electronic instrument transformer
TRANSCRIPT
-
8/18/2019 Electronic Instrument Transformer
1/6
Electronic Instrument T ransformers
for Integrated Substation Systems
M. S a i t oh ,
T.
K i mur a , Y. Minami,
N.
Yamanaka,
S.
Maruyama,
T. Nakajima, M.
Kosakada, Member, IEEE,
Abstract-In orde r to integrate prima ry equipm ent to digitized
integrated substation systems, the digitizing procedure of
instrument transformers is indispensable.
Electronic current transformers (ECTs) and electronic voltage
transformers Ems)have achieved high performance with a very
small size. The ECTs and
EVTs
play a sensing and digitizing role
for current and voltage information offered by Rogowski coils
and capacitive voltage dividers respectively with the processing
capabilities
of
digital electronics, and link up with protection
relays and bay control units via process level
LAN.
The sensed
current and voltage signals are transmitted as digital signals.
This paper discusses the system construction of the electronic
instrument transformers, which are applied for digitized
substation systems integrated with primary equipment. The
results
of
performance that can be achieved by the electronic
instrument transformers are evaluated.
Index Terms-Electronic CTs, Electr onic VTs, Process BU S,
Rogowski coil, Capacitive Voltage divider, Sensing Unit, M erging
Unit.
I. INTRODUCTION
Being encouraged by recent progress in information
technology and requirements of the com petitive power market,
it is proposed to make a substation information-terminal in
which precise and sophisticated d ata from substation primary
equipment can be acquired. These data are needed not only for
operational, engineering, maintenance staff in the operation
center but also for sales, marketing, quality engineering, and
management people at remote places. Digital information
technology assures realization of this scheme. Current and
voltage information in the main high-voltage circuits are one
of the most important information dealt with substation system,
so the digitizing procedure of instrument transformers is
indispensable to integrate primary equipment to digitized
integrated substation system, that
is
to make a substation
information-terminal.
Today, electronic current transformers (ECTs) and
electronic voltage transformers (EVTs) have achieved high
performa nces with a very small size In addition their
digital output com plies with the m ost stringent requirement of
the digitized integrated substation system. The ECTs and
EVT s play a sen sing and digitizing role for current and voltage
M. Saitoh, T. Kimura, Y Minami, N. Yarnanaka,
S.
Maruyarna, T.
Nakajima, and M. Kosakada are with Toshiba Corporation, Tokyo, Japan
(e-mail: [email protected]).
information with the processing cap abilitie s of digital
electronics. The designs of ECTs and EVTs are based on IEC
60044-8 and IEC 60044-7 respectively, and take into account
the harshest environm ental cond itions of temperature,
vibrations, and electromagnetic compatibility. On the other
hand the designs of the digital output interfaces of the digital
electronics are based on IEC
61850-9.
The ECTs and EVTs
link up with protection relay units, Bay C ontrol Units (BCUs),
Control and Monitoring Units (CMUs) mounted on primary
equipment instead in the local co ntrol cubicle, via the process
level
LAN.
The sensed current and voltage information are
transmitted to them as optical digital signals. By do ing this, the
primary equipment and substation system wiring can be
simplified due to the extensive use of optical fibers for
communication of current and voltage information, operating
commands, state condition of primary equipment, and
so
on.
This also lead to important savings in civil engineering at the
time of installation. In addition, the compactness and
economics of the substation facilities are improved, which is
always an advantage.
This pa per discusses the electronic instrument transformers,
which are applied for digitized substation systems integrated
with primary equipment. The optimum system configuration
and the reliability of the electronic instrument transform ers are
described. T he results of performance that can b e achieved by
the electronic instrument transformers are evaluated.
11. GENERALONFIGURATION OF ELECTRONIC T S AND
VTS
A . The System Configuration
o
Electronic CTs and
VTs
Fig. 1 shows an example of the system configuration of
electronic CTs and VTs. The ECT is based on the principle of
a Rogowski coil by taking into account of saturation free
characteristics and economical efficiency. As for the voltage
detection se nsor of EVT , a capacitive voltage divider of high
reliability a nd simple insulated construction was applied.
Sensing Units (SUS) are arranged near the Rogowski coil
and the capacitive voltage divider on each bay, respectively,
and one Merging Unit (MU) is provided. Each SU is
connected to the MU by optical fiber, and the MU is
connected to the process bus by optical fiber. In order to
secure high reliability, all Rogowski coils,
SUS,
MUS, and
process bus are duplicated, except for the capacitive voltage
divider. The E CT and EV T are designed based
on
I E C 60044-
8 and IEC
60044-7 ,
respectively.
0-7803-7525-4/02/$17.00 002 IEEE. 459
-
8/18/2019 Electronic Instrument Transformer
2/6
Time
Synchronizat ion
Signal
Fig. 2 The View
of
Printed Circuit Board Type Rogowski Coil.
D. SU MU, and Process Bus
The analogue voltage signals from the Rogowski coil and
he divided vo ltage signals are con verted into digital signals at
Processus
- -
-
each
SU,
synchronized by a time synchro nization signal from
the MU, and transmitted to the MU. The MU adds time stamps
to the sampled digital signals from each SU, and merges them
Fig. 1The System Configuration of Electronic CTs and VTs.
B.
Rogowski Coil
A known p roblem regarding Rogowski coils without an iron
core is the large ratio error that results from manufacturing
difficulties, such as lack of uniformity for coil pitch or coil
cross section, and changes in the operating temperature
conditions. In order to solve this problem, the authors
developed the Rogowski coil by making coils in the form of
patterns on printed circuit board. By applying the
manufacturing technology of the printed circuit board it
became possible
to
manufacture the Rogowski
coil
with
a
uniform and highly prec ise winding pitch.
As
a result, a very
small and high accuracy Rogowski co il is achieved, suc h as the
printed circuit board type Rogowski coil shown in Fig. 2. As
the energized part of ECTs utilizing Rogowski coils are very
small, it is possible to integrate them directly not only on a
dead tank type circuit breaker
or
gas insulated switchgear
(CIS) but also on a live tank type circuit breaker or air
insulated switchgea r (AIS). By do ing this it is possible to limit
the number of insulators and the architecture of the substation.
C. Capacitive Voltage Divider
The high-voltage side capacitor of the capacitive voltage
divider is formed with the primary electrode at the high
voltage conductor and the middle electrode floating. The
dielectric is the gas used in switchgear: pure SF6. Using a
capacitive voltage divider, the risk of the ferroresonance
phenomena can be restricted. CIS size can be reduced
drastically by adopting the developed Rogowsk i coil and
capacitive voltage divider instead of conventional
CTs
and
VTs.
to comb ined serial current and voltage data, an d transmits this
data to a protection relay unit and bay control unit via the
process bus.
The time-synchronization function of the MU utilizes the
timing signal from a sampling master, for instance it may
generate the sampling signal based o n the standard signal of
the Global Positioning System (GPS). The time signal is
shared within the substation.
The process bus connects the MU for ECTs and EVTs,
protection relay units, BCU s and CMUs. T he process bus uses
the standard communication protocol of IEC 61850-9 for
interoperability.
In
the digitized integrated su bstatio n, primary
equipment and substation system are connected by process
level LAN, for almost all the information in the substation,
such as sampled digital values o f the currents and the voltages,
operating commands, state condition of primary equipment.
Th e digital interface of the MU and the transmitted data frame
is designed based
on
IEC 61850-9,
so it
is suitable to apply
ECTs and EVTs to the digitized integrated sub station.
111. I-AIS
w m
LECTRONICTs
I-AIS
[41 is Toshiba’s new concept high voltage switchgear.
The switchgear is an integration
of
live tank type gas circuit
breaker, live tank type disconnector, earthing switch and
electronic CT,
so
called Integrated Air Insulated switchgear (1-
AIS). The
I-AIS
ith
ECT
is described here.
A. Configurationof I-AIS with Electronic CT s
Fig. 3 shows the system configuration of 245kV I-AIS with
Electronic CT. he Rogowski coil and
SU
are mounted at top
of the circuit breaker charged to a high-voltage. Power to
supply the SU with a high-voltage potential is transmitted as
laser light from a Laser D iode Unit (LDU) at ground potential.
The SU at high-voltage potential and the MU at ground
460
-
8/18/2019 Electronic Instrument Transformer
3/6
potential are connected by high-voltage optical sens or link that
is optical fiber cable with insulator, so the Rogowski coil and
the
S U
is insulated completely against the
M U
at ground
potential. The analogue signal from the Rogowski coil is
converted into 16bit optic digital signal at the SU, and is
transmitted
to MU
through the optical fiber insulator.
The specification of Electronic
CT
for 245kV
I-AIS
is
shown in Table 1
For Protection :OlCF H
B.
Experimental Results
1 Linearity
of
Current M easurements
The linearity of current measurements of the E CT applying
a printed circuit board type Rogowski coil with SU is shown in
Fig. 4. The ratio error at 200
% In
and
1 % In (In =
3150
A)
are
0.02
%
and 0.68
%
respectively. The EC T satisfies fully
the accuracy lim it of IEC C lass 0.5.
The ratio error of the printed circuit board type Rogowski
coil alone is less than 2 0.1
%
under the primary current
between
1%
In
and 200
% In
(not shown).
1.5
1
-
0.5
B
0
.-
2
0.5
-1
1.5
0 1000 2000 3000 4000
5000
6000 7000
Primary
Current [A]
0 1000 2000 3000
4000 5000 6000
7000
Primary
Cumnt
[A]
F O ~
rotection :
EC
Class 5~
Standard IEC60044-8
100
80
60
B 40
-
-
g 20
- 0
g
-20
-40
e
-60
80
100
(a) I-AIS ith ElectronicCT.
Fig. 4 The Linearity
of
Current Measurem entsof Electronic
CT.
2 Temperature Characteristics
The temperature characteristic of the ECT applying the
printed circuit board type Rogowski coil with SU is show n in
Fig. 5 . Under an operating temperature range between -40
C
and +60
C,
the ratio error drift of the ECT
is
less than +0.1 %
and the drift of phase displacement is less than d 0 min
without temperature compensation.
The temperature characteristic of the printed circuit board
type Rogowski coil alone is less than
2 0.05 %
of the ratio
error and less than 2 min of the phase displacement under an
operating temperature range between
-40
C and
+60
C (not
shown) when the burden (pure resistance), normally mean
of
the input impedance
of
SU, is suitably chosen.
In
the case of
I
AIS
the input impedance of the
S U
was set to 1.25
kQ.
@) Merging U nit (Left) and Laser Diode U nit (Right) at ground potential.
Fig.
3
The System C onfigurationof 245kV I-AISwith ElectronicCT
46
1
-
8/18/2019 Electronic Instrument Transformer
4/6
60 40
-20
0
20 40
60 80
Temperature [“c]
30
I I I
I I I
60 40 -20 0 20 40 60 80
Temperature
[“c]
Fig. 5 The Temperature Char acteristicof Electronic
m.
3 Transient Response
For protection purposes the transient response of the ECT t
the time of fault current is important. Fig.
6
shows the
ECT
secondary output waveform (digital signal waveform) (lower)
and primary current waveform measured with a shunt (upper)
which were recorded in a 50 kA short circuit current breaking
test with 52 % DC component. The Rogowski coil is linear, so
that no saturation occurs even when
a
large current
of
several
lOkA with DC component is measured.
Another problem concerning conventional C T s is the low
frequency characteristic, which can be defined as a
transmission time constant. In contrast to conventional C T s
where the DC transmission performance is a characteristic
which can not be adjusted, the ECT allows the time constant to
be adjusted according to the specifications of the customer.
This is done in the digital processing
of
the MU.
IV. ELECI’RONICVTS M)R AIS
A .
Configuration of Electronic VTsfor
AIS
Fig. 7 shows Electronic VT or 245kV AIS The reduced
size and weight compared to a conventional oil-filled
VT
allows placement in a compact substation.
A
capacitive
voltage divider with an SF 6 gas capacitor as the high-voltage
side capacitor and a mica capacitor as the voltage divider
capacitor is constructed in the lower tank on ground potential.
The
SU
is arranged near the lower tank and the power to
supply the SU is
DC
l lOV. The S U is connected to the
MU
by
optical fiber.
60
40
20
3 0
c
= -20
f -40
-60
E 80
120
-1
40
a 100
60
40
3
20
g
20
4 0
-40
-60
80
100
120
-140
I
t
\ I
v
I
0 20 40 60
EO
100
Time
[ms]
+
+
+ +
+ +
+ ++
0
20 40 60 80 100
Time [ms]
Fig.
6
The ECT econdary Ou tput Waveform (Lower) and Primary Current
Waveform measured with a Shunt (Upper) which were R ecordedin a
50
kA
Short Circuit Current Breaking T est.
The analogue signal from the capacitive voltage divider is
converted into 16bit digital signal at the SU, nd is transmitted
to the MU that is the com mon unit with the ECT which merges
the sampled signals of ECTs and
EVTs
to combined serial
data.
The specification
of
the Electronic
VT
or
245kV
AIS
is
shown in Table 2.
Fig.
7
The Electronic
V T
or245kV AIS
462
-
8/18/2019 Electronic Instrument Transformer
5/6
Rated Primarv Voltaee I
245
/
\13
kV
Rated Frequency
Rated Secondar y Output
(16bit Digital Output)
Sampling Rate
Accuracy Class
Standard
5 O H z l 6 o H z
For measuring
:
2D41 H
For Protection
:
2D41
H
2.4
lrHz
or50Hz
2.88 kHz for 60Hz
For measuring
:
EC Class 0.5
For Protection : EC Class 3P
IE C6 0 0 4 4 - 7
(Decimal : 1585)
(Decimal : 11585)
B. Experimental Results
1 Linearity of Voltage Measurements
The linearity of Voltage Measurements of the capacitive
voltage divider for EVT is shown in Fig. 8. The ratio error of
the capacitive voltage divider is less than 0.1
%
under the
primary voltage between 2
Vn
and 150%
Vn
(Vn
=
245h/3
kV). It is suggested that the EVT with the SU and the
capacitive voltage divider satisfy fully the accuracy limit of
IEC C lass 0.5.
-4
...........
J . . . . . . . . . . . . .
L..........
,
U
0
20
40 60
80 100 120 140 160
Primary Voltage [%Vn]
:
00 Vn
= 245 /
$3
3An
zoo
160
1
80
8
-
0
9 40
6
$ -80
-
g 120
40
g -120
-160
-200
I
I I
I I I
I
I I
.
-__
0
20
40
60
80 1 0 0
120
140
160
Primary Voltage [%Vn] : 100%Vn
=
245 / 3
Fig. 8 The finearity of Voltage Measurementsof Capacitive Voltage Divider
for
Electronic
VT.
2 Temperature Characteristics
The temperature characteristic of Voltage Measurements of
the capacitive voltage divider for EVT is shown in Fig. 9.
Under the operating temperature range between
-20 C
and
+60
C, the error drift of the capacitive voltage divider is less
than 0.1 % without temperature com pensation.
0.5
0.4
0.3
0.2
0.1
-
g o
;0.1
w
a
.-
-0.2
-0.3
0.4
-0.5
I
-20
-10
0
10
20 30 40 50 60
Temperature [ c]
Fig. 9 The Temperature Characteristicof Capacitive Voltage Divider for
ElectronicVT.
V INTEGRATED GIS
m
L E ~ O N I C
Ts
AND VTs
Fig.
10
shows the system configuration of the GIS with
electronic C T s and VTs
for
the digitized integrated substation.
The SUS are attached close to the printed circuit board type
Rogowski
coils and the capacitive voltage dividers
respectively. The M U is mounted on the primary apparatus in
the
GIS
application as part of the Process Control Unit (PCU)
which is an integrated unit of protection relay unit (PU),
control unit (CU) and MU. The PU, CU, MU, and CMU
(instead of local control cubicle) are interfaced with each other
via the process bus, and the station bus links these components
to
the station control unit (SCU). Information
on
the station
bus
is
transmitted to the remote office through the remote
terminal unit (RTU) r the gateway (GW).
Control
Room
Equipment
Yard
PC U Process Control Una
CU: Contro l unit
PU: Protectionunit
MU: Merging unit
SU: Sensing un il
G W
Gateway
ECT: Electronics Current ransformer
EVT: ElectronicsVoltage ransfo rmer Bui -n
CMU: Controland monilor ingunit
BP:Bus protectionunit
SCU: S ta l in umt ro l un i t
HMI: Human interface
RTU: Remote erminal unit
Fig. 10 The System Configuration of the GIS with Electronic C T s and
VTs
for the Digitized Integrated Substation.
463
-
8/18/2019 Electronic Instrument Transformer
6/6
Almost all the information in the digitized integrated
substation, such as current and voltage information, is
transmitted as digitized data via the process bus and station
bus, so that easy data acquisition of such digitized data is
possible not only for operational, engineering, maintenance
staff in operation center but also for sales, marketing, quality
engineering, and management people at remote places.
VI. CONCLUSIONS
Electronic instrument transformers, which are applied to
digitized substation systems integrated w ith primary equipment,
were developed. The system has following features.
(1)
The EC T is based
on
the principle of a Rogowski coil of
printed circuit board type, and the
EVT
applies a capacitor
voltage divider principle.
(2) The analogue voltage signals from the Rogowski coil
and the divided voltage signals are converted into digital
signals at each SU, and the MU merges sampled digital
signals to combined serial data, and transmits it to a
protection and control unit via the process bus.
(3)
Almost all the information in the digitized integrated
substation, such as current and voltage information, is
transmitted as digitized data, so that people from various
places should be able to access the required information.
(4)
The configuration and the experimental results of
ECTs
and EVTs, which are applied for I-AIS, AIS, GIS in
digitized integrated substation, were presented. The linearity
of current and voltage measurement, temperature
characteristic, transient response show ed good performance.
(5) The electronic CTs and VTs on primary equipment can
be connected with protection and control unit via process
bus using standardized protocol instead of a huge number of
wire cables. Therefore civil work for the cable pit, and wire
connection and check work w ill be greatly reduced.
VII.
REFERENCES
(11
A. Kaczkowski
et
al, “Combined sensors for current and voltage are ready
for applications in GIS”, CIGRE 1998 session 12-106
(21
J.
P. Dupraz et al, “The integration of electronic a s nd VTs in power
switchgear : challenges and choices”, CIGRE 2000 session 12/23/34/-01
(31 R. Gross, et ai, “Substation control and protection system for novel
sensors”, CIGRE 2000 session 12/23/34/-03
[4] A.
Kobayashi,
et
al,
“252kV
New-Concept Integrated Air-Insulated-
Switchgear”, The Beijing International Conference Power Transmission
and Distribution Technology 2001, p.743
VIII. BIOGRAPHIES
Minoru Saitoh received his
B.S.
nd M.S. degree in electrical engineering
from Science University of Tokyo in 1992 and 1994 respectively. In 1994, he
joined Toshiba Corporation. Since then, he has been engaged in the
development and design of Non-conventional
CTs
and VTs, and control,
monitoring and diagnostic system of gas-insulated switchgear. MI. Saito is a
member of IEE of Japan and a member of the Japan Society of Applied
Physics.
Tatsuya Kimura received his B.S. nd M.S. degree in electrical engineering
from Doshisha University in 1990 and 1992 respectively. In 1992, he joined
Toshiba Corporation. Since then, he has been engaged in the research and
development of communication system and sensing system. MI. Kimura is a
member of IEICE of Japan.
Yyii Minami
received his B.S degree in control engineering from Kyushu
Institute of Technology in 1991. In 1991, he joined Toshiba Corporation.
Since then, he has been engaged in the development of diagnostic technology
of electronic device, the development and design of power protection relay.
Mr. Minam i is a member of
IEE
of Japan.
Naoyoshi Yamanaka received his B.S degree in electrical engineering from
Hiroshima Institute of Technology in
1990.
In
1990,
he joined Toshiba
Corporation. Since then, he has been engaged in the development and design
of power protection relay.
Shiro Maruyama received his
B.S.
and M.S. degree in electrical and
electronics engineering from Nagoya University in 1980 and 1982
respectively. In
1982,
he joined Toshiba C orporation. Since then, he h as been
engaged in the development and design of high-voltage gas-insulated
substations and their monitoring and diagnostic system. MI. Maruyama is a
member of DEE of Japan.
Takashi Nakajima
received his
B S
and M.S. degree in electrical
engineering from Yamagata University in
1976
and
1978
respectively.
In
1978, he joined Toshiba Corporation. Since then, he has been engaged in the
development and design of high-voltage gas-insulated substations (GIS) and
their monitoring and diagnostic systems. Mr. Nakajima is a member of E E of
Japan.
Masayuki Kosakada (M’1991) received his
B.S.
degree in electrical
engineering from the University
of
Tokyo in 1986. In 1986, he joined To shiba
Corporation. Since then, he has been engaged in system engineering of
substation equipment such as gas-insulated switchgear, circuit breaker,
transformer and substation system. MI. Kosakada is a member of IEEE and
IEE of Japan.
464