emf & mmf methods
TRANSCRIPT
Voltage Regulation
When the alternator is subjected to a varying load, the voltage at the armature
terminals varies, the magnitude of this change in terminal voltage depends upon
the load current I and power factor cos Ø.
The voltage regulation of an alternator is defined as the increase in terminal
voltage when full load is thrown off, assuming field current and speed remaining
the same.
The percentage regulation is defined as the ratio of change in terminal voltage form
full load to no load and rated terminal voltage.
i.e. Percentage regulation = Eo - V /V X 100
where E0 is no load terminal voltage and V is full load rated terminal voltage.
Note : In case of leading power factor E0 is less than V, so regulation will be -ve.
Determination Of Voltage Regulation
It is not usually possible or desirable to determine the voltage regulation by direct
testing, indirect methods being adopted which do not need the alternator
loading. For this purpose OC and SC tests are performed to give OC and SC
characteristics. The various methods used for determination of voltage regulation
are given below:
Synchronous EMF or Impedance Method.
After determining Re and Xs from OC and SC tests the open circuit voltage can be
determined form the following relation
E0 = √(V cosØ + IRe)2 + (V sin Ø + IXs)
2
And %age regulation = Eo - V /v X 100
For leading pf Ø is taken negative and for unity pf Ø is taken zero.
The synchronous impedance obtained by this method is always higher than actual
value owing to the fact that the synchronous impedance Zs at short-circuit
condition is too large due to very low degree of saturation. Hence this method is
called the pessimistic method.
Amp-Turn or MMF Method.
From the OC and SC characteristics determined from OC and SC tests the field
currents If1 and If2 are determined to give rated voltage V on no-load (neglecting
armature resistance drop) and cause short-circuit current, equal to full load current,
on short-circuit. If1 gives full load rated voltage and If2 gives demagnetizing
ampere-turns at full load.
This method of determination of synchronous impedance is known as optimistic
method since it gives values lower than actual values. The reason of it is that the
excitation to overcome armature reaction is determined on unsaturated part of the
saturation curve.