SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers 369241l 1 03.05.18 Energi Savr Node for 0–10 V - Energi Savr Node with Softswitch The Energi Savr Node (ESN) family is a group of modular products for the control of lighting and other loads. This document describes the following products: • ESN unit for 0 –10 V- (models QSN-4T16-S and QSN-4T16-S-347 — 0 –10 V- Control / Softswitch) • Softswitch ESN unit (models QSN-4S16-S and QSN-4S16-S-347 — Softswitch) Features • Default configuration requires no commissioning. • Programming using integral interface on the ESN unit. • Four occupancy sensor inputs for automated control of lights in 4 zones. • Four daylight sensor inputs automatically adjust light levels based on the amount of natural light entering through the windows. • Four IR receiver inputs for personal control. • Four inputs for IEC PELV/NEC® Class 2 dry contact switches. • Includes QS control link for seamless integration of lights, control stations, and QS sensor modules. • Softswitch technology yields 1,000,000 cycle relay lifetime. • Contact Lutron for compatibility with Quantum system. System Example QS link Control Power 120–277 V~ Load Input Feeds (4) 120–277 V~; 347 V~ 3 0–10 V Channels (4) QSN-4T16-S and QSN-4T16-S-347 Emergency Contact Closure Input Contact Closure Input Switched Load Outputs (4) 16 A Softswitch 120–277 V~; 347 V~ 3 Wireless Communication Wired Daylight Sensors (up to 4) 2 Wired Daylight Sensors (up to 4) 1,2 Wired Occupancy Sensors (up to 4) Wired Occupancy Sensors (up to 4) 1 Wired Wallstation or IR receivers (up to 4) Wired Wallstation or IR Receivers (up to 4) 1 IEC PELV / NECR Class 2 Dry Contact Switch (up to 4) (by others) IR Transmitter IR Transmitter OR OR OR OR Notes: 1 Up to 4 wired sensors total (of any type). 2 The maximum number of daylight sensors (wired and wireless) that an ESN unit can support is four (1 per zone). 3 For 347 V~ models only. QSM seeTouch QS Wallstation ESN Programming Interface Radio Powr Savr Occupancy Sensor (up to 10 per QSM) Radio Powr Savr Daylight Sensor (up to 10 per QSM) 2 Pico Wireless Controller (up to 10 per QSM)

Upload: buidang

Post on 13-Jul-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 1 03.05.18Energi Savr Node for 0–10 V- Energi Savr Node with SoftswitchThe Energi Savr Node (ESN) family is a group of modular products for the control of lighting and other loads. This document describes the following products:

•ESN unit for 0 –10 V- (models QSN-4T16-S and QSN-4T16-S-347 — 0 –10 V- Control / Softswitch)

•Softswitch ESN unit (models QSN-4S16-S and QSN-4S16-S-347 — Softswitch)

Features•Defaultconfigurationrequiresnocommissioning.•ProgrammingusingintegralinterfaceontheESN unit.•Fouroccupancysensorinputsforautomatedcontrolof

lights in 4 zones.•Fourdaylightsensorinputsautomaticallyadjustlight

levels based on the amount of natural light entering through the windows.

•FourIRreceiverinputsforpersonalcontrol.•FourinputsforIECPELV/NEC® Class 2 dry contact

switches.•IncludesQScontrollinkforseamlessintegrationoflights,controlstations,andQSsensormodules.

•Softswitchtechnologyyields1,000,000cyclerelaylifetime.

•ContactLutronforcompatibilitywithQuantumsystem.

System Example

QSlink

ControlPower120–277 V~

LoadInputFeeds (4) 120–277 V~; 347 V~3

0–10 V Channels (4)QSN-4T16-S and QSN-4T16-S-347

Emergency Contact Closure

Input

Contact Closure Input

SwitchedLoadOutputs (4) 16 A Softswitch 120–277 V~; 347 V~3

Wireless Communication

WiredDaylight Sensors (up to 4)2

Wired Daylight Sensors (up to 4)1,2

WiredOccupancy Sensors (up to 4)

Wired Occupancy Sensors (up to 4)1

Wired Wallstation orIRreceivers(upto4)

Wired Wallstation orIRReceivers (up to 4)1

IECPELV/ NECR Class 2 DryContactSwitch (up to 4) (by others)

IRTransmitter

IRTransmitterOR OR

OR OR

Notes: 1 Up to 4 wired sensors total (of any type).2 The maximum number of daylight sensors (wired and

wireless) that an ESN unit can support is four (1 per zone).

3 For347V~ models only.

QSMseeTouch QS Wallstation

ESN Programming

Interface

RadioPowrSavrOccupancy Sensor (up to 10 per QSM)

RadioPowrSavr DaylightSensor (up to 10 per QSM)2

PicoWirelessController (up to 10 per QSM)

Page 2: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 2 03.05.18

SpecificationsRegulatory Approvals

•UL Listed•CSA•NOM•LutronQualitySystemsregisteredtoISO9001:2015• Complieswithrequirementsforuseinotherspaces

used for environmental air (plenums) per NEC® 2014 300.22(C)(3)

•MeetstheCanadianNationalBuildingCodeplenumrequirementsforaconcealedspaceusedasaplenumwithin a floor or roof assembly

•Forcommercialuse,ClassAonly

Power•ControlPower:120V~; 220–240 V~; 277 V~ 50/60Hz

•LightningstrikeprotectionmeetsANSI/IEEEstandard62.41-1991.Canwithstandvoltagesurgesofupto 6,000V~andcurrentsurgesofupto3,000A

•Currentdraw:0.5Amax•10-yearpowerfailurememory:restoreslightingtolevels

prior to power interruption•Latchingrelayskeeppreviouslyilluminatedzoneson

when control power feed is lost

Environment•AmbientTemperatureOperatingRange:32ºFto104ºF(0ºCto40ºC)

•Relativehumidity:lessthan90%non-condensing•Forindooruseonly•Thermaldissipation:40BTU/hr

Terminal Wiring•ControlPowerWiring:14 AWGto12 AWG(2.5 mm2 to 4.0 mm2)

•LoadWiring:14 AWGto12 AWG(2.5 mm2to4.0 mm2)•0–10V-Wiring:20 AWGto12 AWG(0.5 mm2to4.0 mm2)•InputGroupWiring:20 AWGto12 AWG(0.5 mm2 to 4.0 mm2) — maximum wire run length to each input not toexceed150ft(46m)

•QSLinkWiring:22 AWGto12 AWG(0.5 mm2 to 4.0 mm2)

•ContactClosureWiring:20 AWGto12 AWG(0.5 mm2 to4.0 mm2)

Physical Design and Mounting•NEMAType1,IP-20protection•Surfacemount

Load Types (relay ratings)•16ATungsten,120to277V~

•16AACGeneralUse,120to277V~

•16AElectricDischargeLamp(ballast),120to 277 V~,347V~ (347 V~ models only)

•16AInductive,120to277V~

•0.5HP,120V~

•1.5HP,220to277V~

•WorkswithallballastsanddriversthatprovideacurrentsourcethatiscomplianttoIEC60629 AnnexE.2,andwhoseinrushcurrentdoesnotexceedNEMA410 standards for electronic ballast/driver

Input Default AssociationsInputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4

Group 1

Occ XPhoto XIR XSwitch X

Group 2

Occ XPhoto XIR XSwitch X

Group 3

Occ XPhoto XIR XSwitch X

Group 4

Occ XPhoto XIR XSwitch XCCI X X X XEmergencyCCI X X X X

Softswitch: 120 V~ to 277 V~, 347 V~ (347 V~ models only)

•Softswitch relay is rated for 16 A continuous use per channel,whichisthemaximumcontinuousloadfora20AOvercurrentProtectionDevice(BranchBreaker).

•PatentedSoftswitch circuit eliminates arcing at mechanical contacts when loads are switched. Extendsrelaylifetoanaverageof1,000,000cycles(on/off)forresistive,capacitive,orinductivesources.

•Relayismechanicallyheld.

Page 3: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 3 03.05.18

Specifications (continued)

0–10 V- Product Ratings (QSN-4T16-S and QSN-4T16-S-347)

•Eachoutputsinksupto50mAmaximum.•Eachoutputsinkscurrentonly(loaddevicemust

provide 10 V- supply). •ProvidesanIECPELV/NEC® Class 2 isolated 0–10 V- outputsignalthatconformstoIEC60929.

Occupancy Sensors•Upto16occupancysensorscanbeprogrammedto

the ESN device.•ManualProgramming:upto4occupancysensorswireddirectlytotheESNdevice,upto4occupancysensorswiredtoaQSSensorModule(QSM),andupto10wireless occupancy sensors through the same QSM; the total programmed to the ESN device cannot exceed 16.

•HHD(iPod / iPhone)Programming:upto16occupancysensors from any source (wired directly to the ESN device,wiredtoanyotherESNdevice,orwired/wirelessfromanyQSMontheQSlink);thetotalprogrammedtothe ESN device cannot exceed 16.

•UseLutronoccupancysensorstocontroloneormorezones.

•UseLutronoccupancysensorsinvacancymodeto automatically turn the lights off in an area after it becomes vacant.

•Eachzonecanbeprogrammedtoautomaticallyturnthe lights on when occupied and turn the lights off when vacant.

•EachwiredoccupancyinputcanpoweroneLutronoccupancy sensor.

•Eachoccupiedsceneandunoccupiedscenecanbeprogrammed independently.

•Lutron occupancy sensors can be programmed to automatically turn the lights on in area when it becomes occupied and turn the lights off in an area after it becomes vacant.

•EachofthefouroccupancyinputscanpoweroneLutron occupant sensor.

•Eacharea’soccupiedsceneandunoccupiedscenecanbe programmed independently.

•Occupancysensormustprovideadrycontactclosure or solid-state output.

•AdditionaloccupancysensorscanbeusedwiththeESNdevice.Refertothe“ProgrammingOptionsandFeatures”tableforsystemrules.

seeTouch QS Controls

•seeTouchQSwallstationscanbeconfiguredtocontrol ESN unit scenes or zones.

•Inzonetogglemode,zonebuttonscanbeassignedtooneor more zones on any ESN unitconnectedtotheQSLink.

•Inscenemode,wallstationscanbeassignedtooneor more ESN unitsconnectedtotheQSLink.

•LEDindicatordisplayszoneorscenestatus.Table 1: seeTouch QS Wallstation Configurations

# Buttons

Wallstation Function 1 2 3 5 7Zone Toggle Scene 1,Off

(toggle)1,Off 1,2

Off1-4,Off

N/A

IR Wallstation or Receiver Input

•FourinputsforIRreceiversorwallstationsforcontroloflighting zones can be connected directly to the ESN unit.

•UseLutronCC-1BRL-WHorCC-4BRL-WHwallstations to control one or more zones.

•UseLutron EC-DIR-WHorEC-IR-WHceilingmountsensors to control one or more zones.

•UptofouradditionalwiredwallstationsorIRreceiverscan be assigned when associated with a QSM.

•AssociateadditionalQSMsandsensors/controlswith ESN unit when programming with an Apple iPod touch or iPhone.Referto"ProgrammingOptions"section for details.

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 4: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 4 03.05.18

Specifications (continued)

Daylight Sensors

•Lutrondaylightsensorsallowdaylightharvestingwithprogrammable effect on light output.

•FourdaylightsensorscanbeconnecteddirectlytotheESN unit.

•UseLutronEC-DIR-WHsensorstocontroloneormorezones.

•Alternatively,uptofoursensors(LutronWiredDaylightSensorsorRadioPowrSavrDaylightSensors)canbeassigned when associated with a QSM.

•ThemaximumnumberofLutrondaylightsensors(wiredorwireless),eitherwireddirectlytotheunitorindirectly(associated with a QSM) cannot exceed four.

•AssociateadditionalQSMsandsensors/controlswithESN unit when programming with an Apple iPod touch or iPhone.Referto"ProgrammingOptions"sectionfordetails.

Contact Closure Input (CCI) Default behavior:•Activatescenesusingmomentaryormaintainedclosuresfromanexternaldevicesuchasatimeclock.

•StartorstopAfterhoursModeusingamaintainedclosure.

•Theattacheddevicemustprovideadrycontactclosureor solid-state output.

•ConfigurableforNormally-Open(NO)orNormally-Closed(NC) operation.

•Inputismiswire-protectedupto36V-.

Emergency Contact Closure Input

•Bydefault,contactclosureinputfromLutronEmergencyLightingInterface(LUT-ELI-3PH),security,orfirealarmsystemsturnsallzonesontofulloutputwhen emergency state is detected.

•Emergencycontactclosureinputisnormallyclosed(NC). The ESN unitisshippedwithajumperpre-installed.

•Responseofeachzoneisconfigurable.•Attacheddevices,bydefault,willgotomaximum

output and ignore control inputs.•Nooperationswillbealloweduntilemergencysignal

is cleared.•Theattacheddevicemustprovideadrycontact

closure or solid-state output.•Inputismiswire-protectedupto36V-.•EmergencyCCIcannotcontrolotherESNunits.

Functionality with GRAFIK Eye QS

•ESN unitfollowsGRAFIKEye QS scene activations whenassociatedwiththeGRAFIKEye QS.

•ESN unit responds to commands initiated by the GRAFIKEyeQS astronomictimeclockwhenassociatedwiththeGRAFIKEyeQS.

•ESN unit operates in afterhours mode when associatedwithaGRAFIKEyeQSthatisinafterhoursmode.

Functionality with QSE-IO

•ESN unit responds to scene commands initiated by theQSE-IO,iftheQSE-IODIPswitcheshavebeensettoeithersceneselectionmode,zonetogglemode,partitionmode,oroccupancysensormode.

Functionality with QSE-CI-NWK-E

•IntegrateESN unitwithtouchscreens,PCs,A/Vsystems,orotherdigitalsystemsanddevices.

•Recallscenesandset/adjustzonelevels.

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 5: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 5 03.05.18

Specifications (continued)

IEC PELV / NEC® Class 2 Dry Contact Switches

•FourinputsforIECPELV/NEC® Class 2 dry contact switches can be assigned to turn on and off one or more zones.

•Configureformomentaryormaintainedoperation.

QS Link Limits

•EachESN unitcanprovideupto14PowerDrawUnits(PDUs)forotherQSdevices.RefertotheQSLink PowerDrawUnitspecificationsubmittal(Lutron P/N369405)formoreinformationconcerningPDUs.

•TheQSLinkcanhaveupto100devicesand100zones.•EachESN unit counts as 1 device towards the

100 device limit. •EachESN unit counts as 4 zones towards the

100 zone limit.

QSM (QS Sensor Module)

•UsetheQSMtointegrateRadioPowrSavrOccupancysensors,RadioPowrSavr Daylightsensors,andPicoWirelessControllerstocontrolzones on the ESN unit.

•Associate1QSMperESN unit with manual programming.

•AssociatemultipleQSMsperESN unit with Apple iPod touch or iPhoneprogramming(requires QSE-CI-AP-DandWi-Firouter).See"ProgrammingOptions"fordetails.

•Assignupto10RadioPowrSavrOccupancysensorsper ESN unit via QSM.

•Assignupto4RadioPowrSavrDaylightsensorsperESN unit via QSM.

•Assignupto10PicoWirelessControllersperESN unit via QSM.

•ThesensorsandPicoWirelessControllersassociatedwith the QSM should be mounted within 60 ft (18 m) lineofsight,or30ft(9m)throughwalls,oftheQSM.

•Wireandpowerupto4wiredsensorsperQSM –DaylightSensors –OccupancySensors –Infrared(IR)ReceiversorWallstations

•RefertoQSMSpecificationSubmittalformoreinformation.

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 6: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 6 03.05.18

Programming Options

Manual Programming:

•Use buttons on the front of the ESN unit.•UsemanualprogrammingininstallationswithonlyoneESNunitandwithoneQSMorfewerontheQSlink.

HHD Programming•RequiresESNProgrammingInterface(QSE-CI-AP-D).•RequiresApple iPod touch or iPhone mobile digital device.•Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple

ESN unitsandQSMsintheQSlink.•WirelessrouteronlyrequiredforprogrammingwithanApple iPod touch or iPhone.

•Wirelessroutermayberemovedfornormaloperation.•EthernetconnectionmaybemadeviaanESNProgrammingInterface(QSE-CI-AP-D)oranESNQSunitwithintegralEthernetjack.

•LutronrecommendsthatanESNProgrammingInterface(orESNQSunitwithEthernetjack)bewiredtoanEthernetjackinthespaceforeaseofaccessandproximitytopowerforthewirelessrouter.

•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.•Apple iPod touch or iPhone can program all ESN QSunitsconnectedtoanESNProgrammingInterfaceviatheQSLink(exceptwhenpartofaQuantumsystem).

•ESNappisrequiredandisavailablefromtheApple iTunes Storeonlinemarketplace.

QSLink

QSM QSM QSM

ESN Unit

Apple iPod touch or iPhone mobile digital device

Wireless Router

(by others)

ESN Programming Interface

QSE-CI-AP-D

DedicatedEthernetConnection for ESN

units1,2

ESN Unit ESN Unit

QSLink

1 StandardCAT5/CAT5Ecable:Totallengthnottoexceed300ft(100m)2 Note:ESNunitsarenotdesignedtoexistonanopennetwork.

ConnectiontoanopennetworkcouldresultinreducedperformanceandEthernet connectivity issues.

Apple,iPhone,iPodtouchandiTunesStorearetrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 7: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 7 03.05.18

Programming Options and Features

Manual Programming

HHD Programming:• Requires ESN Programming Interface

QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile

digital device

ESN units connected to 1 QS Link

Not more than 1 Multiple—100 QS devices and 100 zone limits apply

QSMs connected to 1 QS link Not more than 1 Multiple—100 QS devices limit applies

Wired Occupancy SensorsSystem Limits 4 connected directly to ESN unit

Up to 4 wired to QSMUp to 100 total occupancy sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Occupancy Dependency Supported

No Yes

Wireless Occupancy SensorsSystem Limits Associate 10 occupancy sensors to QSM

to control zones on the ESN unitUp to 100 total occupancy sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Occupancy Dependency Supported

No Yes

Wired Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone

4 connect directly to the ESN unit Additional daylight sensors can connect to the QSM

Maximum of 2 daylight sensors per zone Up to 100 total daylight sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Disable daylighting in Scenes No Yes

Wireless Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone

Associate wireless daylight sensors to the QSM

Maximum of 2 daylight sensors per zone Associate up to 10 wireless daylight sensors per QSM Up to 100 total daylight sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Disable daylighting in Scenes No YesApple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 8: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 8 03.05.18

Programming Options and Features (continued)

Manual Programming

HHD Programming:• Requires ESN Programming Interface

QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile

digital device

Pico Wireless ControllersSystem Limits Associate 10 Pico wireless controllers to

QSM to control zones on the ESN unitUp to 100 total controls per QS link (wired wallstations, Pico wireless controllers, IR receivers)

Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same QS link

IR Receivers and WallstationsSystem Limits 4 connect directly to the ESN unit

Up to 4 wired to the QSMUp to 100 total controls per QS link (wired wallstations, Pico wireless controllers, IR receivers)

Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same QS link

NEC® dry contact Switches InputsCan be assigned to… Any zone(s) on the connected ESN Any zone(s) on the connected ESN

Contact Closure InputCan be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones

Functions • Sweep to off• Enable/disable afterhours• Turn on to preset and turn off

• Sweep to off• Enable/disable afterhours• Turn on to preset and turn off

Afterhours Configuration afterhours timeout – 15 minutes blink-warn timeout – 5 minutes

Afterhours timeout and blink-warn timeouts are configurable

Emergency Contact Closure InputCan be assigned to… Any zone(s) on the ESN unit Any or all local ESN zones

Emergency Light level Configurable Configurable

Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 9: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 9 03.05.18

Programming Options and Features (continued)

Manual Programming

HHD Programming:• Requires ESN Programming Interface

QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile

digital device

seeTouch QS wallstationsScene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link

Scene + off keypads assigned to…

Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link

Zone toggle keypad buttons assigned to…

Any zone(s) on the ESN unit Any zone(s) on on or more ESN units on the link

Change Keypad to Scene or Zone

Yes Yes

Changing keypads to shade, panic, fine tune

No Yes

Zone Configuration ParametersLoad type 0-10, 10-0, or switched 0-10, 10-0, or switched

High-end trim Adjustable Adjustable

Low-end trim Adjustable Adjustable

Absolute minimum level Adjustable Adjustable

ScenesAvailable scenes Scenes 1-16 Scenes 1-16

GRAFIK Eye QS N/A Share scenes, timeclock events, or afterhours events to ESN units on QS Link

QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy

QSE-CI-NWK-E Yes Yes

Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 10: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 10 03.05.18

Mechanical Dimensions

All dimensions shown as in (mm)

11.25 (285.75)

0.20(5.16)diameter

1.00 (25.40)

1.22 (30.99)

1.66 (42.16)

1.31 (33.27)

0.88 (22.35)

9.25 (234.95)

7.50 (190.50)

3.16 (80.26)

13.25 (336.55)

Donotuse side knockoutsLine Voltage Shield

Page 11: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 11 03.05.18

Wiring: QS Link

Onlyterminals1,3,and4connected betweendevicesthatsupplyPDUs

Terminal 2 NEVER connected between devices that supply PDUs

Terminal 2 (+24 V) NEVERconnected*

Devicesthat supplyPDUs

Devicesthat consumePDUs

COM+24 VMUXMUX

COM

MUXMUX

ESN QS unit

ESN QS unit

QS Input/ Output Interface

Wired QS Keypad

QSM

QSMQSMWired QS Keypad

Wired QS Keypad

Wired QS Keypad

QS Input/ Output Interface

QS Link power supply**

QSLink;all 4 terminals

QSLink;

no te

rmin

al 2

QSLink;

no te

rmin

al 2

QSLink;all 4 terminals

QSLink;all 4 terminals

Terminal 2 (+24 V) NEVERconnected*

Terminal 2 (+24 V) NEVERconnected*

All4terminalsconnectedtoQSlink devicesthatconsumePDUs

QS Link Wiring Rules * Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.** ForQSLinkpowersupplywiringconnectiondetails,refertotheinstallationinstructions

for the specific power supply model being used.

Page 12: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 12 03.05.18

Wiring: IEC PELV / NECR Class 2 Inputs

OccupancySensor

Daylight/ IRSensor*

IR Transmitter

IR Transmitter

Note: Maximum wire run length to each input not to exceed 150ft(46m).

IRReceiveror Wired

Wallstation*

IECPELV/NEC® Class 2

DryContactSwitch

Red

Black

Yello

w

Blue/Gray**

Black

Red

20 V – 20 V-

Occ–OccupancySensor

Daylight–DaylightSensor

IR–IRReceiver*Switch – IECPELV/NEC® Class 2

Com – Common

LUTRON

Input Group Wiring:•20 AWGto12 AWG (0.5 mm2to4.0 mm2)

•Striplength:1/4 in(6 mm)•Torque:5in•lb(0.5N•m)

NOTE: There are four input groups. Each group has the same inputs as shown in the diagram below.

* Note:OnlyoneIRdevicemaybeconnectedperinput.IftheIRsignalfromadaylightsensorisconnected,awallcontrolmaynotbeconnectedtothesameinput,and vice-versa.

** Connectthegraywireon-Rmodeloccupancysensors.

Group1shown Group2shown

Red

20V

Black

COM

Whi

te

IR

Page 13: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 13 03.05.18

Wiring: Contact Closure Inputs (CCI and Emerg)

Com – Common Emerg – Emergency

CCI–ContactClosureInput Com – Common

Contact Closure Wiring:•20 AWGto12 AWG (0.5 mm2to4.0 mm2)

•Striplength:1/4 in(6 mm)•Torque:5in•lb(0.5N•m)

Page 14: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 14 03.05.18

Wiring Diagram: Example A – 4 circuits, multiple feeds

Zone Switching:120–277 V~; 347 V~*

0–10 V- Zones:(QSN-4T16-S and QSN-4T16-S-347)

Switc

hed

Hot (

1B)

Hot F

eed

(1A)

Hot F

eed

(2A)

Hot F

eed

(3A)

Hot F

eed

(4A)

Switc

hed

Hot (

2B)

Switc

hed

Hot (

3B)

Switc

hed

Hot (

4B)

Ground Lug

Neutral Wires

Distribution Panel

LOAD

LOAD

LOAD

LOAD

Load Wiring:•Two(2)14 AWGto12 AWG(2.5 mm2 to4.0 mm2)

•Striplength:3/8 in(8.5 mm)

•Torque:7in-lb (0.79N•m)

0–10 V- Wiring(QSN-4T16-S and QSN-4T16-S-347)

Hot

Hot

Hot

Hot

Hot

Neutral

Neutral

Neutral

NeutralNeutral

Neutral

Ground

Hot

*For347V~ models only.

0-10 V- Wiring (QSN-4T16-S and QSN-4T16-S-347)•20 AWGto12 AWG(0.5 mm2to4.0 mm2)•Striplength:1/4 in(6 mm)•Torque:5in-lb(0.5N•m)•ConnectonlyIECPELV/NEC® Class 2 circuits or connect only non-IECPELV/NEC® Class 2 circuits to 0-10 V zones 1-4.

•0-10V- zones 1-4 are not isolated from each other.•Negative(–)terminalsarenotinternallyconnectedtoeach

other - both positive (+) and negative (–) connections must be made.

•Followallnationalandlocalcodesforseparationrequirements.

Page 15: Energi Savr Node for 0–10 V with Softswitch SPEC (369241) · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QSN 0–10 V-/Softswitch Fixture Controllers

369241l 15 03.05.18

Wiring Diagram: Example B – 4 circuits, single feed

0-10 V Wiring (QSN-4T16-S and QSN-4T16-S-347)•20 AWGto12 AWG(0.5 mm2to4.0 mm2)•Striplength:1/4 in(6 mm)•Torque:5in-lb(0.5N•m)•ConnectonlyIECPELV/NEC® Class 2 circuits or connectonlynon-IECPELV/NEC® Class 2 circuits to 0-10 V- zones 1-4.

•0-10V- zones 1-4 are not isolated from each other.•Negative(–)terminalsarenotinternallyconnected

to each other - both positive (+) and negative (–) connections must be made.

•Followallnationalandlocalcodesforseparationrequirements.

Zone Switching:120-277 V~; 347 V~*

0-10 V- Zones:(QSN-4T16-S and QSN-4T16-S-347)

HotNeutralGround

HotNeutralGround

Ground Lug

“A” Terminals Jumpered

Neutral Wires

Distribution Panel A

Distribution Panel B

LOAD

LOAD

LOAD

LOAD

Load Wiring:•Two(2)14 AWGto12 AWG(2.5 mm2 to4.0 mm2)

•Striplength:3/8 in(8.5 mm)

•Torque:7in-lb (0.79N•m)

0-10 V- Wiring(QSN-4T16-S and QSN-4T16-S-347)

Switc

hed

Hot (

1B)

Hot F

eed

(1A)

Switc

hed

Hot (

2B)

Switc

hed

Hot (

3B)

Switc

hed

Hot (

4B)

*For347V~ models only.

)Lutron,Lutron,Softswitch,seeTouch,Pico,QuantumandGRAFIKEyearetrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.

EnergiSavrNodeandRadioPowrSavraretrademarksofLutronElectronicsCo.,Inc.