en fiessler ulvt short

11
BG zugelassen U L R LISTED Telefon: 0711 / 91 96 97-0 Internet: http://www.fiessler.de Telefax: 0711 / 91 96 97-50 eMail: [email protected] Infrared accident prevention safety curtains ESPE Type 4 ULVT / ULVTK / BLVT / BLVTK INHALT: Safety instructions Application notes Installation Electric Connection Commissioning Specifications Accessories FIESSLER E L E K T R O N I K ULVT BLVT (with blanking features) Muting, cycle operation .... with safety switching units as option Fiessler Elektronik Kastellstr. 9 D 73734 Esslingen ULVTK / BLVTK (Cascading of Light Curtains) FIESSLER E L E K T R O N I K Typ: ULSG 230V 2 3 1 18 19 Schaltgerät BWS Typ 4 Switching unit ESPE Type 4 Boîtier de commande ESPS Type 4 Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 970 Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten! AttentionTurn off the supply voltage ! Attention Couper l'alimentation ! Nr./Baujahr No./year of construction No./année de fabrication ................................. Ansprechzeit response time temps de réponse 20 mS Temp. temp. temp. -10… + 55 °C Schutzart enclosure rating degré de protection IP 20 Versorgung supply voltage tension d'alimentation 230 VAC -15% +10 %, 50Hz Kontaktbel. contact max. charge contact maxi. 2 A, 250 VAC Made in Germany 230V 115V 24V - N 6 A 1 2 3 7 4 5 8 10 9 17 B C 12 13 14 15 16 18 19 20 21 22 D 11 FIESSLER E L E K T R O N I K Schaltgerät BWS Typ 4 Switching unit ESPE Type 4 Boîtier de commande ESPS Type 4 Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel. Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0 LSUW NSR 3-1 K No./year of construction response time temp. enclosure rating supply voltage contact max No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi. ................................. 30 mS -10… + 55 °C IP 20 230 VAC -15% +10 %, 50Hz 2 A, 250 VAC Netz tension power LS Frei BS libre LC free output interupted sortie interrompue Ausgang unterbrochen output free sortie libre Ausgang frei interdiction de redémarrage restart interlock Wiederanlaufsperre LS unterbrochen BS interrompue LC interrupted Made in Germany Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten! Attention Turn off the supply voltage ! Attention Couper l'alimentation ! 11 14 2 6 5 3 4 1 17 15 20 21 22 D 7 9 12 10 B C A Schaltgerät BWS Typ 4 Switching unit ESPE Type 4 Boîtier de commande ESPS Type 4 Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel. Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0 LSUWN1 Muting K No./year of construction response time t emp. enclosure rating supply voltage contact max No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi. Netz tension power LS Frei BS libre LC free output free sortie libre Ausgang frei interdiction de redémarrage restart interlock Wiederanlaufsperre LS unterbrochen BS interrompue LC interrupted Made in Germany ................................. 30 mS -10… + 55 °C IP 20 230 VAC -15% +10 %, 50Hz 2 A, 250 VAC LC muted BS desaktiveé LS gebrückt Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten Attention Turn off the supply voltage ! Attention Couper l'alimentation ! Operating instructions

Upload: tomy1969

Post on 01-Dec-2015

8 views

Category:

Documents


2 download

DESCRIPTION

EN-Fiessler-ULVT-short

TRANSCRIPT

Page 1: En Fiessler ULVT Short

BGzugelassen

ULR

LISTED

Telefon: 0711 / 91 96 97-0 Internet: http://www.fiessler.deTelefax: 0711 / 91 96 97-50 eMail: [email protected]

Infrared accident prevention safety curtains ESPE Type 4

ULVT / ULVTK / BLVT / BLVTK

INHALT:

Safety instructions

Application notes

Installation

Electric Connection

Commissioning

Specifications

Accessories

FIESSLER

E L E K T R O N I K

ULVT BLVT (with blanking features)

Muting, cycle operation .... with safety switching units as option

Fiessler Elektronik Kastellstr. 9D 73734 Esslingen

ULVTK / BLVTK (Cascading of Light Curtains)

A

A

AAAAAAAAA

AAAAAAAAA

AAAAAAAAA

AAAAAA

A

AA

FIESSLER

E L E K T R O N I K

Typ: ULSG 230V

TÜV Rheinland

AAAAAA

2 31 18 19 14 12 15 13 17 16 21 20

Schaltgerät BWS Typ 4Switching unit ESPE Type 4Boîtier de commande ESPS Type 4

Kastellstr.9 73734 EsslingenTel. 0711/ 91 96 970

Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten! Attention Turn off the supply voltage ! Attention Couper l'alimentation !

Nr./Baujahr No./year of construction No./année de fabrication .................................Ansprechzeit response time temps de réponse 20 mSTemp. temp. temp. -10… + 55 °CSchutzart enclosure rating degré de protection IP 20Versorgung supply voltage tension d'alimentation 230 VAC -15% +10 %, 50HzKontaktbel. contact max. charge contact maxi. 2 A, 250 VACMade in Germany

SK230V 115V 24V - +LS -LS A1 A2N

6A 1 2 3 74 5 8 109 17B C 12 13 14 15 16 18 19 20 21 22 D11

FIESSLER

E L E K T R O N I K

Schaltgerät BWS Typ 4Switching unit ESPE Type 4Boîtier de commande ESPS Type 4

Nr./BaujahrAnsprechzeitTemp.SchutzartVersorgungKontaktbel.

Kastellstr.9 73734 EsslingenTel. 0711/ 91 96 97-0

LSUW NSR 3-1 K

No./year of construction response time temp.enclosure rating supply voltage contact max

No./année de fabricationtemps de réponsetemp.degré de protectiontension d'alimentationcharge contact maxi.

.................................30 mS-10… + 55 °CIP 20230 VAC -15% +10 %, 50Hz2 A, 250 VAC

Netz tensionpower

LS Frei BS libreLC free

output interuptedsortie interrompueAusgang unterbrochenoutput freesortie libreAusgang frei

interdiction de redémarragerestart interlock Wiederanlaufsperre

LS unterbrochen BS interrompueLC interrupted

Made in Germany

TÜV Rheinland

AAAAAA

TÜV Rheinland

Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten! Attention Turn off the supply voltage ! Attention Couper l'alimentation !

11 142 653 41 1715 20 21 22 D7 9 1210 B CA

Schaltgerät BWS Typ 4Switching unit ESPE Type 4Boîtier de commande ESPS Type 4

Nr./Baujahr

AnsprechzeitTemp.

SchutzartVersorgung

Kontaktbel.

Kastellstr.9 73734 Esslingen

Tel. 0711/ 91 96 97-0

LSUW N1 Muting K

No./year of construction

response time temp.

enclosure rating supply voltage

contact max

No./année de fabrication

temps de réponsetemp.

degré de protectiontension d'alimentation

charge contact maxi.

Netz tensionpower

LS FreiBS libre

LC free

output freesortie libre

Ausgang freiinterdiction de redémarrage

restart interlock Wiederanlaufsperre

LS unterbrochen BS interrompue

LC interrupted

Made in Germany

TÜV Rheinland

.................................

30 mS-10… + 55 °C

IP 20230 VAC -15% +10 %, 50Hz

2 A, 250 VAC

LC mutedBS desaktiveéLS gebrückt

Achtung Vor Abziehen der Klemmleiste Netzspannung abschaltenAttention Turn off the supply voltage !

Attention Couper l'alimentation !

O p e r a t i n g i n s t r u c t i o n s

Page 2: En Fiessler ULVT Short

Sector Contents Page

1 Safety Instructions 51.1 Prerequisites for the utilisation of the safety light curtains 5

2 Terminology 6

3 System Description and Technical Data 83.1 Features 83.2 Application Areas 83.3 Structure and Function 93.4 Tables: Protective fields, constructional lengths, ranges, resolutions, beam spacing, number of beams 93.5 LED-displays (in general) 103.6 Operating modes selector (with/without restart interlock, with/without contactor check, equivalent/antivalent outputs) 103.7 Technical data 113.8 Dimensions drawing (Light curtain and standard fastening brackets) 12

4 Installation 134.1 Response times ULVT, BLVT, cascaded systems and optional safety switching units 134.2 Safety distance from the hazardous areas 144.2.1 - vertical protection for hazardous areas (≤ 40 mm resolution) 144.2.2 - horizontal protection for hazardous areas 15

4.2.3 - vertical protection for hazardous areas by light grids (> 40 mm resolutiion and single beams) 164.3 Construction requirements 174.3.1 - Installation without additional screening 174.3.2 - Protection against reaching over or under barriers 174.3.3 - Protection against avoiding barriers through cascading or additional screening 174.3.4 - Distance from reflective surfaces 184.3.5 - Arrangement of two safety light barriers 18

4.4 Mounting and Adjustment 194.4.1 Adjustment Instructions with standard fastening brackets 194.4.2 Option: angular brackets (dimension drawing included) 204.4.3 Option: rubber-metal connection (to avoid intense vibrations) 21

4.4.4 Option: multi-sided screening by using tilted mirrors (dimension drawing included) 21 4.4.5 Option: Assembly columns / Shock Protection (dimension drawing included) 23

5 Electric Connection ULVT / BLVT 255.1 Integrated connector plug 255.2 Electric connection ratings 255.3 Connectors 255.4 Connection examples - without optional safety switching units 265.4.1 ULVT 500/2R: connecting advice 265.4.2 Safety mode with restart interlock/ with valve or contactor check 26

5.4.3 Safety mode without restart interlock/ without valve or contactor check 26 5.4.4 SPS drive 26

6 Commissioning 276.1 Commissioning 276.2 Adjustment instructions / LED-displays 276.3 Trouble-shooting / LED-displays 28

12 Service 43

3

FIESSLERE L E K T R O N I K

Table of contents

BA - ULVT / BLVT

Page 3: En Fiessler ULVT Short

All safety instructions are marked with this symbol and must be observed under all circumstances!

1.1 Prerequisites for the utilisation of the safety light curtains:

On request by the customer, the Fiessler Elektronik company will carry out the initial approval and annual inspection. In addition, customer-training seminars concerning the implementation of the annual inspection are held at regular intervals.

5

FIESSLERE L E K T R O N I K

1 Safety advice Please observe!

BA - ULVT / BLVT

The unintentional repetition of a hazardous movementmust be prevented by the appropriate safety facilities.

- The safety category (Type 4) of the accident-preventionlight barrier should be at least the same as safety categoryof the machine.

Approval:Approval of the construction and the tests should becarried out by competent personnel who are in possessionof all information provided by the supplier of the machineand the BWS.

Annual inspection:The operator must ensure that a competent person isassigned with the task of inspecting the light barrier on ayearly basis. This person may, for example, comprise anemployee of the light barrier manufacturer or of theoperator.

The safety distance between the protective field and thehazardous area must be large enough to ensure that whenpenetrating the protective field, the hazardous areas cannotbe reached before the hazardous movement is interruptedor ended.

Access to the hazardous area must only be possiblethrough the protective field (reaching under, over or aroundthe field must not be possible).

Passing through the light barrier must only be possible ifthe restart interlock is activated subsequent to the lightbarrier being interrupted.A new command to activate the next hazardous movementmust only be implemented via a dead-man switch. It mustnot be possible for this start button to be actuated fromwithin the hazardous area: The switch must be located at apoint from which the accessible area can be viewed withoutobstruction.

The hazardous state of a machine must be interrupted bythe sensory function of the ESPE.

The safe operation of the entire system can only be ensured through adherence to these operatinginstructions and the corresponding accident prevention regulations. These operating instructions comprise part of the light barrier and must be retained at the installationsite.

All specifications of these operating instructions must be observed at all times. These operating instructions providethe user with important information concerning the proper use of the ULVT/BLVT safety light barriers. .

When using safety light barriers, the effective standards and guidelines must be observed! The local authorities ortrade associations will provide you with the relevant information. Currently effective conditions and the regulations of the tradeassociations must also be adhered to.

Qualified personnel. Installation, commissioning and maintenance must only be carried out by qualified personnel.

Danger sign When operating a machine with ULVT/BLVT ... safety light barriers, it must be ensured that nobody is locatedwithin a hazardous area. A danger sign to this effect must be attached to the machine.

Light barriers do not provide protection from flying objects resulting from the operation of the machine.

When using the ULVT/ BLVT with an external switching unit or similar succeeding controls, it must be ensured by ap-propriate, either contructional or organisatorial means, that at least once within 24 hours, a close-down of the light curtain byintentional interruption ot testing of the protective field takes place in order to prevent any unnoticed accumulation of mal-functions.

Caution, daily inspection (after 24 hours at the latest): Before the start of a shift, the light barrier must be checked asfollows: Using the test rod*, the light barrier is to be interrupted on the transmitting side from start to finish in such a way thatthe light field is only covered by this part. The green LED (or the yellow LED in the operating mode with restart interlock) mustnot light up from start to finish. * The diameter of the test rod must correspond to the obstacle size specified on the nameplate of the receiving side.Acht

When using the BLVT Blanking features, the additional safety advices and all other instructions in chapter 7 must beobserved!

When using the Cascading features, the additional safety advices and all other instructions in chapter 8 must beobserved!

Page 4: En Fiessler ULVT Short

FIESSLERE L E K T R O N I K

9

3.3 Structure and function

The ULVT/BLVT safety light barriers consist of twocomponents: The light transmitter and receiver. The distancebetween the two components and the installation height arecalculated from the width and height of the protective field (Fig.9/1).

Due to its modular structure, protective field heights between100 mm and 1900 mm can be attained (Table 8/1).

The transmitter and receiver are synchronous, i.e., at any onetime, only one light beam and one receiving element are active.Synchronization is implemented by the first light beam and thefirst receiving element. An electric connection between thetransmitter and receiver is therefore not required.

The transmitter generates infrared light beams which areswitched on an off in quick succession. The parallel light beamsat a distance of 7.5 mm are assessed by two single-chipmicrocontrollers. The beam distance produces a definition of 14mm. (see table 9/2).

If an object is located within the protective field, i.e., at least oneof the light beams is blacked out, the two outputs of the receiverwill stop the hazardous movement of the machine and/or prevent a start. In the operating mode with restart interlock, themachine can only be restarted by actuating the start button when the protective field is free again.

3.4 Protective field height, constructional length, ranges, resolutions, beam spacings and number of beams

3 System description: Structure and Function, tables

ø of test rod = obstacle size

protective field width

prot

. fie

ld h

eigh

t

Protective

Field height

(mm)

Constr

length

L (mm)

Beam spacing7,5 mm

No. of beams

Beam spacing14 mm

No. of beams

Beam spacing 100 mm

No. of beams

Beam spacing 200 mm

No. of beams

Beam spacing 300 mm

No. of beams

Beam spacing400 mm

No. of beams

Beam spacing500 mm

No. of beams

Beam spacing500 mm

No. of beams

100 196 13 7 - - - - -

200 296 26 14 3 2 - - -

300 396 39 21 4 - 2 - -

400 496 52 28 5 3 - 2 -

500 596 65 35 6 - - - 2

500 650 ULVT500/2R: beam diversion via mirror. Wiring required to only on one head. 2

600 696 78 42 7 4 3 - -

700 796 91 49 8 - - - -

800 896 104 56 9 5 - 3 -

900 996 117 63 10 - 4 - -

1000 1096 130 70 11 6 - - 3

1100 1196 143 77 12 - - - -

1200 1296 156 84 13 7 5 4 -

1300 1396 169 91 14 - - - -

1400 1496 182 98 15 8 - - -

1500 1596 195 105 16 - 6 - 4

1600 1696 208 112 17 9 - 5 -

1700 1796 221 119 18 - - - -

1800 1896 234 126 19 10 - - -

1900 1996 247 133 20 - - - -

Table 9/2 Available standard sizes

Finger protection

resolution 14 mm

Hand protection

resolution 30 mm

Pedestrian Ac-cess Protec-

tion

Pedestrian Ac-cess Protec-

tion

Pedestrian Ac-cess Protec-

tion

Pedestrian Ac-cess Protec-

tion

Pedestrian Ac-cess Protec-

tion

Pedestrian Ac-cess Protec-

tion

Range7 m

Range24 m

Range24 m

Range24 m / 60 m

Range24 m / 60 m

Range24 m / 60 m

Range24 m / 60 m

Range8 m

Table

Bau

län

ge

L

fig. 9/1 transmitter and receiver form the protecfive field

BA - ULVT / BLVT

Page 5: En Fiessler ULVT Short

FIESSLERE L E K T R O N I K

10

3.5 LED-displays (also refer to chap. 6.2 and 6.3 Commissioning and Trouble-Shooting)Several LEDs on the receiver indicate the current operating status (Fig. 10/1). If the system test detects an internal or externalfault, the machine will be switched off immediately and the LEDs on the receiver and/or transmitter (if the fault lies within thetransmittter) indicate the fault status to the user by quick flashing.When a fault is present, the flashing LEDs together with a fault code provide visual output of the detected fault and display in thediagnostics device.

3.6 Operating mode switchesThe DIP switches in the connector cover enable the following operating modes to beselected:- Safety mode with / without restart interlock- With / without contactor check- equivalent / antivalent outputs (Fig. 9/1)

In the condition when delivered, the preset operating mode comprises safety mode with:restart interlock, contactor check and equivalent outputs.

Caution!The operating mode may only be selected when no voltage is present. If the DIP switches are actuated duringoperation, the light barrier will switch off the outputs and go to locking status. This is indicated by flashing of theyellow and orange LEDs. Locking status will only be ended once the power supply has been switched off.

without contactor controlwith contactor control The operating mode with contactor control serves to monitor the

driven succeeding contactors.After each interruption of the light path and before each release ofthe switching outputs, it is checked whether the succeedingcontactors have fallen. Only then will a new release be possible. Ifthe contactors do not respond within 300 ms, the light barrierswitches off the outputs and goes into locking status.

without restart interlock with restart interlock With the operating mode with restart interlock selected, a buttonmust be connected to the start button input for a start release of theoperating movement.

When the protective field is free, the yellow LED lights up on thereceiver as a start prompt. Only once the start button has beenpressed will the outputs of the ULVT/BLVT be switched to active.

equivalent outputs antivalent outputsIn the equivalent outputs operating mode, both PNP outputs arefailsafe and monitored internally for short-circuits and cross-circuits.With a free light path, both outputs are high (+24 V). In the antiva-lent outputs operating mode, output 1 is high (+24 V) and output 2low (0 V) when the light path is free. Output 2 is not failsafe in thisoperating mode. This operating mode is only permissible inconjunction with the safety switchgears LSUW NSR 3-1K,LSUW N1-Muting K, or another safe sequential phase controldevice which monitors output 2!

3 System description: - LED-displays/operation modes

Bild 10/2 The operating modes can be setusing the DIP switches. Thecondition when delivered isshown here.

AAAAAAAAAAAAAAAA

AAAAAAAAAAAA1 2 3 4 5 6

offAAAAAAAAAAAA

AAAAAAAAAAAA

1 2 3 4 5 6

off

AAAAAAAAAAAA

AAAAAAAAAAAA1 2 3 4 5 6

off AAAAAAAAAAAA

AAAAAAAAAAAA

1 2 3 4 5 6

off

AAAAAAAA

AAAAAAAAAAAAAAAA

1 2 3 4 5 6

offAAAAAAAAAAAA

AAAAAAAAAAAA1 2 3 4 5 6

off

1 2 3 4 5 6

off

Table 10/3 programming of operation modes

Bild 10/1 LED indicate the operating and/or fault status

ReceiverGreen ON light barrier free

Red ON light barrier interrupted

Orange ONcontamination (no reserve)

Yellow ON Start promptfast orange flashingca. 4 x /s faultfast yellow flashingca. 4 x /s faultslow orange flashingca. 1 x /s BLVT only:: reduced resolslow yellow flashing ca. 1 x /s BLVT only:: reduced resol

ULVTE Empfänger

Made in Germany

D-73734 Esslingen, Kastellstr.90711/91 96 97 -0

1 2 3 4 5 6 7

3:OSSD2 6: 0V5: 2: EDM

7: 24VDC ±20%

4: OSSD11: Start

ULVT Receiver/Récepteur

interdiction de redémarrage

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompu

BWS Typ4, ESPE Type4 , ESPS Type4

Wiederanlauf

Justierhilfe

LS

LS frei

unterbrochen

sperre

outputs are fail safe output 2 = not fail-safe!

TransmitterYellow ON Transmitter active

Yellow OFF Transmitter off

Fast Yellow flas-hing ca. 4 x /s fault

Slow Yellow flas-hing ca. 1 x /s

cascading only:succeeding recei-ver: interrupted

Sender ein Transmitter on

1 2 3

ULVT Sender

TÜV Rheinland

AAAAAA

Made in Germany

D-73734 Esslingen, Kastellstr.90711/3 45 19 44

ULVT Transmitter/EmetteurBWS Typ4, ESPE Type4, ESPS Type4

Emetteur en marche

O

BA - ULVT / BLVT

Page 6: En Fiessler ULVT Short

FIESSLERE L E K T R O N I K

11

3 System description: -Technical data

ULVT/ BLVT Characteristics

Mechanical data

Operating data

Electric Data

Safety category 4 pursuant to EN 954-1 and IEC 61496 / EN 61496

Protective field heights 100 mm ... 3000 mm (depending on number of beams) refer to table in chapter 3.4 (optional until 3000 mm)

Protective field width

(Range)0,3… 7 m, 0,3...24 m / 60m (depending on design) refer to table in chapter 3.4 (ULVT500/2R:0,3...8m)

Construction lengths 196 mm … 1996 mm (depending on design) refer to table in chapter 3.4 (optional bis zu 3096 mm)

Strahlabstand 7,5 mm , 14 mm, 100 mm, 200 mm, 300 mm, 400 mm, 500 mm(depending on design) refer to table chapter 3.4

Resolution 14 mm , 30 mm (depending on design and beam spacing) refer to table in chapter 3.4, (higher beam spacing change resolution)

Number of beams 2… 247 beams (depending on number of beams) refer to table in chapter 3.4

Table 11/4

Table 11/1

Table 11/2

Table 11/3

3.7 Technical data

BA - ULVT / BLVT

Housing designAluminium profile, plastic-coated RAL 1020, yellow, end pieces made from non-corrosive, spherically reinforcedplastic (polyamide). Plexiglass light outlet and inlet, optional with solvent-resistant silicate glass.

Attachment Shifting fastening brackets on rear side of housing

WeightTransmitter: 0.45 kg to 4.5 kg depending on construction lengthReceiver: 0.5 kg to 5.0 kg depending on construction length

Protection category IP 65

Protection class III

Operating ambient temperature -10 bis 55 °C

Storage temperature -25 bis 70 °C

ULVTS Transmitter ULVTE Receiver

Power supply 24 V DC, + 20 % - 10 %, SELV 24 V DC, ±20%, SELV

Current draw max. 250 mA max. 250 mA (no load)

Outputs -

OSSD 1 and 2:Failsafe PNP outputs, max. 0.5 A,short-circuit and cross-circuit monitoring(in operating mode with antivalent outputs, output 2 isnot failsafe, max. 20 mA)

Inputs -Contactor check and start button inputs:

0 V to 24 VDC _+ 20% / 10 mA

Electric connectionIntegrated connector plug with PG9 as strain relief,alternatively conventional connector plug

Integrated connector plug with PG9 as strain relief,alternatively conventional connector plug

Connecting cable 3-pol. max. 1,5 mm2 5 to 7-pin (depending on operating mode), max. 1.5 mm2

Page 7: En Fiessler ULVT Short

5.1 Integrated connector plugThe ULVT/BLVT construction series is supplied with PGthreaded joints as standard. Various conventionalconnector plugs can also be obtained as optionalaccessories.

The electric connection is implemented via terminalscrews in the connector cover (Fig. 25/1). The cover canbe removed once the 4 screws have been loosened.

The transmitter and receiver require a power supply of 24V DC. The ULSG switchgear performs the power failure bridging of 20 ms pursuant to EN 60204 and is thus suitable as thepower supply for ULVT/BLVT light barriers. The receiver is equipped with 2 inputs and 2 outputs. The transmitter is connectedvia one 3-pin cable and the receiver via one 5 to 7-pin cable (depending on operating mode). The permissible cable cross-section is max. 1.5 mm2. The cables must be routed separately from power lines.

5.2 Electric connection ratings

5.3 Connectors

- Outputs 1 and 2 (OSSD 1 and OSSD 2)The outputs are not potential-free and must not be switched in seriesor parallel, but must be connected and processed separately!In the operating mode with equivalent outputs, both PNP outputs arefailsafe and feature internal short-circuit and cross-circuit monitoring. Bothoutputs are high (+24 V) when the light path is free.

In the operating mode with antivalent outputs, output 1 is high (+24 V)and output 2 low (0 V) when the light path is free. Output 2 is not failsafein this operating mode. This operating mode is only permissible inconjunction with the safety switchgears LSUW NSR 3-1K, LSUW N1-Muting K, or another safe sequential phase control device whichmonitors output 2!

- Input contactor check (EDM)If the operating mode with contactor check is set, the auxiliary contactsk1 and k2 of the driven contactors k1 and k2 must be connected to thecontactor check input in series and with +24 V as shown in Fig. 25/4. The OSSD1 and OSSD 2 of the ULVT will only switch on the twocontactors when contactor check input has detected the idle status of thecontactors (+24 V at contactor check input).Once the contactors have been driven, both of them must respond within300 ms. The two auxiliary contacts must then be open (0 V at contactorcheck input).If the operating mode without contactor check is set, the inputcontactor check must be unoccupied.

FIESSLERE L E K T R O N I K

25

5 Electric connection - Connection of receiver and transmitter

The electric connection must only be carriedout when no voltage is present.

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

OSSD 2

OSSD 1

3

4

7+24V DC±20%

0V6

K 1 K 2

fig 25/3 outputs 1 and 2

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

0V

7

2

+24V DC±20%

Eingang Schützkontrolle

6

Hilfsöffner k1

Hilfsöffner k2

fig 25/4 input contactor control

1 2 3 4 5 6 7

3: OSSD15: 2: EDM

7: 24VDC ±20%

4: OSSD21: Start

1 2 3 4 5 6

off

1 2 3 4 5 6 7 1 2 36: 0V

fig. 25/1 Integrated connector plug with terminal screws in connectorcover Receiver 7-pin, transmitter 3-pin.

BA - ULVT / BLVT

+24V DC± 20%

auxiliary contact k1

auxiliary contact k 2

input contactor control

Table 25/2 electri connection ratings

ULVTS/BLVTS transmitter ULVTE/BLVTE receiver

Power supply 24 V DC, + 20% - 10%, SELV 24 V DC, ±20%, SELV

Current draw max. 250 mA max. 250 mA (without load)

Outputs -

OSSD 1 and 2: Failsafe PNP outputs,max. 0.5 A, short-circuit and cross-circuit monitoring (in

operating mode with antivalent outputs, output 2 is a non-failsafe PNP output, max 20 mA)

Inputs -Inputs contactor check and start button:

0 V to 24 V DC _+ 20%, 10 mA

Electric connectionIntegrated connector plug with PG9 as strain relief,

alternatively conventional connector plug.Integrated connector plug with PG9 as strain relief,

alternatively conventional connector plug.

Connecting cable 3-pin max. 1.5 mm2 5 to 7-pin (depending on operating mode) max. 1.5 mm2

Page 8: En Fiessler ULVT Short

- Input start buttonIf the operating mode with restart interlock is set, a button must be connected onthe start button input for the start release of the operating movement (Fig. 26/1).

With a free protective field, the yellow LED on the receiver lights up as a startprompt. Only once the start button has been pressed will the two outputs OSSD1and 2 of the ULVTE receiver be switched to active.

If the operating mode without restart interlock is set, the start button input (start)must be unoccupied).

5.4 Connection examples (without the additional function such as Muting or cycle mode, please refer to the operation manual of the respective switching unit)

5.4.2 Operating mode with restart interlock / contactor control

5.4.3 Operating mode without restart interlock / contactor control

5.4.4 PLC driveWhen connecting to a safe stored program control (PLC) the outputs of the ULVT/BLVT must be connec-ted to separate inputs of the PLC

FIESSLERE L E K T R O N I K

26

5 Electric connection - Connection of receiver and transmitter

Caution! Error-free operation can only be ensured when the safety light barrier is connected according to one of thefollowing connection diagrams and also complies with effective national and international accident prevention regu-lations!Any deviation from these connection specifications can lead to hazardous conditions and is therefore not permitted.

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

0V

7

1

+24V DC±20

Start-Taster

6

Eingang Start-Taster

fig. 26/1 input start button

BA - ULVT

+24V DC± 20%

Start- Taster

Eingang Start- Taster

rece

iver

tran

smitt

er

rece

iver

r

tran

smitt

er

rece

iver

K2

K1

k1 k2

13

45

67

13

45

67

2

K2

K1

13

45

67

13

45

67

21

34

56

71

34

56

72

tran

smitt

er

31

23

12

31

2

+24V DC ± 20%

0V

functional ground

OSSD2

OSSD1

contactor control

start button

+24V DC ± 20%

0V

functional ground

OSSD2

OSSD1

unoccupied

unoccupied

+24V DC ± 20%

0V

functional ground

OSSD2

OSSD1

unoccupied, if contactor control is done by the safety PLC

unoccupied, if contactor control is done by the safety PLC

Safety PLC

+24V DC ± 20%

functional ground

0V

+24V DC ± 20%

functional ground

0V

+24V DC ± 20%

functional ground

0V

fig 26/2

fig 26/3

5.4.1 There is no need of a connection of the light transmitter at the light grid ULVT 500/2R, because the transmitter is in-tegrated in the receiver unit.

BA - ULVT / BLVT

E2

E1

fig 26/4

Page 9: En Fiessler ULVT Short

6.1 CommissioningPrior to commissioning, the appropriate operating mode for the respective application case must be set via the DIP switches inthe terminal strip compartment (refer to Section 3.6). When delivered, the operating mode with restart interlock, contactorcheck and equivalent outputs is pre-set . The electrical connection must be made according to the selected operating mode.(refer to chapter 5).

6.1 Adjustment informationThe visual alignment is advantageously carried out with intensely dimmed ambient lighting in order to be able to better detectthe LED indications of the receiver even from a long range.When aligning, it must be ensured that the housings do not become distorted.

An adjustment laser can be obtained for the precise alignment of the ULVT/BLVT lightbarriers, particularly where large distances are involved. The device is attached to the frontpanel of the transmitter and receiver. When the button is pressed, the laser produces a redlight spot which can also be seen from long distances. The light spot must hit the centre ofthe opposite device. This test should be performed at both ends of the transmitter andreceiver. The arrangement must be adjusted if necessary.

Adjustment with operation via tilted mirrors: Place the adjustment laser onto the frontpanel of the transmitter, switch it on and swivel the transmitter until the light spot hits thecentre of the mirror. Then adjust the mirror so that the light spot also hits the centre of thesecond mirror / receiver.

Adjustment LED: The orange LED extinguishes when sufficient light reserve is present.

Fine tuningSubsequent to the face-parallel installation and/orto the alignment using the adjustmentlaser, fine tuning is carried out by means of the adjusting screws on the supplied fasteningbrackets, provided that the orange LED is lit. To swivel along the longitudinal axis, the respective adjusting screw on one of the fasteningbrackets is turned whilst both screws on the other fastening bracket are loose. To swivel thelateral axis, both screws of one fastening bracket are turned at the same time whilst bothscrews on the other fastening bracket are loose.

Subsequently, the green or yellow LED on the receiver should light up, and the orangeLED must have extinguished.

FIESSLERE L E K T R O N I K

27

6 Commissioning

longitudinal axis

lateral axis

LED without restart interlock LED with restart interlock

BA - ULVT / BLVT

Enlarged LED --> Lights up --> ONsmall LED --> Does not light up --> OFF

fig. 27/2 lateral and longitudinal axis

fig 27/1 adjustemnt laser

Table 27/3 Operating modes

Test rod: Using the test rod, the light barrier is to be interrupted on the transmitting side from start to finish in sucha way that the light field is only covered by this part. The green LED must not light up from start to finish. Thediameter of the test rod must correspond to the obstacle size specified on the nameplate of the receiving side.

green LED ON Outputs active, light barrierfree and correctly adjusted

Outputs not active,

(Prompt for start release with start button)

light barrier free and correctly adjusted

green LED ON

orange LED ON

Outputs active, light barrierfree, but insufficient reserve

To swivel along longitudinal orlateral axis until orange LED

extinguishes

Outp

Outputs not active, (Prompt for start release with start

button)light barrier free, but insufficientreserve

To swivel along longitudinal or lateral axisuntil orange LED extinguishes

interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompuunterbrochen

sperre interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompuunterbrochen

sperre

interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompuunterbrochen

sperre interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´ajustement

libre

interrompuunterbrochen

sperre

Page 10: En Fiessler ULVT Short

6.3 trouble shooting The prerequisite for the troubleshooting

process is a correctly adjusted light barrier. (see chapter 6.2)

FIESSLERE L E K T R O N I K

28

LED-display possible causes remedy

Yellow LED OFF no power supply check power supply

Yellow LED flashingquickly (ca 4 x /s)

Fehlerzustand!

a) internal fault. Transmitter inactive

b) voltage surge at the transmitter

switch off power supply and then switch onagain. If yellow LED still flashes: Transmitter isdefective and must be replaced.

reduce voltageYellow LED flashing slowly (ca 1 x /s)

only with cascadable transmitter

no fault!

following light curtain is interrupted. please refer to chapter 8.10 on page 39

6 Commissioning - Trouble shooting

Transmitter

LED-display possible causes remedy

no LED illuminated no power supply check power supply

red LED on

Orange LED on

a) Transmitter inactive

b) Light path interrupted

c) Light barrier maladjusted or very dirt

d) Max. range exceeded

a) Check transmitter

b) Remove obstacle from light path

c) Readjust and/or clean system

d) Check range

Green LED ont

Orange LED on

a) Insufficient reserve, light barriermaladjusted or slightly dirty

b) Max. range exceeded

a) Readjust and/or clean system

b) Check range

yellow and / or

Orange flashing

quickly (ca 4 x /s)

Fault!

a) In operating mode with contactorcheck: Contactors not responding ornot fallen

b) short-circuit, overcharge or side-cir-cuit of the outputs OSSD1/OSSD2

c) Operating mode setting does notmatch the electric wiring and/or DIPswitches are not set as specified inchapter. 3.6.

d) External or Internal error

e) Electromagnetic interferences

a) Check auxiliary contact k1 and k2 and/or wiring

b) check connection, wiring and output charge(max. 0,5A!)

c) Check operating mode setting

d) Switch off power supply and then switch onagain. If LED still flashes: Disconnect all connec-tions after having turned of the light curtain ex-cept for the power supply, and set the DIP-swit-ches onto the operating mode: no restart inter-lock, no contactor control and equivalent out-puts. If the LED continue flashing, replace thereceiver.

e) use insulated brackets.

yellow and / or

Orange flashing

slowly (ca 1 x /s)

reduced resolution (BLVT only)

no fault! only display if:

a) operating mode: floating blanking

b) operating mode: 1-beam or 2-beamsreduces resolutionc) combination of both operating modesd) skip 1 or 2 beams only once

-

check contactor connections and contactor con-trol wiring and connection (EDM)

receiver

interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompuunterbrochen

sperre

Sender ein Transmitter onEmetteur en marche

interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompuunterbrochen

sperre

interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompuunterbrochen

sperre

Sender ein Transmitter onEmetteur en marche

BA - ULVT / BLVT

Tabelle 28/1 Fehlersuche Sender

Table 28/2 troubleshooting receiver

Enlarged LED --> LED lights up Small LED --> LED does not light up Flashing LED

interdiction de redémarrage

Wiederanlauf

Justierhilfe

LS

LS frei

restart interlock

adjustment

LC interrupt

LC free

Aide d´àjustement

libre

interrompuunterbrochen

sperre

Sender ein Transmitter onEmetteur en marche

during operating mode with contactor control: OSSDs connect, contactors do not attract, OSSDs disconnect again and, when inoperating mode without restart interlock, connect again shortly after that.

Maintenance information: The ULVT/BLVT... system is maintenance-free depending on the construction. (This does not,however, release the obligation to carry out the prescribed annual inspection pursuant to EN 61496, ZH 1/281 and/or ZH1/597.) The protective panels in front of the transmitter and receiver should simply be cleaned at regular intervals with asolvent-free detergent. Solvents can damage the plexiglass panels of the transmitter and receiver. As an alternative, lightbarriers with silicate glass are available.

Page 11: En Fiessler ULVT Short

FIESSLERE L E K T R O N I K

12 Service

43

Service

If you have questions that cannot be answered by reading this operation instruction manual, please contact us directly.

When calling, please have the following dara ready:

-Exact unit type and model-Serial number(s)-Symptom of the malfunction and/or fault description

Fiessler Elektronik OHGKastellstrasse 9D-73734 Esslingen

phone ++49-711 / 91 96 97 - 0Fax ++49-711 / 91 96 97 - 50eMail [email protected]

Returning of a unit

If, in the case of default, the necessity of returning the unit to Fiessler Elektronik arises, it will be very advantageous for a fastdefault diagnosis if the following topics are observed and observed:

-exact description of malfunction:-did you frequently notice malfunctions at the machine where the light curtains are installed?-any defaults or malfunctions in the past?-etc..

-which operating mode has been used with this unit?

The more exactly the malfunction is described, the more accurate and faster we can determine it and repair it.

Download site

Please visit our homepage. Here you will find the most recent operating instructions, appliance descriptions, data sheets etc. re-ady for download at no charge.

http://www.fiessler.de

BA - ULVT / BLVT