Energy & Heat Transfer in Healthcare HVAC

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 1

Shawn Wilson, PE

TME, Inc.

[email protected]

Page 2: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Agenda

• Why target HVAC Systems?

• Shifting the Paradigm

• Controls are the Key

• 4 Opportunities

– Chilled Water Pumping

– Cooling Tower Relief

– Air Handler Controls, Resets

– Air Terminal Controls, Troubleshooting

• Closing, Q&A

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 2

Page 3: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Hospital HVAC

• Unique regulatory requirements for temperature and RH, airflow, and pressure relationships.

• Special applications (Surgery, Lab, Pharmacy, Sterile Processing etc…)

• Energy intensive facilities.

• Complex Systems, Complex Controls

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 3

Page 4: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Hospital Operating Costs

60% 20%

10% 3% 7%

People

Supplies

Debt Service

Energy

Other

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 4

Page 5: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Hospital Business Environment

• Higher Costs

• Lower Revenues

• Insufficient Margins for Reinvestment

• Mounting Backlog of Deferred Maintenance

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 5

Page 6: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Hospital Energy Costs

Average $4.09/SF

Page 7: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Hospital Operating and Maintenance Budgeting

27%

8%

14%

51%

Materials

Service Contracts

Staffing

Energy

Typical Hospital Operating and

Maintenance Budget ($7 to $12 per SF)

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 7

Page 8: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

• Reduced Operating Budgets

• Staffing Levels are already too Low

27%

8%

14%

51%

Materials

Service Contracts

Staffing

Energy

Hospital Operating and Maintenance Budgeting

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 8

Page 9: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

• Reduced Operating Budgets

• Staffing Levels are already too Low

• Higher Material Costs 27%

8%

14%

51%

Materials

Service Contracts

Staffing

Energy

Hospital Operating and Maintenance Budgeting

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 9

Page 10: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

• Reduced Operating Budgets

• Staffing Levels are already too Low

• Higher Material Costs

• Higher Service Contract Costs

27%

8%

14%

51%

Materials

Service Contracts

Staffing

Energy

Hospital Operating and Maintenance Budgeting

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 10

Page 11: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

• Reduced Operating Budgets

• Staffing Levels are already too Low

• Higher Material Costs

• Higher Service Contract Costs

• Energy Costs must be Reduced

27%

8%

14%

51%

Materials

Service Contracts

Staffing

Energy

Hospital Operating and Maintenance Budgeting

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 11

Page 12: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Energy Use In Hospitals

HAAHE/TAFHM Facility Manager Basic Training 12 12/5/2013

Page 13: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Agenda

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 13

• Why target HVAC Systems?

• Shifting the Paradigm

• Controls are the Key

• 4 Opportunities

– Chilled Water Pumping

– Cooling Tower Relief

– Air Handler Controls, Resets

– Air Terminal Controls, Troubleshooting

• Closing, Q&A

Page 14: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Current Paradigm

• Selecting Systems and Equipment based on First Cost

• Using the Same Design for Every Project

• Conservative Over-Sizing of Equipment

• Selecting Systems and Equipment without Considering Current and Future Utility Rates

• Control Systems Designed by Control System Manufacturers (not the Engineer)

• Commissioning included but often becomes construction phase QC and documentation exercise.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 14

Page 15: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Current Best Practices Don’t Always Yield High Performance

• LEED

• Efficient Design

• Standard Commissioning

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 15

Page 16: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

LEED Certification

• LEED Buildings are no more Energy Efficient than their Peers

• More than half of LEED Buildings not eligible for Energy Star Label

• 15% of LEED Buildings have an Energy Star Rating less than 30

• LEED is not Bad…

Some Buildings not Living up to Green Label

By Mirya Navarro August 30, 2009

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 16

Page 17: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Standard Commissioning

• LEED Certified Facilities have been Commissioned

• Many low Performing Hospitals were Commissioned

• Standard Commissioning is not bad…

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 17

Page 18: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Potential Causes of Low Performance

• Energy Efficient Features are frequently “Value Engineered” out of the Project

• Systems are too complex for O&M Staff to Operate and Maintain

• “Drive By” Commissioning does Occur

• Facility Performance is not Measured and Verified

• Commissioning Agent Design Reviews are restricted to “Commissionability” Only

• O&M Staff have traditionally focused on Regulatory Compliance, Infection Rates, Comfort, and not Energy Efficiency

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 18

Page 19: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Potential Causes of Low

Performance

• Control System Programming is not Consistent with the Design Intent

• Energy Management Systems are under Utilized

• Air Terminal Air Flow Setpoints are not Programmed in Correctly

• O&M Staff Training by Contractors does not Focus on Energy Conservation

• CxA is not Responsible for Building Performance

• O&M Staff are not Vested in a Positive Outcome

• Excess Simultaneous Heating and Cooling

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 19

Page 20: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Shifting the Paradigm

Albert Einstein’s Definition of Insanity:

“Doing the same thing over and over again and expecting different results.”

12/5/201

3

HAAHE/TAFHM Facility Manager Basic Training 20

Page 21: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

ASHE’s Commissioning Guidelines and Handbook

• Meeting the Energy Efficiency Goals is not Optional

• Current Best Practices don’t always Work

• Causes of Low Performance are Known

• ASHE’s Commissioning Guidelines and Handbook focus on Meeting Facility and Project Energy Efficiency Goals

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 21

Page 22: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

New Paradigm

• Construction Costs and Operating Costs must be Considered Holistically

• Minimize Reheat

• Create Synergy between Systems that Remove and Generate BTUs

• Pay Attention to the Control Programming

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 22

Page 23: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Setting the Energy Efficiency Goal

“If you aim at nothing, you’ll hit it every time.”

Zig Ziglar

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 23

Page 24: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Benchmarking

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 24

• EPA “Target Finder”

• Weather Adjusted

• Occupancy Adjusted

• Free Service

• Internet Based

• Simplified Input

• Percentile Ranking

Page 25: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Measurement and Verification

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 25

• Measuring on routine basis is critical.

• Review regularly.

Page 26: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Agenda

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 26

• Why target HVAC Systems?

• Shifting the Paradigm

• Controls are the Key

• 4 Opportunities

– Chilled Water Pumping

– Cooling Tower Relief

– Air Handler Controls, Resets

– Air Terminal Controls, Troubleshooting

• Closing, Q&A

Page 27: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Designing the Control System

• Consider Design Conditions and Off-Design Conditions

• Design should Include Diagram, Sequence of Operation, Point List, Valve Schedule, and Damper Schedule

• Design should be Detailed, but not Manufacturer Specific

• Control System Design, Sequence, and Programming have more Impact on Hospital Energy Efficiency than System and Equipment Selections

27 HAAHE/TAFHM Facility Manager Basic Training 12/5/2013

Page 28: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Developing the Sequence of Operation

• Goal is Optimum Performance

• Include Fail-Safe Provisions

• Identify Inputs, Loop Statements, Table Statements, Logical Operators, Setpoints, Local Variables, and Outputs

• Consider Using a Flow Chart to Convey Design Intent

• Must be Very Detailed to Prevent Misunderstandings

• Lack of a Detailed Sequence is the Reason why most Buildings Fail to Achieve their Energy Efficiency Goals

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 28

Page 29: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Developing the Sequence of Operation

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 29

AHU Supply Air Temperature Reset

Control Loops

Cooling Loopout /Chilled Water Control Valve is equal to the

output of the following PI loop:

Action – Direct

Input – Supply Air Temperature

Setpoint – Cooling Setpoint

Minimum Output – 0

Maximum Output – 100

Supply Air Temperature: The supply air temperature setpoint

(“cold deck temperature”) is increased and decreased from the

minimum to the maximum and vice versa according to the

following logic:

Input – Request for more cooling from Air Terminals

Output – Supply Air Temperature Setpoint. Equal

to the lower of comparison of Calculated Supply Air

Temperature Setpoint (reset based on polling

zones described in this section) and

Dehumidification Override Supply Air Temperature

Setpoint (section 9.c).

Minimum SAT Setpoint (60F)

Maximum SAT Setpoint (65F)

Sampling Rate/Rate of Change: 1F/5 mins

Page 30: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Agenda

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 30

• Why target HVAC Systems?

• Shifting the Paradigm

• Controls are the Key

• 4 Opportunities

– Chilled Water Pumping

– Cooling Tower Relief

– Air Handler Controls, Resets

– Air Terminal Controls, Troubleshooting

• Closing, Q&A

Page 31: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Chilled Water System Issues

• Improper Chiller, Cooling Tower, and/or Pump Sequencing

• Differential Pressure Setpoint Reset Overridden

• Condenser Water Supply Temperature Reset Overridden (or not programmed).

• Low Chilled Water Temperature Difference (Low Delta T)

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 31

Page 32: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

CV Primary/ Variable Flow Secondary

Chilled Water System

• First developed by B&G in 1954.

• 2 Hydraulically Independent loops via Decoupler bypass pipe (“neutral bridge”).

• Primary pumps interlocked with each Chiller to provide design (constant) gpm.

• Secondary pumps are modulated to meet system DP requirement.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 32

Page 33: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

CV Primary/ Variable Flow Secondary Chilled Water System

• Perfect world – Primary Loop GPM = Secondary Loop GPM.

• No flow in Decoupler pipe.

• In the real world this is seldom the case.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 33

Page 34: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

CV Primary/ Variable Flow Secondary Chilled Water System

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 34

Page 35: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

CV Primary/ Variable Flow Secondary Chilled Water System

KEY PERFORMANCE INDICATORS

• Secondary Loop Delta T.

– Low Delta T indicates excessive pumping.

– Chillers, AHU Coils are more efficient at higher delta T.

• System Operating DP.

– High system differential pressure can mask other problems.

– Higher DP = higher pumping horsepower.

– High DP’s can adversely affect control valve/coil performance.

T500Btu/h GPM

For a given load, Flow and ΔT are inversely proportional.

As GPM increases, ΔT drops.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 35

Page 36: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

CV Primary/ Variable Flow Secondary Chilled Water System

Control Sequence

• Reset DP setpoint based on actual AHU demand (chilled water valve positions).

• Stage chillers based on tonnage but watch the temperature of water in decoupler and secondary loop Delta T for fault detection.

• Add secondary loop Delta T to dashboard.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 36

Page 37: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Variable Primary Chilled Water

• Variable Flow through Chillers

• Only 1 Set of Pumps

• Pumps Sequenced to Maintain Delta P and Minimum Flow

• Bypass Valve Modulates to Maintain Minimum Flow

• Requires Electronic Flow Safeties

• Lower Capital Cost, Energy Cost, and Maintenance Cost

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 37

Page 38: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Agenda

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 38

• Why target HVAC Systems?

• Shifting the Paradigm

• Controls are the Key

• 4 Opportunities

– Chilled Water Pumping

– Cooling Tower Relief

– Air Handler Controls, Resets

– Air Terminal Controls, Troubleshooting

• Closing, Q&A

Page 39: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Condenser Water Relief

• Still many plants control tower water to single setpoint (80F aquastat)

• Chiller Efficiency improves with colder condenser water.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 39

Page 40: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Lots of hours of operation – even in South Texas…

Page 41: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

It’s all about LIFT

• Condensing temperature minus the suction temperature

• Two ways to decrease Lift by adjusting DDC:

– Lower Condenser Water Temperature

– Raise Chilled Water Supply Temperature

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 41

Page 42: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Condenser Water Relief Implementation for Constant Volume Pumping

• Tower fan energy versus lower chiller kW

• Reset loop setpoint based on wet bulb and run the condenser loop as cold as possible

– 2 tower cells paired with 1 Chiller

• Be aware of lower limit.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 42

Page 43: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Variable Volume Condenser Water

System

• Valves Modulate to Maintain Proper Flow

• Flow at Design with Minimum Refrigerant Lift Override

• Chillers can Operate with Very Cold Condenser Water (eliminates transition issues with hydronic free cooling)

• Any Chiller with any Tower with any Pump

• Pumps Sequenced in a Best Efficiency Manner

• Towers Sequenced in Best Efficiency Manner

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 43

Page 44: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

3.0 GPM per Ton Condenser Water Flow Rate

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 44

Page 45: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Agenda

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 45

• Why target HVAC Systems?

• Shifting the Paradigm

• Controls are the Key

• 4 Opportunities

– Chilled Water Pumping

– Cooling Tower Relief

– Air Handler Controls, Resets

– Air Terminal Controls, Troubleshooting

• Closing, Q&A

Page 46: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Air Handling Unit Issues

• Static Pressure Setpoint Reset Overridden

• Malfunctioning Control Valves

• Supply Air Temperature Setpoint Reset Overridden

• Failed Air Flow Measuring Stations

• Malfunctioning Dampers

• Weekly Schedules Overridden

• Simultaneous Heating and Cooling

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 46

Page 47: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Multiple Loop Temperature Control

Loop 1

Loop 2 Loop 3

Loop 4

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 47

Page 48: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Multiple Loops

2022 Loop (0, Input, Output, Setpoint, P, I, D, Min, Max, Bias)

• 4 Setpoints

• 4 Sets of Proportional and Integral Gains

• Setpoints may Inadvertently Overlap

• Tuning is very Difficult

• Outputs will Overlap due to Hunting

• Simultaneous Heating and Cooling

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 48

Page 49: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Multiple Loops

Time

Mixed Air Preheat CHW Coils

Mixed Air Temperature

Mixed Air Setpoint

Output Preheat

Temperature Preheat Setpoint

Output Coil Leaving

Air Temperature

Supply Air Temperature

Supply Air

Setpoint Output

3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24

3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27

3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26

3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30

3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23

3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23

3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28

3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33

3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21

3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 49

Page 50: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Overlapping Setpoints

Time

Mixed Air Preheat CHW Coils

Mixed Air Temperature

Mixed Air Setpoint

Output Preheat

Temperature Preheat Setpoint

Output Coil Leaving

Air Temperature

Supply Air Temperature

Supply Air

Setpoint Output

3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24

3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27

3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26

3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30

3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23

3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23

3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28

3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33

3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21

3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20

50 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 50

Page 51: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Simultaneous Heating and Cooling

Time

Mixed Air Preheat CHW Coils

Mixed Air Temperature

Mixed Air Setpoint

Output Preheat

Temperature Preheat Setpoint

Output Coil Leaving

Air Temperature

Supply Air Temperature

Supply Air

Setpoint Output

3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24

3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27

3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26

3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30

3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23

3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23

3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28

3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33

3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21

3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 51

Page 52: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

What is the Problem?

Time

Mixed Air Preheat CHW Coils

Mixed Air Temperature

Mixed Air Setpoint

Output Preheat

Temperature Preheat Setpoint

Output Coil Leaving

Air Temperature

Supply Air Temperature

Supply Air

Setpoint Output

3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24

3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27

3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26

3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30

3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23

3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23

3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28

3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33

3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21

3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 52

Page 53: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Single Loop Temperature Control

0

20

40

60

80

100

0 20 40 60 80 100

Ta

ble

Sta

tem

en

t

Ou

tpu

t

Supply Air Temperature Control Statement Output

Preheat Valve

First Stage Economizer Cycle(Maximum OSA Damper)

Second Stage EconomizerCycle (Return Air and ReliefAir Dampers)

Secondary Chilled Water Valve

Primary Chilled Water Valve

Stage 1

Stage 4

Stage 3

Stage 2

Stage 5

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 53

Page 54: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Single Loop Humidity Control

0

20

40

60

80

100

0 20 40 60 80 100

Ta

ble

Sta

tem

en

t O

utp

ut

Return Air Humidity Control Statement Output

Disable Second Stage ofEconomizer Cycle (OpensReturn and Closes ReliefDampers)

Disable First Stage ofEconomizer Cycle (ClosesMaximum OSA Damper)

Humidifier Steam Valve

Stage 3 Stage 2 Stage 1

12/5/2013 ©2012 American Society for Healthcare Engineering of the American Hospital

Association 54

Page 55: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Adaptive Resets

• Reset Supply Air Temperature (“Cold Deck Reset”).

• Reset Duct Static Pressure Setpoint

• ASHRAE 90.1, Energy Code

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 55

Page 56: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Dedicated Outside Air AHU

• Pre-treat ventilation air. Ducted to outside air damper on individual AHUs.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 56

Page 57: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Air-Side Economizer Cycles

• Air-Side Economizer Cycles often incorrectly programmed/configured and difficult to maintain.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 57

Page 58: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Economizer Damper Control Loop not Tuned

0

10

20

30

40

50

60

70

80

90

3:0

0

3:0

5

3:1

0

3:1

5

3:2

0

3:2

5

3:3

0

3:3

5

3:4

0

3:4

5

EconomizerDamper Output

Mixed Air Setpoint

Mixed AirTemperature

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 58

Page 59: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Air-Side Economizer Cycles on AHU’s with Humidifiers

• ASHRAE Standard 90.1 Requires Hydronic Free Cooling if Humidification Dewpoint is > 35 deg. F (30% RH at 68 deg. F)

• Cooling Savings are more than Offset by Higher Humidification Costs

• Air-Side Economizer Cycles are Costly to Implement and Difficult to Maintain

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 59

Page 60: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Operating Room Challenges

• Surgeons/staff want 60F/50% rh

• Difficult if not impossible to achieve with typical chilled water system

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 60

Page 61: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Operating Room Challenges

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 61

Page 62: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Operating Room Challenges

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 62

• Desiccant Technology provides lower dewpoints.

• Dedicated OSA AHU with Type III passive dessicant wheel shown.

Page 63: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Operating Room Challenges

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 63

Air change rates, pressure differentials difficult to optimize – often are not reset based on occupancy.

Page 64: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Unoccupied/Occupied Reset for Operating Rooms

• Occupied – 15 to 25 ACH

• Unoccupied – 5 to 8 ACH

• DP – 0.01” w.g.

Page 65: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Agenda

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 65

• Why target HVAC Systems?

• Shifting the Paradigm

• Controls are the Key

• 4 Opportunities

– Chilled Water Pumping

– Cooling Tower Relief

– Air Handler Controls, Resets

– Air Terminal Controls, Troubleshooting

• Closing, Q&A

Page 66: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Air Terminal Issues

• Failed Averaging Velocity Sensors

• Malfunctioning Terminal Dampers

• Malfunctioning Heating Water Control Valves

• Insufficient Air Flow to Accommodate Space Sensible Cooling Load

• Incorrect Air Flow Setpoints

• Deadband too Small

• Thermostat Range not Restricted

• Weekly Schedules Overridden

• Occupancy Sensors Overridden

• Failed Points

• Simultaneous Heating and Cooling

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 66

Page 67: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

VAV Air Terminal with Heating

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 67

Page 68: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

VAV Air Terminal with Heating – Minimizing Reheat

Best Practice: Modulate HW Valve to a Discharge Setpoint and Reset the Setpoint from Minimum up to Maximum before Increasing Air Flow.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 68

Page 69: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

VAV Air Terminal Troubleshooting

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 69

• Failed Averaging Velocity Sensors

• Malfunctioning Terminal Dampers

• Malfunctioning Heating Water Control Valves

• Insufficient Air Flow to Accommodate Space Sensible Cooling Load

• Don’t apply a system wide correction to a zone level problem.

Page 70: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Closing Thoughts • You can’t manage what you

don’t measure.

• The code is the key. Get it right and good things happen.

• Don’t use a sledge hammer to drive a finish nail.

12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 70

Page 71: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting

Thank You! Questions?