  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 1

    ´FA

    CP

    ´ N/C

    CO

    NTA

    CTS

    ´FA

    CP

    ´ N/O

    CO

    NTA

    CTS

    12 11 10 9 8 7 6 5 4 3 2 112 11 10 9 8 7 6 5 4 3 2 1CLASS 2 LOW VOLTAGE WIRING

    GND

    SE

    NS

    E

    DR

    AIN

    MU

    X

    MU

    X

    +24

    VFW

    CO

    MM

    ON

    NO

    T U

    SE

    D

    LED

    1

    LED

    3

    LED

    2

    RA

    DIO

    TOU

    CH

    PH

    AS

    E

    FAC

    F

    S1

    TES

    T

    System Ratings• Voltage:100-347V 50/60Hz30mA• Current:20Amaximumcircuitbreaker ForusewithLutron®:GRAFIK Eye®GP,LP,andXP

    panels;LCP128TMpanels;Softswitch128panels;EcoSystem®lightingcontrolsystem;EnergiSavrNodeTM units;Quantum® systems;GRAFIK EyeQSunits,andRadioTouch®lightingcontrollers.

    Note:Thisdevicedoesnotprovideemergencypower.AnEmergency(Essential)powersourcemustbeprovided.

    Please read this guide before installing.

    Contents Page Ratingsandmodelnumberoverview............................1 MountingtheInterface.................................................2 WiringOverviewforLUT-ELI-3PHunitson: RadioTouchSystems...............................................2 Panel-BasedSystems..............................................4 EcoSystemorQuantumbussupplies.......................8 GRAFIKEyeQSunits...............................................9

    EnergiSavrNodeunits..........................................10 EmergencyPowerModeSetup:LCPPanels..............11 NECClass2/PELVWiringtoFireAlarm

    ControlPanel(FACP).............................................12 Troubleshooting RadioTouch ............................................................13 PanelBasedSystems............................................14 EnergiSavrNode Installations................................15 EcoSystemorQuantumSystem............................16 GrafikEyeQSInstallation.......................................17

    Listing TheEmergencyLightingInterface–LUT-ELI-3PHis

    UL924Listedas“EmergencyLightingandPowerEquipment”.Theinterfaceshallbeusedwith:Lutron GRAFIK EyeGP,XP,andLPpanels;LCP128panels;Softswitch128panels;EcoSystem;Quantum;GRAFIK Eye QS,RadioTouchcontrollers,andEnergi Savr Nodeunits.

    Description TheLUT-ELI-3PHunitsensesthelinevoltageon

    allthreephasesorasinglephaseandcontrolstheemergencysignaltothefollowingcompatibleLutronproducts/systems:

    • CircuitSelectorforGP,LP,XPpanels• LCP/XPScontrollerforLCP128,and Softswitch 128panels• EcoSystemBusSupply• QuantumBusSupply• Grafik EyeQSunit• RadioTouchcontroller• Energi Savr Nodeunit Whenoneormorephasesofnormalpowerarelost,

    theLUT-ELI-3PHunitsendsasignaltotheaffecteddevice(s),activatingtheemergencymode.Anylightscontrolledbythesedeviceswillgototheemergencylightlevelsetting(factorysetto100%intensity).Whennormalpowerisrestored,thelightswillreturntotheirpreviousintensities.

    Important Safeguards• Followallnationalandlocalelectricalcodesandsafety

    standards.• Turnoffpowerbeforeinstallation.• LinevoltageinputtotheLUT-ELI-3PHunitmustbe

    fromtheNORMAL(non-essential)powersource.• Readandfollowallsafetyinstructions.• Forindooruseonly.• Equipmentshouldbemountedinlocationsand

    atheightswhereitwillnotreadilybesubjectedtotamperingbyunauthorizedpersonnel.

    • Donotusethisequipmentforotherthanintendeduse.• Allservicingshouldbeperformedbyqualifiedservice

    personnel.

    System Limits (per / LUT-ELI-3PH)• 32circuitselectors• 100RadioTouchControllers• 32EcoSystembussupplies• 32Quantumbussupplies• 32Energi Savr Nodeunits• 32LCP/XPSControllers

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 2 LUT-ELI-3PH Installation Guide

    Mounting the Interface1. Turnpoweroff.2. Wirethelinevoltageleadsthatprotrudefrombackof

    LUT-ELI-3PHunitintothejunctionbox.3. MounttheLUT-ELI-3PHunitontoa4x4-inch (102x102mm)junctionbox(notincluded,but

    available;Lutronpartnumber241-496).4. Besureallthepowerwiresarecompletelyinsidethe

    junctionboxbeforetighteningthemountingscrews.5. Removefrontenclosurecovertoexposetheterminal

    blocks,testswitch,andstatusLEDs.6. InserttheNEC®Class2/PELVwiresthroughknockouts

    intheLUT-ELI-3PHenclosureasshowninthediagram.7. ConnecttheNECClass2/PELVwirestotheLutron®

    productorsystem,whichtheLUT-ELI-3PHwillbecontrolling.Specificwiringtothesedeviceswillbedescribedinthefollowingsections.

    8. Reinstallfrontenclosurecover. Note:CalltheLutronTechnicalSupportCenterat (800)523-9466forrestrictionsandwiringrequirements

    foremergencyfixtures(fixturesthatneverturnofforhaveabatterybackupballastinthefixture).

    InsertNECClass2/PELVwiresthroughknockouts

    4x4in(102x102mm)JunctionBox

    SideView(Cross-Section)

    Installing a LUT-ELI-3PH Unit in a RadioTouch® SystemLine Voltage Connections

    WARNING! Danger of shock. May result in serious injury or death.DONOTWIREWHENLIVE!SwitchoffpowertoallpowerfeedsviacircuitbreakerorisolatorbeforewiringorservicingtheLUT-ELI-3PHunitandRadioTouchSystem

    Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit must be accessed by a certified electrician, following local codes.

    Note: Providepropershort-circuitandovercurrentprotectionatthedistributionpanel.Maximumcircuitbreakerratingof20A.

    Single-PhaseWiring

    GroundNeutralHot

    NormalPower

    Normal

    Ligh

    ts

    Red

    Red

    Red

    White

    Green

    Three-PhaseWiring

    GroundNeutralPhaseCPhaseBPhaseA

    NormalPower

    Normal

    Ligh

    ts

    Red

    Red

    Red

    White

    Green

    WALL

    LUT-ELI-3PHUNIT

    Figure #1 Figure #2

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 3

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16CLASS 2 LOW VOLTAGE WIRING

    1 2 3 4 5 Power Status Program Burn-In1 2 3

    3 7 8 9 10 11 12 13 14 15 16CLASS 2 LOW VOLTAGE WIRING

    1 2 3 4 5 Power Status Program Burn-In1 2 3

    4 5 61 2

    ´FACP´N

    /C

    CONTA

    CTS

    ´FACP´N

    /O

    CONTA

    CTS

    CLASS2LOWVOLTAGEWIRING

    GND

    SENSE

    DRAIN

    MUX

    MUX

    +24

    VFW

    COMMO

    N

    NOTUSED

    LED1

    LED3

    LED2

    RADIOTO

    UCH

    PHASE

    FACF

    S1

    TEST

    12 11 10 9 8 7 6 5 4 3 2 112 11 10 9 8 7 6 5 4 3 2 1

    RadioTouch TM

    Coopersburg,PA18036USA

    RTA-RX-F-SCLISTED243CInd.Cont.Eq.

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

    Occ

    .Com

    Occ

    Sig

    24V

    CirCom

    CCO1

    CCO2

    CCO3

    CCO4

    CCO5

    CCOCom+ _

    PELV

    (Class2:U

    SA)

    PWR STAT PROG 100Hr/100%

    ®

    PSSig

    P/N

    500

    -106

    34©

    2006

    LutronElectronicsCo.,Inc

    .

    1 2 3 4 5

    ON

    PowerWiringCableadodePoderCâblaged'alimentation

    DistributionPanelPaneldeDistribuciónPanneaudeDistribution

    Ground/Tierra/Terre

    Neutral/Neutro/Neutre

    Black/Negro/Noir

    Green/V erde/Vert

    White/Blanco/Blanc

    Red/Rojo/RougeOR

    Orange/Anaranjado/Orange*

    SwitchedHot/InterruptorVivo/CourantCommuté

    DimmedHot/AtenuadorVivo/CourantTamisé*

    Dimmed Hot is for use only with Lutron Hi-Lume FDB-series or Eco-10 ECO-series dimming ballasts.

    El Atenuador V ivo es para ser utilizado únicamente con las series de balastosde atenuaci ón Hi-Lume FDB o Eco-10 ECO de Lutron.Courant T amisé doit être utilisé seulement avec le Hi-Lume FDB-series ou avecle ballast de gradation Eco-10 ECO-series de Lutron.

    P/N 500-10634

    ***

    Hot/Vivo/Chargé

    For 120 V~ use black wire, cap red. For 277 V~ use red wire, cap black.

    Blue/Bleu/Azul

    120V277V

    *

    USA,Canada 1-800-523-9466Mexico 1-888-235-2910

    ®

    www .lutron.com

    RTA-R X-F-SC

    15V

    CONFIGURACIONESREGLAGESSETTINGS

    RefertotheInstallersGuideformoredetailedinstructions.ConsultelaGuíadeInstaladoresparainformaciónmásdetallada.RéférerauGuided’installationpourplusderenseignementsdétaillés.

    120/277V60Hz16AMax.

    0-10V

    Red&Black/Rojo&Negro/Rouge&Noir

    RadioTouch TM

    Coopersburg,PA18036USA

    RTA-RX-F-SCLISTED243CInd.Cont.Eq.

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

    Occ

    .Com

    Occ

    Sig

    24V

    CirCom

    CCO1

    CCO2

    CCO3

    CCO4

    CCO5

    CCOCom+ _

    PELV

    (Class2:U

    SA)

    PWR STAT PROG 100Hr/100%

    ®

    PSSig

    P/N

    500

    -106

    34©

    2006

    LutronElectronicsCo.,Inc

    .

    1 2 3 4 5

    ON

    PowerWiringCableadodePoderCâblaged'alimentation

    DistributionPanelPaneldeDistribuciónPanneaudeDistribution

    Ground/Tierra/Terre

    Neutral/Neutro/Neutre

    Black/Negro/Noir

    Green/V erde/Vert

    White/Blanco/Blanc

    Red/Rojo/RougeOR

    Orange/Anaranjado/Orange*

    SwitchedHot/InterruptorVivo/CourantCommuté

    DimmedHot/AtenuadorVivo/CourantTamisé*

    Dimmed Hot is for use only with Lutron Hi-Lume FDB-series or Eco-10 ECO-series dimming ballasts.

    El Atenuador V ivo es para ser utilizado únicamente con las series de balastosde atenuaci ón Hi-Lume FDB o Eco-10 ECO de Lutron.Courant T amisé doit être utilisé seulement avec le Hi-Lume FDB-series ou avecle ballast de gradation Eco-10 ECO-series de Lutron.

    P/N 500-10634

    ***

    Hot/Vivo/Chargé

    For 120 V~ use black wire, cap red. For 277 V~ use red wire, cap black.

    Blue/Bleu/Azul

    120V277V

    *

    USA,Canada 1-800-523-9466Mexico 1-888-235-2910

    ®

    www .lutron.com

    RTA-R X-F-SC

    15V

    CONFIGURACIONESREGLAGESSETTINGS

    RefertotheInstallersGuideformoredetailedinstructions.ConsultelaGuíadeInstaladoresparainformaciónmásdetallada.RéférerauGuided’installationpourplusderenseignementsdétaillés.

    120/277V60Hz16AMax.

    0-10V

    Red&Black/Rojo&Negro/Rouge&Noir

    LUT-ELI-3PHUnit RadioTouchUnitA RadioTouchUnitB

    120/277V feedbackup/Emergencypower

    120/277V feedbackup/Emergencypower

    FlipDipSwitch2tothedownposition

    FlipDipSwitch2tothedownposition

    (2)Signal(6)CircuitCommon

    ToadditionalRadioTouchcontrollers(100maximum)

    AdditionalRadioTouchControllerforBackup/EmergencyLight(s)

    Availablepowerfromthisunitfordaylightsensorsmustbederatedto15mA.

    (8) (2)(7) (4)(1) (6)

    Installing a LUT-ELI-3PH Unit in a RadioTouch® System (continued)NEC® Class 2/PELV ConnectionsNote: Whenwiringforabackup/emergencysourceofpower,theRadioTouchController(modelsRTA-RX-F,RTA-RX-F-SC,RTA-RXSW),beingusedforthebackup/emergencylights(UnitAandB)cannotbecontrolledbyanoccupancysensor.UnitsAandBDIPswitch2mustbeinthedownposition.

    NEC Class 2/PELV Wiring to RadioTouch ControllersOneLUT-ELI-3PHcanbeconnectedinparallelwithupto100RadioTouchControllers.

    1. FlipDIPswitch2ontheRadioTouchControllertothedownposition.

    2. DisconnectanyoccupancysensorswiredtotheRadioTouchController.

    3. Makethefollowingconnections.

    From LUT-ELI-3PH Unit To RadioTouch ControllerTerminal8(+VInput) Terminal4(24V ),UnitAonlyTerminal7(CircuitCommon)

    Terminal6(CirCom)

    Terminal1(Signal) Terminal2(OccSig)

    Test the System Pleaseperformthefollowingteststoensureproper

    installation.1. TurnoffoneoftheNormal(Non-Essential)phase(s)

    breaker(s)thattheLUT-ELI-3PHunitismonitoring. You should see the following: •AlllightscontrolledbyEmergency(Essential)panel

    willgotoFULLINTENSITY(factoryset). •PHASEON/OFFstatusIndicator(green)willturn

    OFFastheabovetestcreatesaphasefailure. •Uponturningthebreakerbackon,alllightsshould

    returntotheirpreviousintensity.2. PressandholdswitchSW1ontheLUT-ELI-3PHunit. You should see the following: •TESTLED(orange)willturnON. •AlllightscontrolledbyEmergencyRadioTouch

    controllerwillgotoFULLINTENSITY(factoryset). Note: PHASEON/OFFstatusindicator(green)will

    notturnOFFastest#2doesnotcreateaphasefailure.

    •UponreleasingswitchSW1,alllightswillreturntotheirpreviousintensities.

    Note:OnlyoneRadioTouchunitcanhaveits24V (number4)terminalconnectedtoterminal8(+VInput)ontheLUT-ELIunitregardlessofthenumberofwiredRadioTouchunits.

    (2) (6)

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 4 LUT-ELI-3PH Installation Guide

    Installing a LUT-ELI-3PH Unit in a Panel-Based System

    Line Voltage Connections

    WARNING! Danger of shock. May result in serious injury or death.DONOTWIREWHENLIVE!SwitchoffpowertoallpowerfeedsviacircuitbreakerorisolatorbeforewiringorservicingtheLUT-ELI-3PHunitandPanel-BasedSystem.

    Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit must be accessed by a certified electrician, following local codes.

    Note: Providepropershort-circuitandovercurrentprotectionatthedistributionpanel.Maximumcircuitbreakerratingof20A.

    WiringfromMainswithGP,LP,XP,andXPS/LCPPanels

    PhaseA

    NormalPower

    Normal

    topan

    el

    Red

    Red

    Red

    White

    Green

    PhaseBPhaseCNeutralGround

    WiringfromNormal(Non-Essential)GPPanel

    DH1 SH1 H1 DH2 SH2 H2 DH3 SH3 H3

    ´FACP´N

    /C

    CONTA

    CTS

    ´FACP´N

    /O

    CONTA

    CTS

    12 11 10 9 8 7 6 5 4 3 2 1CLASS2LOWVOLTAGEWIRING

    GND

    SENS

    E

    DRAIN

    MUX

    MUX

    +24

    VFW

    COMMO

    N

    NOTUSED

    LED1

    LED3

    LED2

    RADIOTO

    UCH

    PHASE

    FACF

    S1

    TEST

    RedRedRedWhite

    Green(togroundlug)

    Typicalloadcircuit

    Controlwiringtocircuitselector

    GP3panelshown

    Branchcircuitbreakers

    Normalpowerfeedwiring

    Terminalblocks

    Neutralblock

    Groundlug

    N

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 5

    Installing a LUT-ELI-3PH Unit in a Panel-Based System (continued)

    NEC® Class 2/PELV: USA Connections

    Notes• PullNECClass2/PELVwiringforsystem

    communications.• NECClass2/PELVwiringmustbedaisy-chained.• NECClass2/PELVwiringmustberunseparatelyfrom

    line(mains)voltage.• ALUT-ELI-3PHunitcanbeplacedanywhereonthe powerpanellink.

    Wiring Notes• NECClass2/PELVwiringlinkis500to2000feet (152to610m),useLutron®cableGRX-CBL-46L: -Two12AWG(2.5mm2)forcontrolwiring (+Vandcom) -Onetwisted,shieldedpair22AWG(0.5mm2)

    fordatalink -One18AWG(1.0mm2)forsenselinebetween

    panels.• Lutronhasalsoapprovedsmaller-gaugecable

    fromBelden®,LibertyWire&Cable®,AlphaWireCompany,andSignatureWireCorp.AskforLutronGRAFIKEye®Cable.

    PaneltopanelwiringSeeaboveforwiringnotes

    Dimmingpanel

    Powerpanellink

    LUT-ELI-3PHUnit

    Processorpanel

    Wallstationlinks

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 6 LUT-ELI-3PH Installation Guide

    ´FACP´N

    /C

    CONTA

    CTS

    ´FACP´N

    /O

    CONTA

    CTS

    CLASS2LOWVOLTAGEWIRING

    GND

    SENS

    E

    DRAIN

    MUX

    MUX

    +24

    VFW

    COMMON

    NOTUSED

    LED1

    LED3

    LED2

    RADIOTO

    UCH

    PHASE

    FACF

    S1

    TEST

    DataAOK Power DataBOK

    1 2 3 4 D 5

    Com

    mon

    Com

    mon

    +24

    VFW

    Sen

    se

    MUX

    MUX

    Drain

    Drain

    MUX

    MUX

    Circuit

    1

    2

    Link

    A

    1

    23,4

    5

    1

    2

    3,4

    DataAOK Power DataBOK

    1 2 3 4 D 5 C D

    Com

    mon

    Com

    mon

    +24

    VFW

    Sen

    se

    MUX

    MUX

    Drain

    Drain

    MUX

    MUX

    Circuit

    1

    2

    1 2 3 4 D 5

    SELECT CIRCUIT SELECT CIRCUIT

    Link

    BLink

    ALink

    B1 2 3 4 D 5 C D12 11 10 9 8 7 6 5 4 3 2 112 11 10 9 8 7 6 5 4 3 2 1

    Shield/Drain

    Tolightingcontrolsorprocessors

    ControlWiring:(2)12AWG(2.5mm2)1:Common2:24V

    DataLink:(1)shielded,twistedpair18AWG(1.0mm2)3:MUX4:MUX

    Sense:(1)18AWG(1.0mm2)5:Senseline

    Installing a LUT-ELI-3PH Unit in a Panel-Based System (continued)NEC® Class 2/PELV Panel to Panel Wiring Notes

    • EmergencyPower:Theadditional18AWG(1.0mm2)wireisa“sense”linefromterminal12ontheLUT-ELI-3PH.ThissenselineallowsanEmergency(Essential)lightingpanelto“sense”whenNormal(Non-Essential)powerislost.IfmorethanoneemergencylightingpanelneedstosenseNormal(Non-Essential)fromaspecificLUT-ELI-3PHunit,youmayhavetorunadedicatedwirebetweeneachLUT-ELI-3PHunitandEmergency(Essential)panel(s).

    • Shield/Drain:ConnectshieldingasshownbelowinwiringexampleA:

    -DonotconnecttoGround(Earth)orcircuitselector. -Connectthebaredrainwiresandcutofftheoutside

    shield.

    ConnectionsLUT-ELI-3PH Circuit Selector

    Terminal12(Sense) Terminal5(Sense)

    Terminal11(Drain) TerminalD(Drain)

    Terminal10(MUX) Terminal4(MUX)

    Terminal9(MUX) Terminal3(MUX)

    Terminal8(+VInput) Terminal2(+24VFW)

    Terminal7(CircuitCommon)

    Terminal1(Common)

    Panel1 Panel2

    Data A OK Data B OKPower OK

    1 2 3 4 5D

    2

    1

    Circuit

    AB

    Com

    mon

    24VFW

    MUX

    MUX

    Drain

    Sen

    se

    Com

    m

    Drain

    MUX

    MUX

    C1 2 3 4 D 5 D

    Link Link

    SELECT CIRCUIT

    SELECT VALUEVIEW VALUE

    (4)12AWG(2.5mm2)

    • EachNECClass2/PELVterminalcanacceptonlytwo18AWG(1.0mm2)wires.Two12AWG

    (2.5mm2)conductorswon'tfit.ConnectasshownbelowinwiringexampleB.

    Wiring Example A

    Wiring Example B

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 7

    Installing a LUT-ELI-3PH Unit in a Panel-Based System (continued)

    Setting the Circuit Selector Normal/Emergency Switch (SW6) Position

    PanelsareshippedwithSW6(locatedatthebaseofeachCircuitSelector)inthemiddleposition.Terminal5(sense)hasnoaffectonthecircuitselectoroperation.

    All Emergency Panels •MoveSW6totherightEmergency(Essential)position.In

    thisarrangement,theLUT-ELI-3PHunitwillbetheonlyunitcontrollingthesenseline.Ifoneormorephasesgodown,theLUT-ELI-3PHunitsendsasignalthroughthesenselinetoEmergency(Essential)panel(s).Thelightscontrolledbythesepanelswillgoto‘ord’overridelevels(factorysettofullintensity).Whennormalpowerisrestored,lightswillreturntotheirpreviousintensities.

    Note: Whenin‘ord’overridemode(factorysettofullintensity),‘ord’willappearonvaluedisplaytoconfirmthatEmergency(Essential)positionisineffect.

    Test the System Pleaseperformthefollowingteststoensureproper

    installation.1. TurnoffoneoftheNormal(Non-Essential)phase(s)

    breaker(s)thattheLUT-ELI-3PHunitismonitoring. You should see the following: •PHASEON/OFFstatusIndicator(green)willturnOFFas

    theabovetestcreatesaphasefailure. •CircuitselectoronEmergency(Essential)panelwillgoto

    ‘ord’overridemode. •AlllightscontrolledbyEmergency(Essential)panelwillgo

    toFullIntensity(FactorySet). •ThecircuitselectorinEmergency(Essential)panelwillread

    ‘ord’onthevaluedisplaywheninEmergencymode. •AlllightscontrolledbyNormal(Non-Essential)panelwill

    freezeattheirrespectiveintensities.2. PressandholdswitchSW1ontheLUT-ELI-3PHunit. You should see the following: • TESTLED(orange)willturnON. Note: PHASEON/OFFstatusindicator(green)willnotturn

    OFFastest#2doesnotcreateaphasefailure. • CircuitSelectoronEmergency(Essential)Panelwillgoto

    ‘ord’overridemode. • AlllightscontrolledbyEmergency(Essential)panelwillgo

    toFULLINTENSITY(factoryset). • ThecircuitselectoronEmergency(Essential)panelwill

    read‘ord’onthevaluedisplaywheninEmergencyMode. • AlllightscontrolledbyNormal(Non-essential)panelwill

    freezeattheircurrentintensities. • UponreleasingswitchSW1,alllightswillreturntotheir

    originalintensities.

    DataAOK DataBOKPowerOK

    1 2 3 4 5D

    Load Type (See Instructions)

    High-End Trim

    Circuit Level

    Low-End Trim

    5

    4

    3

    Value

    Link A

    Link B

    2

    1

    Circuit

    A B

    Com

    mon

    24V

    FW

    MU

    X

    MU

    X

    Dra

    inS

    ense

    Com

    m

    Dra

    in

    MU

    X

    MU

    X

    C1 2 3 4 D 5 D

    Link Link

    1-1

    2-12-2

    3-1

    4-1Incandescent

    Neon / CC

    Non-Dim

    --- Unassigned

    Fluorescent Lutron Tu-WireTM Ballast

    Address ('Ad' displayed)

    Zone Assignment w/ Circuit ScheduleZone Assignment w/ Zone CaptureTM

    Warning - Read instructions to set the LoadType. Instructions show more load types.

    Load Type Quick Reference:

    SELECT CIRCUIT

    SELECT VALUEVIEW VALUE

    SELECT VALUE DISPLAYED

    Normal Emergency

    (Essential)(Non-Ess)

    Fluorescent Lutron Hi-lume R FDB Ballast

    LINK 1 LINK 2

    DataAOK DataBOKPowerOK

    1 2 3 4 5D

    Load Type (See Instructions)

    High-End Trim

    Circuit Level

    Low-End Trim

    5

    4

    3

    Value

    Link A

    Link B

    2

    1

    Circuit

    A B

    Com

    mon

    24V

    FW

    MU

    X

    MU

    X

    Dra

    inS

    ense

    Com

    m

    Dra

    in

    MU

    X

    MU

    X

    C1 2 3 4 D 5 D

    Link Link

    1-1

    2-12-2

    3-1

    4-1Incandescent

    Neon / CC

    Non-Dim

    --- Unassigned

    Fluorescent Lutron Tu-WireTM Ballast

    Address ('Ad' displayed)

    Zone Assignment w/ Circuit ScheduleZone Assignment w/ Zone CaptureTM

    Warning - Read instructions to set the LoadType. Instructions show more load types.

    Load Type Quick Reference:

    SELECT CIRCUIT

    SELECT VALUEVIEW VALUE

    SELECT VALUE DISPLAYED

    Normal Emergency

    (Essential)(Non-Ess)

    Fluorescent Lutron Hi-lume R FDB Ballast

    LINK 1 LINK 2

    CircuitSelectorinNormal(Non-Emergency)Panel

    CircuitSelectorinEmergency(Essential)Panel

    Switchisincenterposition

    Switchismovedtotheright(emergency)position

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 8 LUT-ELI-3PH Installation Guide

    Installing a LUT-ELI-3PH Unit in an EcoSystem® or Quantum® SystemLine Voltage and NEC® Class 2/PELV Connections

    WARNING! Danger of shock. May result in serious injury or death.DONOTWIREWHENLIVE!SwitchoffpowertoallpowerfeedsviacircuitbreakerorisolatorbeforewiringorservicingtheLUT-ELI-3PHunitandEcoSystemlightingcontrolsystemorQuantumsystem.Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit must be accessed by a certified electrician, following local codes.

    Note: Providepropershort-circuitandovercurrentprotectionatthedistributionpanel.Maximumcircuitbreakerinstallationof20A.ALutron®PP-120HorPP-277HpowerpackmustbeusedtopowertheLUT-ELI-3PHunitwhenusedwithabussupply.Boththepowerpackandthebussuppliesmustbefedfromanormal/emergencysupply.

    ´FACP´N

    /C

    CONTA

    CTS

    ´FACP´N

    /O

    CONTA

    CTS

    CLASS2LOWVOLTAGEWIRING

    GND

    SENSE

    DRAIN

    MUX

    MUX

    +24

    VFW

    COMMO

    N

    NOTUSED

    LED1

    LED3

    LED2

    RADIOTO

    UCH

    PHASE

    FACF

    S1

    TEST

    E2E1

    12

    34

    56

    78

    E2E1

    EM C

    12 11 10 9 8 7 6 5 4 3 2 112 11 10 9 8 7 6 5 4 3 2 1

    24V(Red)

    Common(Black)

    Hot

    Neutral

    From120or277VNormal/Emergencysupply

    Common

    Emerg.signalConnectupto8

    Quantumhubs

    100-277V Normal/Emergencysupply

    Powerpack*

    WiringtoQuantumsystems *PP-120HorPP-277H

    WiringtoEcoSystemBusSupply

    ´FA

    CP

    ´ N/C

    CO

    NTA

    CTS

    ´FA

    CP

    ´ N/O

    CO

    NTA

    CTS

    12 11 10 9 8 7 6 5 4 3 2 1CLASS 2 LOW VOLTAGE WIRING

    GND

    SE

    NS

    E

    DR

    AIN

    MU

    X

    MU

    X

    +24

    VFW

    CO

    MM

    ON

    NO

    T U

    SE

    D

    LED

    1

    LED

    3

    LED

    2

    RA

    DIO

    TOU

    CH

    PH

    AS

    E

    FAC

    F

    S1

    TES

    T

    100-347V 50/60Hz3-phasenormalsupply

    SeeFigure#1orFigure#2onpage2ofthisguide.

    Common

    24V

    24V(Red)

    Common(Black)

    Common(pin5)

    Emerg.signal(pin6)

    Hot

    Neutral

    Powerpack*

    From120or277VNormal/Emergencysupply

    Bussupply Bussupply

    Connectupto32bussupplies

    100-277V Normal/Emergencysupply

    *PP-120HorPP-277H

    (8) (7) (1)

    (8) (7) (1)

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 9

    Installing a LUT-ELI-3PH Unit in a GRAFIK Eye® QS UnitNEC® Class 2/PELV Connections

    WARNING! Danger of shock. May result in serious injury or death.DONOTWIREWHENLIVE!SwitchoffpowertoallpowerfeedsviacircuitbreakerorisolatorbeforewiringorservicingtheLUT-ELI-3PHunitandGRAFIK EyeQSunit.Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit must be accessed by a certified electrician, following local codes.

    WiringtoaGRAFIK EyeQSControlUnit

    Notes • Providepropershort-circuitandovercurrent

    protectionatthedistributionpanel.Maximumcircuitbreakerinstallationof20A.

    • Whennormalpowerlossisdetectedatthe LUT-ELI-3PHunit,allzonesintheGRAFIK EyeQS

    unitswillgototheiremergencystates.• TheGRAFIK EyeQSunitMUSTbepoweredfroma

    normal/emergencypowerfeed.

    Note:For1-phase2-wireapplication,connectphaseA,B,andCwiresonLUT-ELI-3PHtogetherforphasesensing.

    ´FACP´N

    /O

    CONTA

    CTS

    TAGEWIRING

    GND

    SENSE

    NOTUSED

    LED1

    LED3

    LED2

    RADIOTO

    UCH

    PHASE

    FACF

    S1

    TEST

    12 9 8 7 6 5 4 3 2 1

    ´FACP´

    CP´N

    /O

    CCONTA

    CTS

    TAGEWIRING

    SE

    NS

    E

    NOTUS

    ED

    LED

    RADIO

    TOUCH

    12 8 7 6 5 4 379 8 7 6 5 4 3 2 1

    ´FACP´N

    /C

    CONTA

    CTS

    ´FACP´N

    /O

    CONTA

    CTS

    CLASS2LOWVOLTAGEWIRING

    SENS

    E

    DRAIN

    MUX

    MUX

    +24

    VFW

    COMMO

    N

    NOTUSED

    LED3

    RADIOTO

    UCH

    12 11 10 9 8 7 6 5 4 3 2 1

    Signal+24V

    Common

    (3)18AWG

    GRAFIK EyeQSunitQSGRJmodel(backview)

    Normal/Emergency20A120V1-Phase2-Wirepowerfeed(3)12AWG(2.5mm²)120-127Vor220-240Vdistributionpanel

    100-347V 50/60Hz3-phaseNormalsupply

    SeeFigure#1orFigure#2onpage2ofthisguide.

    CCI SIG24 VCCI Com

    (8) (7) (1)

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 10 LUT-ELI-3PH Installation Guide

    ´FA

    CP

    ´ N/C

    CO

    NTA

    CTS

    ´FA

    CP

    ´ N/O

    CO

    NTA

    CTS

    12 11 10 9 8 7 6 5 4 3 2 112 11 10 9 8 7 6 5 4 3 2 1CLASS 2 LOW VOLTAGE WIRING

    GND

    SE

    NS

    E

    DR

    AIN

    MU

    X

    MU

    X

    +24

    VFW

    CO

    MM

    ON

    NO

    T U

    SE

    D

    LED

    1

    LED

    3

    LED

    2

    RA

    DIO

    TOU

    CH

    PH

    AS

    E

    FAC

    F

    S1

    TES

    T

    Installing a LUT-ELI-3PH Unit with an Energi Savr NodeTM Unit(s)NEC® Class 2/PELV Connections

    WARNING! Danger of shock. May result in serious injury or death.DONOTWIREWHENLIVE!SwitchoffpowertoallpowerfeedsviacircuitbreakerorisolatorbeforewiringorservicingtheLUT-ELI-3PHandEnergi Savr Nodeunit.

    Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit must be accessed by a certified electrician, following local codes.

    Notes: Providepropershort-circuitandovercurrentprotectionatthedistributionpanel.Maximumcircuitbreakerinstallationof20A.

    • ALutron®PP-120HorPP-277HpowerpackmustbeusedtopowertheLUT-ELI-3PHunitwhenusedwithanEnergi Savr Nodeunit(s).BoththepowerpackandtheEnergi Savr Nodeunit(s)mustbefedfromanormal/emergencysupply.

    • WhennormalpowerlossisdetectedattheLUT-ELI-3-PHunit,allzonesintheEnergi Savr Nodeunitwillgototheiremergencystates.

    • TheEnergi Savr NodeunitMUSTbepoweredfromanormal/emergencypowerfeed.

    WiringfromEnergi Savr NodeUnits

    Note: For1-phase2-wireapplication,connectphaseA,B,andCwiresonLUT-ELI-3PHtogetherforphasesensing.

    ConnectionsLUT-ELI-3PH Energi Savr Node Unit Power Pack

    Terminal8(+VInput) ------------------------- RedWire

    Terminal7(CircuitCommon)

    Com(EmergencyCCIInput)

    BlackWire

    Terminal1(Signal) Emerg(EmergencyCCIInput) ---------------

    *NECClass2/PELVWiring18AWG(1.0mm²)

    Note:Upto32QSN-4T16-SorQSN-4S16-Sunitscanbeconnectedto1LUT-ELI-3PH

    *Signal

    *Common(Black)

    *+24V (Red)

    PP-120HorPP-277H

    *Signal

    *Common

    *Common

    2#12InputPower

    (120or277V )Normal/EmergencyPower

    (8) (7) (1)

    100-347V 50/60Hz3-phaseNormalsupply

    SeeFigure#1orFigure#2onpage2ofthisguide.

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 11

    Emergency Power ModeSetup: LCP128TM / Softswitch128®with LUT-ELI-3PH

    Thisstepisonlyperformedifanemergencypattern*isneededwhennormalpowerislost.Allcontroldeviceinputsandtimeclockeventsareignoredwhileinemergencypowermode.Thisstepwilldefineifthepanelhasemergencycircuitsandhowtoconfiguretheemergencypattern.

    •Foralltheemergency(essential)lightingpanels,movetheemergency switchestotherightposition(seeillustrationbelow).

    •Theessentialandnon-essentialpanelsmustbecon-nectedbyasenselinewiredtoterminal 5onthelinkconnectorontheLCP128/Softswitch128controller(seeillustrationbelow).Forwiringdetails,seetheInstallationGuide.

    *Inthisconfiguration,theemergency(essential)lightingpanelwill“sense”thenormalpanels’power.Whennormalpowerislost,theemergencypanelwillgototheemergencypattern(factorysettoallcircuitsOn).Whennormalpowerisrestored,lightingcircuitsandcontactclosureoutputsreturntotheirpreviousstate.

    UseTerminal5toconnectasenselinebetweenemergencyandnormalpanels,orbetweentheLUT-ELI-3PHunitandoneormoreemergencypanels.An#18AWGwireisrecommendedforthesenseline. ThreepositionEmergency Switchislocatedatthe

    bottomoftheLCP128/Softswitch128controller.

    1 2 3 4 5D

    TopoftheLCP128/Softswitch128Controller

    LeftPosition RightPosition

    (Non-Essential) (Essential)

    CenterPosition(NoresponsetoEmergency)

    Notes:•IfUL924certificationisrequired,theLutron®

    EmergencyLightingInterface(LUT-ELI-3PH)maybeusedtomeetcode.TheLUT-ELI-3PHunitsensesthenormal(non-essential)linevoltageonallthreephases(3PH)ofnormalpower.Whenoneormorephasesofpowerarelost,theLUT-ELI-3PHunitwillsendasignaltoterminal 5ontheLCP128/Soft-switch128controller(s).Whentheemergency switchissettotherightposition(essential)theemergencypatternwillberecalled.TheLUT-ELI-3-PHunitcanbeusedwithoneormultiplepanelsystems.

    •Lossofnormalpowercanbesimulatedbyturningoffallconnectednormal(non-essential)panelcontrolbreakers.

    •Whentheemergencyswitchisinitscenterposition(asshipped),terminal5thepaneldoesnotrespondtoemergency.

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 12 LUT-ELI-3PH Installation Guide

    ´FACP´N

    /C

    CONTA

    CTS

    ´FACP´N

    /O

    CONTA

    CTS

    CLASS2LOWVOLTAGEWIRING

    GND

    SENSE

    DRAIN

    MUX

    MUX

    +24

    VFW

    COMMO

    N

    NOTUSED

    LED1

    LED3

    LED2

    RADIOTO

    UCH

    PHASE

    FACF

    S1

    TEST

    12 11 10 9 8 7 6 5 4 3 2 112 11 10 9 8 7 6 5 4 3 2 1

    NormallyOpenFACPInput

    LUT-ELI-3PHunit

    To24V power

    FireAlarmControlPanel(providedbyothers)

    CommonNormallyopen

    NEC® Class 2/PELV Wiring to Fire Alarm Control Panel (FACP)

    • Useonlywithnormallyopen(terminals3and4)ornormallyclosed(terminals5and6)drycontactclosure.Whenthepropercontactstateistriggered,itmustbemaintainedfortheLUT-ELI-3PHunittogointoEmergencyMode.Oncethecontactisreleased,theLUT-ELI-3PHunitwillreturntheGRAFIKSystemsTMGP,LP,XPpanels,XPS,LCP,RadioTouch®controller,EcoSystem®BusSupply,EnergiSavrNodeTMunit,orQuantum®BusSupplybacktoNormaloperationmode.

    • TheLUT-ELI-3PHunitwillhaveafactoryinstalledjumpertoprovidethenormallyclosedinputsignalforthesupervisorycircuitwhenanormallyclosedFACPinputisnotprovided.

    • ConsultyourFireAlarmControlPanel’sinstructionmanualbeforeconnectingtotheLUT-ELI-3PHunit.

    • DonotconnectanyvoltagesourcetotheFACPinputsontheLUT-ELI-3PHunit.IfvoltageisprovidedbytheFACPandconnectedtotheLUT-ELI-3PHunit,itcandamagetheLUT-ELI-3PHunit.

    ´FACP´N

    /C

    CONTA

    CTS

    ´FACP´N

    /O

    CONTA

    CTS

    CLASS2LOWVOLTAGEWIRING

    GND

    SENSE

    DRAIN

    MUX

    MUX

    +24

    VFW

    COMMO

    N

    NOTUSED

    LED1

    LED3

    LED2

    RADIOTO

    UCH

    PHASE

    FACF

    S1

    TEST

    12 11 10 9 8 7 6 5 4 3 2 112 11 10 9 8 7 6 5 4 3 2 1

    SupervisoryCircuit(NormallyClosedFACPInput)

    LUT-ELI-3PHunit

    To24V power

    FireAlarmControlPanel(providedbyothers)

    CommonNormallyclosed

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 13

    Troubleshooting RadioTouch®Symptom Possible Cause Solution

    Lightsareatfullintensityandcannotbecontrolledbyanaddressedtransmitter

    LUT-ELI-3PHunitisnotconnectedtoSignalontheRadioTouchController

    Connectterminal2‘OccSig’fromtheRadioTouchControllertoterminal1‘Signal’ontheLUT-ELI-3PHunit

    OneormoreofthephasesfeedingtheLUT-ELI-3PHunitareoff(phaseLEDontheLUT-ELI-3PHunitwillbeoff)

    TurnONallnormalpowerphasestoLUT-ELI-3PHunit

    NeutralisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectneutral

    24V isnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectterminal4‘24V ’fromRadioTouchControllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit

    ThereisashortacrossFACPandnormallyopencontact(FACPLEDwillbeON)

    Removeshort

    LightsdonotturnONanddonotgotohighendwhenthetestswitchispressed

    DIPswitch2ontheRadioTouchControllerisintheUPposition

    MoveDIPswitch2ontheRadioTouchControllertotheDOWNposition

    24V andsignalwiresareswapped

    Connectterminal4‘24V ’fromtheRadioTouchControllertoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectterminal2‘OccSig’fromtheRadioTouchControllertoterminal1‘Signal’ontheLUT-ELI-3PHunit

    24V andcommonwiresareswapped

    Connectterminal4‘24V ’fromtheRadioTouchControllertoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectterminal6‘CirCom’fromtheRadioTouchControllertoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    Commonandsignalwiresareswapped

    Connectterminal6‘CirCom’fromtheRadioTouchControllertoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunitandconnectterminal2‘Occsig’fromtheRadioTouchControllertoterminal1‘Signal’ontheLUT-ELI-3PHunit

    LightsdonotturnONanddonotgotohighendwhenoneormoreofthenormalpowerphasesareturnedOFF

    DIPswitch2ontheRadioTouchControllerisintheUPposition

    MoveDIPswitch2ontheRadioTouchControllertotheDOWNposition

    24V andsignalareswapped Connectterminal4‘24V ’fromtheRadioTouchControllertoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectterminal2‘OccSig’fromtheRadioTouchControllertoterminal1‘Signal’ontheLUT-ELI-3PHunit

    ThatRadioTouchControllerisnotpoweredbytheemergencycircuitpower

    PowertheRadioTouchControllerfromtheemergencycircuitandnotfromnormal

    Theemergencytransferswitchisnotswitchingover

    Consulttransferswitchmanufacturefortroubleshooting

    LUT-ELI-3PHunitisconnectedtotheemergencycircuit

    ConnecttheLUT-ELI-3PHunittonormalpower

    24V andcommonwiresareswapped

    Connectterminal4‘24V ’fromtheRadioTouchControllertoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectterminal6‘CirCom’fromtheRadioTouchControllertoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    Commonandsignalwiresareswapped

    Connectterminal6‘CirCom’fromtheRadioTouchControllertoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunitandconnectterminal2‘OccSig’fromtheRadioTouchControllertoterminal1‘Signal’ontheLUT-ELI-3PHunit

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 14 LUT-ELI-3PH Installation Guide

    Troubleshooting Panel Based SystemsSymptom Possible Cause Solution

    Lightsareatfullintensityandcannotbecontrolledbythewallstation(Circuitselector/controllerreads“ord”),orcontrollerreadsEmergencyMode

    SensewireisnotconnectedfromtheCircuitselector/controllertotheLUT-ELI-3PHunit

    Connectterminal5‘Sense’fromtheCircuitselector/controllertoterminal12‘Sense’ontheLUT-ELI-3PHunit

    OneormoreofthephasesfeedingtheLUT-ELI-3PHunitareoff(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    TurnONallnormalpowerphasestoLUT-ELI-3PHunit

    NeutralisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectneutral

    24VFWisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectterminal2‘24VFW’fromtheCircuitselector/controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit

    ThereisashortacrossFACPandnormallyopencontact(FACPLEDwillbeON)

    Removeshort

    24VFWandsensewiresareswapped

    Connectterminal2‘24VFW’fromtheCircuitselector/controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectterminal5‘Sense’fromtheCircuitselector/controllertoterminal12‘Sense’ontheLUT-ELI-3PHunit

    Commonandsensewiresareswapped

    Connectterminal1‘Common’fromtheCircuitselector/controllertoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunitandconnectterminal5‘Sense’fromtheCircuitselector/controllertoterminal12‘Sense’ontheLUT-ELI-3PHunit

    LightsdonotturnONanddonotgotohighendwhenthetestswitchispressed

    SW6ontheCircuitselector/controllerisinthemiddlepositionorfarleftposition

    MoveSW6ontheCircuitselector/controllertothefarrightposition

    24V andcommonwiresareswapped

    Connectterminal2‘24VFW’fromtheCircuitselector/controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectterminal1‘Common’fromtheCircuitselector/controllertoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    LightsdonotturnONanddonotgotohighendwhenoneormoreofthenormalpowerphasesareturnedOFF

    SW6ontheCircuitselector/controllerisinthemiddlepositionorfarleftposition

    MoveSW6ontheCircuitselector/controllertothefarrightposition

    24V andcommonwiresareswapped

    Connectterminal2‘24VFW’fromtheCircuitselector/controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectterminal1‘Common’fromtheCircuitselector/controllertoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    ThatEmergencyPanelisnotpoweredbytheemergencycircuit

    PowertheEmergencyPanelfromtheemergencycircuitandnotfromnormalpower

    Theemergencytransferswitchisnotswitchingover

    Consulttransferswitchmanufacturefortroubleshooting

    LUT-ELI-3PHunitisconnectedtotheemergencycircuit

    ConnecttheLUT-ELI-3PHunittonormalpower

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 15

    Troubleshooting Energi Savr NodeTM InstallationsSymptom Possible Cause Solution

    Lightsareatfullintensity.Unitwillnotrespondtolocalcontrolorinputsignals.

    SignalwireisnotconnectedfromtheLUT-ELI-3PHunittotheEnergi Savr Nodeunit

    Connect‘Emerg’terminalfromtheEnergi Savr Nodeunittoterminal1‘Signal’ontheLUT-ELI-3PHunit

    OneormoreofthephasesfeedingtheLUT-ELI-3PHunitareoff(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    TurnONallnormalpowerphasestoLUT-ELI-3PHunit

    NeutralisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectneutral

    24VFWisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectredwire(24V )fromthePP-120HorPP-277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PHunit

    ThereisashortacrossFACPandnormallyopencontact(FACPLEDwillbeON)

    Removeshort

    LightsdonotturnONanddonotgotohighendwhenthetestswitchispressed

    24V andcommonwiresareswapped

    Connectredwire(24V )fromthePP-120HorPP-277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectblackwire(Common)fromthePP-120HorPP-277Hunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    LightsdonotturnONanddonotgotohighendwhenoneormoreofthenormalpowerphasesareturnedOFF

    24V andcommonwiresareswapped

    Connectredwire(24V )fromthePP-120HorPP-277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectblackwire(Common)fromthePP-120HorPP-277Hunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    EmergencyPanelisnotpoweredbytheemergencycircuit

    PowertheEmergencyPanelfromtheemergencycircuitandnotfromnormalpower

    Theemergencytransferswitchisnotswitchingover

    Consulttransferswitchmanufacturerfortroubleshooting

    LUT-ELI-3PHunitisconnectedtotheemergencycircuit

    ConnecttheLUT-ELI-3PHunittonormalpower

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    Lutron® | 16 LUT-ELI-3PH Installation Guide

    Troubleshooting EcoSystem® or Quantum® System InstallationsSymptom Possible Cause Solution

    Lightsareatfullintensity.Systemwillnotrespondtolocalcontrolorinputsignals.

    SignalwireisnotconnectedfromtheLUT-ELI-3PHunittotheEcosystembussupply

    Connect‘CCI-EMERG’terminalfromtheEcosystembussupplytoterminal1‘Signal’ontheLUT-ELI-3PHunit

    SignalwireisnotconnectedfromtheLUT-ELI-3PHunittotheQuantum bussupply

    Connect‘EM’terminalfromtheQuantumbussupplytoterminal1‘Signal’ontheLUT-ELI-3PHunit

    OneormoreofthephasesfeedingtheLUT-ELI-3PHunitareoff(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    TurnonallnormalpowerphasestoLUT-ELI-3PHunit

    NeutralisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectneutral

    24VFWisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectredwire(24V )fromthePP-120HorPP-277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PHunit

    ThereisashortacrossFACPandnormallyopencontact(FACPLEDwillbeON)

    Removeshort

    LightsdonotturnONanddonotgotohighendwhenthetestswitchispressed

    24V andcommonwiresareswapped

    Connectredwire(24V )fromthePP-120HorPP-277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectblackwire(Common)fromthePP-120HorPP-277Hunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    LightsdonotturnONanddonotgotohighendwhenoneormoreofthenormalpowerphasesareturnedOFF

    24V andcommonwiresareswapped

    Connectredwire(24V )fromthePP-120HorPP-277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectblackwire(Common)fromthePP-120HorPP-277Hunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    EmergencyPanelisnotpoweredbytheemergencycircuit

    PowertheEmergencyPanelfromtheemergencycircuitandnotfromnormalpower

    Theemergencytransferswitchisnotswitchingover

    Consulttransferswitchmanufacturerfortroubleshooting

    LUT-ELI-3PHunitisconnectedtotheemergencycircuit

    ConnecttheLUT-ELI-3PHunittonormalpower

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide Lutron® | 17

    Troubleshooting a GRAFIK Eye® QS InstallationSymptom Possible Cause Solution

    Lightsareatfullintensity.Systemwillnotrespondtolocalcontrolorinputsignals.

    LUT-ELI-3PHunitisnotconnectedto‘CCISIG’ontheGRAFIK EyeQSunit

    Connectthe‘CCISIG’terminalfromtheGRAFIK EyeQSunittoterminal1‘Signal’ontheLUT-ELI-3PHunit

    OneormoreofthephasesfeedingtheLUT-ELI-3PHunitareoff(phaseLEDontheLUT-ELI-3PHunitwillbeoff)

    TurnonallnormalpowerphasestoLUT-ELI-3PHunit

    NeutralisnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectneutral

    24V isnotconnectedontheLUT-ELI-3PHunit(phaseLEDontheLUT-ELI-3PHunitwillbeOFF)

    Connectthe‘24V ’terminalfromtheGRAFIK EyeQSunittoterminal8‘+VInput’ontheLUT-ELI-3PHunit

    ThereisashortacrossFACPandnormallyopencontact(FACPLEDwillbeON)

    Removeshort

    LightsdonotturnONanddonotgotohighendwhenthetestswitchispressed

    24V andsignalareswapped Connectthe‘24V ’terminalfromtheGRAFIK EyeQSunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectthe‘CCISIG’terminalfromtheGRAFIK EyeQSunittoterminal1‘Signal’ontheLUT-ELI-3PHunit

    24V andcommonwiresareswapped

    Connectthe‘24V ’terminalfromtheGRAFIK EyeQSunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectthe‘CCICom’terminalfromtheGRAFIK EyeQSunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    Commonandsignalareswapped Connectthe‘CCICom’terminalfromtheGRAFIK EyeQSunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunitandconnectthe‘CCISIG’terminalfromtheGRAFIK EyeQSunittoterminal1‘Signal’ontheLUT-ELI-3PHunit

    GRAFIK EyeQSunit‘CCISIG’inputhasnotbeensetupasanemer-gencyinput

    RefertoprogrammingguidefortheGRAFIK EyeQSunitonhowtoprogramthe‘CCISIG’inputasanemergencyinput.

    LightsdonotturnONanddonotgotohighendwhenoneormoreofthenormalpowerphasesareturnedOFF

    24Vandsignalareswapped Connectthe‘24V ’terminalfromtheGRAFIK EyeQSunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectthe‘CCISIG’terminalfromtheGRAFIK EyeQSunittoterminal1‘Signal’ontheLUT-ELI-3PHunit

    TheGRAFIK EyeQSunitisnotpow-eredbytheemergencycircuitpower

    PowertheGRAFIK EyeQSunitfromtheemergencycircuitandnotfromnormal

    Theemergencytransferswitchisnotswitchingover

    Consulttransferswitchmanufacturefortroubleshooting

    LUT-ELI-3PHunitisconnectedtotheemergencycircuit

    ConnecttheLUT-ELI-3PHunittonormalpower

    24V andcommonwiresareswapped

    Connectthe‘24V ‘terminalfromtheGRAFIK EyeQSunittoterminal8‘+VInput’ontheLUT-ELI-3PHunitandconnectthe‘CCICom’terminalfromtheGRAFIK EyeQSunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunit

    Commonandsignalwiresareswapped

    Connectthe‘CCICom’terminalfromtheGRAFIK EyeQSunittoterminal7‘CircuitCommon’ontheLUT-ELI-3PHunitandconnectthe‘CCISIG’terminalfromtheGRAFIK EyeQSunittoterminal1‘Signal’ontheLUT-ELI-3PHunit

    GRAFIK EyeQSunit‘CCISIG’inputhasnotbeensetupasanemer-gencyinput

    RefertoprogrammingguidefortheGRAFIK EyeQSunitonhowtoprogramthe‘CCISIG’inputasanemergencyinput.

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide

    NOTES:

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide

    NOTES:

  • Emergency Lighting Interface LUT-ELI-3PH | Installation Guide

    LUT-ELI-3PH Installation Guide

    PrintedintheU.S.A.P/N031-353Rev.A09/10

    Internet:www.lutron.com

    WORLD HEADQUARTERSLutronElectronicsCo.,Inc.7200SuterRoadCoopersburg,PA18036-1299U.S.A.TOLLFREE:1.800.523.9466(U.S.A.,Canada,andtheCaribbean)Tel:+1.610.282.3800Fax:+1.610.282.1243

    EUROPEAN HEADQUARTERSLutronEALtd.LutronHouse6SovereignCloseWappingLondon,E1W3JF,UKFREEPHONE:0800.282.107(U.K.)Tel:+44.(0)20.7702.0657Fax:+44.(0)20.7480.6899

    ASIAN HEADQUARTERSSingaporeLutronGL,Ltd.15HoeChiangRoad#07-03TowerFifiteenSingapore089316TOLLFREE:800.120.4491Tel:+65.6220.4666Fax:+65.6220.4333

    HONG KONG SALES OFFICETel:+852.2104.7733Fax:+852.2104.7633

    LutronElectronicsCo.,Inc.,reservestherighttomakeimprovementsorchangesinitsproductswithoutpriornotice.Althougheveryattemptismadetoensurethatthisinformationisaccurateanduptodate,pleasecheckwithLutrontoconfirmproductavailability,latestspecificationsandsuitabilityforyourapplication.

    Lutron Electronics Co., Inc.One Year Limited WarrantyFor a period of one year from the date of purchase, and subject to the exclusions and restrictions described below, Lutron warrants each new unit to be free from manufacturing defects. Lutron will, at its option, either repair the defective unit or issue a credit equal to the purchase price of the defective unit to the Customer against the purchase price of comparable replacement part purchased from Lutron. Replacements for the unit provided by Lutron or, at its sole discretion, an approved vendor may be new, used, repaired, reconditioned, and/or made by a different manufacturer. If the unit is commissioned by Lutron or a Lutron approved third party as part of a Lutron commissioned lighting control system, the term of this warranty will be extended, and any credits against the cost of replacement parts will be prorated, in accordance with the warranty issued with the commissioned system, except that the term of the unit’s warranty term will be measured from the date of its commissioning.EXCLUSIONS AND RESTRICTIONS This Warranty does not cover, and Lutron and its suppliers are not responsible for:1. Damage, malfunction or inoperability diagnosed by Lutron or a Lutron approved third party as caused by normal wear and tear, abuse, misuse, incorrect installation, neglect, accident, interference or environmental factors, such as (a) use of incorrect line voltages, fuses or circuit breakers; (b) failure to install, maintain and operate the unit pursuant to the operating instructions provided by Lutron and the applicable provisions of the National Electrical Code and of the Safety Standards of Underwriter's Laboratories; (c) use of incompatible devices or accessories; (d) improper or insufficient ventilation; (e) unauthorized repairs or adjustments; (f) vandalism; or (g) an act of God, such as fire, lightning, flooding, tornado, earthquake, hurricane or other problems beyond Lutron’s control.2. On-site labor costs to diagnose issues with, and to remove, repair, replace, adjust, reinstall and/or reprogram the unit or any of its components.3. Equipment and parts external to the unit, including those sold or supplied by Lutron (which may be covered by a separate warranty).4. The cost of repairing or replacing other property that is damaged when the unit does not work properly, even if the damage was caused by the unit.EXCEPT AS EXPRESSLY PROVIDED IN THIS WARRANTY, THERE ARE NO EXPRESS OR IMPLIED WARRANTIES OF ANY TYPE, INCLUDING ANY IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY. LUTRON DOES NOT WARRANT THAT THE UNIT WILL OPERATE WITHOUT INTERRUPTION OR BE ERROR FREE. NO LUTRON AGENT, EMPLOYEE OR REPRESENTATIVE HAS ANY AUTHORITY TO BIND LUTRON TO ANY AFFIRMATION, REPRESENTATION OR WARRANTY CONCERNING THE UNIT. UNLESS AN AFFIRMATION, REPRESENTATION OR WARRANTY MADE BY AN AGENT, EMPLOYEE OR REPRESENTATIVE IS SPECIFICALLY INCLUDED HEREIN, OR IN STANDARD PRINTED MATERIALS PROVIDED BY LUTRON, IT DOES NOT FORM A PART OF THE BASIS OF ANY BARGAIN BETWEEN LUTRON AND CUSTOMER AND WILL NOT IN ANY WAY BE ENFORCEABLE BY CUSTOMER.IN NO EVENT WILL LUTRON OR ANY OTHER PARTY BE LIABLE FOR EXEMPLARY, CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF PROFITS, CONFIDENTIAL OR OTHER INFORMATION, OR PRIVACY; BUSINESS INTERRUPTION; PERSONAL INJURY; FAILURE TO MEET ANY DUTY, INCLUDING OF GOOD FAITH OR OF REASONABLE CARE; NEGLIGENCE, OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER), NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON’S WRITTEN CONSENT ARISING OUT OF OR IN ANY WAY RELATED TO THE INSTALLATION, DEINSTALLATION, USE OF OR INABILITY TO USE THE UNIT OR OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY, OR ANY AGREEMENT INCORPORATING THIS WARRANTY, EVEN IN THE EVENT OF THE FAULT, TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY, BREACH OF CONTRACT OR BREACH OF WARRANTY OF LUTRON OR ANY SUPPLIER, AND EVEN IF LUTRON OR ANY OTHER PARTY WAS ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.NOTWITHSTANDING ANY DAMAGES THAT CUSTOMER MIGHT INCUR FOR ANY REASON WHATSOEVER (INCLUDING, WITHOUT LIMITATION, ALL DIRECT DAMAGES AND ALL DAMAGES LISTED ABOVE), THE ENTIRE LIABILITY OF LUTRON AND OF ALL OTHER PARTIES UNDER THIS WARRANTY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, USE, REPAIR, OR REPLACEMENT OF THE UNIT, OR ANY AGREEMENT INCORPORATING THIS WARRANTY, AND CUSTOMER'S SOLE REMEDY FOR THE FOREGOING, WILL BE LIMITED TO THE AMOUNT PAID TO LUTRON BY CUSTOMER FOR THE UNIT. THE FOREGOING LIMITATIONS, EXCLUSIONS AND DISCLAIMERS WILL APPLY TO THE MAXIMUM EXTENT ALLOWED BY APPLICABLE LAW, EVEN IF ANY REMEDY FAILS ITS ESSENTIAL PURPOSE.TO MAKE A WARRANTY CLAIMTo make a warranty claim, promptly notify Lutron within the warranty period described above by calling the Lutron Technical Support Center at (800) 523-9466. Lutron, in its sole discretion, will determine what action, if any, is required under this warranty. To better enable Lutron to address a warranty claim, have the unit's serial and model numbers available when making the call. If Lutron, in its sole discretion, determines that an on-site visit or other remedial action is necessary, Lutron may send a Lutron Services Co. representative or coordinate the dispatch of a representative from a Lutron approved vendor to Customer's site, and/or coordinate a warranty service call between Customer and a Lutron approved vendor.NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts. Belden is a registered trademark of Belden, Inc., Richmond, Indiana. Liberty Wire & Cable is a registered trademark of Liberty Wire & Cable, Colorado Springs, Colorado.

    Lutron, EcoSystem, GRAFIK Eye, Quantum, RadioTouch, Softswitch128, and the sunburst logo are registered trademarks and Energi Savr Node and LCP128 are trademarks of Lutron Electronics Co., Inc.

    © 2010 Lutron Electronics Co, Inc.