Energy Efficient HVAC Design for Cold Storage. Michael Huang, LEED AP Energy Engineer UC Davis. What’s an Ultra Low Freezer?. Ultra-low temperature (ULT) freezers reach -86 o F 400,000 units nationwide, 650-1000 at UCD. Why do we care about them?. - PowerPoint PPT Presentation

TRANSCRIPT

Energy Efficient HVAC Design for Cold Storage

Michael Huang, LEED APEnergy EngineerUC Davis

What’s an Ultra Low Freezer? Ultra-low temperature (ULT) freezers reach -

86o F 400,000 units nationwide, 650-1000 at UCD

Why do we care about them?

Very low cost to store priceless samples

Samples are safer Energy is saved

If Your Freezer is Operating Efficiently...

 

Conventional Cooling Approach

heat load 1.08

Size plug load in kW, convert to kBtu/hr, convert to tons, then purchase AC unit (or CHW HX) to cool space

Q = 1.08 × m × ∆T X

Hot Aisle/Cold Aisle Arrangement

𝑄=1.08∗𝑚∗∆𝑇

UCD Primate Center

~50 ULT Freezers of various size/capacity

No economizer

Wall mounted BARD units

BARD units

Heat Gradient Across Room

Engineering Model

UCD Primate Center

Cold Aisle

Hot Aisle

Estimated Savings

Economizer annual (kWh)

No economizer

annual (kWh)Annual

savings (kWh)Annual savings

($)PG&E

IncentiveRetrofit

CostRetrofit Cost -

PG&E IncentiveSimple

ROI

76,095

180,057

103,962

$ $8,036

$ 24,951

$ 75,000

$ 50,049

6.2

Based off economizer savings & EER rating

Conclusion

Hot aisle/cold aisle containment Maintenance, maintenance,

maintenance!

𝑄=1.08∗𝑚∗∆𝑇

Thank you

Michael HuangUC [email protected]