energy management systems control panel construction ... · pdf fileenergy management systems...

37
Energy management systems control panel construction Standard control specification Users guide to Allen Martin heating controls Resources directorate

Upload: duonghanh

Post on 06-Feb-2018

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management

systems control panel

construction

Standard control specification

Users guide to Allen Martin heating

controls

Resources directorate

Page 2: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

2

Issue/

Revision No

Date Originator Purpose for Issue/

Nature of Change

0 05/0//05 R C Smith First issue

A 07/08/07 T N Thomas Regular Updates

B 14/06/10 T N THOMAS Regular Updates

Page 3: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

3

GENERAL DETAILS

Preamble

It is intended that this specification shall be read in conjunction with the Standard Technical Specification (ELECTRICAL INSTALLATION SERVICES)

and the Standard Technical Specification (MECHANICAL INSTALLATION SERVICES).

Certain sections of this specification may not relate to the drawings

supplied and accordingly should be disregarded.

Regulations

The installation shall be designed, installed, tested and commissioned in accordance with:

� The Health and Safety at Work Act together with all relevant

approved Codes of Practice and Memorandum of Guidance

� The most recent issue of BS 7671 together with all relevant

approved Codes of Practice and Guidance Notes

� The latest requirements of the Building Regulations

� The Electricity at Work Regulations together with all relevant

approved Codes of Practice and Memorandum of Guidance

� The Electricity Safety, Quality and Continuity Regulations

� Construction (Design and Management) Regulations

� Control of Substances Hazardous to Health – COSHH

� The Control of Asbestos Regulations 2006 including future

amendments and editions

The above shall not be seen as definite list of relevant standards and

regulations and, unless stated otherwise, the whole of the works shall comply with the requirements of all relevant British Standards and

European Harmonised standards and documents pertinent to the works. Relevant standards and regulations shall be those that are in force three

months prior to the return of tender or commencement of work unless stated otherwise in the particular specification documents.

Definitions

For the purpose of this document, terms and definitions shall be as those of the most recent edition of BS 7671 Part 2.

Page 4: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

4

British Standards

Where a British Standard or Code of Practice issued by the British Standards Institute is current at the date of tender and appropriate to the

case, the contract shall require that goods, materials and works shall be in conformity.

General Operating Conditions

This specification is written as general guidance to the methods of panel manufacture.

It is not intended as a definitive method, as all systems are slightly different and will have different control methods.

The requirements and standards for equipment and wiring within the control panel will however apply for all projects.

The electrical equipment shall be such that its installation, operation and

maintenance shall comply with the above legislation and any subsequent relevant legislation.

CONTROL PANEL

Construction

As far as practicable, all controls, indicator lamps and instruments shall be grouped and mounted together in a floor or wall-mounted panel.

The control panel shall be constructed within a suitably sized powder coated steel enclosure, with a cream/grey finish (Bowthorpe Hellerman –

Himel type or equivalent). The enclosure shall incorporate removable gland plates at both top and bottom.

The control panel shall be constructed to give a protection rating of not less than IP55 and shall be so constructed as to prevent the ready ingress

of dust. The joints of plates and doors shall be suitably packed, using neoprene or equal (not rubber).

Mechanical ventilation shall be provided where it is likely that the operating temperature within the panel will be greater than those limits

set by the equipment manufacturer. That ventilation system shall maintain the panel temperature to within the manufacturers limits regardless of the panel environment.

Panels shall be supplied with hinged and lockable access doors at the front

of the panel. Two keys shall be provided which shall be common to all locks on all panels.

Page 5: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

5

All equipment within the enclosure shall be mounted on a removable back plate such that if required, the complete system can be removed from the

enclosure to aid installation.

Access doors or covers shall be so arranged that access cannot be made until an isolating device, interlocking with each door or cover, is opened and all equipment accessible through that door or cover is isolated. A

purpose made device or suitable isolator shall be provided to enable a competent engineer to override the interlock when the door has been

opened. Panels secured to the floor shall be provided with metal plinths of a

suitable size and strength i.e. ‘Unistrut’ or equivalent. This plinth must be earthed in accordance with BS7671 and BS 7430. Where mounting is on

raised builders work bases, metal plinths are not required, but in all cases fixing holes and detachable lifting eyes shall be provided.

Control panels shall, as far as is practicable, be manufactured, equipped, wired and tested before delivery to site.

Indicating lamps, instruments and controls shall be, as far, as is

practicable, from the same manufacturer and of the same style to provide uniformity of appearance and to facilitate maintenance. Externally visible equipment shall be flush mounted, with minimum projection and fixed

securely to the front panel.

Internal equipment shall be secured to the back plate using a suitable DIN type rail. Fixings shall incorporate shake-proof washers or other vibration resistant fastenings.

The control panel shall be designed and built by an approved control

specialist and shall comply in general with the details given by the Energy Management Unit and the project documentation supplied.

The control specialist shall supply working drawings and fully numbered interconnection diagrams to enable an electrical contractor to make all

connections between the control panel, plant and sensors.

This shall be deemed to include all valves, pumps, sensors, remote relays and all other forms of ancillary equipment associated with the controls package.

The electrical contractor shall be responsible for all connections external

to the control panel and for this reason, the panel shall be constructed such that all connections for both low voltage mains wiring and extra low voltage control, monitoring and data and monitoring wiring are made to a

single DIN rail terminal strip located at the top or alternatively the bottom of the enclosure.

The DIN rail terminal strip shall be arranged such that low voltage mains wiring and extra low voltage control, monitoring and data connections are

Page 6: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

6

segregated and suitably labelled. Mains voltage and low voltage cables must be segregated by a fixed barrier in accordance with IEE Regulations.

All terminals shall be numbered using appropriate slip on numbers, in

accordance with the panel wiring diagram. Note - the Users Guide to Wiring Allen-Martin Heating Controls

contains drawings for connections to all common equipment.

A label shall be fitted inside each control panel, adjacent to the main isolator indicating:

� Supply voltage � Control voltage

� Current rating � Date of manufacture

After installation the electrical contractor shall ensure that all swarf, dust and cable debris is removed from the panel.

Particular care shall be exercised when working around the energy control

system. The electrical contractor shall be responsible for and damage resulting

from this cleaning.

Control equipment The building management control equipment shall be from the Allen-Martin range of controllers unless specified otherwise by Cornwall Council.

The BMS controller shall be contained within the control panel. It shall be fed from a 5A rated un-switched spur taken from the live side of the

incoming isolator such that the supply to the controller is not isolated when the panel supply is switched off.

A durable yellow notice with black text to this affect shall be located adjacent to the isolator. This label shall be engraved traffolyte type and

affixed with mechanical fixings, not adhesive.

A single data socket shall be located within the panel for connection to the building intranet system.

A single socket outlet shall be fitted within the panel for the connection of a power supply for dialup modem communications when used.

A space shall be set aside for the subsequent mounting of a suitable power supply and modem unit. Both shall be fixed via proprietary

mechanical fixings.

Page 7: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

7

No interface whatsoever shall be made with the BMS module. All connections shall be via the incoming terminal strip.

All wiring within the control panel shall be identified at each end with a

number unique to that cable. Numbers shall only change due to a control device.

All wiring within the control panel shall be terminated using ferrule type crimp lugs constructed in accordance with the manufacturer’s instructions.

All panel wiring shall be single core, flexible plain annealed copper conductor, heat resistant PVC insulation. Panel wire to BS6231 type CK

and UL/CSA approved. 600/1000 volts grade.

Wiring within the control panel shall be contained within slotted trunking with close fitting lids. Trunking shall be Critchley betaduct or approved equivalent.

Internal wiring shall be colour coded to BS7671 for LV cables

ELV cables shall be coloured as follows:

24V a.c. White 24v (0V) Black 15V + ve Orange

15V –ve Grey Analogue input Purple

Analogue output Brown with marker Digital output Brown Digital input Pink

MCB’s shall be used in preference to BS88 fuses and these shall be type C

M9 to BS 60898 for all motor circuits. They shall be selected from the Merlin Gerin Multi 9 range.

All protective devices shall be so sized and co-ordinated that they provide shock and overload protection to BS7671.

Contactors shall be DIN rail mounted and from the Telemechanique range. Overload protection is required for all circuits. The full load current of all

circuits shall be recorded on the as fitted drawings and established to provide the correct setting of the overcurrent element.

Relays shall be DIN rail mounted and from the Omron/Shrack plug in range.

Panel indicator lights shall be from the Telemechanique high output LED

range. All indicator lamps shall be coloured for their mode according to BS EN 60073:1993, IEC 60073:1991.

Page 8: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

8

Running Green Tripped Red

Healthy White Fault Red

Warning Orange/Amber Abnormal Blue

Switches shall be from the Telemechanique range such that they match the selected indicators.

Volt Free Contacts (v.f.c.) shall be provided for all items of plant to enable alarm/status signal to be sent to the BMS.

The control panel shall be fitted with a key operated (tumbler type)

maintenance override switch. The switch shall be fitted on the front of the panel. Operating the switch shall run all plant and open all 240V operated valves and solenoids.

It shall not be possible to open to open any other valves by using the

plant maintenance override switch.

A red indicator lamp shall be fitted adjacent to the override switch and shall be illuminated when the switch is operated.

The switch shall be labelled “Plant maintenance override ON/OFF” The indicator shall be labelled “Override ON”.

Pressure switches

Two pressure switches shall be fitted on the cold feed to the system, these shall be the high and low limit switches. The set points shall be agreed

with a representative of Cornwall Council/Principal Mechanical Services Engineer at the commissioning stage.

Activation of either of these pressure switches shall cause the plant to be shut down immediately and display a “Pressure Fault” on the main control

panel. The control specialist shall also allow for the provision of “Closed when Healthy” signal to open under these fault conditions and initiate a fault alarm on the BMS. The fault condition will latch and will require local

or remote manual resetting.

Commissioning The contractor is to allow for the programming of all testing and

commissioning works to suit the programme of works.

This is to include inspecting, testing and commissioning of all works by any sub contractors and specialist contractors works arranged by the contractor.

Page 9: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

9

Commissioning shall mean the advancement of the systems from static completion to working order, to the specification, and relevant works to

achieve compliance with Part L of the building regulations and functionality to the complete satisfaction of Cornwall Council’s approved

representative/s. All shall be conducted without prejudice to the need to comply with all

Health and Safety requirements.

Commissioning works shall include, but not be limited to, the following: • Demonstrate the correct operation of all items of equipment

necessary to provide a working building energy control system • Demonstrate the correct operation of all alarm systems and provide

instruction to appointed site personnel involved in daily use and maintenance of the system

• Demonstrate the correct operation of all specialist plant and

equipment supplied and installed as part of the contract/works • Demonstrate the correct procedures for fault finding and reporting

in the event of mechanical or electrical faults within the installed works

The specialist contractor shall appoint an engineer to commission the complete system. The whole or part of the process shall be witnessed by

a representative of Cornwall Council/Principal Mechanical Services Engineer. The data link shall not be accessed until that representative is

present. Failure to comply could result in damage to either the new or existing

equipment.

The processor shall not be energised. As fitted control drawings shall be supplied immediately upon completion

of the project.

Page 10: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

10

HEATING/HWS CONTROLS

GENERAL TECHNICAL

SPECIFICATION

Page 11: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

11

General Technical Specification

Heating/HWS Controls

Preface

This technical specification is written as general guidance to the methods of control and the required standards for new and retrofit heating/hws

control systems. It shall be read in conjunction with the STANDARD CONTROL SPECIFICATION.

It is not intended as a definitive method statement, as all systems are slightly different and will have different control requirements. It should

therefore be read in conjunction with the relevant project documentation.

The requirements and standards for equipment and wiring within the control panels will however apply for all projects.

Heating System Operation (General)

The Allen Martin Series of Controllers are fully microprocessor controlled Building Management Systems which can be used to control heating and

ventilation plant. The controllers have a self learn facility which will determine the optimum warm up time of the building from the inside and

outside sensors fitted in various locations within the building. The controller will start the pump(s), fire the boiler(s), open the valve to

each zone (where applicable) and energise the supply to heat emitters (e.g. fan convectors - where applicable) to heat each zone as required.

When each heating zone is up to temperature, the controller may close or modulate the valve to that particular zone.

In the case of mixed flow (variable temperature) circuits with modulating

valves, the pumps shall continue to run to provide circulation. For constant temperature circuits fitted with 2 port isolating valves, the

pumps shall be stopped as soon as the valve closes by the use of an auxiliary switch within the valve actuator.

When all heating zones are up to temperature and switched off by the controller, the boiler shall be shut down.

Primary loop pumps (where applicable) or selected zone heating pumps

(dependant upon the type of installation) shall continue to run on for a predetermined time to dissipate excess heat within the boiler.

In general, the boiler and loop pumps (where applicable) shall be interlocked such that if the loop pump trips, the boiler will be shut down.

Page 12: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

12

If a pressurisation unit is fitted to the system, high and low pressure switches shall be fitted to the cold feed line. Operation of either switch

will indicate an abnormal system pressure condition and shall cause all plant to be shut down. This may be achieved by wiring the main control

circuit through the pressure switch system. Pressure fault indication shall be made available to the BMS in the form of

a volt free normally closed contact.

Compensation/optimisation of the system shall be achieved by the use of immersion type flow and return sensors within the system pipe work.

The type and number of such sensors will be dependant upon the requirements and degree of control required for each project.

Control of air handling plant shall be achieved in the same way except that the sensors shall be of a type suitable for installation within ducts.

The control panel shall be fitted with a plant over ride timer. This will

operate the plant so that the engineer can test pumps etc. This timer should be of a run back type so that the plant can not be left on.

Control Panel/Outstation

The control panel/outstation shall be designed and built by a control specialist and shall comply in general with the details given on the one

line schematic drawing provided with the project documentation and within this specification.

The control specialist shall issue working drawings and fully numbered interconnection diagrams to enable an electrical contractor to make all

interconnections between the control panel, plant and sensors.

This shall be deemed to include all valves, pumps, sensors, remote relays and all other items of ancillary equipment associated with the controls package.

All terminals shall be numbered in accordance with the panel wiring

diagram. No plant or sensors shall be directly connected to the mother board or

modules thus bypassing the main terminal strip.

All wiring within the control panel/outstation shall be easily identifiable by the use of wire and terminal numbers. All cables shall be marked at both

ends within the panel. All cables to be tri rated to BS 6231. Outgoing wiring from the terminal strip shall be fitted with terminal

numbers at the panel and remote ends such that they can be easily identified during testing and commissioning.

Page 13: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

13

Wiring within the control panel to be contained within suitable trunking with access slots (e.g. Critchley Betaduct).

Volt free contacts shall be provided for all items of plant to enable

alarm/status signals to be sent to the BMS. E.g. each zone pump will have volt free contacts for both running and

tripped states.

Alarms and trips shall be closed contacts that open on trip, running contacts will open when running.

Panel Installation

The electrical contractor shall be responsible for the fixing and connection of the control panel and shall ensure that the control system is protected

during installation.

The electrical contractor shall remove all gland plates and panel entries for drilling and slotting for cable entries. He shall not drill gland plates with the control equipment in place unless suitable precautions have been

taken to prevent the ingress of swarf and filings into the contactors/relays etc.

The contractor shall ensure that the trunking/conduit connection to the panel is of sufficient width such that only the removable gland plate needs

to be perforated.

Any stray swarf or filings found within the panel after installation shall be cleaned out with a vacuum cleaner.

Any damage to equipment within the panel which can be attributed to the ingress or swarf and filings shall be rectified at

the expense of the installer.

Pump Control

Zone heating and HWS pumps within the boiler house area shall be controlled by the BMS via the control panel.

Remote pumps shall be controlled from the BMS by the use of extra low voltage relays in the remote location, which will switch the

pump/associated equipment. Supplies to remote equipment shall be derived from a local distribution board and suitably labelled.

If 2 port valves are used (where applicable), pumps shall be prevented from running until the two port valves are full open by the use of valve

end switches. Under no circumstances should a pump be made to operate against a closed valve.

Page 14: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

14

Under normal operating conditions, the BMS will control the valve and the pump will only start when the end of travel switch within the valve

actuator operates as the valve approaches the full open position.

The controls specialist shall be made aware if there are valve end switches and their required function.

The end switches are usually supplied as a separate item and will require fitting into the valve actuator at installation and adjusting to the required

end of travel tolerance. End switches shall not be used for direct control of signals or supply. End

switches shall operate slave relays in the control panel only.

Switches shall be provided on the control panel for each pump. These switches shall be Off/Auto only. No hand override shall be provided.

Twin head pumps shall be controlled on an either/or basis and no automatic changeover shall be allowed.

All pumps shall be fitted with appropriately sized overload relays wired

into the contactor control circuit or a suitable alternative.

Remote Relays

Remote relays used to drive equipment not located within the boiler house

shall in general be an extra low voltage type capable of being driven directly by the digital output from the BMS or through a relay located

within the control panel. If the output from the BMS is of insufficient capacity to drive the number

of relays required, a suitable transformer shall be fitted within the control panel to provide an extra low voltage supply for these relays.

The remote relays must be wired such that they are energised to switch off the plant they control. For this reason, if they are controlled by a LV

transformer and relay within the panel, the control specialist shall ensure that the system is capable of providing the required output.

This is required so that in the event of a control system failure, all plant will run.

For connection of remote relay, see enclosed drawing.

Boiler house wiring

Wiring within boiler houses and/or plant rooms shall be in PVC single core

tri rated cable contained within galvanised steel conduit and trunking. Final connection to sensors shall be made in flexible conduit with the cable drawn through.

Page 15: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

15

Two compartment trunking shall be installed within the boiler house where required to carry extra low voltage and data and low voltage mains wiring.

It is not acceptable to run data cables and mains cables in the same

conduit or trunking unless a metallic barrier is fitted (ref section 528 of British Standard BS 7671). In all instances of cable routing the manufacturers recommendations shall be adhered to.

Data cable will be terminated in a suitable galvanised box. The box will

have a numbered din rail mounted terminal strip. The cable will be numbered at both ends and the box lid will have a label stating DATA.

Sensor and Control Wiring

The zone sensors shall be wired in the type of cable as specified by the appropriate control drawing but generally to BS5308.

This cable shall physically isolated in the data isolation box for remote

sensors and in by the compartment trunking in the boiler room. Immersion sensors and outside sensors shall be wired in data cable to CT

units (where applicable) and then to BMS via the terminal strip in the control panel.

Connection from the CT unit (where applicable) to immersion and duct sensors shall be in “Kopex” or equal and approved with the data cable

drawn through.

Connections to pressure switches etc shall be made as detailed for sensors.

Where room sensors are fitted to back boxes or other outlets, the end of the conduit or back plate of the sensor shall be sealed with a suitable non

setting compound to prevent the ingress of air and draughts from areas external to the controlled space.

Sensors and thermostats shall be mounted at 1650mm above finished floor level. Spur for the thermostat shall be mounted at 150mm below

finished ceiling level.

In rooms containing both thermostats and room sensors, the units shall be mounted adjacent to each other in the same location within the space.

Isolation

All boilers shall be fed via a multipole isolator mounted adjacent to the

equipment for mechanical maintenance purposes. This shall be capable of interrupting all live conductors of the supply to each boiler/boiler module.

(Note as BS7671 the neutral is viewed as a live conductor).

Page 16: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

16

Pumps shall be fed from the control panel via 16A European standard IEC plug and sockets (e.g. Mk Commando range or similar) and using heat

resisting flexible cable to the pump heads.

The socket shall be installed socket facing downwards. Pressurisation units shall be fed on a permanently live supply from the

control panel via a 16A IEC plug and socket.

Pressurisation unit (where applicable)

Two pressure switches shall be fitted on the cold feed to the system, these shall be high and low limits. The high limit shall be a break on rise unit

and the low limit shall be a break on fall. These limit switches shall control slave relays in the control panel.

The set points shall be agreed with the mechanical engineer at commissioning stage.

Operation of either switch shall cause all plant to be shut down immediately and display a pressure fault indication on the main control

panel. The control specialist shall also allow for the provision of volt free normally closed contacts that open under fault conditions to enable the

fault alarm to be detected by the BMS. The pressurisation unit shall be wired on an exclusive circuit from the

control panel via a 16A European standard fused spur.

Control valves/AHU Dampers

Control valves (where applicable) shall be 2 port for isolation and three port for mixing or diverting.

The valves/actuators selected shall be dependant upon the particular project and may be either mains or low voltage operation.

All extra low voltage (e.g. 0-10V) operated valves shall be wired with a

suitable multicore cable with a cross sectional area of not less than 1.5mm2 to allow for the possibility of voltage drop.

Refer to the appropriate control drawing.

Telephony/Belden type cable shall not be used for this purpose. The mechanical contractor shall in general supply the valves and actuators

and the type/operating voltage shall be indicated on the one line schematic provided as part of the project documentation.

Mains operated valves shall be terminated with in the valve head. Labels shall be installed to warn about voltage.

Page 17: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

17

The control specialist shall ensure that the panel is fitted with a suitable transformer, which is capable of supplying the total connected extra low

voltage load.

HWS Controls

In general, the HWS system shall be controlled by the BMS by the use of a three port diverting valve on the primary circuit controlled via an immersion type sensor within the cylinder.

High limit control shall be achieved by a 230v 50Hz spring return 2 port

isolating valve that cuts off all primary flow to the cylinder. This shall be controlled by a high limit thermostat located within the cylinder.

Immersion heaters for standby use shall be fitted within the cylinder and controlled by the BMS on a timetable basis if there are sufficient outputs

on the control system. If the heaters are to be manually controlled, they shall be switched from

the plant control panel. A visual indicator shall be provided on the panel to show that the standby immersions are in use.

Page 18: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

18

Responsibilities (heating/hws plant)

The electrical contractor shall be responsible for:

E1. Mounting and positioning of all equipment

E2. Running of all cables

E3. All wiring and final connections to sensors plant and control

systems to clear and concise wiring/installation diagrams provided by the control specialist

E4. All wiring and final connections to heating equipment as detailed

on the project drawings

E5. Supply and installation of all controls, sensors and ancillary

equipment E6. Full inspection and test of the whole electrical installation

including mechanical control. Certificate to be produced.

E7. The purchase of all control equipment and associated items from one of the nominated controls specialists for the particular project

Controls Specialist

The control specialist shall be responsible for:

a) Designing and building of the control panel/outstation

b) Final testing and commissioning of plant and control system

c) Liaison with Cornwall Council Energy Management Unit and/or Clerk of Works

d) Provision of all wiring and interconnection diagrams as detailed

within this specification. This shall include a fully annotated

termination diagram giving terminal number/letters for all items of plant and the respective connections within the control panel

terminal strip. It shall also give details of cable type, cross sectional area and colour coding where applicable.

These diagrams will provide the electrical contractor with sufficiently detailed information to enable him to make all necessary

interconnections between plant items and controls. e) As fitted controls drawings on completion of the project.

Page 19: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

19

Data Link (where applicable)

The electrical contractor shall allow for the supply and installation of a data link from any existing compatible BMS controls to the new control

panel/BMS. This link shall be a multi-core data cable to BS5308 and shall be run to the nearest energy management outstation within an existing

building/area. The data link between new and existing equipment shall be left

disconnected until the new control system is ready to be commissioned. Failure to do this can result in damage to either the existing or new

control equipment. If the installation is a completely new project or there are no existing

compatible controls, the above shall not apply.

Page 20: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

20

LPHW Heating Systems Control Philosophy

If Then

Heating zone calls for heat Valve opens (2 or 3 port)

Loop pump starts (where fitted) Zone heating pump starts

Fan convector circuit energised (Where fitted) Boiler(s) fire Run indication for each item to BMS and on

panel

Zone up to temperature (variable temp circuit)

3 port valve modulates under BMS control Pump continues to run to circulate pipework

Zone up to temperature

(constant temp circuit)

2 port isolating valve (where fitted) closes

Circulating pump stops Fan convector zone controls (where fitted) switched off

All zones up to temperature Boiler stops Loop pump (where fitted) runs on to dissipate heat in boiler

This may be a zone pump if no loop pumps fitted

Pressurisation unit failure

(where applicable) or system pressure fault

All plant stops

Alarm signal sent to BMS Pressure fault indication on control panel

Boiler lockout occurs Alarm signal to BMS

Lockout indication on control panel

Zone pump trips Alarm signal to BMS Trip indication on control panel

Loop pump trips (where fitted)

Alarm signal to BMS Trip indication on control panel

Boiler shuts down

Plant override switch operated

All valves open (except 0-10V analogue control)

All pumps run Boilers fire (controlled by integral stats)

Fan convector circuits energised

Control system fails All plant runs Boilers control on integral stats Fan convectors control on local room stats

Page 21: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

21

Fire alarm operates (interlocked via f/a auxiliary

contact in control circuit)

All plant shuts down Gas solenoid valve closes (if fitted)

Gas drop valve solenoid releases (if fitted)

Page 22: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

22

Ventilation and Air Handling Control Philosophy

If Then

Space requires ventilation (over

temp/poor air quality)

Control system checks outside and

inside air temperature

Outside air temperature low Heater battery (if fitted) brought on line (operates in a similar way to a

mixed flow heating zone except that 3 port valve is used for diverting rather

than mixing)

Outside air temp below 5c (measured by stat on heater battery

Fans held off to prevent chilling/freezing of heater battery

If above conditions satisfied Supply and extract fans start

Dampers open to allow fresh air into space (incoming air tempered by heater battery if required)

Space at required temperature Supply/extract air dampers modulate

to provide partial fresh/recirculated air via heat exchanger

Summer cooling required Supply and extract fans start, dampers

open allowing fresh air into space thus providing free cooling. Temperature within space monitored by duct sensor

in return duct

Low space temperature Heater battery brought on line, supply (external) air damper closes, system

recirculates until space temperature comes up to required level

Dampers then modulate to maintain temperature/air quality Space temperature monitored by return

air duct sensor

Space up to temperature Heater battery 3 port valve modulates to divert flow away from battery

Valve controlled by system based on return air temperature as monitored by return air duct sensor

Dampers modulate to maintain temperature and air quality based on

return air temperature as measured by return duct sensor

Page 23: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

23

Air handling fans trip Trip indication shows on control panel Alarm signal to BMS

Fire alarm operates All fire dampers close (where fitted) Fans stop

System requires manual reset after fire alarm cleared

Page 24: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

24

Page 25: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

25

Page 26: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

26

Page 27: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

27

Page 28: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

28

Page 29: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

29

Page 30: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

30

Page 31: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

31

Page 32: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

32

Page 33: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

33

Page 34: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

34

Page 35: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

35

Page 36: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

36

Prepared by:

Terry Thomas

Principal Electrical Engineer

Property Services

26 August 2010

Page 37: Energy management systems control panel construction ... · PDF fileEnergy management systems control panel construction ... A durable yellow notice with black text to this ... Energy

Energy management systems control panel construction

Standard control specification

37

If you would like this information in another format please contact:

Cornwall Council County Hall

Treyew Road Truro TR1 3AY

Telephone: 0300 1234 100

Email: [email protected]

www.cornwall.gov.uk