Page 1: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

w w w. n e x a n s . u s

LEAD FREERoHS

ENERGEX Armored CablesType MC and AC

®

Page 2: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92671

Type MC and Type AC

ENERGEX® Armored Cables

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Applications Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

ENERGEX® MC 120 Aluminum Armored Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

ENERGEX® MC 120 Steel Armored Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

ENERGEX® MC 277 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

ENERGEX® MC 120 Aluminum Armored with PVC Jacket Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

ENERGEX® MC Mega Neutral Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

ENERGEX® MC Ground Plus Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

ENERGEX® MC Multi Conductor Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

ENERGEX® AC Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

ENERGEX® AC Health Care Facilities Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

Metric Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Page 3: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92672

Nexans is one of the largest wire and cable manufacturers in the world, and in North America . In North America we manufacture in locations across the United States and Canada . We design and produce a wide range of cables used in power, industrial, construction and communication applications .

With more than a century of experience as a leader in the industrial and power cable markets, Nexans is contracted by heavy industry and utilities world wide to provide turnkey solutions for the bulk transmission of power – from generating station through the transmission and distribution systems to commercial, residential and industrial areas .

This catalogue has been prepared for the convenience of those using electrical conductors in industrial, commercial and residential applications . The information included in the many tabulations will be of particular value to the architect, engineer, electrician, and layperson alike . For your convenience, we have referenced applicable Articles and Tables from both the 2008 NEC and the 2011 NEC .

Introduction

Although we have listed the types of wires and cables suitable for most conditions, we are equipped to manufacture other types to suit special needs . We would be pleased to recommend the most suitable construction for any special condition that you may encounter .

The determination of the correct cable size and type, and the selection of methods of installation suitable for the type and location of particular circuits, should be made in accordance with local regulations . Any questions in this respect should be directed primarily to the local Electrical Inspection Authority .

We are pleased to note that all the cables in this catalog are LEAD FREE and RoHS compliant .

“Lead Free” indicates that the Nexans cable components have less than 300 ppm of lead, which is well below the 1000 ppm level indicated in RoHS (restriction of hazardous substances) regulations and below the level requiring labeling by California Proposition #65 .

Page 4: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92673

Applications Guide

Nexans ENERGEX® MC and ENERGEX® AC series of armored cables are used in a wide variety of applications in accordance with various sections of the National Electric Code (NEC) 2008 or 2011 . For ease of use, the following table summarizes typical application environments .

NEC 2008 and NEC 2011 Article 330 and 518

517

330

330 and 645

250.118(10), 517 and 645

300.22(C)

320 and 330

330

230.43, 330.10, 511.7(A)(1), 513.7(A), 514.7, 515.7(A), and 516.7(A)

Typical Application

Typical places of assembly for 100 or more peopleCommercial and Industrial

Health care facilities, such as hospitals, medical offices and nursing homes

Installations where multi-conductor runs are called for

Applications where computer and other business equipment, as well as electronic discharge lighting, are present

Applications where a redundant ground is required

Applications where environmental air handling spaces are present

Applications in hotels and multi-family dwellings where branch circuits are present

Factory installations, air conditioners, with wet and oily conditions

Direct buried applications and in hazardous locations up to Class I, Div. 2

ENERGEX® Type MC

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC 120 and 277, Aluminum Armored• ENERGEX®MCMegaNeutral• ENERGEX® MC Multi-Conductor• ENERGEX®MCGroundPlus

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC120 and 277, Aluminum Armored• ENERGEX®MCMegaNeutral• ENERGEX®MC120,Aluminum,PVCJacket• ENERGEX® MC Multi-Conductor• ENERGEX®MCGroundPlus

• ENERGEX®MCMegaNeutral

• ENERGEX® MCGroundPlus

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC 120 and 277, Aluminum Armored• ENERGEX®MCMegaNeutral• ENERGEX® MC Multi-Conductor• ENERGEX®MCGroundPlus

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC 120 and 277, Aluminum Armored

• ENERGEX® MC 120 Aluminum Armored with PVCJacket

• ENERGEX® MC 120 Aluminum Armored with PVCJacket

ENERGEX® Type AC

• ENERGEX® HCF

• ENERGEX® HCF

• ENERGEX® AC• ENERGEX® HCF

• ENERGEX® AC

Page 5: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92674

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

ENERGEX® MC 120

Applications

ENERGEX® MC 120 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC 2008 and NEC 2011 Article 330 . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY . Nexans MC 120 cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid bare annealed copper conforming to ASTM B3 .Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test for sizes 14 to 1 AWG . Colored cross-linked polyethylene Type XHHW-2 per UL 44 for sizes 1/0 AWG and larger .

Ground Wire: Green PVC/Nylon Type THHN insulation for phase conductor sizes from 14 to 1 AWG, sized in accordance with NEC 2008 and NEC 2011, and UL, (green cross-linked polyethylene Type XHHW-2 for phase conductors sized 1/0 and larger) .

Assembly: Conductors are cabled with grounding wire . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE) .

Specifications

•MeetsUL44:Thermoset-InsulatedWires and Cables (1/0 AWG and larger)

•MeetsUL83:Thermoplastic-InsulatedWires and Cables (14 to 1 AWG)

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNEC2008and NEC 2011 Article 330

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 2008 Article 330 .10(A)(6) or NEC 2011 Article 330 .10(6)

•ULlistedforuseinClassI,Div.2perNEC 2008 and NEC 2011 Article 501 .10(B)(1), Class II, Div .2 per NEC 2008 and NEC 2011 Article 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 2008 and NEC 2011 Article 503 .10(A) and with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanical&physical

properties•Lightweightaluminumarmor•StandardNexansENERGEX®MC

120 from 14 AWG to 1 AWG is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation(non-RoHS

compliant) on sizes 14 to 1 AWG•Conductorsizeslargerthan1/0

AWG

Page 6: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92675

Bend Radius: 7 × overall diameterNotes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes.•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC2008Table310.16orNEC2011

Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed15amperesfor14AWG,20amperesfor12AWG,and30

amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

(1) Where the 4th (white) conductor is the neutral of a balanced 3 phase system .

ENERGEX® MC 120

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

UL 44UL 83

UL 1569

Part Number

Number of Conductors

Conductor SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C250 ft coil 1000 ft reel 618777 642876 2 14 (1) 14 (1) white/black 0.446 11.33 87 129 15 15 15618785 642884 3 14 (1) 14 (1) white/black/red 0.473 12.01 106 158 15 15 15670050 670051 4 14 (1) 14 (1) white/black/red/blue 0.505 12.83 123 183 15(1) 15(1) 15(1)

618793 635045 2 12 (1) 12 (1) white/black 0.483 12.27 118 176 20 20 20618801 635052 3 12 (1) 12 (1) white/black/red 0.514 13.06 145 216 20 20 20618819 635060 4 12 (1) 12 (1) white/black/red/blue 0.550 13.97 173 257 20(1) 20(1) 20(1)

618827 636977 2 10 (1) 10 (1) white/black 0.550 13.97 164 244 30 30 30618835 636985 3 10 (1) 10 (1) white/black/red 0.588 14.94 207 308 30 30 30618843 640177 4 10 (1) 10 (1) white/black/red/blue 0.643 16.33 244 363 30(1) 30(1) 30(1)

642892 642900 2 12 (19) 12 (19) white/black 0.483 12.27 118 176 20 20 20644997 645002 3 12 (19) 12 (19) white/black/red 0.514 13.06 145 216 20 20 20645010 645028 4 12 (19) 12 (19) white/black/red/blue 0.550 13.97 173 257 20(1) 20(1) 20(1)

672972 672980 2 10 (19) 10 (19) white/black 0.550 13.97 164 244 30 30 30672576 672584 3 10 (19) 10 (19) white/black/red 0.588 14.94 207 308 30 30 30670017 672634 4 10 (19) 10 (19) white/black/red/blue 0.643 16.33 244 363 30(1) 30(1) 30(1)

200 ft reel 500 ft reel670085 670190 2 8 (19) 10 (19) white/black 0.656 16.66 229 341 40 50 55670086 642918 3 8 (19) 10 (19) white/black/red 0.713 18.11 300 446 40 50 55

——— 670208 4 8 (19) 10 (19) white/black/red/blue 0.777 19.74 371 552 40(1) 50(1) 55(1)

125 ft reel 500 ft reel670088 670182 2 6 (19) 8 (19) white/black 0.742 18.85 330 491 55 65 75670089 643445 3 6 (19) 8 (19) white/black/red 0.811 20.60 435 647 55 65 75

——— 670174 4 6 (19) 8 (19) white/black/red/blue 0.886 22.50 541 805 55(1) 65(1) 75(1)

——— 670539 3 4 (19) 8 (19) white/black/red 0.941 23.90 624 929 70 85 95 ——— ——— 4 4 (19) 8 (19) white/black/red/blue 1.056 26.82 855 1272 70(1) 85(1) 95(1)

——— 673848 3 3 (19) 6 (19) white/black/red 1.016 25.81 795 1183 85 100 115——— 670237 4 3 (19) 6 (19) white/black/red/blue 1.129 28.68 1049 1561 85(1) 100(1) 115(1)

——— 670521 3 2 (19) 6 (19) white/black/red 1.091 27.71 966 1438 95 115 130——— 673871 4 2 (19) 6 (19) white/black/red/blue 1.201 30.51 1245 1853 95(1) 115(1) 130(1)

——— ——— 3 1 (19) 6 (19) white/black/red 1.203 30.56 1427 2124 110 130 145——— ——— 3 1/0 (19) 6 (19) white/black/red 1.272 32.31 1585 2359 125 150 170

Page 7: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92676

ENERGEX® MC 120

Applications

ENERGEX® MC 120 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY .

Nexans MC 120 cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid bare annealed copper conforming to ASTM B3 . Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Ground Wire: Green PVC/Nylon Type THHN insulation, sized in accordance with NEC 2008 and NEC 2011, and UL .

Assembly: Conductors are cabled with grounding wire . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: Interlocking galvanized steel tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNEC2008and NEC 2011 Article 330

Steel Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 2008 Article 330 .10(A)(6) or NEC 2011 Article 330 .10(6)

•ForuseinClassI,Div.2perNEC501 .10(B)(1), Class II, Div .2 per NEC 2008 and NEC 2011 Article 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 2008 and NEC 2011 Article 503 .10 with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanical&physical

properties•StandardNexansENERGEX®

MC 120 is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation(non-RoHS

compliant)

Page 8: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92677

Bend Radius: 7 × overall diameter

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG .75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes. •ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed15amperesfor14AWG,20

amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

(1) Where the 4th (white) conductor is the neutral of a balanced 3 phase system .

ENERGEX® MC 120

Steel Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

UL 83UL 1569

Number of Conductors

Conductor SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C2 14 (1) 14 (1) white/black 0.441 11.20 144 214 15 15 153 14 (1) 14 (1) white/black/red 0.468 11.89 167 249 15 15 154 14 (1) 14 (1) white/black/red/blue 0.499 12.67 189 281 15(1) 15(1) 15(1)

2 12 (1) 12 (1) white/black 0.477 12.12 179 266 20 20 203 12 (1) 12 (1) white/black/red 0.509 12.93 213 317 20 20 204 12 (1) 12 (1) white/black/red/blue 0.544 13.82 247 368 20(1) 20(1) 20(1)

2 10 (1) 10 (1) white/black 0.544 13.82 238 354 30 30 303 10 (1) 10 (1) white/black/red 0.584 14.83 287 427 30 30 304 10 (1) 10 (1) white/black/red/blue 0.628 15.95 333 496 30(1) 30(1) 30(1)

2 12 (19) 12 (19) white/black 0.483 12.27 215 320 20 20 203 12 (19) 12 (19) white/black/red 0.514 13.06 252 375 20 20 204 12 (19) 12 (19) white/black/red/blue 0.550 13.97 290 432 20(1) 20(1) 20(1)

2 10 (19) 10 (19) white/black 0.550 13.97 164 244 30 30 303 10 (19) 10 (19) white/black/red 0.588 14.94 207 308 30 30 304 10 (19) 10 (19) white/black/red/blue 0.643 16.33 244 363 30(1) 30(1) 30(1)

3 8 (19) 10 (19) white/black/red 0.713 18.11 300 446 40 50 553 6 (19) 8 (19) white/black/red 0.811 20.60 435 647 55 65 75

Page 9: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92678

ENERGEX® MC 277

Applications

ENERGEX® MC 277 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC 2008 and NEC 2011 Article 330 . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY .

Nexans MC 277 cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid bare, annealed copper conforming to ASTM B3 . Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Ground Wire: Green PVC/Nylon Type THHN insulation, sized in accordance with NEC 2008 and NEC 2011, and UL .

Assembly: Conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE) .

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNEC2008and NEC 2011 Article 330

Aluminum Armored MC Cable277 Volt and Special Color Codes UL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 2008 Article 330 .10(A)(6) or NEC 2011 Article 330 .10(6)

•ForuseinClassI,Div.2perNEC2008 and NEC 2011 Article 501 .10(B)(1), Class II, Div . 2 per NEC 2008 and NEC 2011 Article 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 2008 and NEC 2011 Article 503 .10 with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanical&physical

properties•Lightweightaluminumarmor•StandardNexansENERGEX®

MC 277 is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation(non-RoHS

compliant)

Page 10: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-92679

Bend Radius: 7 × overall diameter

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes.•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed20amperesfor12AWG,and30

amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

(1) Where the 4th (gray) conductor is the neutral of a balanced 3 phase system .

ENERGEX® MC 277

Aluminum Armored MC Cable277 Volt and Special Color CodesUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

UL 83UL 1569

Part Number

Number of Conductors

Conductor SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C250 ft coil 1000 ft reel 654269 652537 2 12 (1) 12 (1) brown/gray 0.483 12.27 118 176 20 20 20654251 671917 2 12 (1) 12 (1) orange/gray 0.483 12.27 118 176 20 20 20654244 671925 2 12 (1) 12 (1) yellow/gray 0.483 12.27 118 176 20 20 20

——— ——— 2 12 (1) 12 (1) purple/gray 0.483 12.27 118 176 20 20 20——— ——— 2 12 (1) 12 (1) brown/yellow 0.483 12.27 118 176 20 20 20652263 670570 2 12 (1) 12 (1) red/white 0.483 12.27 118 176 20 20 20652271 670554 2 12 (1) 12 (1) blue/white 0.483 12.27 118 176 20 20 20669762 669770 3 12 (1) 12 (1) brown/orange/gray 0.514 13.06 145 216 20 20 20

——— ——— 3 12 (1) 12 (1) brown/purple/gray 0.514 13.06 145 216 20 20 20——— ——— 3 12 (1) 12 (1) purple/yellow/gray 0.514 13.06 145 216 20 20 20——— ——— 3 12 (1) 12 (1) brown/yellow/gray 0.514 13.06 145 216 20 20 20——— ——— 3 12 (1) 12 (1) red/blue/white 0.514 13.06 145 216 20 20 20——— ——— 3 12 (1) 12 (1) black/blue/white 0.514 13.06 145 216 20 20 20671891 669812 4 12 (1) 12 (1) brown/orange/yellow/gray 0.550 13.97 173 257 20(1) 20(1) 20(1)

——— ——— 4 12 (1) 12 (1) brown/purple/yellow/gray 0.550 13.97 173 257 20(1) 20(1) 20(1)

——— 672923 2 10 (1) 10 (1) brown/gray 0.550 13.97 164 244 30 30 30——— 672949 3 10 (1) 10 (1) brown/orange/gray 0.588 14.94 207 308 30 30 30672592 672600 4 10 (1) 10 (1) brown/orange/yellow/gray 0.643 16.33 244 363 30(1) 30(1) 30(1)

——— ——— 2 12 (19) 12 (19) brown/gray 0.483 12.27 118 176 20 20 20——— ——— 3 12 (19) 12 (19) brown/orange/gray 0.514 13.06 145 216 20 20 20——— ——— 4 12 (19) 12 (19) brown/orange/yellow/gray 0.550 13.97 173 257 20(1) 20(1) 20(1)

——— ——— 2 10 (19) 10 (19) brown/gray 0.550 13.97 164 244 30 30 30——— ——— 3 10 (19) 10 (19) brown/orange/gray 0.588 14.94 207 308 30 30 30——— ——— 4 10 (19) 10 (19) brown/orange/yellow/gray 0.643 16.33 244 363 30(1) 30(1) 30(1)

500 ft reel 1000 ft reel642918 ——— 3 8 (19) 10 (19) brown/orange/gray 0.713 18.11 300 446 40 50 55643445 ——— 3 6 (19) 8 (19) brown/orange/gray 0.811 20.60 435 647 55 65 75

Page 11: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926710

ENERGEX® MC 120

Applications

ENERGEX® MC 120 cables may be used in standard commercial and industrial power, control, and lighting circuits . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011Article300.22(C)withthejacketremoved . The cables may also be installed in direct burial applications .

Nexans MC 120 cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid bare annealed copper conforming to ASTM B3 . Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Ground Wire: Green PVC/Nylon Type THHN insulation, sized in accordance with NEC 2008 and NEC 2011, and UL .

Assembly: Conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Jacket:BlackPVCjacket.

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNEC2008and NEC 2011 Article 330

Aluminum Armored, PVC Jacketed MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 2008 Article 330 .10(A)(6) or NEC 2011 Article 330 .10(6)

•ForuseinClassI,Div.2perNEC2008 and NEC 2011 Article 501 .10(B)(1), Class II, Div . 2 per NEC 2008 and NEC 2011 Article 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 2008 and NEC 2011 Article 503 .10 with approved termination fittings .

•Temperatureratingof90°Cdry•Suitablefordirectburial•Excellentmechanical&physical

properties•Lightweightaluminumarmor•StandardNexansENERGEX®

MC 120 is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation(non-RoHS

compliant)

Page 12: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926711

Bend Radius: 7 × overall diameter

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayordirectburiedat30°Cambienttemperatures.

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes.•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed15amperesfor14AWG,20

amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

(1) Where the 4th (white) conductor is the neutral of a balanced 3 phase system .

ENERGEX® MC 120

Aluminum Armored, PVC Jacketed MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

UL 83UL 1569

Number of Conductors

Conductor SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

Nominal Diameter over Armor

Nominal Diameter over Jacket

Approximate Net Cable Weight

Ampacity amps

inches mm inches mm lb/kft kg/km 60°C 75°C 90°C2 14 (1) 14 (1) white/black 0.446 11.33 0.550 13.97 147 219 15 15 153 14 (1) 14 (1) white/black/red 0.473 12.01 0.578 14.68 166 247 15 15 152 12 (1) 12 (1) white/black 0.483 12.27 0.588 14.94 183 272 20 20 203 12 (1) 12 (1) white/black/red 0.514 13.06 0.619 15.72 210 313 20 20 204 12 (1) 12 (1) white/black/red/blue 0.550 13.97 0.655 16.64 238 354 20(1) 20(1) 20(1)

2 10 (1) 10 (1) white/black 0.550 13.97 0.655 16.64 239 356 30 30 303 10 (1) 10 (1) white/black/red 0.568 14.94 0.693 17.60 283 421 30 30 304 10 (1) 10 (1) white/black/red/blue 0.643 16.33 0.748 19.00 319 475 30(1) 30(1) 30(1)

2 8 (19) 10 (1) white/black 0.656 16.66 0.761 19.33 309 460 40 50 553 8 (19) 10 (1) white/black/red 0.713 18.11 0.818 20.78 380 566 40 50 554 8 (19) 10 (1) white/black/red/blue 0.777 19.74 0.882 22.40 451 671 40(1) 50(1) 55(1)

2 6 (19) 8 (19) white/black 0.742 18.85 0.847 21.51 410 610 55 65 753 6 (19) 8 (19) white/black/red 0.811 20.60 0.916 23.27 515 766 55 65 754 6 (19) 8 (19) white/black/red/blue 0.886 22.00 0.991 25.17 612 911 55(1) 65(1) 75(1)

3 4 (19) 8 (19) white/black/red 0.941 23.90 1.046 26.57 714 1063 70 85 954 4 (19) 8 (19) white/black/red/blue 1.056 26.82 1.161 29.49 945 1406 70(1) 85(1) 95(1)

3 2 (19) 6 (19) white/black/red 1.091 25.88 1.196 30.38 1086 1616 95 115 1304 2 (19) 6 (19) white/black/red/blue 1.201 30.51 1.306 33.17 1345 2002 95(1) 115(1) 130(1)

Page 13: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926712

Applications

ENERGEX® MC Mega Neutral cables are for use in applications where increased neutral capacity is required due to non-linear switching loads which can cause additive harmonic currents to be present on the neutral conductors . They may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . It is also suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY .

Nexans MC Mega Neutral Cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid bare annealed copper conforming to ASTM B3 . Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Neutral Conductor(s): Solid or stranded bare annealed copper, with white Type THHN insulation and colored stripe where indicated . Cable has either one neutral per phase conductor or one over-sized neutral .

Ground Wire(s): Sized in accordance with NEC 2008 and NEC 2011, and UL, one with green THHN insulation, one with green THHN insulation with a yellow stripe (in cables with two ground wires) .

Assembly: Conductors are cabled with neutrals and grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

ENERGEX® MC Mega Neutral

Aluminum Armored MC Mega Neutral CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNEC2008and NEC 2011 Article 330

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 2008 Article 330 .10(A)(6) or NEC 2011 Article 330 .10(6)

•ForuseinClassI,Div.2perNEC2008 and NEC 2011 Article 501 .10(B)(1), Class II, Div . 2 per NEC 2008 and NEC 2011 Article 502 .10(B)(1) and Class III, Div . 1 and 2 per NEC 2008 and NEC 2011 Article 503 .10 with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•StandardNexansENERGEX® MC

Mega Neutral is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation(non-RoHS

compliant)

Page 14: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926713

Oversize Neutral Conductor (ONC)

Bend Radius: 7 × overall diameter

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes.•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed20amperesfor12AWG,and

30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

(1) Where the 4th white conductor is the neutral of a balanced 3 phase system .

ENERGEX® MC Mega Neutral

Aluminum Armored MC Mega Neutral CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Neutral Per Leg (NPL)

UL 83UL 1569

Number of Power

Conductors

Conductor SizeAWG

Neutral SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

White Neutral Stripe Color

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C2 12 (1) 2x12 (1) 2x12 (1) black/red black/red 0.515 13.08 120 179 20 20 203 12 (1) 3x12 (1) 2x12 (1) black/red/blue black/red/blue 0.528 13.41 163 243 20 20 204 12 (1) 3x12 (1) 2x12 (1) black/red/pink/tan none/pink/tan 0.549 13.94 191 284 20(1) 20(1) 20(1)

2 10 (1) 2x10 (1) 2x10 (1) black/red black/red 0.603 15.32 226 336 30 30 303 10 (1) 3x10 (1) 2x10 (1) black/red/blue black/red 0.655 16.64 300 446 30 30 30

Number of Power

Conductors

Conductor SizeAWG

Neutral SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

White Neutral Stripe Color

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C1 12 (1) 10 (1) 12 (1) black no stripe 0.515 13.08 120 179 20 20 202 12 (1) 10 (1) 12 (1) black/red no stripe 0.528 13.41 163 243 20 20 203 12 (1) 10 (1) 12 (1) black/red/blue no stripe 0.549 13.94 191 284 20 20 203 12 (1) 8 (19) 12 (1) black/red/blue no stripe 0.603 15.32 226 336 20 20 204 12 (1) 2x10 (1) 2x12 (1) black/red/blue/pink none/pink 0.655 16.64 300 446 20(1) 20(1) 20(1)

2 10 (1) 8 (19) 10 (1) black/red no stripe 0.595 15.11 215 320 30 30 303 10 (1) 6 (19) 10 (1) black/red/blue no stripe 0.575 14.61 320 476 30 30 304 10 (1) 2x8 (19) 2x10 (1) black/red/blue/pink none/pink 0.790 20.07 400 595 30(1) 30(1) 30(1)

Page 15: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926714

ENERGEX® MC Ground Plus

Applications

ENERGEX® MC Ground Plus cables are for use in applications where isolated, dedicated or redundant ground is required . They may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are also suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY .

Nexans MC Ground Plus cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid bare annealed copper conforming to ASTM B3 . Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Ground Wire(s): Sized in accordance with NEC 2008 and NEC 2011, and UL, one with green THHN insulation, one with green THHN insulation with a yellow stripe (in cables with two ground wires) .

Assembly: Conductors are cabled with grounding wire(s) . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNEC2008and NEC 2011 Article 330

Aluminum Armored Isolated Ground MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 2008 Article 330 .10(A)(6) or NEC 2011 Article 330 .10(6)

•ForuseinClassI,Div.2perNEC2008 and NEC 2011 Article 501 .10(B)(1), Class II, Div . 2 per NEC 2008 and NEC 2011 Article 502 .10(B)(1) and Class III, Div . 1 and 2 per NEC 2008 and NEC 2011 Article 503 .10 with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•StandardNexansENERGEX® MC

Ground Plus is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation(non-RoHS

compliant)

Page 16: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926715

Bend Radius: 7 × overall diameter

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed15amperesfor14AWG,20

amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

(1) Where the 4th (white) conductor is the neutral of a balanced 3 phase system .

ENERGEX® MC Ground Plus

Aluminum Armored Isolated Ground MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

UL 83UL 1569

Part Number

Number of Conductors

Conductor SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C250 ft coil 1000 ft reel ——— ——— 2 14 (1) 2x14 (1) white/black 0.475 12.07 106 158 15 15 15——— ——— 3 14 (1) 2x14 (1) white/black/red 0.485 12.32 123 183 15 15 15——— ——— 4 14 (1) 2x14 (1) white/black/red/blue 0.525 13.34 140 208 15(1) 15(1) 15(1)

671818 671826 2 12 (1) 2x12 (1) white/black 0.514 13.06 145 216 20 20 20——— ——— 3 12 (1) 2x12 (1) white/black/red 0.550 13.97 173 257 20 20 20——— ——— 4 12 (1) 2x12 (1) white/black/red/blue 0.583 14.81 201 299 20(1) 20(1) 20(1)

——— ——— 2 10 (1) 2x10 (1) white/black 0.580 13.97 207 308 30 30 30——— ——— 3 10 (1) 2x10 (1) white/black/red 0.620 15.75 244 363 30 30 30——— ——— 4 10 (1) 2x10 (1) white/black/red/blue 0.675 17.15 281 418 30(1) 30(1) 30(1)

——— ——— 2 8 (19) 2x10 (1) white/black 0.660 16.76 300 446 40 50 55——— ——— 3 8 (19) 2x10 (1) white/black/red 0.750 19.05 371 552 40 50 55——— ——— 4 8 (19) 2x10 (1) white/black/red/blue 0.825 20.96 442 658 40(1) 50(1) 55(1)

——— ——— 2 6 (19) 2x8 (19) white/black 0.822 20.88 435 647 55 65 75——— ——— 3 6 (19) 2x8 (19) white/black/red 0.900 22.86 541 805 55 65 75——— ——— 4 6 (19) 2x8 (19) white/black/red/blue 0.977 24.82 647 963 55(1) 65(1) 75(1)

Page 17: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926716

ENERGEX® MC Multi Conductor

Applications

ENERGEX® MC Multi Conductor cables are designed for applications that require six or more conductors . They may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY .

Nexans MC Multi Conductor cables are lead free and RoHS compliant .

Construction

Conductor: Solid Bare, annealed copper conforming to ASTM B3 .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Ground Wire: Green PVC/Nylon Type THHN insulation, sized in accordance with NEC 2008 and NEC 2011, and UL .

Assembly: Conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

Color Code:(tan is stripe color)6 conductor: black, red, white, black/tan, red/tan, white/tan8 conductor: black, red, white, blue, black/tan, red/tan, white/tan, blue/tan

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNEC2008and NEC 2011 Article 330

Product features

Aluminum Armored MC Multi Conductor CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 2008 Article 330 .10(A)(6) or NEC 2011 Article 330 .10(6)

•ForuseinClassI,Div.2perNEC2008 and NEC 2011 Article 501 .10(B)(1), Class II, Div . 2 per NEC 2008 and NEC 2011 Article 502 .10(B)(1) and Class III, Div . 1 and 2 per NEC 2008 and NEC 2011 Article 503 .10 with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•StandardNexansENERGEX® MC

Multi Conductor is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation(non-RoHS

compliant)

Page 18: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926717

Bend Radius: 7 × overall diameter

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.Ampacitiesforcableshavingmorethanthreecurrentcarryingconductorshavebeen derated per NEC 2008 Table 310 .15(B)(2)(a) or NEC 2011 Table 310 .15(B)(3)(a) .

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed20amperesfor12AWG,and

30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

ENERGEX® MC Multi Conductor

Aluminum Armored MC Multi Conductor CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

UL 83UL 1569

Number of Conductors

Conductor SizeAWG

Ground SizeAWG

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C6 12 (1) 12 (1) 0.570 14.48 225 335 16 20 208 12 (1) 12 (1) 0.645 16.38 290 432 14 18 20

10 12 (1) 12 (1) 0.700 17.78 320 476 10 13 1512 12 (1) 12 (1) 0.750 19.05 350 521 10 13 1514 12 (1) 12 (1) 0.800 20.32 410 610 10 13 1516 12 (1) 12 (1) 0.825 20.96 465 692 10 13 1518 12 (1) 12 (1) 0.835 21.21 475 707 10 13 1520 12 (1) 12 (1) 0.870 22.10 565 841 10 13 1524 12 (1) 12 (1) 0.950 24.13 650 967 9 11 146 10 (1) 10 (1) 0.675 17.15 340 506 24 28 308 10 (1) 10 (1) 0.760 19.30 390 580 21 25 28

10 10 (1) 10 (1) 0.825 20.96 470 699 15 18 2012 10 (1) 10 (1) 0.880 22.35 560 833 15 18 2014 10 (1) 10 (1) 0.940 23.88 635 945 15 18 2016 10 (1) 10 (1) 0.980 24.89 730 1086 15 18 2018 10 (1) 10 (1) 0.990 25.15 805 1198 15 18 2020 10 (1) 10 (1) 1.025 26.04 915 1362 15 18 2024 10 (1) 10 (1) 1.130 28.70 1130 1682 14 16 18

Page 19: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926718

ENERGEX® AC

Applications

ENERGEX® AC cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are suitable for installations in accordance to NEC 2008 and NEC 2011 Article 320 . These cables may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY .

Nexans ACTHH cable is lead free and RoHS compliant .

Aluminum Armored AC CableUL Type ACTHH, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Construction

Conductor: Solid bare, annealed copper conforming to ASTM B3 . Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Bond Wire: Longitudinal bare aluminum bond wire in continuous contact with armor .

Assembly: Conductors are cabled and paper wrapped with a marker tape/core protection tape combination which assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: ALUMINUM ARMORED CABLE NOT FOR USE ON DC CIRCUITS / CAUTION NOT TO BE USED WITH SET SCREW CONNECTOR / FOR CT USE LEAD FREE (MFG DATE)

Specifications

•MeetsUL4:ArmoredCable•MeetsUL83:Thermoplastic-Insulated

Wires and Cables •MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeACperNEC2008and NEC 2011 Article 320

Product features

•CablesareULlistedasTypeACTHH,600 V

•ULlistedinsulatedconductors•ULlistedforuseincabletraysper

NEC 2008 and NEC 2011 Article 320 .10(2)

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•StandardNexansENERGEX® AC is

Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts

Page 20: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926719

Bend Radius: 7 × overall diameter installed

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes.•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed15amperesfor14AWG,20

amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through (G) .

(1) Where the 4th (white) conductor is the neutral of a balanced 3 phase system .

ENERGEX® AC

Aluminum Armored AC CableUL Type ACTHH, 600 V, 90°C dry rated - Lead FreeCopper Conductors

UL 4UL 83

Number of Conductors

Conductor SizeAWG

Circuit Conductor Color Code

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C2 14 (1) white/black 0.475 12.07 89 132 15 15 153 14 (1) white/black/red 0.495 12.57 109 162 15 15 152 12 (1) white/black 0.502 12.75 109 162 20 20 203 12 (1) white/black/red 0.524 13.31 137 204 20 20 204 12 (1) white/black/red/blue 0.560 14.22 168 250 20(1) 20(1) 20(1)

2 10 (1) white/black 0.564 14.33 146 217 30 30 303 10 (1) white/black/red 0.591 15.01 190 283 30 30 304 10 (1) white/black/red/blue 0.635 16.13 236 351 30(1) 30(1) 30(1)

3 8 (19) white/black/red 0.635 16.13 246 366 40 50 553 6 (19) white/black/red 0.737 18.72 357 531 55 65 75

Page 21: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926720

Applications

ENERGEX® AC HCF cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They may be used in patient areas of hospitals, out-patient centers and medical and dental offices . They are not permitted where hazardous anesthetizing is performed . They may also be used in applications which require AC cable with a redundant ground in accordance with NEC 2008 and NEC 2011 Article 250 .118(8) . They are suitable for installations in accordance to NEC 2008 and NEC 2011 Article 320 . These cables may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300 .22(C) ONLY .

Nexans AC HCF cable is lead free and RoHS compliant .

Construction

Conductor: Solid bare, annealed copper conforming to ASTM B3 . Stranded bare annealed copper conforming to ASTM B3 and ASTM B787 .

Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test .

Bond Wire: Longitudinal bare aluminum bond wire in continuous contact with armor .

Ground Wire: Green PVC/Nylon Type THHN insulation, sized in accordance with NEC 2008 and NEC 2011 and UL .

Assembly: Conductors are cabled and paper wrapped with a marker tape/core protection tape combination which assembles the core in an essentially round configuration .

Armor: Interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: ALUMINUM ARMORED CABLE NOT FOR USE ON DC CIRCUITS / CAUTION NOT TO BE USED WITH SET SCREW CONNECTOR / FOR CT USE LEAD FREE (MFG DATE)

ENERGEX® AC HCF

Aluminum Armored Health Care Facilities AC CableUL Type AC, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Specifications

•MeetsUL4:ArmoredCable•MeetsUL83:Thermoplastic-Insulated

Wires and Cables •MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•DesignatedTypeACperNEC2008and NEC 2011 Article 320

•MeetsUL2556:WireandCable Test Methods

•MeetsNEC2008andNEC2011Articles: 250 .94, 250 .118(8), 300 .22(C), 320, 517 .13 and 645

Product features

•CablesareULlistedasTypeAC,600 V

•ULlistedinsulatedconductors•ULlistedforuseincabletraysper

NEC 2008 and NEC 2011 Article 320 .10(2)

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•StandardNexansENERGEX®

AC HCF is Lead Free and RoHS compliant

Options

The following constructions can be provided on special orders:•Specialconductorcounts

Page 22: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926721

Bend Radius: 7 × overall diameter

Notes:•Dimensionsandweightsshownarenominalvalues,subjecttostandardindustrytolerances.•AmpacitiesareinaccordancewithNEC2008Table310.16orNEC2011Table310.15(B)(16)forconductorsinaracewayat30°Cambienttemperatures.

60°C-Whenterminatedtoequipmentforcircuitsrated100amperesorlessormarkedforconductorsizes14through1AWG.75°C-Whenterminatedtoequipmentforcircuitsratedover100amperesormarkedforconductorslargerthansize1AWG.90°C-Wetordrylocations.Forampacityderatingpurposes.•ForcorrectionfactorsfordifferentambienttemperaturesandampacitiesatdifferentconductortemperatureratingsseeNEC

2008 Table 310 .16 or NEC 2011 Table 310 .15(B)(16) .•NEC2008andNEC2011Article240.4(D)requiresthatovercurrentprotectionnotexceed20amperesfor12AWG,and

30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied . Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240 .4(E) through(G) .

(1) Where the 4th (white) conductor is the neutral of a balanced 3 phase system .

ENERGEX® AC HCF

Aluminum Armored Health Care Facilities AC CableUL Type AC, 600 V, 90°C dry rated - Lead FreeCopper Conductors

UL 4UL 83

Part Number

Number of Conductors

Conductor SizeAWG

Ground SizeAWG

Circuit Conductor Color Code

Nominal Diameter over Armor

Approximate Net Cable Weight

Ampacity amps

inches mm lb/kft kg/km 60°C 75°C 90°C250 ft coil 1000 ft reel 671560 672170 2 12 (1) 12 (1) white/black 0.487 12.37 133 198 20 20 20672188 672196 3 12 (1) 12 (1) white/black/red 0.521 13.23 157 234 20 20 20673426 673434 4 12 (1) 12 (1) white/black/red/blue 0.547 13.89 187 278 20(1) 20(1) 20(1)

673715 ——— 2 10 (1) 10 (1) white/black 0.503 12.78 181 269 30 30 30——— ——— 3 10 (1) 10 (1) white/black/red 0.537 13.64 226 336 30 30 30673756 ——— 4 10 (1) 10 (1) white/black/red/blue 0.585 14.86 279 415 30(1) 30(1) 30(1)

——— ——— 2 12 (19) 12 (19) white/black 0.487 12.37 133 198 20 20 20——— ——— 3 12 (19) 12 (19) white/black/red 0.521 13.23 157 234 20 20 20

Page 23: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926722

Length mils x 0 .0254 = mm (millimeters) inches x 25 .4 = mm feet x 0 .3048 = m (meters) miles x 1 .609344 = km (kilometers)

Area circular mils x 0 .0005067 = mm2 (square millimeters) sq . in . x 645 .16 = mm2

sq . ft . x 0 .092903 = m2 (square meters) sq . yd . x 0 .836127 = m2

sq . mi . x 2 .58999 = km2 (square kilometers)

Volume cu . in . x 16 .387 = cm3 (cubic centimeters) cu . ft . x 0 .028317 = m3 (cubic meters) gallons x 4 .54609 = l (liters)

Mass pounds x 0 .45359 = kg (kilograms) tons (2000 lbs .) x 0 .907185 = t (metric tons)

Mass per unit length lb/1000 ft x 1 .48816 = kg/km (kilograms per kilometer) lb/mi x 0 .28185 = kg/km mm2 x 8 .89 = kg/km (for copper) mm2 x 2 .70 = kg/km (for aluminum) mm2 x 7 .83 = kg/km (for steel)

Force or Tension pounds (force) x 4 .448 = N (newtons) mass (in kg) x 9 .8066 = N (Weight at or near sea level)

Force per unit area lbf/in2 = (psi) x 6 .895 = kPa (kilopascals)(Stress, pressure, lbf/in2 x 0 .006895 = MPa (megapascals)tensile strength, etc .) N/mm2 = MPa

Temperature °Fto°C:°C=(°Fminus32)x5/9 °Cto°F:°F=(°Cx9/5)plus32

Note: Kilopascals are used generally for fluid pressures . Megapascals are used generally for stress in materials, i .e . for tensile stress, modulus of elasticity, etc .

Metric Conversions

Page 24: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926723

Contact us for all your wire and cable needsNexans Energy USA inc .25 Oakland AvenueChester, NY 10918Tel: 1-866-663-9267www .nexans .us

Nexans wire and cable

A t t h e c o r e o f p e r f o r m a n c e

Page 25: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,

1-866-663-926724

WARNING

FLAMMABLENon-metallic covering of electrical cables will burn and under certain conditions may transmit fire when ignited .

TOXICBurning non-metallic coverings may emit acid gases, which are highly toxic, and may generate dense smoke .

CORROSIVEEmission of acid gases may corrode metal in the vicinity, such as sensitive instruments and reinforcing rod in concrete .

NOTICE

Nexans has endeavoured to ensure the accuracy of the data in this publication, however we cannot be liable for the consequences of errors oromissions.Alldataissubjecttochange without notice . The installer and / or user assumes all liability for the consequences of the installation and / or use of any of our products in contravention of any applicable law, regulation or code .

Page 26: ENERGEX Armored Cables - Nexans...B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger . Insulation: Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,