DESCRIPTIONSYMBOL
POWER DEVICESDESCRIPTIONSYMBOL
DISTRIBUTION & EQUIPMENTDESCRIPTIONSYMBOL
LIGHTING
DESCRIPTIONSYMBOL
SWITCHING CONTROLS
DESCRIPTIONSYMBOL
DIAGRAMS
DESCRIPTIONSYMBOL
SIGNAL DEVICES
DESCRIPTIONSYMBOL
REFERENCE SYMBOLS
DESCRIPTIONSYMBOL
WIRING
DESCRIPTIONSYMBOL
SECURITY SYSTEM
DESCRIPTIONSYMBOL
FIRE ALARM SYSTEM
DESCRIPTIONSYMBOL
GROUNDING SYSTEM
ABBREVIATIONS ELECTRICAL DESIGN CRITERIA
ELECTRICAL DRAWING LIST
ELECTRICAL EQUIPMENT NAMING CONVENTION LEGEND
ELECTRICAL LEGEND
ELECTRICAL BASIS OF DESIGN
ELECTRICAL ADD ALTERNATES
P
15
30
15
15
R/C,F,R
P,B,R,C
D
DETAILS APPLY TO ALL APPLICABLE SITUATIONS, UON.NOT ALL DETAIL REFERENCES ARE SHOWN. ALLREFER TO DETAIL NO. ON DRAWING INDICATED
MECHANICAL EQUIPMENT IDENTIFICATION TAG
TYPE; REFER TO BRANCH CIRCUIT AND FEEDER
SHEET NOTE REFERENCE
ELEVATION TAG: REFER TO ELEVATION NUMBER ONDRAWING INDICATED
DRAWING INDICATEDSECTION TAG: REFER TO SECTION NUMBER ON
KITCHEN EQUIPMENT REFERENCE, REFER TO KITCHENEQUIPMENT SCHEDULE
BRANCH CIRCUIT OR FEEDER NOMINAL AMPACITY &
SCHEDULES FOR WIRE AND CONDUIT SIZES & QTY.
EQUIPMENT BY OTHERS IDENTIFICATION TAG
INCLUDES ALL PIPING BY DIV. 16.EARLY WARNING SMOKE DETECTION SYSTEM -
HORN - CEILING, WALL MOUNTED
FLAME DETECTOR (FLICKER DETECTOR)
LIGHT (LAMP, SIGNAL LIGHT,INDICATOR LAMP, STROBE)
FIREMAN'S PHONE JACK, WALL MOUNTED
END OF LINE RESISTOR (NOT SHOWN ON PLANS)
ADDRESSABLE MONITOR MODULE
ADDRESSABLE CONTROL MODULE
RISE AND FIXED TEMPERATURE TYPE, UON.
SPRINKLER VALVE TAMPER SWITCH CONNECTION
(# = CANDELA RATING)
STROBE LIGHT - WALL, CEILING MOUNTED
SPEAKER - WALL, CEILING MOUNTED
ALARM BELL OR GONG
WALL MOUNTED
FIRE ALARM SYSTEM ANNUNCIATOR
COMBINATION SPEAKER/STROBE, WALL MOUNTED
FIRE ALARM SYSTEM MANUAL PULL STATION,
(# = CANDELA RATING)
SPRINKLER FLOW SWITCH CONNECTION
RECEIVER, BT=BEAM TRANSMITTER)
WIDTH SAMPLING TUBES. PHOTOELECTRIC TYPE
LIGHT BEAM TYPE SMOKE DETECTOR (BR=BEAM
HEAT DETECTOR, CEILING MOUNTED. RATE OF
FIREMAN'S PHONE HANDSET, WALL MOUNTED
FIRE ALARM OUTPUT OR RELEASE ABORTPUSHBUTTON, REFER TO SPECIFICATIONS AND
COMPONENTS. PROVIDE 120V POWER AS REQUIREDFIRE ALARM CONTROL PANEL AND ASSOCIATED
OR AS INDICATED.
SMOKE DETECTOR, DUCT MOUNTED, WITH FULL
MINI HORN - WALL, CEILING MOUNTED
DETAILS.
UON.
SMOKE DETECTOR, LOW AIR VELOCITY IN DUCTMOUNTED PHOTOELECTRIC TYPE U.O.N.
SMOKE DETECTOR MOUNTED BELOW RAISED FLOOR
DATA LOOP ISOLATION MODULE
COMBINATION HORN/STROBE - WALL, CEILINGMOUNTED (# = CANDELA RATING)
COMBINATION MINI HORN/STROBE - WALL, CEILINGMOUNTED (# = CANDELA RATING)
HEAT DETECTOR (R/C=RATE OF COMBUSTION,F=FIXED TEMP. ONLY, R=RATE OF RISE ONLY)
AGENT RELEASE INITIATING VALVE
BELL SILENCE SWITCH
AGENT DISCHARGE SWITCH
ELECTROMAGNETIC DOOR HOLDER - WALL, FLOOR,DOOR CLOSURE MOUNTED. PROVIDED BY DIV. 8UON.
SMOKE DETECTOR - WALL, CEILING MOUNTED(P=PLENUM MOUNTED, B=W/RELAY BASE,R=ELEVATOR RECALL, C=INTEGRAL TO DOORCLOSURE)
FIRE/SMOKE DAMPER BY DIV 15. WIDTH OFSYMBOL WILL VARY WITH DUCT WIDTH. PROVIDEPOWER AND MONITORING AS INDICATED.
GROUND ROD LOCATION
24" GROUND BAR
LIGHTNING PROTECTION CONDUCTOR ROUTED DOWN
60" GROUND BAR
LIGHTNING PROTECTION BIMETAL CONNECTION
LIGHTNING PROTECTION BOND PLATE
GROUND GRID BOND POINT
LIGHTNING PROTECTION AIR TERMINAL
GROUND ROD IN TEST WELL
GROUND GRID BOND POINT - MECHANICALCONNECTION
GROUND GRID BOND POINT - EXOTHERMICWELD CONNECTION
LIGHTNING PROTECTION PARAPET MOUNTED AIRTERMINAL
LIGHTNING PROTECTION MID ROOF MOUNTEDAIR TERMINAL
BARE GROUNDING GRID OR CONDUCTORS, UON.
GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZEDCONDUIT, UON.
WW DIRECTION
WW DIRECTION
A1LHXFR-
A1H MMCC-
DP- U L D 1 A
A1SNHMSWBD-
EXAMPLES / LEGEND EQUIPMENT TYPE POWER SYSTEM
PNL- E H K 2 B
NOT ALL SYMBOLS, ABBREV., ETC. ARE NECESSARILY USED ON THIS PROJECT
REFER TO DETAILS FOR MOUNTING HEIGHTS OF DEVICES
BUSWAY RISER
DAMPER MOTOR
MAGNETIC MOTOR STARTER (CONTROLLER)
WITH CODE CLEARANCES SHOWN
SHOWN SIZE PER CONNECTED MOTOR SIZE AND
CONNECTION TO MOTOR PROVIDED BY OTHERS
SERVICE AND/OR DISTRIBUTION EQUIPMENT
TRANSFORMER WITH CODE CLEARANCES SHOWN
SHOWN, DASHED EQUIP. = FUTURE
BRANCH CIRCUIT PANELBOARDS, SURFACE AND
MOTOR CONTROL CENTER W/ CODE CLEARANCES
BUILDING GROUND BUS, SEE DETAILS
FUSE PER MANUFACTURER'S RECOMMENDATIONS
SURFACE AND RECESS MOUNTEDEQUIPMENT OR TERMINAL ENCLOSURE AS NOTED,
FREQUENCY DRIVE WITH INTEGRAL DISCONNECT
FUSED DISCONNECT SWITCH, SIZE AS NOTED. SIZE
RECESS MOUNTED
(CONTROLLER) OR CONTACTOR. SIZE PER
ENCLOSED CIRCUIT BREAKER DISCONNECTSWITCH, TRIP SIZE AS NOTED.
DISCONNECT SWITCH, SIZE AS NOTED OR IF NOT
MOTOR DISCONNECT SCHEDULE
CONNECTION TO DIV. 15 FURNISHED VARIABLE
DIV. 16 TO INSTALL VFD EQUIPMENT
INTEGRAL DISCONNECT THAT IS PROVIDED BY
DIV. 16 CONNECTION TO EQUIPMENT PROVIDED BYOTHERS. SHADED = ON ALT. POWER SOURCE NOTED
DIV. 16 CONNECTION TO EQUIPMENT WITH
BUSWAY STAB-IN TYPE CIRCUIT BREAKEROR FUSE DISCONNECT. SIZE AS NOTED.
OTHERS. SHADED = ON ALT. POWER SOURCE NOTED
DISCONNECT W/ MAGNETIC MOTOR STARTER
LOAD SERVED. NEMA SIZE #1 MINIMUM.
OR CONTACTOR. SIZE PER LOAD SERVED.NEMA SIZE #1 MINIMUM.
"ON ALT."
AB
STANDBY, UPS, ETC.) PER CIRCUITING INDICATED
SHADED RECEPTACLES NOTED "ON ALT." ABOVE ARE
IN RAISED FLOOR - SEE ARCH DWGS; WITH
SIMPLEX RECEPTACLE - WALL, CEILING, ON ALT.
DUPLEX RECEPTACLE - WALL, CEILING, ON ALT.
DOUBLE DUPLEX RECEPTACLE - WALL, CLG, ON ALT.
DUPLEX RECEPTACLE - WALL - HALF SWITCHED
ON ALT. POWER; NEMA CONFIGURATION AS NOTED
FLUSH FLOOR BOX DEVICE - DEVICE TYPE PERSYMBOLS ABOVE
PEDESTAL FLOOR DEVICE - DEVICE TYPE PERSYMBOLS ABOVE
TELE/POWER POLE, POWER POLE
RECEPTACLE TYPE SHOWN -WALL -ABOVE COUNTERBACKSPLASH. SEE ARCHITECTURAL DRAWINGS.
FLUSH, PEDESTAL MOUNTED.
NEUTRAL, 1 ISOLATED GROUND) NEUTRALS
POKE THRU UNIT WITH DUPLEX RECEPTACLE -
ELECTRIFIED FURNITURE. PROVIDE 8 WIRES
(4 HOTS, 1 DEDICATED NEUTRAL, 1 COMMON
RECEPT. TYPE SHOWN AT SPECIAL HEIGHT+42"
CLOCK HANGER RECEPTACLE
TWO-PIECE SURFACE METAL RACEWAY WITHRECEPTACLES AS NOTED, LENGTH AS
FITTINGS AS REQUIRED.
CONNECTED TO ALTERNATE POWER SOURCE (EMERG.,
L5-15R
COMBINATION SWITCH/DUPLEX RECEPTACLE
GFIDUPLEX RECEPTACLE - WALL - WITH INTEGRALGROUND FAULT CIRCUIT INTERRUPTER
WP RECEPT. TYPE SHOWN W/ WEATHERPROOF COVER
SPECIAL PURPOSE RECEPTACLE -WALL, CEILING
WALL MOUNTED ELECTRICAL CONNECTION TO
TO BE #10 AWG. USE LIQUID-TIGHT FLEX.
INDICATED ON THE DRAWINGS AND WITH ALL
INDICATED, LENGTH AS INDICATED ON THEDRAWINGS. PROVIDE ALL FITTINGS AS
RACEWAY WITH RECEPTACLES AND OUTLETS ASTWO OR THREE COMPARTMENT SURFACE METAL
REQUIRED.
POKE THRU UNIT WITH DOUBLE DUPLEXRECEPTACLE - FLUSH, PEDESTAL MOUNTED.
POKE THRU UNIT WITH JUNCTION BOX.RACEWAY COMPONENTS RC-700 SERIES.
COMBO POKE THRU UNIT WITH DUPLEXRECEPTACLE AND TELEPHONE OUTLET - FLUSH,
MULTI-SERVICE FLOOR BOX CAST IN CONC. OR
RECEPTACLES & SIGNAL OUTLETS AS NOTED.
PEDESTAL MOUNTED.
TELE/POWER POLE WITH WHIP CONNECTION TOELECTRIFIED FURNITURE
AND INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER
CCTV SECURITY PAN/TILT/ZOOM CAMERA
CCTV SECURITY INDOOR DOME CAMERA
CARD READER- WALL MOUNTED/MULLION MOUNTED
REQUEST TO EXIT DEVICE WALL,MULLION MOUNTED
M
INTELLIGENT CARD READER INTERFACE
ROLL-UP DOOR MOTOR CONTROL OUTPUT
LOCAL DOOR MONITOR WARNING NOISE DEVICE
DURESS PUSHBUTTON STATION
DOOR POSITION MONITOR SWITCH
ELECTRIC STRIKE
ELECTRIC LOCK/LATCH
ELECTRIC BOLT
SECURITY ELECTRONIC MOTION SENSOR
CCTV SECURITY FIXED CAMERA - WALL,CEILING
EMERGENCY DOOR RELEASE BREAK-GLASS STATION
M = MASTER STATIONINTERCOM STATION - WALL, DESK MOUNTED.
MAGNETIC LOCK
ELECTRIC POWER TRANSFER HINGE
GLASS BREAK SENSOR
SWBD - SWITCHBOARD
U - UNINTERRUPTIBLE POWER (UPS)
UTX - UTILITY MAIN TRANSFORMER
BIATS - BYPASS ISOLATION ATS
MCC - MOTOR CONTROL CENTER
XFR - TRANSFORMER
DSW - NON-FUSED DISCONNECT SW.
MTS - MANUAL TRANSFER SWITCH
CB - ENCLOSED CIRCUIT BREAKER
FSW - FUSED DISCONNECT SWITCHTYPE
PNL - BRANCH PANEL
DP - DISTRIBUTION PANEL
SUB - UNIT SUBSTATION
C - CRITICAL POWER (Hospital)
M - MAIN UTILITY SERVICE
EM - EMERGENCY POWER (Life Safety)
S - STANDBY POWER
LETTERSSEQ.
EQUIP.DESIG.
SYSTEMPOWER
SYSTEMVOLTAGE
DESIG.ADDN'L
FLOOR
Q - EQUIPMENT POWER (Hospital)
S - LIFE SAFETY POWER (Hospital)
BLANK - NORMAL LOADS
ATS - AUTOMATIC TRANSFER SWITCH
SWGR - SWITCHGEAR
D
INTEGRAL AMMETER DISPLAY
CONNECTION TO DIV. 15 CHILLER
CAPACITOR, POWER FACTOR CORRECTION, SIZE
KEY INTERLOCK
MONITORING COMMUNICATION MODULE
SHUNT TRIP UNIT, 120VAC OR VOLTAGE AS NOTED
GROUND FAULT TRIP UNIT
DRAWOUT CIRCUIT BREAKER
INDIVIDUALLY MOUNTED CIRCUIT BREAKER
FUSED SWITCH, WITH FUSE AND SWITCH AMPERE
RATINGCIRCUIT BREAKER, WITH TRIP & FRAME AMPERE
GROUNDED WYE CONNECTION
DELTA CONNECTION
LED INDICATOR LIGHT, PUSH TO TEST, R=RED
TERMINAL FOR FIELD CONNECT, SIZE & TYPE
CURRENT TRANSFORMER SHORTING TERMINAL BLOCK.
INSTALLED. SQUARE = REMOTE MOUNTEDUTILITY CO. APPROVED SOCKET WITH METER
METER: KILOWATT HOUR
METER: POWER FACTOR
FUSED VOLTAGE SENSE LEADS
NORMALLY CLOSED PUSH BUTTON
CURRENT TRANSFORMER
CLASS I = INTERMEDIATE CLASS
CONTACTOR COIL
PIPE GROUND
BATTERY GENERAL
CONTACTS
OVERLOADS
TO DESTINATION SHOWN, U.O.N.
HAND/OFF/AUTO SWITCH
BUS DUCT
IN KVAR
MECHANICAL INTERLOCK
TRANSIENT VOLTAGE SURGE SUPPRESSOR
DIGITAL METER UNIT. REFER
FUSE, HOLDER & PULLER
10
CIRCUIT BREAKER, MEDIUM VOLTAGE, DRAWOUT
SOLENOID
400AS225AF
G= GREEN, B= BLUE, Y= YELLOW, W= WHITE
SUITABLE FOR CONDUCTOR INSTALLED.
225AF100AT
POTENTIAL TRANSFORMER
BELL ALARM TRIP MODULE CONTACTS
BUS BAR
LIGHTNING SURGE ARRESTOR D= DISTRIBUTION
RELAY COIL
GENERATOR
NORMALLY OPEN CONTACTOR OR RELAY CONTACTS
RATING
NORMALLY OPEN PUSH BUTTON
CONNECTION TO GROUND
TO SPECIFICATIONS.
FIELD INSTALLED CONTROL CIRCUIT WIRING
SWITCH
RESISTOR
CONNECTOR, FEMALE AND MALE RESPECTIVELY
NORMALLY CLOSED CONTACTOR OR RELAY
IN PANEL AND BRANCH CIRCUIT SCHEDULES TO
STROKES INDICATE QUANTITY OF #12 AWG.
20A BRANCH CIRCUITS ARE NOT SHOWN ON
PROVIDE REQUIRED CIRCUITING.
CONDUCTORS, UON. NOTE: WIRING STROKES FOR
DRAWINGS. CONTRACTOR SHALL USE INFORMATION
G
T
MV MEDIUM VOLTAGE CONDUIT
BARE GROUNDING GRID OR CONDUCTORS, UON.
TELEPHONE SYSTEM CONDUIT
GC GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZEDCONDUIT, UON.
SHADED= ON ALT. POWER SOURCE (EMERG,UPS,ETC.)WIRE IN EXPOSED OR "HARD" CEILING AREAS.
JUNCTION BOXES, WALL, CEILING AND FLUSH FLOOR
BRANCH CIRCUIT SCHEDULES.
HOME RUN WIRING TO INDICATED DESTINATION,
HD1ASCHEDULES AND INFORMATION IN THE FEEDER ANDSHALL USE CIRCUIT SIZES NOTED IN RESPECTIVE
INSTALLER(S) PRIOR TO ROUGH-IN.
SIDES. TERMINATE WITH BUSHINGS. (1) 1.25" CO
PULL BOX, MIN. SIZE PER NEC., UON.
NEUTRAL
CONDUIT RUN TURNED UP THROUGH FLOOR ORCEILING. CORE & FIREPROOF AS REQUIRED.
CONDUIT STUBBED OUT AT LOCATION SHOWN.PROVIDE INSULATED BUSHING & PULLROPE.
TELEPHONE/DATA SLEEVE THROUGH WALL, ABOVE
UON. COORDINATE LOCATIONS WITH CABLE
WIRING EXTENSION POINT - CONDUIT TO MC CABLE
UNDERFLOOR RACEWAY
FLEXIBLE CONDUIT CONNECTION
GROUND
HOT
CEILING. CORE & FIREPROOF AS REQUIRED.CONDUIT RUN TURNED DOWN THROUGH FLOOR OR
CEILING. EXTEND TO ACCESSIBLE TILE CLG. BOTH
OR MANUFACTURED WIRING SYSTEM J-BOX ABOVE
MOUNTED. 4" SQ. BOX MIN., LARGER IF REQUIRED
ACCESSIBLE CEILINGS AREAS, OR EXTEND CONDUIT &
POWER CONNECTION TO DIV 15 FIRE/SMOKE DAMPER.REFER TO FSD CONNECTION DETAIL IF NOT SHOWN
L1A-1,33/4"C. MIN. OR AS OTHERWISE NOTED. CONTRACTOR
ASSISTIVE LISTENING INFRARED TRANSMITTER PANEL,
AV INPUT OUTLET, 1"C WITH 3-GANG BOX. CONDUIT
SURFACE, RECESSED MOUNTEDSIGNAL SYSTEM EQUIPMENT ENCLOSURES AS NOTED-
ACCESSIBLE TILE CEILING.1"C WITH 2-GANG BOX. CONDUIT STUBBED ABOVE
STUBBED ABOVE ACCESSIBLE TILE CEILING.
MOUNTING HEIGHT PER MOUNTING HT. DETAILTELEPHONE OUTLET - WALL, W = USE HIGHER
W
SHOWN, FIRE TREATED.TERMINAL/MOUNTING BOARD, 8' HIGH X WIDTH AS
CHIME
BUZZER
BELL
COMBO TELEPHONE/DATA OUTLET - WALL
DATA OUTLET - WALL
DUAL COIL SPEAKER - SURFACE CEILING,
PAGING SYSTEM HORN (OUTDOOR)
SPEAKER - WALL, CEILING
VOLUME CONTROL - WALL
SYSTEM CLOCK - WALL , CEILING
SYMBOLS ABOVEPEDESTAL FLOOR DEVICE - DEVICE TYPE PER
SYMBOLS ABOVEFLUSH FLOOR DEVICE - DEVICE TYPE PER
RECESSED CEILING.
PAGING OR PAGING/SOUND MASKING SPEAKER,MOUNTED ABOVE ACOUSTIC TILE CEILING.
INDICATED. SEE RISER DIAGRAM.PROVIDE 120V POWER AS REQUIRED OR ASRF COAX CABLE DISTRIBUTION AMPLIFIER.
PUSHBUTTON OR PUSHBUTTONS
RF COAX CABLE OUTLET (TV, VCR, ETC.)
RF COAX CABLE SIGNAL SPLITTER
INTERCOM STATION - WALL, DESKM = MASTER STATIONM
MICROPHONE JACK - WALL, FLOOR
COMBINATION RF COAX CABLE AND DATA OUTLET
MOUNTEDCORRIDOR/AISLE OCCUPANCY SENSOR - CEILING
360 DEGREE OCCUPANCY SENSOR - CEILING MTD.
180 DEGREE OCCUPANCY SENSOR - CEILING MTD.
OCCUPANCY SENSOR - WALL MOUNTED
PUSHBUTTON OR PUSHBUTTONS, BY DIV. 16
REMOTE MOUNTED LINE TO LOW-VOLTAGE FUSEDTRANSFORMER. CONCEAL FROM VIEW.
COMPONENTS. PROVIDE 120V OR 277V CONTROLPOWER AS REQUIRED OR AS INDICATED.
LIGHTING CONTROL PANEL AND ASSOCIATED
SINGLE POLE SWITCH (SUPERSCRIPT DENOTESSIMILARLY MARKED LUMINAIRES CONTROLLEDTOGETHER)
TWO POLE SWITCH
PHOTOCELL
TIME CLOCK
PROVIDED WITH EQUIPMENT, INSTALLED AND
THERMOSTAT - WALL, CEILING. PROVIDED BY DIV.15, INSTALLED AND WIRED BY DIV. 16
EQUIPMENT OPERATOR PUSH BUTTON STATION.
CONNECTED BY DIV. 16, UON.
EMERGENCY POWER OFF, HEAVY-DUTY, OIL-TIGHTRED MUSHROOM-HEAD PUSHBUTTON W/ GUARD.
LIGHTING CONTROL OVERIDE SWITCH, SEQ. NUMBER
LINE VOLTAGE, VARIABLE SPEED FAN CONTROL
DIMMER SWITCH. NUMBER INDICATES WATTAGERATING. IF NOT SHOWN THEN EQUAL TO LOAD.
SWITCH, PROVIDED BY DIV. 15, INSTALLEDBY DIV. 16. LOCATE ADJACENT TO ADJACENT
SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN
MOTOR-RATED THERMAL OVERLOAD SWITCH
EXPLOSION PROOF SWITCH
SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN
DIMMER SWITCH UNDER SEPARATE COVERPLATE
SWITCH IS "OFF").
TO LIGHT SWITCHES.
WEATHERPROOF SWITCH
TIMER SWITCH
SWITCH IS "ON").
KEY OPERATED SWITCH
FOUR WAY SWITCH
THREE WAY SWITCH
LOW VOLTAGE MOMENTARY CONTACT SWITCH,UPPER CASE LETTER SUPERSCRIPT INDICATESCONNECTION TO LOW VOLTAGE RELAYCONTROLLING SIMILARLY MARKED LUMINAIRES.
BASKET TYPE CABLE TRAY WITH 90 DEGREE ELBOWSHOWN
LADDER TYPE CABLE TRAY WITH 90 DEGREE ELBOWSHOWN
G
GC
1. OREGON ELECTRICAL SPECIALTY CODE (OREGON AMENDED VERSION OF 2014 NATIONALELECTRIC CODE).
2. FIRE/LIFE SAFETY CODE: 2007 IFC WITH OREGON AMMENDMENTS.
3. 2010 STATE OF OREGON STRUCTURAL SPECIALTY CODE: OREGON AMMENDED VERSION OF2009 IBC.
4. AMERICANS WITH DISABILITIES ACT, (ADA).
COMBINATION OCCUPANCY SENSOR & SWITCHGANGED UNDER A COMMON COVER PLATE.OCCUPANY SENSOR TO CONTROL ALL LUMINAIRES INROOM WITH 1/2 LIGHT REDUCTION CONTROLLED BYSWITCH, DESIGNATED BY LETTER. 2-GANG BOX WITHSINGLE-GANG MUDRING, UON SPECIFIED
3c
3A
RECESSED 2X4 LUMINAIRE
SURFACE MOUNTED 2X4 LUMINAIRE
RECESSED 1X4 LUMINAIRE
SURFACE MOUNTED 1X4 LUMINAIRE
RECESSED 2X2 LUMINAIRE
SURFACE MOUNTED 2X2 LUMINAIRE
SHADING OF ANY LUMINAIRE INDICATES CONNECTIONTO ALTERNATE POWER SOURCE (EMERGENCY, UPS,STANDBY, ETC.) PER CIRCUITING INDICATED
SUSPENDED LINEAR LUMINAIRE (SIZE VARIES)
WALL MOUNTED LINEAR LUMINAIRE (SIZE VARIES)
SUSPENDED PENDANT LUMINAIRE (SIZE VARIES)
RECESSED DOWNLIGHT, CEILING MOUNTED
SURFACE DOWNLIGHT, CEILING MOUNTED
RECESSED WALLWASH
SURFACE WALLWASH
RECESSED LINEAR WALLWASH
SURFACE LINEAR WALLWASH
RECESSED WALL MOUNTED LUMINAIRE
TRACK LIGHTING WITH HEADS AS INDICATED.
RECESSED CEILING ADJUSTABLE POINT SOURCE
SURFACE CEILING ADJUSTABLE POINT SOURCE
WALL MOUNTED LUMINAIRE
WALL MOUNTED DIRECTIONAL (SIZE VARIES)
FLUORESCENT STRIPLIGHT - POWER FEED SECTION,FEED THROUGH SECTION. LENGTH AS SHOWN.
WALL MOUNTED FLUORESCENT STRIPLIGHT
UNDERCABINET FLUORESCENT STRIPLIGHT
CONTINUOUS LINEAR SOURCE (LED, COLD CATHODE,NEON, FIBER OPTIC, ETC...)
BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEELUMINAIRE SCHEDULE FOR QUANTITY OF HEADS) -WALL, CEILING MOUNTED.
ILLUMINATED EXIT SIGN, SHADED QUADRANTINDICATES FACES, ARROWS AS SHOWN
BOLLARD
POLE MOUNTED LUMINAIRE- SINGLE OR DUAL HEAD
INDICATES ROTATED OPTICS
POST TOP MOUNTED LUMINAIRE
IN-GRADE POINT SOURCE
GARAGE LIGHTING LUMINAIRE WITH CUTOFF LOUVERS
LUMINAIRE MARKING CONVENTION LEGEND: HA = LUMINAIRE TYPE IDENTIFICATION. SEE LUMINAIRE SCHEDULE. 3c = CIRCUIT NUMBER VIA LOCAL SWITCH (LOWERCASE LETTER) THAT SERVES THE LUMINIARE. 3A = CIRCUIT NUMBER/UPPERCASE LETTER COMBINATION INDICATES LOW VOLTAGE RELAY OR LIGHTING CONTACTOR THAT SERVES THE LUMINAIRE
FC
C
DM
VFD
F
J
S
J
J
J
J
JJ
J
PTZ
CR
II
RXRX
MRIB
DS
CR
ER
EB
ML
GB
ES
EL
H
D
N
MO
TVSS
R
C
K
52
DMU
KWH
PF
BA
ST
CM
C
AM
M
GF
M
PB
JJ J
D
PA
D
V
S
CC
S
SS
S
S
B
AV
IR
M M
I I
LCP ?
ab OS
OS
OS
OS
OS
T T
TC
EPO
PC
TX
REFER TO FSD CONNECTION DETAIL.
S
S
S
S
S
S
S
S
S
S
S
S
D
D
S
S
S
S
C
12
125.4
1
E4.1
2
E4.1
3
E4.1
K112
CH
1
EQUIP NAME
STB
3
2
a
4
K
P
PL
TS
5A
5C5A,5B
XP
WP
V
T
OR1
D
(E)(F)(R)(RL)ABACUACA, AMPAFAFFAFGAIC
ALALCASATATSAUTOAUXAWGBATBGBRKRCCABCBCFMCKTCLGCOCPTCTCUDCDISCDIADIVDPDPDTDPSTDWGE,EMERGEFEMTENCLEOEOLEWCEWHFAFAAFBOFCFFFLAFLEXFPBFSDFWFUGENGFIGNDGRAPGRCHLOHPHPFHTRHZIESIBCIDIGIMCKCMILKOKWKVALTGLCPMAXMCAMFRMINMISCMLOMOMTDMTR-N-NCNEC-,NEGNEMANLNONTSNPOCODOFCI
OFOIOSPPBPH, ØPNL+,POSPRIREQDRNCRSRSTS.A.D.SECSNSOLSPDTSPSTSUBSWBDSWGRTBTDCTDOTELTYPULUONUPSUTXVVAVFDWW/W/OWPXFRXPZ", IN', FTØ><>
EXISTING TO REMAINFUTUREEXISTING TO BE REMOVEDEXISTING TO BE RELOCATEDABOVE COUNTER BACKSPLASHAIR CONDITIONING UNITALTERNATING CURRENTAMPERESAMPERE (RATED) FUSE OR CB FRAMEABOVE FINISHED FLOORABOVE FINISHED GRADEEQUIPMENT SHORT CIRCUIT INTERRUPTRATING (RMS SYM. AMPS)ALUMINUM (ALLOY)AUTOMATIC LIGHTING CONTROLAMPERE (RATED) SWITCHCIRCUIT BRKR TRIP SETTING (AMPS)AUTOMATIC TRANSFER SWITCHAUTOMATICAUXILIARYAMERICAN WIRE GAUGEBATTERYBELOW GRADECIRCUIT BREAKERCONDUIT (CIRCULAR RACEWAY)CABINETCIRCUIT BREAKERCUBIC FEET PER MINUTECIRCUITCEILINGCONDUIT ONLYCONTROL POWER TRANSFORMERCURRENT TRANSFORMERCOPPERDIRECT CURRENTDISCONNECTDIAMETERDIVISIONDISTRIBUTION PANELDOUBLE POLE DOUBLE THROWDOUBLE POLE SINGLE THROWDRAWINGEMERGENCYEXHAUST FANELECTRICAL METALLIC TUBINGENCLOSUREELECTRICALLY OPERATEDEND OF LINEELECTRIC WATER COOLERELECTRIC WATER HEATERFIRE ALARMFIRE ALARM ANNUNCIATORFURNISHED BY OTHERSFOOT CANDLESFLUSH FLOOR MOUNTEDFULL LOAD AMPERESFLEXIBLEFAN POWERED BOXFIRE/SMOKE DAMPERFLUSH WALL MOUNTEDFUSEGENERATORGROUND FAULT CIRCUIT INTERRUPTERGROUNDGENERATOR REMOTE ANNUNCIATOR PNLGALVANIZED RIGID STEEL CONDUITHANDLE LOCK-ON(OFF)HORSEPOWERHIGH POWER FACTORHEATERHERTZ (CYCLES PER SECOND)ILLUMINATING ENGINEERING SOCIETYINDIVIDUAL BRANCH CIRCUITINSIDE DIAMETERISOLATED GROUNDINTERMEDIATE METAL CONDUITTHOUSAND CIRCULAR MILSKNOCK OUTKILOWATTSKILOVOLT-AMPERESLIGHTINGLIGHTING CONTROL PANELMAXIMUMMINIMUM CIRCUIT AMPERESMANUFACTURERMINIMUMMISCELLANEOUSMAIN LUGS ONLYMANUAL OPERATORMOUNTEDMOTORNEUTRAL (GROUNDED CONDUCTOR)NORMALLY CLOSEDNATIONAL ELECTRICAL CODENEGATIVENATIONAL ELECTRICAL MFGR'S ASSOC.NIGHT LIGHT (UNSWITCHED)NORMALLY OPENNOT TO SCALENAMEPLATEON CENTEROUTSIDE DIAMETEROWNER FURNISHED CONTRACTORINSTALLEDOWNER FURNISHED, OWNER INSTALLEDOCCUPANCY SENSORPOLEPUSHBUTTONPHASEPANELPOSITIVEPRIMARYREQUIREDRIGID NON-METALLIC CONDUIT (PVC)RAPID STARTREMOTE STATION TRANSMITTERSEE ARCHITECTURAL DRAWINGSSECONDARYSHEET NOTESOLENOIDSINGLE POLE DOUBLE THROWSINGLE POLE SINGLE THROWSUBSTATIONSWITCHBOARDSWITCHGEARTERMINAL BOARDTIME DELAY CLOSINGTIME DELAY OPENINGTELEPHONETYPICALUNDERWRITERS LABUNLESS OTHERWISE NOTEDUNINTERRUPTIBLE POWER SUPPLYUTILITY TRANSFORMERVOLTSVOLT-AMPERESVARIABLE FREQUENCY DRIVEWATTWITHWITHOUTWEATHERPROOF, SEE RECEPT. SYMBOLTRANSFORMEREXPLOSION PROOFZONEINCHESFEETPHASEGREATER THANLESS THANGREATER THAN OR EQUAL TO
(E)
(D)
(F)
NEW WORK
WIRING CONCEALED IN FLOOR OR UNDER GRADEOR ROUTED IN CEILING SPACE OF FLOOR BELOW.
EXISTING WORK TO REMAIN
EXISTING WORK TO BE REMOVED
FUTURE WORK
1. THE EXISTING OLD GENERATOR, LOCATED IN THE PENTHOUSE AND SERVING THEBUILDING'S ELEVATORS, WAS REMOVED. THIS PROJECT IS TO RECONNECT THEEXISTING ATS SERVING THE ELEVATORS TO THE RECENTLY ADDED GENERATORLOCATED IN THE SUB-BASEMENT..
2. DUE TO SELECTIVE COORDINATION REQUIRMENTS OF THE 2014 NATIONAL ELECTRICCODE, THE EXISTING PENTHOUSE EMERGENCY PANEL EM2 WAS REPLACED WITH AFUSED PANELBOARD AND ONLY ONE ELEVATOR CAN BE OPERATED WHILE OPERATINGON THE GENERATOR..
3. PSU HAS CONFIRMED THAT THE ELEVATOR CONTROLLER IS LAREADY PROGRAMMEDTO ALLOW ONLY ONE ELEVATOR TO OPERATE AT ONE TIME WHILE ON EMERGENCYPOWER. .
4. SOME WALLS WILL NEED TO BE REMOVED TO ALLOW ACCESS TO THE EXISTINGCONDUIT RISER THAT IS PART OF THIS PROJECT. THE OWNER WILL PROVIDE DEMOAND PATCHING OF THOSE WALLS. FIRE AND WATER PROOFING OF ANY NEW FLOOR ORFIRE RATED WALL PENETRATIONS ARE PART OF THE ELECTRICAL CONTRACTORSSCOPE OF WORK..
5. SHORT CIRCUIT FAULT CURRENT CALCULATIONS AND A COORDINATION STUDY OFBREAKERS AND FUSES WERE PERFORMED.
1. ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO REPLACE ANDRECONNECT EXISTING PANEL EM2 INI THE PENTHOUSE PER THE NOTE ON THESINGLE-LINE DIAGRAM..
2. ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO PROVIDE A NEW 400A, 4P,208Y,120V ATS IN PLACE OF THE EXISTING ONE.
TM
en
gin
ee
rsfo
ra
su
sta
ina
ble
futu
re
2014 - GLUMAC ALL RIGHTS RESERVEDTHESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BEUSED OR REPRODUCED IN ANY MANNER,WITHOUT PRIOR WRITTEN PERMISSION
SHEET
JOB NO.
SHEET TITLE:
CHECKED BY:
DRAWN BY:
Project
©
Client
Job N
o.:
Conta
ct:
ww
w.g
lum
ac.c
om
900 S
W F
ifth
Ave.
, S
uit
e 1600
Port
land, O
R 9
7204-2
640
T. 503.2
27.5
280 F
. 503.2
74.7
674
7/30/2014 11:19:18 AM 12" = 1'-0"
E0.1
LEGENDS,
ABBREVIATIONA
AND DRAWING
LIST
Author
LRH
PSU ELEVATOR
RECONNECTION TO
GENERATOR
PORTLAND STATE
UNIVERSITY
02.14.00651
7/30/14100% CD'S/ PERMIT SET
02.1
4.0
0651
LR
H
E0.1 LEGENDS, ABBREVIATIONA AND DRAWING LIST
E3.1 PARTIAL FLOOR PLANS - POWER PLAN
E5.1 ELECTRICAL SINGLE-LINE DIAGRAM
E9.1 ELECTRICAL DETAILS
Revisions
# Description Date
(E) PNL- EMDP
(E) XFR-EM1
(E) ATS-EM1
(E) DISC-EM1
(E) PNL- EM1
(E) 400ADISC-FIRE
PUMP
(E) GENSET TERMINAL CABINET
(E) PULL BOX
(E) CONDUIT SERVINGPENTHOUSE PANEL-EM2.DEMO CONDUCTORS.PROVIDE LABEL ONCONDUIT AS "SPARECONDUIT" USING KROY3/4" LABEL
PROVIDE FEEDER TO (E)PULL BOX FOR ROUTING OFFEEDER TO XFR-EM2
(E) PANEL-EM2 FEEDER RISER CONDUIT
PROVIDE CONTROL WIRINGAND CONDUIT TOPENTHOUSE ATS. CONNECTTO (E) GENERATORCONTROLS
PROVIDE SEPARATION BETWEEN EMERGENCY AND NORMAL FEEDERS
DISC-EM2
PNL- EM2(E)
DISC-UNUSED
(E) ATS-EM2
(E) DISCPNL-EM2
(E) DISCELEV-MECH
XFR-EM2
DISC-EM2
ROUTE PRIMARY CONDUITUNDER SLAB.CORE DRILLAS REQUIRED
ROUTE SECONDARY EMTCONDUIT OVERHEAD ASREQUIRED.
MOUNT DISCONNECT ON UNISTRUT FRAME
(E) EMPTY J-BOX AND CONDUIT.EXTEND 1" CONDUIT TO PENTHOUSEAND PROVIDE CONTROL WIRING PERSINGLE-LINE DIAGRAM
ROUTE CONTROL CONDUIT NEXT TOEXISTING CONDUIT RISERS. PROVIDEWATER AND FIRE PROOFING ATPENETRATION
(E) GRAP-1
CONNECT (E) SPARE WIRING TOTHIS (E) GENERATOR REMOTEANNUNCIATOR. PROGRAM ASREQUIRED TO ALLOW PENTHOUSEATS "ATS IN EMERGENCY" STATUSTO DISPLAY. ADD LABELS TODISPLAY PANEL
TM
en
gin
ee
rsfo
ra
su
sta
ina
ble
futu
re
2014 - GLUMAC ALL RIGHTS RESERVEDTHESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BEUSED OR REPRODUCED IN ANY MANNER,WITHOUT PRIOR WRITTEN PERMISSION
SHEET
JOB NO.
SHEET TITLE:
CHECKED BY:
DRAWN BY:
Project
©
Client
Job N
o.:
Conta
ct:
ww
w.g
lum
ac.c
om
900 S
W F
ifth
Ave.
, S
uit
e 1600
Port
land, O
R 9
7204-2
640
T. 503.2
27.5
280 F
. 503.2
74.7
674
7/30/2014 11:19:26 AM As indicated
E3.1
PARTIAL
FLOOR PLANS -
POWER PLAN
LRH
JJE
PSU ELEVATOR
RECONNECTION TO
GENERATOR
PORTLAND STATE
UNIVERSITY
02.14.00651
7/30/14100% CD'S/ PERMIT SET
02.1
4.0
0651
JJE
0 84
SCALE: 1/4" = 1'-0"1BASEMENT - ENLARGED ELECTRICAL ROOM PLAN
SCALE: 1/4" = 1'-0"4PENTHOUSE - ENLARGED ELECTRICAL ROOM
SCALE: 1/8" = 1'-0"3SECOND FLOOR - PARTIAL PLAN
SCALE: 1/8" = 1'-0"2FIRST FLOOR - PARTIAL ELECTRICAL PLAN
0 168
0 84 0 168
Revisions
# Description Date
125.3
GEN-1(E) DIESEL GENSET
300KW/ [email protected] PF277Y/480V,3P,4WEMERGENCY
5.41
CONTROLS
500AT600AF
.
500.4(E)
??(E)
70.3(E)
(E) XFR
45 KVA
EM1
208Y/120V
.
.
(E) XFR
7.5 KVA
G1
480Y/277V
.
.
G1(E) PNL
PWR ZONE??KAIC
400.3(E)
400.3(E)
(E) FP-1?? HP???
SUB-BASEMENTSUB-BASEMENT
BASEMENTBASEMENT
FIRST FLRFIRST FLR
SECOND FLRSECOND FLR
THIRD FLRTHIRD FLR
FOURTH FLRFOURTH FLR
FIFTH FLRFIFTH FLR
1600 A ,480Y/277V, 3P, 4W ,42 KAIC ,100% NEUTRAL(E) MAIN SWITCHBOARD- ???
MAIN BRKRMETERPULL ?
M
1600AT1600AF GF
??(E)
.400A
.125A
400.4(E)
200.4(E)
A(E) PNL
35 KAIC
(E) XFR
75 KVA
T1
208Y/120V
.
.
(E)200AF200AS
F
B(E) PNL
??KAIC
100.4(E)
A(E) PNL
??KAIC
.600A
.250A
125.4(E)
1H(E) PNL
??KAIC
.125A
.250A
250.?(E)
(E)400A
400.3(E)
.125A
125.?(E)
(E)200A
.300A
??(E)
(E) BREW 580-CVAC FURNACE
220A
.125A
??(E)
??(E)
.100A
??(E)
.250AT400AF
??(E)
(E)??AF
F
(E) EMCO MAIER342 CNC
80A
(E)15AF30AS
F
??(E)
(E)??AF
F
??(E)
(E)??AF
F
(E) ARC MELTER200A
20.3(E)
(E) GENERATOR7.5 HP
REMOTERADIATOR
20.3(E)
400.4(E)
DPB(E) DIST
??KAIC
30.2(E)
(E) SATEC TUBEFURNACE
80A 10A(E) BREW 424-CVAC FURNACE
100A
(E) GLEEBLE1500 SYSTEM
200A
(E) FIRE PUMPDISC
400AF F
.200A
200ASPACE
.200A
.200A
.200A
.200A
.200A
.200A
.200A
.400A
SIXTH FLRSIXTH FLR
SEVENTH FLRSEVENTH FLR
EIGHT FLREIGHT FLR
NINTH FLRNINTH FLR
TENTH FLRTENTH FLR
ELEVENTH FLRELEVENTH FLR
TWELFTH FLRTWELFTH FLR
FOURTEENTH FLRFOURTEENTH
FLR
FIFTHEENTH FLRFIFTHEENTH
FLR
PENTHOUSEPENTHOUSE
ROOFROOF
0 A ,480Y/277V, 3P, 4W ,?? KAIC(E) MAIN SWITCHBOARD-- ???
DIST
EM1(E) ATS
EMERGENCY100 A3-POLE??KAIC
??
150.4(E)
(E)150AF200AS
F
EM1
??
(E) PNL
??KAIC
FP-1(E) ATS-FIRE PUMP
EMERGENCY400 A3-POLE??KAIC
??
200.4(E)
(E)200AF200AS
F
ELEC RM ??
PGEUTX
0 KVA12???V DELTA, 3P, 3W480 WYE/277VPAD-VAULT MOUNTEDUTILITY PROVIDED
?.?
125.3(E)
125.3(E)
(E) XFR
75 KVA
T2
480Y/277V
.
.
C(E) PNL
??KAIC
(E)400A
(E)100A
(E)100A
250AF400AS
F
250.?(E)
600.?(E)
2H(E) PNL
??KAIC
DPA(E) DIST
??KAIC
250.4
125.3
400.4(E)
80.4
80.4
100.3M?(E)
100.3M?(E)
(E) ELEV-125 HP
(E)100AF100AS
F
XFR
75 KVA
EM2
480Y/277V
.
.
EM2(E) ATS
EMERGENCY100 A3-POLE??KAIC
6.8
125.3
EMDP
??
(E) PNL
??KAIC
GARAGE
FIRE PUMP ROOM
60.4(D)
(E)60AF60AS
F
CS
GRAP (E)
TERM (E)
DISC-EM2125AF200AS
F
PB
CS
100.3M?(E)
100.3M?(E)
(E) ELEV-225 HP
(E)100AF100AS
F
100.3M?(E)
100.3M?(E)
(E) ELEV-325 HP
(E)100AF100AS
F
80.2(E)
(E)80AF
100AS
F
80.2M?(E)
(E) ELEVMACHINE RM
HVAC?? TONS
EM2
3.0
PNL
10 KAIC
(E)80AF
100ASF
125.3
J
4
52
3
1
67
8
9
10
11
12
8
13
15
16
14
12
TRANSFORMER SCHEDULE
15 30/3 50/3 275
C.B.FEEDERC.B.
208Y/120V SECONDARY480V PRIMARYKVA
340100/350/330
475150/370/345
1060225/3125/375
1250400/3175/3112.5
2130500/3225/3150
2665800/3350/3225
41901000/3450/3300
34801600/3800/3500 800.3
450.3
350.3
225.3
175.3
125.3
70.3
50.3
30.3
480Y/277V SECONDARY
C.B.
800/3
450/3
350/3
225/3
175/3
125/3
70/3
50/3
30/3
GND GND
#8
#8
#6
#2
#1/0
#2/0
#3/0
#3/0
#4/0
#8
#8
#6
#2
#1/0
#2/0
#3/0
#3/0
#4/0
5.
NOTES:
1.
2.
3.
4.
THIS SCHEDULE APPLIES TO 3-PHASE, 480:480Y/277V AND
480:208Y/120V DRY-TYPE STEP-DOWN TRANSFORMERS ONLY.
ON ONE-LINE DIAGRAMS AND SCHEDULES WHERE FEEDERS AND
CIRCUIT BREAKERS ARE SHOWN AS "XFR", PROVIDE RESPECTIVE
FEEDERS, GROUND CONDUCTORS AND BREAKERS NOTED ABOVE.
PROVIDE SECONDARY BREAKER NOTED ABOVE AS MAIN CIRCUIT
BREAKER INTEGRAL IN DISTRIBUTION, PANEL AND SWITCH
BOARDS, UON.
GROUND CONDUCTOR SIZES INDICATED ABOVE SUPERSEDE
GROUND CONDUCTORS SHOWN ON FEEDER SCHEDULE. ROUTE
COPPER GROUNDING CONDUCTOR TO GROUNDING ELECTRODE
PER NEC. PROVIDE BONDING ALSO PER NEC. COMMON LEAD
OF LARGEST REQUIRED SIZE MAY BE EMPLOYED TO SERVE
MULTIPLE TRANSFORMERS.
NOT ALL TRANSFORMER SIZES INDICATED IN THIS SCHEDULE
ARE NECESSARILY USED ON THIS PROJECT.
WEIGHTS INDICATED ABOVE ARE APPROXIMATE, ACTUAL VALUES
MAY VARY. CONFIRM WITH SUBMITTAL INFO.
WEIGHT
37102500/31200/3750 1200.3 1200/3 #4/0 #4/0
FEEDER
800.4
450.4
350.4
225.4
175.4
125.4
70.4
50.4
30.4
1200.4
FEEDER
1600.4
1000.4
800.4
500.4
400.4
225.4
150.4
110.4
50.4
2500.4
COPPER FEEDER SCHEDULE
(4) #2 #8 -
(3) #2 #8 -100.3
100.4
GROUNDPHASE/NEUTRALTAG
FEEDER CONDUCTORS PER SET NOTESCONDUITS
(4) 400 KCMIL #4/0 -
(3) 400 KCMIL #4/0 -
(4) 350 KCMIL #3/0 -
(3) 350 KCMIL #3/0 -
(4) 400 KCMIL #2/0 -
(3) 400 KCMIL #2/0 -
-250 KCMIL(3) 400 KCMIL
-250 KCMIL(4) 400 KCMIL
-350 KCMIL(3) 500 KCMIL
-350 KCMIL(4) 500 KCMIL
-400 KCMIL(3) 500 KCMIL
-400 KCMIL(4) 500 KCMIL
-500 KCMIL(3) 500 KCMIL
-500 KCMIL(4) 500 KCMIL
-500 KCMIL(3) 500 KCMIL
-500 KCMIL(4) 500 KCMIL
-#1/0(3) 500 KCMIL
-#1/0(4) 500 KCMIL
-#2(3) 500 KCMIL
-#2(4) 500 KCMIL
-#2(3) 3/0
-#2(4) #3/0
-#2(3) #4/0
-#2(4) #4/0
-#2(3) 250 KCMIL
-#2(4) 250 KCMIL
-#1(3) 350 KCMIL
-#1(4) 350 KCMIL
-#1/0(3) 300 KCMIL
-#1/0(4) 300 KCMIL
(4) #2/0 #6 -
(3) #3/0 #6 -
-#6(4) #3/0
(4) #4/0 #4 -
-#4(3) #4/0
(3) 250 KCMIL #4 -
-#10
-#10(4) #6
-#8(3) #4
-#8(4) #4
-#8(3) #4
-#8(4) #4
-#8(3) #2
-#8(4) #2
-#6(3) #2
-#6(4) #2
-#6(3) #1
-#6(4) #1
-#6(3) #1/0
-#6(4) #1/0
-#6(3) #2/0
-#4(4) 250 KCMIL
-#4(3) 350 KCMIL
-#4(4) 350 KCMIL
4000.4
4000.3
3500.4
3500.3
3000.4
3000.3
2500.4
2500.3
2000.4
2000.3
1600.4
1600.3
1200.4
1200.3
1000.4
1000.3
800.4
800.3
700.4
700.3
600.4
600.3
500.4
500.3
450.4
450.3
400.4
400.3
350.4
350.3
300.4
300.3
250.4
250.3
225.4
225.3
200.4
200.3
175.4
175.3
150.4
150.3
125.4
125.3
110.4
110.3
90.4
90.3
80.4
80.3
70.4
70.3
60.4
60.3
SCHD
20.3
20.4
30.3
30.4
40.3
40.4
50.3
50.4
XFR
(3) #6
(4) #6 #10 -
(3) #6 #10 -
(4) #8 #10 -
(3) #8 #10 -
(4) #10 #10 -
(3) #10 #10 -
-#12(4) #12
-#12(3) #12
NOTESCONDUCTORS PER SETFEEDER
TAG PHASE/NEUTRAL GROUNDSETSMET RNC
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
3.00"
3.00"
4.00"
3.00"
4.00"
4.00"
3.00"
3.00"
2.50"
3.00"
2.50"
2.50"
2.50"
4.00"
4.00"
3.00"
3.00"
3.00"
MET SETS RNC
CONDUITS
3.00"
3.00"
2.50"
2.50"
2.50"
2.50"
2.00"
2.00"
2.00"
1.50"
1.50"
1.50"
1.50"
1.50"
1.50"
1.50"
1.50"
1.50"
1.50"
1.50"
1.50"
1.00"
1.00"
1.00"
1.00"
NOTES:
7.
8.
9.
6.1.
2.
3.
4.
5.
"MET"= EMT, IMC, GRC, RAC, OR PVC COATED GRC TYPE
CONDUITS. "RNC"= PVC 40, PVC 80 OR FIBERGLASS TYPE
CONDUITS ROUTED UNDERGROUND. REFER TO SIZING ON DRAWINGS
IF "RNC" CONDUITS ARE ROUTED ABOVEGROUND. CONDUIT SIZES
NOTED ON SINGLE-LINE DIAGRAM OR ON PLANS SUPERSEDE SIZES
NOTED ABOVE IF LARGER.
OVERSIZED (173% MIN.) NEUTRAL FOR FEEDERS CONNECTED TO A
K-4 OR HIGHER RATED TRANSFORMER.
REFER TO TRANSFORMER SCHEDULE FOR STANDARD PRIMARY AND
SECONDARY FEEDER SIZES.
REFER TO MCC OR PANEL SCHEDULES FOR FEEDER SIZES TO
EQUIPMENT NOTED WITH THIS TAG.
CONDUCTORS AND CONDUITS SHOWN IN THIS SCHEDULE ARE
BASED ON COPPER CONDUCTORS WITH THHN/THWN INSULATION.
THIS SCHEDULE SHALL BE USED ON ALL FEEDERS SERVING LOADS
WHERE THE CIRCUIT BREAKER SIZE MATCHES THE AMPACITY OF
ITS FEEDER. USE THE "MOTOR CIRCUIT SCHEDULE" FOR LOADS,
SUCH AS MOTORS, PUMPS, FANS, CHILLERS, ETC., WHERE THE
CIRCUIT BREAKER SIZE IS LARGER THAN THE AMPACITY OF ITS
FEEDER.
PROVIDE GROUND WIRE NOTED ABOVE IN ALL FEEDERS AND
BRANCH CIRCUITS. WHERE MULTIPLE CONDUITS ARE INDICATED
PROVIDE NOTED GROUND WIRE IN EACH CONDUIT.
NOT ALL FEEDERS ARE NECESSARILY USED ON THIS PROJECT.
NOMINAL AMPACITIES GREATER THAN 100 AMPS ARE FOR 75
DEG..C TERMINALS.
8
9
10.75"
1.00"10.75"
1.00"10.75"
1.00"10.75"
1.00"10.75"
1.00"10.75"
1.00"10.75"
2.50"
2.50"
2.50"
2.00"
2.00"
2.00"
2.00"
1.50"
2.00"
1.50"
1.50"
1.25"
1.25"
1.25"
1.25"
1.25"
1.25"
1.25"
1.25"
1.25"
1.00"
1.00"
1.00"
1.00"
0.75"
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
111
11
10
10
7
7
8
8
6
6
5
5
4
3
4
1
1
3.50"
3.00"
3.00"
3.50"
3.50"
3.00"
3.00"
3.50"
3.00"
3.00"
3.00"
3.00"
3.00"
3.00"
3.00"
3.00"
2.50"
3.00"
3.00"
3.50"
3.00"
2.50"
2.50"
2.50"
2.50"
2.00"
2.00"
2.00"
3.50"
2.50"
3.00"
2.50"
1
1
2
2
2
2
2
2
2
2
2
2
3
3
3
TM
en
gin
ee
rsfo
ra
su
sta
ina
ble
futu
re
2014 - GLUMAC ALL RIGHTS RESERVEDTHESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BEUSED OR REPRODUCED IN ANY MANNER,WITHOUT PRIOR WRITTEN PERMISSION
SHEET
JOB NO.
SHEET TITLE:
CHECKED BY:
DRAWN BY:
Project
©
Client
Job N
o.:
Conta
ct:
ww
w.g
lum
ac.c
om
900 S
W F
ifth
Ave.
, S
uit
e 1600
Port
land, O
R 9
7204-2
640
T. 503.2
27.5
280 F
. 503.2
74.7
674
7/30/2014 11:19:53 AM As indicated
E5.1
ELECTRICAL
SINGLE-LINE
DIAGRAM
Author
JJE
PSU ELEVATOR
RECONNECTION TO
GENERATOR
PORTLAND STATE
UNIVERSITY
02.14.00651
7/30/14100% CD'S/ PERMIT SET
02.1
4.0
0651
JJE
#KEYED NOTES11 PROVIDE SEPARATE LINE ITEM PRICE TO REPLACE PANEL WITH 100A, 3P, 4W,
208Y/120V, 42-POLE BUSSMAN QUIK-SPEC FUSED PANEL WITH MLO AND BREAKER SIZEAND QUANTITY TO MATCH EXISTING WITH AN ADDITIONAL (4) 20A/1P SPARE BREAKERSAND FUSES.
12 EXISTING PULLBOX LOCATION PER EXISTING SINGLE-LINE. THIS BOX HAS NOT BEENFIELD VERIFIED.
13 EXISTING PULL BOX. PROVIDE PHYSICAL BARRIER INSIDE PULLBOX TO SEPARATENORMAL POWER FROM GENERATOR POWER. USE FLEXIBLE METAL CONDUIT OR SHEETMETAL.
14 EXISTING GENERATOR REMOTE ANNUNCIATOR PANEL. CONNECT (2) EXISTINGCONDUCTORS TO ANNUNCIATOR TO ANNUNCIATE "ATS-EM2 IN EMERGENCY POSITION".LABEL WIRING.
15 EXISTING GENERATOR CONTROL TERMINAL PANEL. CONNECT GENERATOR STARTWIRING FROM PENTHOUSE ATS IN SERIES WITH EXISTING ATS GENERATOR STARTWIRING. CONNECT ATS IN EMERGENCY POSITION WIRING TO EXISTING GENERATORREMOTE ANNUNCIATOR USING EXISTING SPARE CONDUCTORS. REPROGRAMANNUNCIATOR WITH CATERPILLAR'S ASSISTANCE.
16 EXISTING EMPTY J-BOX WITH EMPTY CONDUIT. EXTEND CONDUIT TO PENTHOUSE ATSAND INSTALL GENERAOTR CONTROL AND MONITORING WIRING.
1 CONNECT FEEDER WITH CRIMP LUGS TO EXISTING BUS BARS IN GUTTER
2 REMOVE EXISTING 60A FEEDER COMPLETELY. EXISTING RISER CONDUIT IS TO BEREUSED TO SERVE NEW FEEDER TO TRANSFORMER EM2
3 DEMO EXISTING CONDUIT BELOW SLAB AND REPLACE WITH LARGER SIZE IF REQUIRED
4 MOUNT FUSED DISCONNECT ON UNISTRUT RACK NEXT TO TRANSFORMER
5 PROVIDE LINE ITEM PRICE FOR REPLACING AND INSTALLING A NEW ATS.
6 REMOVE UNUSED DISCONNECT. CLOSE ALL UNUSED HOLES WITH PLUGS.
7 PROVIDE 80A RK1 FUSES IN (E) 100A DISCONNECT
8 PROVIDE CONDUCTOR SUPPORT WEDGE TO MATCH NEW FEEDER SIZE. SUPPORTS TOBE NO MORE THAN 100' APART FOR ALL VERTICAL DROPS.
9 ROUTE CONDUIT OVERHEAD OR BELOW SLAB. CORE-DRILL SLAB AS REQUIRED IFROUTED BELOW. DO NOT ROUTE ON TOP OF FLOOR SLAB.
10 PROVIDE 1" EMT CONDUIT WITH (6) #12 CONDUCTORS OR (6) CONDUCTOR MC CABLE.(2) BLUE FOR GENERATOR START CONTACT, (2) RED FOR ATS IN EMERGENCYPOSITION, (2) BROWN AS SPARE. CONNECT AS REQUIRED TO EXISTING ATS CONTACTS.
Revisions
# Description Date
DIAGRAM HAS BEEN SIMPLIFIED TO SINGLE PHASE FOR CLARITY.
NON-K-RATED (K-1) TRANSFORMER WIRING IS THE SAME EXCEPT NEUTRAL(GROUNDED SECONDARY CONDUCTOR) IS NOT OVERSIZED.
BRANCH
GENERAL NOTES:
ELECTROSTATICSHIELD, WHENPRESENT
STEEL CONDUIT
A.
B.
>173% NEUTRAL
SUBFEED
120VAC
PHASE
GROUND
120V
AC
PR
IMA
RY
BOND TO TRANSFORMERENCLOSURE
K-RATED TRANSFORMERENCLOSURE
GROUNDINGCONDUCTOR SIZEDPER TRANSFORMERSCHEDULE
BOND TO NEARESTSTRUCTURAL STEEL PER NEC250 IF REQUIRED BY LOCALAUTHORITY HAVINGJURISDICTION
TO GROUND BAR ASINDICATED OR MSGB IF NOTINDICATED
NOTE:NEUTRAL-GROUNDCONNECTION IS MADE WITHINTHE TRANSFORMERENCLOSURE ONLY
TRANSFORMER SECONDARYLESS THAN 10' LONG
BOND BOX
POWER RECEPTACLEIN STEEL OUTLET BOX
PROVIDE ONEPER CIRCUIT
SIMILAR FOR LUMINAIRES
DIV 16 TO PROVIDE COPPERGROUND BAR WITHSEPARATE TERMINATIONSFOR EACH CONDUCTOR.
GROUND
NEUTRAL
GND
120VAC
-N-
>173%
NE
UT
RA
L
G
RO
UN
D
PANEL ENCLOSURE
BOND GROUND BAR
STEEL CONDUIT
TO MSGB
EQ
UIP
ME
NT
GR
OU
ND
PR
IMA
RY
TO
SU
BF
EE
D P
AN
EL W
ITH
SA
ME
CO
NN
EC
TIO
NS M
AIN
BR
EA
KE
R
3. CENTER ALL TEXT HORIZONTALLY
4. THIS DETAIL APPLIES TO ALL TRANSFER SWITCHES, MANUAL AND AUTOMATIC
5. DRILL HOLES ON EXTERIOR NAMEPLATES ONLY
NOTES
WIDTH AS REQUIRED, MIN. 8.5"
65 KAIC
2500A, 480Y/277V, 3P, 4-POLE
SERVES: SWBD-MTLL500
ATS-MTLL499
3"
USE "BOLD" STYLE TEXT
3/16"
3/16"
1/4"
3/16"
1/4"
3/8"
3/16"
LINE 4
LINE 3
LINE 2
LINE 1
1/4"
1/4"
LINE 6
LIFE SAFETY POWER SYSTEM
FED FROM: (N)SWBD-MTNL3003 (G)SWBD-MTGL304
3/16"
3/16"
1/4" LINE 5
3/16"
1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.
2. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. REPLACE QUESTION MARKS WITH CORRECT NUMBERS.
WIDTH AS REQUIRED, MIN 5"
2.5"
WIDTH AS REQUIRED, MIN 5"
1"
3/16"
1/4"
3/16"
3/16"
1/2"
3/16"
5/8"
1/4"
1/4"
1/4"
1/4"
3/8"
1/2"
DIST. PANEL L1A
NAMEPLATE MOUNTING LOCATION
CENTERLINE OF INNER DOOR
SECTION 2
USE "BOLD" STYLE TEXT
480V, 3P, 3W, 800A, 65KAIC
CL
CL
ADJACENT ADDITIONAL PANEL SECTIONS
AS REQUIRED
FED FROM MDS-A
DIST. PANEL CRPP1A1
USE RIVETS NOT DOUBLE-STICKTAPE FOR EXTERIOR LOCATIONS
MAIN BUS SIZE IF MAIN LUGS ONLYOR TRIP RATING OF MAIN BREAKER.
NOTES:
1.
2.
3.
4.
SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.
PROVIDE ONE NAMEPLATE FOR EACH PANEL OR MCC SECTION. WHERE SECTION NUMBER TWO AND ABOVE ARE
WITHIN SAME ROOM AND WITHIN 10' OF EACH OTHER USE THE SMALLER SIZE NAMEPLATE.
CENTER ALL TEXT HORIZONTALLY.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.
1"
2"
WIDTH AS REQUIRED, MIN 4"
3/16"
3/16"
1/4"
3/16"
3/16"
1/2"
WIDTH AS REQUIRED, MIN 3.5"
3/16"
1/4"
3/16"
3/16"
3/16"
1/2"
USE RIVOTS ON DIV. 16 PROVIDED ITEMS IN EXTERIORLOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHEDITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT
10 HP., 480V, 3∅
FED FROM DS1A1
EXHAUST FAN EF-1
USE "BOLD" STYLE TEXT
GENERAL EQUIPMENT
CIRCUIT BREAKERS IN DIST. PANELS
EXHAUST FAN EF-11ST FLOOR-COL. A3
DESCRIPTION OF LOAD SERVED
LOCATION OF LOAD
NOTES:
2.
3.
1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS
OF NAMEPLATES FOR DIFFERENT SYSTEMS.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED
TO MATCH EQUIPMENT SPECIFICATIONS.
CENTER ALL TEXT HORIZONTALLY
1/4"
1/4"
3/16"
3/16"
3/16"
3/16"
3/16"
3/16"
3/16"
3/16"
1/4"
1/4"
WIDTH AS REQUIRED, MIN. 6"
2.5"
480Y/277V, 3∅, 3W
PRIMARY FED FROM DS1A1
SECONDARY FEEDS PNL RDP1A1
TRANSFORMER TRR-1A1
USE RIVOTS NOT DOUBLE-STICK TAPE FOR ALL LOCATIONS
USE "BOLD" STYLE TEXT
75 KVA, K-13 RATED
208Y/120V, 3∅, 4W
PROVIDE ONE NAMEPLATE FOR EACH TRANSFORMER.
CENTER ALL TEXT HORIZONTALLY.
NOTES:
1.
2.
3.
4.
SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATIONAND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXTAS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.
WIDTH AS REQUIRED, 6" MIN.
1.25"1/4 "
1/4"
3 / 16 "
1/4"
5/16"
FIRE ALARM SYSTEM FAJB-1PNL??-##
1.
2.
3.
4.
NOTES:
ENGRAVE PANEL NAME AND BRANCH CIRCUITNUMBER SERVING ENCLOSURE, OMITENGRAVING IF ENCLOSURE IS NOT POWERED
USE RIVETS ON DIV. 16 PROVIDED ITEMS IN EXTERIORLOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHEDITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT
USE "BOLD" STYLE TEXT. USE WORDS, NOT ABBREVIATIONS,FOR SYSTEM NAMES AND FUNCTION
REFER TO SPECIFIACTIONS FOR FOR ADDITIONAL INFORMATION ANDCOLORS FOR DIFFERENT SYSTEMS.
PROVIDE ONE NAMEPLATE FOR EACH ENCLOSURE OR J-BOX LARGER THAN 4"
CENTER ALL TEXT HORIZONTALLY AND VERTICALLY IF ONLY ONE LINE.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIREDTO MATCH EQUIPMENT SPECIFICATIONS.
STN0012-22,24,26
GENERAL NOTES
A. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
B. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXTAS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.
GREENWHITE
PURPLE
AQUA
WHITE
WHITE
208/120V STANDBY
208/120V GENERATOR
15KV MEDIUM VOLTAGE
480/277V GENERATOR
CATV/ MATV
TEXT
NAMEPLATE COLOR
BLACK
WHITE
WHITE
BLACK
BACKGROUND
1
NAMEPLATE COLOR LEGEND
YELLOW
WHITE
RED
BLACK
WHITE
GREEN
GREEN
BLACK
WHITE
YELLOW
WHITE
BLUE
RED
WHITE
WHITE ORANGE
GROUND CONDUITS
480V NORMAL
208/120V NORMAL
SECURITY
TELECOM
FIRE ALARM
BMS CONTROLS
208/120V UPS
480/277V UPS
SERVICE
208/120V EMERGENCY
480/277V EMERGENCY
480/277V STANDBY
ENGRAVEDNAMEPLATES
ON POWER CONDUITS SHOWCIRCUIT NUMBERS OF ALLCIRCUITS IN J-BOX. USE 1"WIDE KROY OR BROTHERSLABELING TAPE WITH BLACK 1/2"HIGH HELVETICA BOLD LETTERINGON WHITE BACKGROUND.
2
PANEL MTES0021FED FROM: XX
10 HP., 480V, 3∅
PANEL, MCC,ENCLOSURE, ETC.
C. ROWMARK # IS THE COLOR OF THE PLASTIC ENGRAVINGMATERIAL. USE ROWMARK 1/16" ULTRAMATT AND SATINSTOCK AS NOTED.
122-932
222-582
122-942
322-402
322-402
ROWMARK #
322-704
222-324
322-602
322-992
322-407
322-542
322-602
122-612
WHITE ORANGE 122-612
GREENWHITE
WHITE
BLUE
RED
WHITE
122-932
322-542
322-602
TM
en
gin
ee
rsfo
ra
su
sta
ina
ble
futu
re
2014 - GLUMAC ALL RIGHTS RESERVED
THESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BE
USED OR REPRODUCED IN ANY MANNER,
WITHOUT PRIOR WRITTEN PERMISSION
SHEET
JOB NO.
SHEET TITLE:
CHECKED BY:
DRAWN BY:
Project
©
Client
Job N
o.:
Conta
ct:
ww
w.g
lum
ac.c
om
900 S
W F
ifth
Ave.
, S
uit
e 1600
Port
land, O
R 9
7204-2
640
T. 503.2
27.5
280 F
. 503.2
74.7
674
7/30/2014 11:19:56 AM 1/8" = 1'-0"
E9.1
ELECTRICAL
DETAILS
LRH
JJE
PSU ELEVATOR
RECONNECTION TO
GENERATOR
PORTLAND STATE
UNIVERSITY
02.14.00651
7/30/14100% CD'S/ PERMIT SET
02.1
4.0
0651
JJE
SCALE: NONE7
TRANSFORMER/PANEL/OUTLET/LUMINAIRE WIRING (NON ISOLATED GROUND PANELS)
SCALE: NONE1TRANSFER SWITCH NAMEPLATES
SCALE: NONE3
DISTRIBUTION PANEL, MOTOR CONTROL CENTER & BRANCH PANELNAMEPLATES
SCALE: NONE6EQUIPMENT IDENTIFICATION NAMEPLATES
SCALE: NONE2TRANSFORMER NAMEPLATE
SCALE: NONE5ENCLOSURE INDENTIFICATION NAMEPLATES
SCALE: 1/8" = 1'-0"4RACEWAY AND NAMEPLATE IDENTIFICATION
Revisions
# Description Date