enerboss 400c series 2-pipe vertical fan coil specifications, installation operation...
TRANSCRIPT
Enerboss 400C Series 2-Pipe Vertical Fan Coil
Specifications, Installation Operation and
Maintenance Manual
Coil Data
C SERIES HEATING AND COOLING COIL DATA
Coil Construction
Type
Fin Height x Finned Length (in)
Face Area (sq ft)
Fins per inch
Nominal Ton
Tube OD
Rows Deep
Air Side Performance
Flow cfm 450 450 450 600 600 600 650 650 650
Continuous low speed 284 284 284 264 264 264 247 247 247
Entering Air Dry Bulb F 70 70 70 70 70 70 70 70 70
Entering Air Wet Bulb F
Leaving Air Dry Bulb F 111 104 88 126 114 97 138 128 110
Leaving Air Wet Bulb F
Face Velocity FPM 281 281 281 389 389 389 425 425 425
Liquid Side Performance
Entering Water Temperature F 180.0 160.0 140.0 180.0 160.0 140.0 180.0 160.0 140.0
Leaving Water Temperature F 160.6 140.2 128.39 160.3 140.4 120.86 159.7 140.4 120.5
Number of Circuits ea 5 5 5 4 4 4 4 4 4
Fluid Flow gpm 2.1 1.7 1.5 2.8 2.2 1.4 3.3 2.9 2
Water Pres. Drop ft 6.6 5.3 4.6 7.5 5.6 3.2 7.7 6.3 3.7
Total Capacity Btu/hr
Sensible Capacity Btu/hr 20,323 16,845 8,705 27,562 21,522 13,395 33,492 28,383 19,501
HEATING HEATING HEATING
3/8 1/2 1/2
2 2 3
12.00 12.00 12.00
0.75 1.00 1.50
20 X10 20 x 10 20 x 10
1.39 1.39 1.39
MODEL 409 MODEL 412 MODEL 418
WATER WATER WATER
16,970
13,030
Cooling
51.9
4
4.8
13.8
45.0
67.0
59.8
58.0
432
650
247
80.0
15.6
12,452
9,846
45.0
50.1
4
4.8
396
80.0
67.0
63.3
59.8
Cooling
600
264
10.7
8,434
6,238
45.0
50.0
5
3.3
281
80.0
67.0
65.1
60.2
Cooling
450
284
WATER WATER
MODEL 409 MODEL 412 MODEL 418
WATER
20 x 10
1.39
12.00
20 x 10
1.39
12.00
20 X10
1.39
12.00
0.75 1.00 1.50
1/2
3
3/8
2
1/2
2
Additional operating points can be determined from the following output curves.
Return air filter: 10 x 20 x 1
Output
To calculate Leaving Water Temperature: EWT (F) – {(Btu/hr)/500/(gpm)}
To calculate Leaving Air Temperature: 70 + {(Btu/hr)/1.09/(CFM)}
C409 Heating Output
-
5,000
10,000
15,000
20,000
25,000
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
gpm
Btu
/hr
EWT 100
EWT 180
EWT 160
EWT 140
EWT 120
C412 Output
-
5,000
10,000
15,000
20,000
25,000
30,000
35,000
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Flow (gpm)
Ou
tpu
t (B
tu/h
r)
EWT 100
EWT 180
EWT 160
EWT 150
EWT 140
EWT 120
Water side Pressure Drop The chart below shows the waterside pressure drop for the entire fan coil. This includes coil, valves,
fittings and flex connectors. Pressure drop in the risers is not included.
Water Side Pressure Drop
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0
gpm
ft H
2O
C412
C409
C418
C418 Heating Output
-
5,000
10,000
15,000
20,000
25,000
30,000
35,000
40,000
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
gpm
Btu
/hr
EWT 100 F
EWT 180 F
EWT 160 F
EWT 140 F
EWT 120 F
Fan Curves The supply fan is powered by an ECM operating in constant CFM mode. The delivered airflow remains
relatively constant over varying external static pressures
Supply Fan Performance
0
100
200
300
400
500
600
700
800
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
ESP (inwc)
cfm
0
100
200
300
400
500
600
700
800
Fan
Mo
tor
Po
wer
(W)
C409 CFM
C412 CFM
C418 CFm
C409 Watts
C412 Watts
C418 WattsNote:
Power for Supply fan
and controls. No
HRV Fan
The supply fan also draws outside air through the HRV. The ratio or outside air and return air is governed
by the relative amounts of static pressure in the return air stream and outside air stream. A dampered return
air grille is supplied with each unit. Closing this damper will create more return air static and result in
more outside air. The curves below show outside air flow versus outside air duct static at various damper
positions. The amount of outside air available is anywhere on the chart that falls between the fully open
damper and minimally open damper positions.
C409 HRV OA Fan Curve
0
10
20
30
40
50
60
70
80
90
100
0 0.05 0.1 0.15 0.2 0.25 0.3
ESP(inwc)
CF
M
RA Open % 100
RA Open % 50
RA Open % min
C412 HRV OA Fan Curve
0
20
40
60
80
100
120
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
ESP(inwc)
CF
M
RA Open % 100
RA Open % 50
RA Open % min
C418 HRV OA Fan Curve
0
20
40
60
80
100
120
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
ESP (inwc)
CF
M
RA Open % 100
RA Open % 50
RA Open % min
Power and Static vs OA
0
50
100
150
200
250
300
350
400
450
50 55 60 65 70 75 80 85 90 95 100 105 110
OA Flow(cfm)
Watt
s
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
409 Watts
412 Watts
418 Watts
409 RA Static
412 RA Static
418 RA Static
Example:
to increase OA on unit C409
increase RA static from 0.22 to
0.38.
The resulting power increase
is from 220 W to 235 W
Power & Return Air Static vs OA
Outside Air at Low Speed
The flow rate of outside air is a function of the main blower speed reduction from high
speed to circulation speed and to a lesser extent the duct system. The low speed outside
air flow cannot be adjusted without affecting the high speed flow rate. In most
applications the high speed ventilation rate is set during commissioning and the low
speed flow is left to float. You should expect low speed flow reductions of;
50% with the C409,
40% with the C412 and
33% with the C418.
Low speed range 40%-100% of high
HRV Efficiency
Exhaust Fan 7 Exhaust Fan 9
Power Power
Supply Temperature Net Airflow attributed to HRV SHRE ASE attributed to HRV SHRE ASE
C F l/s CFM W % % W % %
Aluminum Core 0 32 19 41 38 60 74 53 58 74
0 32 22 46 38 62 71 53 60 71
0 32 35 74 58 56 63 73 55 63
Poly Core 0 32 14 30 38 65 90 60 64 90
0 32 24 51 45 66 74 60 65 74
0 32 30 64 58 57 64 73 56 64
Enthalpy Core 0 32 18 39 38 63 73 53 61 73
0 32 24 51 45 57 65 60 56 65
0 32 33 69 59 51 58 74 50 58
HRV Exhaust Air
0
20
40
60
80
100
120
140
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
ESP (inwc)
CF
M
Exhaust Fan 8
Exhaust Fan 9
Exhaust Fan 8
Noise Levels
Operating Mode
Fancoil Type Background Noise Circulation Heating/Cooling High Ventilation
(low ventilation)
(db) (db) (db) (db)
C409 50 54 55 60
C412 50 54 60 62
C418 50 54 62 64
Levels measured 6' in front of fan coil, 40" above floor
HRV ducted, supply air unducted
Fan coil not enclosed in wall at time of measurement
Decibel weighting "C"
Electrical
.
ELECTRICAL SPECIFICATIONS
No Electric Back up 120/1 400 15
1 kW back up 120/1 1400 15
1.5 kW Back up 120/1 1900 20
CONTROLS
POWER CONDUCTOR WIRES
THERMOSTAT 24 VAC 4 18 GA
DEHUMIDISTAT 24 VAC 2 18 GA
Electrical Volts WattsBreaker
MCA
20-80% MAKE ON RISE
DESCRIPTION
HEAT COOL WITH FAN SWITCH
Operational States
The table below defines the operating state of each device (motor, valve, etc) in the unit
for all available inputs. Priority increases from left to right in the tables.
Priority to high speed calls
Defrost Damper
Off ON
D 4 min ON/36 min OFF scan at min 39 and repeat if D ON
no calls
Throttling Damper
ON Off
W+Th>100+!H+!T H
Y+Th<70+!H+!T T Input Definition
G Fan
Y Cool
Water Control Valve W Heat
Off ON Ds Dryer Interlock Switch
Y+Th<70 Th Thermister (Degrees F)
W+Th>100 D Defrost Switch
H Dehumidistat
T Timer
SAMPLE SPECIFICATION – 400C
GENERAL
System Description
Vertical 2-pipe/4-pipe fan coil with ECM motor programmed for constant CFM in heating, cooling and
circulation modes. Back-up electric heat 1kw/1.5kw (optional). Integral heat/energy recovery
ventilator with dedicated wet room exhaust and non-recirculating proportional defrost.
Quality Assurance
Each unit shall be CSA approved or equivalent.
CABINET
Description
Concealed cabinet with drywall return. Pre-finished front service panel with integral return air grill for
a non-ducted return.
Location
Interior or exterior wall within 60’ (equivalent length) of ventilation exterior wall caps.
Casing
The fan coil shall be constructed of 22 ga galvanized steel with insulation where appropriate for
thermal performance and noise reduction. Exterior surfaces shall be finished.
HYDRONIC COMPONENTS
Coils
The coil(s) shall be constructed of 3/8 x 0.014 (1/2 x 0.016) copper tube and return bend connectors.
The tubing shall be mechanically joined to corrugated aluminum fins 0.006” thick with 12 fins per
inch. Coils shall come complete with drain and vent plugs in the supply/return headers.
Coil branches and headers
The coils shall be joined to the riser stub using ⅝” type L copper tube and braided flex connectors.
Risers
The risers shall be supplied integral to the fan coil unit (optional). Risers shall be __ inches long and
flared at the top to accept the riser directly below. Riser pipe shall be insulated with 1” polyethylene
pipe wrap within the height of the fan coil. The riser diameters shall be specified in the equipment
schedule. Flexible braided connectors shall be used for thermal expansion compensation between the
riser and fan coil.
Thermistor
A thermistor attached to the coil supply pipe prevents activation of the cooling cycle when water
temperature is > 70° F and conversely prevents activation of the heating cycle below 100° F.
Control Valve
The fan coil shall come complete with a 2-way (3-way) motorized control valve normally closed to the
coil.
Isolating valves
The fan coil shall come complete with two ball valves.
AIR MOVEMENT COMPONENTS
Blower motor:
The blower motor shall be direct drive electronically commutating (ECM) and operate in constant
CFM mode. The motor shall be capable of delivering constant airflow in fan only, heating, cooling,
and high ventilation speeds.
Main Blower
The main blower shall be a DWDI forward curve GT9-DD with galvanized wheel and housing.
INTEGRAL HRV/ERV
HRV fan
Supply air shall be via the main fan. The unit shall be capable of exhausting stale air from sources of
contamination by way of a duct system and independent exhaust fan. The exhaust fan shall be
backward curved motorized impeller. High and low speed shall be adjustable by way of the fan coil
control for in-suite air balancing.
Core media
The HRV core shall be aluminum/polypropylene/enthalpy fixed plate with a Sensible Heat Recovery
Efficiency of ___% at 0 C.
Sensible heat recovery efficiency SHRE:
Aluminum core: 62% at 22 l/s
Polypropylene core: 66% at 24l/s
Enthalpy core: 57% at 24 l/s
Defrost
Unit shall have continuous non-recirculating air exchange during defrost. Fan shut down and
recirculating defrost are unacceptable.
Interlock
HRV shall be interlocked with in-suite dryer to provide make-up air during dryer operation.
ELECTRICAL
Electrical Disconnect
A 15 amp (20 amp for units with 1500 W electrical elements) dedicated circuit with overload protection is
required. Units with electric elements shall be provided with an overload fuse for the electric heater.
FILTERS
The unit shall be provided with return air, outside air and exhaust air filters.