PRODUCTS ELEVATED FLARE SYSTEMS EFFECTIVE COMBUSTION FOR SMOKELESS OPERATION The Tri-Point High Turn Down Ratio Flare (HTDR-Flare) is the innovative emissions reduction solution to achieve smokeless operation and compliance to Quad-O and 40 CFR 60.18 EPA regulations. Utilizing a proprietary tip design, this non-assisted flare ensures there are no visible smoke emissions across the full operational range of just a few ounces of pressure to in excess of 30 psig. The Tri-Point HTDR Elevated Flare utilizes a variable orifice design to safely and efficiently combust Volatile Organic Compounds (VOC) emissions in excess of 98% efficiency. One HTDR-Flare allows for the inclusion of both high pressure and low pressure gas streams in a single device, mitigating the requirement for multiple flares.

Upload: others

Post on 04-Apr-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

P R O D U C T S

ELEVATED FLARE SYSTEMSEFFECTIVE COMBUSTION FOR SMOKELESS OPERATION

The Tri-Point High Turn Down Ratio Flare (HTDR-Flare) is the innovative emissions reduction solution to achieve smokeless operation and compliance to Quad-O and 40 CFR 60.18 EPA regulations. Utilizing a proprietary tip design, this non-assisted flare ensures there are no visible smoke emissions across the full operational range of just a few ounces of pressure to in excess of 30 psig. The Tri-Point HTDR Elevated Flare utilizes a variable orifice design to safely and efficiently combust Volatile Organic Compounds (VOC) emissions in excess of 98% efficiency. One HTDR-Flare allows for the inclusion of both high pressure and low pressure gas streams in a single device, mitigating the requirement for multiple flares.

HTDR-FLARE PRODUCT LINE

APPLICATIONS• Oil and Gas Production Operations• Crude Oil Storage Batteries• Midstream Facilities• Offshore Platforms• Gas Processing

• Mining Operations• Landfills• Petrochemical and Chemical• Petroleum Refining• Anywhere smokeless flaring is required

STANDARD FEATURES• Flare Tip made of stainless steel construction• Wind resistant retractable electric ignition pilot with thermocouple assembly• Built in wind shroud that induces sufficient air to the flare tip for proper mixing and

combustion throughout the operating range• Flare stacks are mounted on base plate with guyed support for easy installation• Various flow capacities for high and low pressure application eliminating the need for

multiple flares• Simple Single flare tip configuration for safe operation• Patent pending technology• Max Capacities meet EPA 40 CFR 60.18 with less than 400 ft/sec exit fuel gas velocities.

BENEFITS• Operates smokeless throughout entire range of flow; from purge to 100% capacity• High turndown ratio of >50:1• Designed for easy tip access and maintenance (flanged connections, simple assembly)• Retrofit replacement for other manufacturers’ flare tips• Field proven 98%+ combustion VOC destruction efficiency• Scalable design encompassing multiple models with a range of operating capacities

COMPLIANCE• Designed to meet EPA 40 CFR 60.18 requirements• Standard models can be customized to meet individual requirements upon request

OPTIONS• Flare/Burner Management Systems• Continuous pilot• In-Line Detonation Flame Arresters• Upstream liquid knockout

• Cable/Anchor Tie Down Kits• Ladder and Platforms• Dual pressure stream operation (HP/LP

dual streams)

Patent Pending Provisional Application No. 62/807,819 for FLARE TIP ASSEMBLY (172269-011700/US (Tri-Point, LLC)

UPPER SHROUD

LOWER SHROUD

PILOT HOOD

NOZZLE

CONNECTING ROD

NOZZLE TUBE

FLANGED CONNECTION(TO ELEVATED FLARE STACK)

SPRING ASSEMBLY

Model HTDR-Mini HTDR-1 HTDR-2 HTDR-3 HTDR-4

TIP SIZE 2" 3" 4" 6" 8"

STANDARD HEIGHT 25' 35' 45' 65' 85'

Maximum Flow Rate, MMSCFD Max Capacity to meet EPA 40 CFR 60.18 at less than 400 ft/sec exit velocity.

LIGHT FUEL LHV 1068 BTU/SCF 3.81 6.55 9.92 14.49 19.85

MEDIUM FUEL LHV 1543 BTU/SCF 3.36 6.16 9.34 13.64 18.69

HEAVEY FUEL LHV 2251 BTU/SCF 2.97 5.61 8.49 12.41 17

PRODUCT MODEL SPECIFICATIONS

VARIABLE FLOW CAPACITY OPERATION REPLACEMENT FLARE TIPS

Tri-Point HTDR flare operates with a variable area nozzle that optimizes air and waste gas mixing for 100% smokeless operation as the gas stream pressure varies. Specially oriented “pilot” ports allow for ounce pressure operation when the gas pressure is low and main nozzle area is closed.

If the flare you are currently operating is smoking and not meeting the requirements of EPA 40 CFR 60.18, The Tri-Point High Turn Down Ratio Flare replacement tips are a safe and economical retrofit option. Our flanged connection allows the HTDR model line to easily replace other manufacturers’ ineffective flare tips. The Tri-Point Service team can replace your flare tip today!

HIGH PRESSURE MAX OPEN

LOW PRESSURECONE CLOSE / PORT VENTS

THE TRI-POINT HIGH TURN DOWN RATIO FLARE FOR SMOKELESS COMPLIANCE TO EPA 40 CFR 60.18

Tri-Point is an oil and gas production

and processing solutions provider with

locations supporting each of the major

onshore basins in the U.S. The company is

dedicated to working with its customers

to develop tailored products and services

that address needs from the wellhead

through the pipeline.

HEADQUARTERS

5555 SAN FELIPE | SUITE 1250 | HOUSTON, TX

(713) 600-9400

WWW.TRI-POINTLLC.COM

300

800

1300

1800

2300

2800

3300

3800

4300

4800

0 20 40 60 80 100 120 140 160 180 200Radia-

onLevel,Btu/hr-<^2

DistancefromFlareCenterline,Ft

Radia-onCurveforHTDR-Mini

FuelGas:LightLHV:1067.87btu/scf;MW:20.62StackH:[email protected]

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47StackH:[email protected]:MediumLHV:1542.99btu/scf;MW:31.28StackH:[email protected]

Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

0 5 10 15 20 25 30 35 40 45 50

VolumetricFlow,M

MSCFD

GasPressure,psig

CapacityCurveforHTDR-MiniRadia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47FuelGas:MediumLHV:1542.99btu/scf;MW:31.28

300

800

1300

1800

2300

2800

3300

3800

4300

4800

0 20 40 60 80 100 120 140 160 180 200

Radia-

onLevel,Btu/hr-<^2

DistancefromFlareCenterline,Ft

Radia-onCurveforHTDR-1Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62StackH:[email protected]

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47StackH:[email protected]:MediumLHV:1542.99btu/scf;MW:31.28StackH:[email protected]

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

0 5 10 15 20 25 30 35 40Vo

lumetricFlow,M

MSCFD

GasPressure,psig

CapacityCurveforHTDR-1Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47FuelGas:MediumLHV:1542.99btu/scf;MW:31.28

300

800

1300

1800

2300

2800

3300

3800

4300

4800

0 20 40 60 80 100 120 140 160 180 200

Radia-

onLevel,Btu/hr-<^2

DistancefromFlareCenterline,Ft

Radia-onCurveforHTDR-2Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62StackH:[email protected]

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47StackH:[email protected]:MediumLHV:1542.99btu/scf;MW:31.28StackH:[email protected]

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

0 5 10 15 20 25 30

VolumetricFlow,M

MSCFD

GasPressure,psig

CapacityCurveforHTDR-2Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47FuelGas:MediumLHV:1542.99btu/scf;MW:31.28

300

800

1300

1800

2300

2800

3300

3800

0 20 40 60 80 100 120 140 160 180 200

Radia-

onLevel,Btu/hr-<^2

DistancefromFlareCenterline,Ft

Radia-onCurveforHTDR-3Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62StackH:[email protected]

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47StackH:[email protected]:MediumLHV:1542.99btu/scf;MW:31.28StackH:[email protected]

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

0 5 10 15 20 25 30

VolumetricFlow,M

MSCFD

GasPressure,psig

CapacityCurveforHTDR-3Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47FuelGas:MediumLHV:1542.99btu/scf;MW:31.28

300

800

1300

1800

2300

2800

3300

3800

0 20 40 60 80 100 120 140 160 180 200

Radia-

onLevel,Btu/hr-<^2

DistancefromFlareCenterline,Ft

Radia-onCurveforHTDR-4Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62StackH:[email protected]

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47StackH:[email protected]:MediumLHV:1542.99btu/scf;MW:31.28StackH:[email protected]

0.0

10.0

20.0

30.0

40.0

50.0

60.0

0 5 10 15 20 25 30

VolumetricFlow,M

MSCFD

GasPressure,psig

CapacityCurveforHTDR-4Radia-onlevel<=1500BTU/hr-<^2@100<radiusand15MPHwind

FuelGas:LightLHV:1067.87btu/scf;MW:20.62

FuelGas:HeavyLHV:2250.96btu/scf;MW:43.47FuelGas:MediumLHV:1542.99btu/scf;MW:31.28

FLARE RADIATION CURVES FLARE CAPACITY CURVES

s NOTE: The triangle mark on each capacity curve is the maximum capacity at which this flare model will meet the requirements in Code 40 CFR 60.18.