en-tv32gl.pdf
TRANSCRIPT
Isolation Amplifier
Isolation Amplifier With Nominal Value Selector AD-TV 32 GL
DescriptionThe VARIO-isolation amplifier AD-TV 32 GL serves the galvanicseparation, conversion and amplification of DC current and voltagesignals (0/4-20 mA and 0/2-10 V DC). The signal dimensions areadjustable at the front. The starting and end values can here be adjustedindependent of each other. Input, output and the supply voltage areseparate from each other with high insulation. An integral electronic widerange power pack with a high degree of effectiveness allows operation ina supply range of 20...253 V DC or 50...253 V AC. Additionally, anominal value can be specified via switch at the front at the output. Theinput measuring signal is decoupled and without influence during this.The nominal value at the output, which can be activated and adjusted viaa potentiometer at the front.
ApplicationConversion, burden amplification and galvanic decoupling of active DC-current and voltage signals with additional manual / automatic operationvia a nominal value specification, which can be activated.
Specific characteristics• Front panel switch for switching between manual and automatic
operation• Value setting for manual operation by front-face potentiometer
Business dataCatalog number AD-TV 32 GL
Technical specifications
Input currentMeasuring range 0/4 ... 20 mAInput resistance 85 Ohm
Input voltageMeasuring range 0/2 ... 10 VInput resistance > 100 kOhm
Output currentOutput range 0/4 ... 20 mAMax. burden 500 OhmResidual ripple 50 µAss
Output voltageOutput range 0/2 ... 10 VMin. burden > 10 kOhmResidual ripple 50 mVss
Setpoint settingFront mounted potentiometer 0 ... 100 %
SupplyVoltage range AC 50 ... 253 V AC, 50/60 HzNominal voltage AC 230 V ACVoltage range DC 20 ... 253 V DCNominal voltage DC 24 V DCPower consumption AC / DC 2,3 VA / 1W
Transmission behaviourBasic accuracy < 0,2 %Temperature influence 100 ppm/KResponse time ~ 20 ms
HousingDimensions (WxHxD) 18x78x103 mmType of protection IP 20Connection method screw clampTerminals, wire cross section 2,5 mm² flex wire / 4 mm² one wireBolting torque terminals 0,5 NmWeight ~ 100 gManner of fastening 35 mm DIN rail 35mm
Environmental conditionsAmbient temperature 0 ... 50 °CStorage and transport -10 ... 70 °C (no thawing)
EMCProduct family standard EN 61326 1)
Emitted interference EN 55011, CISPR11 Cl. B
Electrical safety requirementsProduct family standard EN 61010-1Overvoltage category IIPollution degree 2
Galvanic isolation, test voltagesInput / output 3,75 kV, 50 Hz (1 min.)Signal / supply unit 4 kV, 50 Hz (1 min.)
Protection circuitsInput electrical surge protectionOutput electrical surge protectionPower supply electrical surge and reverse current
protection
Page 1/2 Printed 25.03.2014 We reserve the right for technical changes.
Isolation Amplifier
Isolation Amplifier With Nominal Value Selector AD-TV 32 GL
1) During checking, slight signal deviations are possible.
Block and wiring diagram
12
87
5 +6
+
Input
Power Supply
Outp.
+
Voltage Current
34
Jumper for voltageoutput
I / U
Dimensions
Powered by TCPDF (www.tcpdf.org)