

e 1600

Port

land, O

R 9

7204-2

640

T. 503.2

27.5

280 F

. 503.2

74.7

674

7/30/2014 11:19:18 AM 12" = 1'-0"

E0.1

LEGENDS,

ABBREVIATIONA

AND DRAWING

LIST

Author

LRH

PSU ELEVATOR

RECONNECTION TO

GENERATOR

PORTLAND STATE

UNIVERSITY

02.14.00651

7/30/14100% CD'S/ PERMIT SET

02.1

4.0

0651

LR

H

E0.1 LEGENDS, ABBREVIATIONA AND DRAWING LIST

E3.1 PARTIAL FLOOR PLANS - POWER PLAN

E5.1 ELECTRICAL SINGLE-LINE DIAGRAM

E9.1 ELECTRICAL DETAILS

Revisions

# Description Date

Page 2: ELECTRICAL LEGEND ABBREVIATIONS ELECTRICAL DESIGN …...not all symbols, abbrev., etc. are necessarily used on this project refer to details for mounting heights of devices ... connection

(E) PNL- EMDP

(E) XFR-EM1

(E) ATS-EM1

(E) DISC-EM1

(E) PNL- EM1

(E) 400ADISC-FIRE

PUMP

(E) GENSET TERMINAL CABINET

(E) PULL BOX

(E) CONDUIT SERVINGPENTHOUSE PANEL-EM2.DEMO CONDUCTORS.PROVIDE LABEL ONCONDUIT AS "SPARECONDUIT" USING KROY3/4" LABEL

PROVIDE FEEDER TO (E)PULL BOX FOR ROUTING OFFEEDER TO XFR-EM2

(E) PANEL-EM2 FEEDER RISER CONDUIT

PROVIDE CONTROL WIRINGAND CONDUIT TOPENTHOUSE ATS. CONNECTTO (E) GENERATORCONTROLS

PROVIDE SEPARATION BETWEEN EMERGENCY AND NORMAL FEEDERS

DISC-EM2

PNL- EM2(E)

DISC-UNUSED

(E) ATS-EM2

(E) DISCPNL-EM2

(E) DISCELEV-MECH

XFR-EM2

DISC-EM2

ROUTE PRIMARY CONDUITUNDER SLAB.CORE DRILLAS REQUIRED

ROUTE SECONDARY EMTCONDUIT OVERHEAD ASREQUIRED.

MOUNT DISCONNECT ON UNISTRUT FRAME

(E) EMPTY J-BOX AND CONDUIT.EXTEND 1" CONDUIT TO PENTHOUSEAND PROVIDE CONTROL WIRING PERSINGLE-LINE DIAGRAM

ROUTE CONTROL CONDUIT NEXT TOEXISTING CONDUIT RISERS. PROVIDEWATER AND FIRE PROOFING ATPENETRATION

(E) GRAP-1

CONNECT (E) SPARE WIRING TOTHIS (E) GENERATOR REMOTEANNUNCIATOR. PROGRAM ASREQUIRED TO ALLOW PENTHOUSEATS "ATS IN EMERGENCY" STATUSTO DISPLAY. ADD LABELS TODISPLAY PANEL

TM

en

gin

ee

rsfo

ra

su

sta

ina

ble

futu

re

2014 - GLUMAC ALL RIGHTS RESERVEDTHESE DRAWINGS ARE THE PROPERTY OF

GLUMAC ARE NOT TO BEUSED OR REPRODUCED IN ANY MANNER,WITHOUT PRIOR WRITTEN PERMISSION

SHEET

JOB NO.

SHEET TITLE:

CHECKED BY:

DRAWN BY:

Project

©

Client

Job N

o.:

Conta

ct:

ww

w.g

lum

ac.c

om

900 S

W F

ifth

Ave.

, S

uit

e 1600

Port

land, O

R 9

7204-2

640

T. 503.2

27.5

280 F

. 503.2

74.7

674

7/30/2014 11:19:26 AM As indicated

E3.1

PARTIAL

FLOOR PLANS -

POWER PLAN

LRH

JJE

PSU ELEVATOR

RECONNECTION TO

GENERATOR

PORTLAND STATE

UNIVERSITY

02.14.00651

7/30/14100% CD'S/ PERMIT SET

02.1

4.0

0651

JJE

0 84

SCALE: 1/4" = 1'-0"1BASEMENT - ENLARGED ELECTRICAL ROOM PLAN

SCALE: 1/4" = 1'-0"4PENTHOUSE - ENLARGED ELECTRICAL ROOM

SCALE: 1/8" = 1'-0"3SECOND FLOOR - PARTIAL PLAN

SCALE: 1/8" = 1'-0"2FIRST FLOOR - PARTIAL ELECTRICAL PLAN

0 168

0 84 0 168

Revisions

# Description Date

Page 3: ELECTRICAL LEGEND ABBREVIATIONS ELECTRICAL DESIGN …...not all symbols, abbrev., etc. are necessarily used on this project refer to details for mounting heights of devices ... connection

125.3

GEN-1(E) DIESEL GENSET

300KW/ [email protected] PF277Y/480V,3P,4WEMERGENCY

5.41

CONTROLS

500AT600AF

.

500.4(E)

??(E)

70.3(E)

(E) XFR

45 KVA

EM1

208Y/120V

.

.

(E) XFR

7.5 KVA

G1

480Y/277V

.

.

G1(E) PNL

PWR ZONE??KAIC

400.3(E)

400.3(E)

(E) FP-1?? HP???

SUB-BASEMENTSUB-BASEMENT

BASEMENTBASEMENT

FIRST FLRFIRST FLR

SECOND FLRSECOND FLR

THIRD FLRTHIRD FLR

FOURTH FLRFOURTH FLR

FIFTH FLRFIFTH FLR

1600 A ,480Y/277V, 3P, 4W ,42 KAIC ,100% NEUTRAL(E) MAIN SWITCHBOARD- ???

MAIN BRKRMETERPULL ?

M

1600AT1600AF GF

??(E)

.400A

.125A

400.4(E)

200.4(E)

A(E) PNL

35 KAIC

(E) XFR

75 KVA

T1

208Y/120V

.

.

(E)200AF200AS

F

B(E) PNL

??KAIC

100.4(E)

A(E) PNL

??KAIC

.600A

.250A

125.4(E)

1H(E) PNL

??KAIC

.125A

.250A

250.?(E)

(E)400A

400.3(E)

.125A

125.?(E)

(E)200A

.300A

??(E)

(E) BREW 580-CVAC FURNACE

220A

.125A

??(E)

??(E)

.100A

??(E)

.250AT400AF

??(E)

(E)??AF

F

(E) EMCO MAIER342 CNC

80A

(E)15AF30AS

F

??(E)

(E)??AF

F

??(E)

(E)??AF

F

(E) ARC MELTER200A

20.3(E)

(E) GENERATOR7.5 HP

REMOTERADIATOR

20.3(E)

400.4(E)

DPB(E) DIST

??KAIC

30.2(E)

(E) SATEC TUBEFURNACE

80A 10A(E) BREW 424-CVAC FURNACE

100A

(E) GLEEBLE1500 SYSTEM

200A

(E) FIRE PUMPDISC

400AF F

.200A

200ASPACE

.200A

.200A

.200A

.200A

.200A

.200A

.200A

.400A

SIXTH FLRSIXTH FLR

SEVENTH FLRSEVENTH FLR

EIGHT FLREIGHT FLR

NINTH FLRNINTH FLR

TENTH FLRTENTH FLR

ELEVENTH FLRELEVENTH FLR

TWELFTH FLRTWELFTH FLR

FOURTEENTH FLRFOURTEENTH

FLR

FIFTHEENTH FLRFIFTHEENTH

FLR

PENTHOUSEPENTHOUSE

ROOFROOF

0 A ,480Y/277V, 3P, 4W ,?? KAIC(E) MAIN SWITCHBOARD-- ???

DIST

EM1(E) ATS

EMERGENCY100 A3-POLE??KAIC

??

150.4(E)

(E)150AF200AS

F

EM1

??

(E) PNL

??KAIC

FP-1(E) ATS-FIRE PUMP

EMERGENCY400 A3-POLE??KAIC

??

200.4(E)

(E)200AF200AS

F

ELEC RM ??

PGEUTX

0 KVA12???V DELTA, 3P, 3W480 WYE/277VPAD-VAULT MOUNTEDUTILITY PROVIDED

?.?

125.3(E)

125.3(E)

(E) XFR

75 KVA

T2

480Y/277V

.

.

C(E) PNL

??KAIC

(E)400A

(E)100A

(E)100A

250AF400AS

F

250.?(E)

600.?(E)

2H(E) PNL

??KAIC

DPA(E) DIST

??KAIC

250.4

125.3

400.4(E)

80.4

80.4

100.3M?(E)

100.3M?(E)

(E) ELEV-125 HP

(E)100AF100AS

F

XFR

75 KVA

EM2

480Y/277V

.

.

EM2(E) ATS

EMERGENCY100 A3-POLE??KAIC

6.8

125.3

EMDP

??

(E) PNL

??KAIC

GARAGE

FIRE PUMP ROOM

60.4(D)

(E)60AF60AS

F

CS

GRAP (E)

TERM (E)

DISC-EM2125AF200AS

F

PB

CS

100.3M?(E)

100.3M?(E)

(E) ELEV-225 HP

(E)100AF100AS

F

100.3M?(E)

100.3M?(E)

(E) ELEV-325 HP

(E)100AF100AS

F

80.2(E)

(E)80AF

100AS

F

80.2M?(E)

(E) ELEVMACHINE RM

HVAC?? TONS

EM2

3.0

PNL

10 KAIC

(E)80AF

100ASF

125.3

J

4

52

3

1

67

8

9

10

11

12

8

13

15

16

14

12

TRANSFORMER SCHEDULE

15 30/3 50/3 275

C.B.FEEDERC.B.

208Y/120V SECONDARY480V PRIMARYKVA

340100/350/330

475150/370/345

1060225/3125/375

1250400/3175/3112.5

2130500/3225/3150

2665800/3350/3225

41901000/3450/3300

34801600/3800/3500 800.3

450.3

350.3

225.3

175.3

125.3

70.3

50.3

30.3

480Y/277V SECONDARY

C.B.

800/3

450/3

350/3

225/3

175/3

125/3

70/3

50/3

30/3

GND GND

#8

#8

#6

#2

#1/0

#2/0

#3/0

#3/0

#4/0

#8

#8

#6

#2

#1/0

#2/0

#3/0

#3/0

#4/0

5.

NOTES:

1.

2.

3.

4.

THIS SCHEDULE APPLIES TO 3-PHASE, 480:480Y/277V AND

480:208Y/120V DRY-TYPE STEP-DOWN TRANSFORMERS ONLY.

ON ONE-LINE DIAGRAMS AND SCHEDULES WHERE FEEDERS AND

CIRCUIT BREAKERS ARE SHOWN AS "XFR", PROVIDE RESPECTIVE

FEEDERS, GROUND CONDUCTORS AND BREAKERS NOTED ABOVE.

PROVIDE SECONDARY BREAKER NOTED ABOVE AS MAIN CIRCUIT

BREAKER INTEGRAL IN DISTRIBUTION, PANEL AND SWITCH

BOARDS, UON.

GROUND CONDUCTOR SIZES INDICATED ABOVE SUPERSEDE

GROUND CONDUCTORS SHOWN ON FEEDER SCHEDULE. ROUTE

COPPER GROUNDING CONDUCTOR TO GROUNDING ELECTRODE

PER NEC. PROVIDE BONDING ALSO PER NEC. COMMON LEAD

OF LARGEST REQUIRED SIZE MAY BE EMPLOYED TO SERVE

MULTIPLE TRANSFORMERS.

NOT ALL TRANSFORMER SIZES INDICATED IN THIS SCHEDULE

ARE NECESSARILY USED ON THIS PROJECT.

WEIGHTS INDICATED ABOVE ARE APPROXIMATE, ACTUAL VALUES

MAY VARY. CONFIRM WITH SUBMITTAL INFO.

WEIGHT

37102500/31200/3750 1200.3 1200/3 #4/0 #4/0

FEEDER

800.4

450.4

350.4

225.4

175.4

125.4

70.4

50.4

30.4

1200.4

FEEDER

1600.4

1000.4

800.4

500.4

400.4

225.4

150.4

110.4

50.4

2500.4

COPPER FEEDER SCHEDULE

(4) #2 #8 -

(3) #2 #8 -100.3

100.4

GROUNDPHASE/NEUTRALTAG

FEEDER CONDUCTORS PER SET NOTESCONDUITS

(4) 400 KCMIL #4/0 -

(3) 400 KCMIL #4/0 -

(4) 350 KCMIL #3/0 -

(3) 350 KCMIL #3/0 -

(4) 400 KCMIL #2/0 -

(3) 400 KCMIL #2/0 -

-250 KCMIL(3) 400 KCMIL

-250 KCMIL(4) 400 KCMIL

-350 KCMIL(3) 500 KCMIL

-350 KCMIL(4) 500 KCMIL

-400 KCMIL(3) 500 KCMIL

-400 KCMIL(4) 500 KCMIL

-500 KCMIL(3) 500 KCMIL

-500 KCMIL(4) 500 KCMIL

-500 KCMIL(3) 500 KCMIL

-500 KCMIL(4) 500 KCMIL

-#1/0(3) 500 KCMIL

-#1/0(4) 500 KCMIL

-#2(3) 500 KCMIL

-#2(4) 500 KCMIL

-#2(3) 3/0

-#2(4) #3/0

-#2(3) #4/0

-#2(4) #4/0

-#2(3) 250 KCMIL

-#2(4) 250 KCMIL

-#1(3) 350 KCMIL

-#1(4) 350 KCMIL

-#1/0(3) 300 KCMIL

-#1/0(4) 300 KCMIL

(4) #2/0 #6 -

(3) #3/0 #6 -

-#6(4) #3/0

(4) #4/0 #4 -

-#4(3) #4/0

(3) 250 KCMIL #4 -

-#10

-#10(4) #6

-#8(3) #4

-#8(4) #4

-#8(3) #4

-#8(4) #4

-#8(3) #2

-#8(4) #2

-#6(3) #2

-#6(4) #2

-#6(3) #1

-#6(4) #1

-#6(3) #1/0

-#6(4) #1/0

-#6(3) #2/0

-#4(4) 250 KCMIL

-#4(3) 350 KCMIL

-#4(4) 350 KCMIL

4000.4

4000.3

3500.4

3500.3

3000.4

3000.3

2500.4

2500.3

2000.4

2000.3

1600.4

1600.3

1200.4

1200.3

1000.4

1000.3

800.4

800.3

700.4

700.3

600.4

600.3

500.4

500.3

450.4

450.3

400.4

400.3

350.4

350.3

300.4

300.3

250.4

250.3

225.4

225.3

200.4

200.3

175.4

175.3

150.4

150.3

125.4

125.3

110.4

110.3

90.4

90.3

80.4

80.3

70.4

70.3

60.4

60.3

SCHD

20.3

20.4

30.3

30.4

40.3

40.4

50.3

50.4

XFR

(3) #6

(4) #6 #10 -

(3) #6 #10 -

(4) #8 #10 -

(3) #8 #10 -

(4) #10 #10 -

(3) #10 #10 -

-#12(4) #12

-#12(3) #12

NOTESCONDUCTORS PER SETFEEDER

TAG PHASE/NEUTRAL GROUNDSETSMET RNC

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

4.00"

3.00"

3.00"

4.00"

3.00"

4.00"

4.00"

3.00"

3.00"

2.50"

3.00"

2.50"

2.50"

2.50"

4.00"

4.00"

3.00"

3.00"

3.00"

MET SETS RNC

CONDUITS

3.00"

3.00"

2.50"

2.50"

2.50"

2.50"

2.00"

2.00"

2.00"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

1.00"

1.00"

1.00"

1.00"

NOTES:

7.

8.

9.

6.1.

2.

3.

4.

5.

"MET"= EMT, IMC, GRC, RAC, OR PVC COATED GRC TYPE

CONDUITS. "RNC"= PVC 40, PVC 80 OR FIBERGLASS TYPE

CONDUITS ROUTED UNDERGROUND. REFER TO SIZING ON DRAWINGS

IF "RNC" CONDUITS ARE ROUTED ABOVEGROUND. CONDUIT SIZES

NOTED ON SINGLE-LINE DIAGRAM OR ON PLANS SUPERSEDE SIZES

NOTED ABOVE IF LARGER.

OVERSIZED (173% MIN.) NEUTRAL FOR FEEDERS CONNECTED TO A

K-4 OR HIGHER RATED TRANSFORMER.

REFER TO TRANSFORMER SCHEDULE FOR STANDARD PRIMARY AND

SECONDARY FEEDER SIZES.

REFER TO MCC OR PANEL SCHEDULES FOR FEEDER SIZES TO

EQUIPMENT NOTED WITH THIS TAG.

CONDUCTORS AND CONDUITS SHOWN IN THIS SCHEDULE ARE

BASED ON COPPER CONDUCTORS WITH THHN/THWN INSULATION.

THIS SCHEDULE SHALL BE USED ON ALL FEEDERS SERVING LOADS

WHERE THE CIRCUIT BREAKER SIZE MATCHES THE AMPACITY OF

ITS FEEDER. USE THE "MOTOR CIRCUIT SCHEDULE" FOR LOADS,

SUCH AS MOTORS, PUMPS, FANS, CHILLERS, ETC., WHERE THE

CIRCUIT BREAKER SIZE IS LARGER THAN THE AMPACITY OF ITS

FEEDER.

PROVIDE GROUND WIRE NOTED ABOVE IN ALL FEEDERS AND

BRANCH CIRCUITS. WHERE MULTIPLE CONDUITS ARE INDICATED

PROVIDE NOTED GROUND WIRE IN EACH CONDUIT.

NOT ALL FEEDERS ARE NECESSARILY USED ON THIS PROJECT.

NOMINAL AMPACITIES GREATER THAN 100 AMPS ARE FOR 75

DEG..C TERMINALS.

8

9

10.75"

1.00"10.75"

1.00"10.75"

1.00"10.75"

1.00"10.75"

1.00"10.75"

1.00"10.75"

2.50"

2.50"

2.50"

2.00"

2.00"

2.00"

2.00"

1.50"

2.00"

1.50"

1.50"

1.25"

1.25"

1.25"

1.25"

1.25"

1.25"

1.25"

1.25"

1.25"

1.00"

1.00"

1.00"

1.00"

0.75"

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

111

11

10

10

7

7

8

8

6

6

5

5

4

3

4

1

1

3.50"

3.00"

3.00"

3.50"

3.50"

3.00"

3.00"

3.50"

3.00"

3.00"

3.00"

3.00"

3.00"

3.00"

3.00"

3.00"

2.50"

3.00"

3.00"

3.50"

3.00"

2.50"

2.50"

2.50"

2.50"

2.00"

2.00"

2.00"

3.50"

2.50"

3.00"

2.50"

1

1

2

2

2

2

2

2

2

2

2

2

3

3

3

TM

en

gin

ee

rsfo

ra

su

sta

ina

ble

futu

re

2014 - GLUMAC ALL RIGHTS RESERVEDTHESE DRAWINGS ARE THE PROPERTY OF

GLUMAC ARE NOT TO BEUSED OR REPRODUCED IN ANY MANNER,WITHOUT PRIOR WRITTEN PERMISSION

SHEET

JOB NO.

SHEET TITLE:

CHECKED BY:

DRAWN BY:

Project

©

Client

Job N

o.:

Conta

ct:

ww

w.g

lum

ac.c

om

900 S

W F

ifth

Ave.

, S

uit

e 1600

Port

land, O

R 9

7204-2

640

T. 503.2

27.5

280 F

. 503.2

74.7

674

7/30/2014 11:19:53 AM As indicated

E5.1

ELECTRICAL

SINGLE-LINE

DIAGRAM

Author

JJE

PSU ELEVATOR

RECONNECTION TO

GENERATOR

PORTLAND STATE

UNIVERSITY

02.14.00651

7/30/14100% CD'S/ PERMIT SET

02.1

4.0

0651

JJE

#KEYED NOTES11 PROVIDE SEPARATE LINE ITEM PRICE TO REPLACE PANEL WITH 100A, 3P, 4W,

208Y/120V, 42-POLE BUSSMAN QUIK-SPEC FUSED PANEL WITH MLO AND BREAKER SIZEAND QUANTITY TO MATCH EXISTING WITH AN ADDITIONAL (4) 20A/1P SPARE BREAKERSAND FUSES.

12 EXISTING PULLBOX LOCATION PER EXISTING SINGLE-LINE. THIS BOX HAS NOT BEENFIELD VERIFIED.

13 EXISTING PULL BOX. PROVIDE PHYSICAL BARRIER INSIDE PULLBOX TO SEPARATENORMAL POWER FROM GENERATOR POWER. USE FLEXIBLE METAL CONDUIT OR SHEETMETAL.

14 EXISTING GENERATOR REMOTE ANNUNCIATOR PANEL. CONNECT (2) EXISTINGCONDUCTORS TO ANNUNCIATOR TO ANNUNCIATE "ATS-EM2 IN EMERGENCY POSITION".LABEL WIRING.

15 EXISTING GENERATOR CONTROL TERMINAL PANEL. CONNECT GENERATOR STARTWIRING FROM PENTHOUSE ATS IN SERIES WITH EXISTING ATS GENERATOR STARTWIRING. CONNECT ATS IN EMERGENCY POSITION WIRING TO EXISTING GENERATORREMOTE ANNUNCIATOR USING EXISTING SPARE CONDUCTORS. REPROGRAMANNUNCIATOR WITH CATERPILLAR'S ASSISTANCE.

16 EXISTING EMPTY J-BOX WITH EMPTY CONDUIT. EXTEND CONDUIT TO PENTHOUSE ATSAND INSTALL GENERAOTR CONTROL AND MONITORING WIRING.

1 CONNECT FEEDER WITH CRIMP LUGS TO EXISTING BUS BARS IN GUTTER

2 REMOVE EXISTING 60A FEEDER COMPLETELY. EXISTING RISER CONDUIT IS TO BEREUSED TO SERVE NEW FEEDER TO TRANSFORMER EM2

3 DEMO EXISTING CONDUIT BELOW SLAB AND REPLACE WITH LARGER SIZE IF REQUIRED

4 MOUNT FUSED DISCONNECT ON UNISTRUT RACK NEXT TO TRANSFORMER

5 PROVIDE LINE ITEM PRICE FOR REPLACING AND INSTALLING A NEW ATS.

6 REMOVE UNUSED DISCONNECT. CLOSE ALL UNUSED HOLES WITH PLUGS.

7 PROVIDE 80A RK1 FUSES IN (E) 100A DISCONNECT

8 PROVIDE CONDUCTOR SUPPORT WEDGE TO MATCH NEW FEEDER SIZE. SUPPORTS TOBE NO MORE THAN 100' APART FOR ALL VERTICAL DROPS.

9 ROUTE CONDUIT OVERHEAD OR BELOW SLAB. CORE-DRILL SLAB AS REQUIRED IFROUTED BELOW. DO NOT ROUTE ON TOP OF FLOOR SLAB.

10 PROVIDE 1" EMT CONDUIT WITH (6) #12 CONDUCTORS OR (6) CONDUCTOR MC CABLE.(2) BLUE FOR GENERATOR START CONTACT, (2) RED FOR ATS IN EMERGENCYPOSITION, (2) BROWN AS SPARE. CONNECT AS REQUIRED TO EXISTING ATS CONTACTS.

Revisions

# Description Date

Page 4: ELECTRICAL LEGEND ABBREVIATIONS ELECTRICAL DESIGN …...not all symbols, abbrev., etc. are necessarily used on this project refer to details for mounting heights of devices ... connection

DIAGRAM HAS BEEN SIMPLIFIED TO SINGLE PHASE FOR CLARITY.

NON-K-RATED (K-1) TRANSFORMER WIRING IS THE SAME EXCEPT NEUTRAL(GROUNDED SECONDARY CONDUCTOR) IS NOT OVERSIZED.

BRANCH

GENERAL NOTES:

ELECTROSTATICSHIELD, WHENPRESENT

STEEL CONDUIT

A.

B.

>173% NEUTRAL

SUBFEED

120VAC

PHASE

GROUND

120V

AC

PR

IMA

RY

BOND TO TRANSFORMERENCLOSURE

K-RATED TRANSFORMERENCLOSURE

GROUNDINGCONDUCTOR SIZEDPER TRANSFORMERSCHEDULE

BOND TO NEARESTSTRUCTURAL STEEL PER NEC250 IF REQUIRED BY LOCALAUTHORITY HAVINGJURISDICTION

TO GROUND BAR ASINDICATED OR MSGB IF NOTINDICATED

NOTE:NEUTRAL-GROUNDCONNECTION IS MADE WITHINTHE TRANSFORMERENCLOSURE ONLY

TRANSFORMER SECONDARYLESS THAN 10' LONG

BOND BOX

POWER RECEPTACLEIN STEEL OUTLET BOX

PROVIDE ONEPER CIRCUIT

SIMILAR FOR LUMINAIRES

DIV 16 TO PROVIDE COPPERGROUND BAR WITHSEPARATE TERMINATIONSFOR EACH CONDUCTOR.

GROUND

NEUTRAL

GND

120VAC

-N-

>173%

NE

UT

RA

L

G

RO

UN

D

PANEL ENCLOSURE

BOND GROUND BAR

STEEL CONDUIT

TO MSGB

EQ

UIP

ME

NT

GR

OU

ND

PR

IMA

RY

TO

SU

BF

EE

D P

AN

EL W

ITH

SA

ME

CO

NN

EC

TIO

NS M

AIN

BR

EA

KE

R

3. CENTER ALL TEXT HORIZONTALLY

4. THIS DETAIL APPLIES TO ALL TRANSFER SWITCHES, MANUAL AND AUTOMATIC

5. DRILL HOLES ON EXTERIOR NAMEPLATES ONLY

NOTES

WIDTH AS REQUIRED, MIN. 8.5"

65 KAIC

2500A, 480Y/277V, 3P, 4-POLE

SERVES: SWBD-MTLL500

ATS-MTLL499

3"

USE "BOLD" STYLE TEXT

3/16"

3/16"

1/4"

3/16"

1/4"

3/8"

3/16"

LINE 4

LINE 3

LINE 2

LINE 1

1/4"

1/4"

LINE 6

LIFE SAFETY POWER SYSTEM

FED FROM: (N)SWBD-MTNL3003 (G)SWBD-MTGL304

3/16"

3/16"

1/4" LINE 5

3/16"

1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.

2. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. REPLACE QUESTION MARKS WITH CORRECT NUMBERS.

WIDTH AS REQUIRED, MIN 5"

2.5"

WIDTH AS REQUIRED, MIN 5"

1"

3/16"

1/4"

3/16"

3/16"

1/2"

3/16"

5/8"

1/4"

1/4"

1/4"

1/4"

3/8"

1/2"

DIST. PANEL L1A

NAMEPLATE MOUNTING LOCATION

CENTERLINE OF INNER DOOR

SECTION 2

USE "BOLD" STYLE TEXT

480V, 3P, 3W, 800A, 65KAIC

CL

CL

ADJACENT ADDITIONAL PANEL SECTIONS

AS REQUIRED

FED FROM MDS-A

DIST. PANEL CRPP1A1

USE RIVETS NOT DOUBLE-STICKTAPE FOR EXTERIOR LOCATIONS

MAIN BUS SIZE IF MAIN LUGS ONLYOR TRIP RATING OF MAIN BREAKER.

NOTES:

1.

2.

3.

4.

SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.

PROVIDE ONE NAMEPLATE FOR EACH PANEL OR MCC SECTION. WHERE SECTION NUMBER TWO AND ABOVE ARE

WITHIN SAME ROOM AND WITHIN 10' OF EACH OTHER USE THE SMALLER SIZE NAMEPLATE.

CENTER ALL TEXT HORIZONTALLY.

TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.

1"

2"

WIDTH AS REQUIRED, MIN 4"

3/16"

3/16"

1/4"

3/16"

3/16"

1/2"

WIDTH AS REQUIRED, MIN 3.5"

3/16"

1/4"

3/16"

3/16"

3/16"

1/2"

USE RIVOTS ON DIV. 16 PROVIDED ITEMS IN EXTERIORLOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHEDITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT

10 HP., 480V, 3∅

FED FROM DS1A1

EXHAUST FAN EF-1

USE "BOLD" STYLE TEXT

GENERAL EQUIPMENT

CIRCUIT BREAKERS IN DIST. PANELS

EXHAUST FAN EF-11ST FLOOR-COL. A3

DESCRIPTION OF LOAD SERVED

LOCATION OF LOAD

NOTES:

2.

3.

1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS

OF NAMEPLATES FOR DIFFERENT SYSTEMS.

TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED

TO MATCH EQUIPMENT SPECIFICATIONS.

CENTER ALL TEXT HORIZONTALLY

1/4"

1/4"

3/16"

3/16"

3/16"

3/16"

3/16"

3/16"

3/16"

3/16"

1/4"

1/4"

WIDTH AS REQUIRED, MIN. 6"

2.5"

480Y/277V, 3∅, 3W

PRIMARY FED FROM DS1A1

SECONDARY FEEDS PNL RDP1A1

TRANSFORMER TRR-1A1

USE RIVOTS NOT DOUBLE-STICK TAPE FOR ALL LOCATIONS

USE "BOLD" STYLE TEXT

75 KVA, K-13 RATED

208Y/120V, 3∅, 4W

PROVIDE ONE NAMEPLATE FOR EACH TRANSFORMER.

CENTER ALL TEXT HORIZONTALLY.

NOTES:

1.

2.

3.

4.

SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATIONAND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.

TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXTAS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.

WIDTH AS REQUIRED, 6" MIN.

1.25"1/4 "

1/4"

3 / 16 "

1/4"

5/16"

FIRE ALARM SYSTEM FAJB-1PNL??-##

1.

2.

3.

4.

NOTES:

ENGRAVE PANEL NAME AND BRANCH CIRCUITNUMBER SERVING ENCLOSURE, OMITENGRAVING IF ENCLOSURE IS NOT POWERED

USE RIVETS ON DIV. 16 PROVIDED ITEMS IN EXTERIORLOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHEDITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT

USE "BOLD" STYLE TEXT. USE WORDS, NOT ABBREVIATIONS,FOR SYSTEM NAMES AND FUNCTION

REFER TO SPECIFIACTIONS FOR FOR ADDITIONAL INFORMATION ANDCOLORS FOR DIFFERENT SYSTEMS.

PROVIDE ONE NAMEPLATE FOR EACH ENCLOSURE OR J-BOX LARGER THAN 4"

CENTER ALL TEXT HORIZONTALLY AND VERTICALLY IF ONLY ONE LINE.

TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIREDTO MATCH EQUIPMENT SPECIFICATIONS.

STN0012-22,24,26

GENERAL NOTES

A. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

B. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXTAS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.

GREENWHITE

PURPLE

AQUA

WHITE

WHITE

208/120V STANDBY

208/120V GENERATOR

15KV MEDIUM VOLTAGE

480/277V GENERATOR

CATV/ MATV

TEXT

NAMEPLATE COLOR

BLACK

WHITE

WHITE

BLACK

BACKGROUND

1

NAMEPLATE COLOR LEGEND

YELLOW

WHITE

RED

BLACK

WHITE

GREEN

GREEN

BLACK

WHITE

YELLOW

WHITE

BLUE

RED

WHITE

WHITE ORANGE

GROUND CONDUITS

480V NORMAL

208/120V NORMAL

SECURITY

TELECOM

FIRE ALARM

BMS CONTROLS

208/120V UPS

480/277V UPS

SERVICE

208/120V EMERGENCY

480/277V EMERGENCY

480/277V STANDBY

ENGRAVEDNAMEPLATES

ON POWER CONDUITS SHOWCIRCUIT NUMBERS OF ALLCIRCUITS IN J-BOX. USE 1"WIDE KROY OR BROTHERSLABELING TAPE WITH BLACK 1/2"HIGH HELVETICA BOLD LETTERINGON WHITE BACKGROUND.

2

PANEL MTES0021FED FROM: XX

10 HP., 480V, 3∅

PANEL, MCC,ENCLOSURE, ETC.

C. ROWMARK # IS THE COLOR OF THE PLASTIC ENGRAVINGMATERIAL. USE ROWMARK 1/16" ULTRAMATT AND SATINSTOCK AS NOTED.

122-932

222-582

122-942

322-402

322-402

ROWMARK #

322-704

222-324

322-602

322-992

322-407

322-542

322-602

122-612

WHITE ORANGE 122-612

GREENWHITE

WHITE

BLUE

RED

WHITE

122-932

322-542

322-602

TM

en

gin

ee

rsfo

ra

su

sta

ina

ble

futu

re

2014 - GLUMAC ALL RIGHTS RESERVED

THESE DRAWINGS ARE THE PROPERTY OF

GLUMAC ARE NOT TO BE

USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION

SHEET

JOB NO.

SHEET TITLE:

CHECKED BY:

DRAWN BY:

Project

©

Client

Job N

o.:

Conta

ct:

ww

w.g

lum

ac.c

om

900 S

W F

ifth

Ave.

, S

uit

e 1600

Port

land, O

R 9

7204-2

640

T. 503.2

27.5

280 F

. 503.2

74.7

674

7/30/2014 11:19:56 AM 1/8" = 1'-0"

E9.1

ELECTRICAL

DETAILS

LRH

JJE

PSU ELEVATOR

RECONNECTION TO

GENERATOR

PORTLAND STATE

UNIVERSITY

02.14.00651

7/30/14100% CD'S/ PERMIT SET

02.1

4.0

0651

JJE

SCALE: NONE7

TRANSFORMER/PANEL/OUTLET/LUMINAIRE WIRING (NON ISOLATED GROUND PANELS)

SCALE: NONE1TRANSFER SWITCH NAMEPLATES

SCALE: NONE3

DISTRIBUTION PANEL, MOTOR CONTROL CENTER & BRANCH PANELNAMEPLATES

SCALE: NONE6EQUIPMENT IDENTIFICATION NAMEPLATES

SCALE: NONE2TRANSFORMER NAMEPLATE

SCALE: NONE5ENCLOSURE INDENTIFICATION NAMEPLATES

SCALE: 1/8" = 1'-0"4RACEWAY AND NAMEPLATE IDENTIFICATION