    Table of Contents

    Cover Page

    Table of Contents

    Intro Page

    1 STRUCTURE

    2 EXTERIOR

    3 PLUMBING

    4(A) ELECTRIC - GARAGE/EXTERIOR

    4(B) ELECTRIC - UTILITY ROOM/INTERIOR

    5(A) HVAC - UPPER LEVEL

    5(B) HVAC - BASEMENT

    6 INTERIOR

    7(A) KITCHEN - BASEMENT

    7(B) KITCHEN - MAIN LEVEL

    Minor Discovery Summary

    MAJOR Discovery Summary

    General Summary

    CliEnlighten Home Inspections, LLC

    Page 2 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    3/67

    Date: 4/30/2013 Time: 10:00 AM Report ID: SampleWebsite

    Property:

    Sample StreetSample Report VA

    Customer:

    Sample ClientReal Estate Professional:

    Sample AgentSample Realty

    Enlighten Home Inspections, LLC is pleased to provide you with this home inspection report. This report is intended toprovide you with an evaluation of the general condition of the home on the date of the inspection. Please read the entire

    report. The areas of the home that were inspected include: Structure, Exterior, Plumbing, Electric, HVAC (Heating,Ventilation and Air Conditioning), Interior and Kitchen. For condominiums and cooperatives, common areas are NOTinspected and are not part of a standard report. The structure and exterior are considered common areas in condominiumsand cooperatives.

    The focus of the inspection was on major problems or concerns. A major problem or concern is a component that issignificantly deficient and would potentially cost $500.00 to repair or replace, or posses a threat to life or health. Theseitems, if any, are contained in this report and can be easily identified by locating an "X" in the "MA" (Major) column in eachsection of this report. Look for the description of the problem or concern in the corresponding explanation below thecolumns. Major problems or concerns can also be accessed by looking directly at the "MAJOR" Summary in this report.

    During the course of identifying major problems or concerns, it is nearly inevitable that minor problems or concerns will belocated. A minor problem or concern is a component that is deficient and would more than likely cost less than $500.00 torepair or replace. Minor problems or concerns can be easily identified by locating an "X" in the "m" (minor) column in eachsection of this report. Look for the description of the problem or concern in the corresponding explanation below thecolumns. Minor problems or concerns can also be accessed by looking directly at the "MINOR SUMMARY" in this report. Iis important to note that this inspection is not an all inclusive inspection and not every minor defect is noted in this report.

    It is my sincere hope that you find this report and our services to be beneficial. Thank you for choosing Enlighten HomeInspections, LLC for your home inspection needs.

    Regards,

    Isaac Kieffer

    Enlighten Home Inspections, LLC

    Style of residence:Detached residence Client is present:Yes Year Built:1970

    Radon Test:Yes

    Weather:Partly cloudy

    Temperature:75

    Precipitation in the last 3 days:Yes - rain

    Client attention:Complete

    Others present:Buyer's agent, Family member(s)

    Occupied:No

    CliEnlighten Home Inspections, LLC

    Page 3 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    4/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    5/67

    2. EXTERIOR

    Recommended that a licensed general contractor perform all repairs noted in this section.

    Styles & Materials

    ACCESS:Typical

    MAIN ROOF:ACCESS: Viewed from groundACCESS: Viewed from roof edgeROOF INACCESSIBLE - Breakableroofing materialLAYERS: 1ROOFING MATERIAL: Slate

    AGE: 30+ yearsSLOPE: ModerateOVERALL CONDITION: GoodPROBABILITY OF REPLACEMENT: Low

    ROOF COVERING 2:ROOF LOCATION: Carport

    SITE/DRAINAGE:GUTTERS: AluminumGUTTERS: AttachedCOMPONENT: DownspoutsCOMPONENT: Underground drain(s) -unable to inspectSURFACE CONTROLS: French drainSURFACE CONTROLS: Retaining wall(s)

    SURFACE CONTROLS: Window well(s)SITE: Above street levelSITE: Ponding/wet areasSITE: Yard slopes toward houseGRADING/DRAINAGE CONTROLS:Improvement(s) needed

    SIDING MATERIAL:BrickStone

    TRIM MATERIAL:Wood

    CHIMNEY:TYPE: StoneLOCATION: GableLOCATION: Ridge

    ATTACHMENTS:Bay windowCarportPatioPorch

    DRIVEWAY:Asphalt

    GARAGE DOOR(S):Motorized door operator with release and

    auto reverse/stop

    OTHER FEATURES:Fencing

    Large tree(s)Water feature - not inspected

    CliEnlighten Home Inspections, LLC

    Page 5 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    6/67

    IN NI MA m RR FYI

    2.0 ROOF COVERING

    2.1 ROOF DRAINAGE

    2.2 ROOF FLASHING

    2.3 SIDING

    2.4 TRIM

    2.5 MASONRY

    2.6 CHIMNEY(S)

    2.7 EXTERIOR DOOR(S)

    2.8 SAFETY RAILS

    2.9 STEPS/STAIRS

    2.10 DRIVEWAY

    2.11 GARAGE DOOR(S)

    2.12 WALKWAY(S)

    2.13 PATIO

    2.14 LANDSCAPING

    2.15 EXTERIOR DRAINAGE

    2.16 DRIVEWAY DRAIN

    2.17 RETAINING WALL(S)

    2.18 WINDOW WELL(S)

    2.19 FENCE(S)

    2.20 FOR YOUR INFORMATION

    IN NI MA m RR FYI

    IN= Inspected - OK at inspection, NI= Not Inspected, MA= Major problem, m= Minor problem, RR= Repair or Replace, FYI= For Your Information

    Comments:

    2.0 MONETARY CONCERN: Damaged/missing/aged slate: Main roof back side (Pictures 1-5) - consult a licensedroofing contractor

    2.1 Improper drainage/damaged underground drain: Downspouts (Picture 1) - recommend extending downspouts a

    minimum of 8-10 feet away from the foundation walls, further if possible. Use smooth wall pipe for extensions

    2.3 Seal siding at penetration points: Multiple areas (Pictures 1, 2) - recommend sealing all siding penetrations with

    duct seal

    2.5 Eroded/cracked/missing mortar: Multiple areas (Pictures 1-16) - point up

    2.6 (1) Missing flue cap and screen: Left chimney (Picture 1), Rear patio fireplace (Picture 2)

    2.6 (2) Cracked crown: Right chimney (Picture 3)

    CliEnlighten Home Inspections, LLC

    Page 6 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    7/67

    2.7 SAFETY CONCERN: Double cylinder deadbolt: Basement (Picture 1), Front door (Picture 2) - recommend

    replacing with a deadbolt that is operable from the interior without a key

    2.8 (1) SAFETY CONCERN - Missing hand rail: Front left stairs (Picture 1), Right side (Picture 2), Backyard(Picture 3) - handrails should be continuous along the entire length of the stairs

    2.8 (2) SAFETY CONCERN - Loose hand/safety rail: Left side stairs (Picture 4)

    2.14 MONETARY CONCERN - Large tree(s) overhanging: Multiple trees (Picture 1) - keep branches trimmed awayfrom roof and house

    2.15 Ponding/wet areas: Front (Picture 1) - maintain a positive flow of surface water away from foundation walls

    2.16 Clogged/debris: Driveway drain (Picture 1) - snake

    2.17 SAFETY CONCERN - Retaining walls bowed/pulling away from the house: Back left side (Pictures 1, 2) -

    monitor

    2.20 For your information: Clean debris from window well(s) to allow water to drain quickly (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 7 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    8/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    9/67

    3.2 (3) Clogged/slow drain: Jack and Jill bathroom bathtub (Picture 4), Upper level bathroom sink (Picture 5),Upper level bathroom bathtub (Picture 6)

    3.3 Faucet leaks: Jack and Jill bathroom shower head (Picture 1), Upper level bathroom shower head (Picture 2)

    3.4 (1) Corroded valve(s): Utility room washer cold water line (Picture 1), Main level kitchen sink ice maker shut-off(Picture 2)

    3.4 (2) Valves leak: Basement bathroom shower (Picture 3), Entryway bathroom sink cold water handle (Picture 4),Jack and Jill bathroom toilet (Picture 5)

    3.4 (3) Hot and cold handles reversed: Basement bar sink (Picture 6)

    3.5 Missing pop-up drain: Basement bathroom sink (Picture 1)

    3.7 (1) Missing/cracked caulk: Bathtub(s)/shower(s) at the tile and floor (Picture 1)

    3.7 (2) Cracked tiles: Basement bathroom (Pictures 2, 3)

    3.7 (3) Cracked grout: Jack and Jill bathroom bathtub tiles (Picture 4)

    3.9 For your information: Freeze vulnerable pipes - Rear hose bibb (Picture 1)

    3.12 Vacuum breaker(s) missing - All hose bibbs (Picture 1) - can compromise public water supply safety

    3.15 SAFETY CONCERN - Missing a gas shut-off valve outside of the fireplace: Rear patio (Picture 1), Basement(Picture 2)

    3.16 (1) For your information: Recommend installing a washer pan with a drain

    3.16 (2) For your information: Recommend installing No Burst orFlood Chek washer hoses

    3.16 (3) For your information: Recommend installing a solid aluminum dryer vent instead of the foil vent (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 9 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    10/67

    4(A) . ELECTRIC - GARAGE/EXTERIOR

    Recommended that a licensed electrician perform all electrical repairs noted in this section.

    Styles & Materials

    SYSTEM ACCESS:Typical

    SERVICE ENTRANCE CABLE:TYPE: AluminumSERVICE: Underground

    AMPERAGE: 200VOLTAGE: 120/240PHASE: SingleMETER: Outside

    PANEL:TYPE: Circuit breakersPANEL: Partially labeledEXPANSION ROOM: NoneSYSTEM: TroughLOCATION: Garage

    PANEL COVER CAPACITY:AMPERAGE: 200

    GROUNDING:Concealed

    MAJOR CIRCUITS:AluminumCopperNon metallic (NM)

    Armored cable (AC)

    GENERAL CIRCUITS:Copper

    Armored cable (AC)

    RECEPTACLES:DISTRIBUTION: TypicalTYPE: 3 prong

    GFCI LOCATION(S):BathExteriorKitchenRECOMMENDED: add at all wet locations

    OTHER FEATURES:FIXTURES: ClosetFIXTURES: ExteriorFIXTURES: RecessedCOMPONENT: Low voltage lighting

    IN NI MA m RR FYI

    4.0.A ELECTRIC PANEL

    4.1.A SUB PANEL

    4.2.A CIRCUIT BREAKERS

    4.3.A CIRCUITS/CABLES

    4.4.A SERVICE ENTRY CABLE (SEC)

    4.5.A METER/METER BASE

    4.6.A GROUND

    4.7.A RECEPTACLES

    4.8.A INSTALLATION/OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTER(S)

    4.9.A SWITCHES/DIMMERS

    4.10.A JUNCTION/WORK BOXES

    4.11.A LIGHT FIXTURES

    4.12.A CEILING FAN(S)

    IN NI MA m RR FYI

    IN= Inspected - OK at inspection, NI= Not Inspected, MA= Major problem, m= Minor problem, RR= Repair or Replace, FYI= For Your Information

    Comments:

    4.0.A Improper cover screws: Electric panel (Picture 1) - pointed screws should never be used to secure the panelcover

    4.2.A SAFETY CONCERN - Overfused circuit(s): Electric panel (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 10 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    11/67

    4.3.A (1) Missing conduit: Rear patio lighting cables (Picture 1)

    4.3.A (2) Unprotected connections: Backyard (Picture 2) - all connections should be made in a covered junctionbox

    4.3.A (3) Improper connections: Electric panel buss neutrals (Picture 1) - there should be no more than one neutralper lug.

    4.7.A Wall plate(s) missing: Garage (Picture 1)

    4.8.A SAFETY CONCERN - Missing GFCI receptacle(s): Multiple exterior receptacles (Pictures 1-6)

    4.10.A Missing cover plate(s): Garage junction box (Picture 1), Front door (Picture 2)

    4.11.A Missing/burned bulb(s): Rear patio ceiling fan (Picture 1), Garage (Picture 2), Front door (Picture 3), Left

    side (Picture 4)

    4.12.A Unbalanced ceiling fan: Rear patio (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 11 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    12/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    13/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    14/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    15/67

    5(B) . HVAC - BASEMENT

    Recommended that a licensed HVAC technician perform all HVAC repairs noted in this section.

    Styles & Materials

    EQUIPMENT LOCATION:Utility room

    HEATING SYSTEM AGE:10 years

    HEATING - FUEL TYPE:Gas with electronic ignition

    HEATING CAPACITY:245000 BTUs

    COMBUSTION GAS VENT/FLUE:TYPE: Metal

    AIR CONDITIONING:NOT TESTED: Temperature below 60

    degrees within the last 24 hoursRETROFITTED: Separate from heatingsystemTYPE: Electric CompressorCAPACITY: 2.5 tons

    CONDENSER AGE:2 years

    THERMOSTAT(S):ElectronicSingle - centralCAUTION: Multiple systems -simultaneous heat and AC operationpossible

    DUCT SYSTEM:Metal

    IN NI MA m RR FYI

    5.0.B COMBUSTION AIR 5.1.B FLUE/COMBUSTION GAS VENT

    5.2.B AIR HANDLER

    5.3.B AIR CONDITIONER

    5.4.B FILTER

    5.5.B THERMOSTAT(S)

    5.6.B AUTOMATIC SAFETY CONTROLS

    5.7.B CONDENSATE PUMP

    5.8.B CONDENSATE DRAIN LINE(S)

    5.9.B DUCTWORK/PLENUM

    5.10.B AIR REGISTERS

    5.11.B REFRIGERANT LINES

    5.12.B BOILER

    5.13.B VALVE(S)

    5.14.B BOILER PIPING

    5.15.B PRESSURE RELIEF VALVE

    5.16.B RADIATORS

    5.17.B FOR YOUR INFORMATION

    IN NI MA m RR FYI

    IN= Inspected - OK at inspection, NI= Not Inspected, MA= Major problem, m= Minor problem, RR= Repair or Replace, FYI= For Your Information

    Comments:

    5.0.B Inadequate combustion air: Utility room (Picture 1) - recommend adding a louvered door

    CliEnlighten Home Inspections, LLC

    Page 15 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    16/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    17/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    18/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    19/67

    7(A) . KITCHEN - BASEMENT

    Recommended that a licensed general contractor perform all repairs noted in this section.

    Styles & Materials

    SYSTEM ACCESS:Typical

    RANGE:FUEL: ElectricAGE: 20-25 yrsCONDITION: GoodREPLACEMENT PROBABILITY:Moderate (average life span = 15-20 yrs$650+)

    DISPOSER:AGE: 10-15 yrsCONDITION: PoorREPLACEMENT PROBABILITY: High(average life span = 5-12 yrs)

    OTHER FEATURE(S):External discharge fan

    IN NI MA m RR FYI

    7.0.A RANGE

    7.1.A DISPOSER

    7.2.A SINK

    7.3.A COUNTERTOPS/CABINETS

    7.4.A DRAWERS/DOORS

    IN NI MA m RR FYI

    IN= Inspected - OK at inspection, NI= Not Inspected, MA= Major problem, m= Minor problem, RR= Repair or Replace, FYI= For Your Information

    Comments:

    7.0.A (1) Inoperative oven light: Range (Picture 1)

    7.0.A (2) SAFETY CONCERN - Anti-tip bracket not installed: Range (Picture 2)

    7.1.A Seized: Basement kitchen sink disposer (Picture 1)

    7.4.A Missing hardware: Basement kitchen cabinet doors and drawers (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 19 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    20/67

    7(B) . KITCHEN - MAIN LEVEL

    Recommended that a licensed general contractor perform all repairs noted in this section.

    Styles & Materials

    SYSTEM ACCESS:Typical

    RANGE:AGE: 10-15 yrsCONDITION: GoodREPLACEMENT PROBABILITY:Moderate (average life span = 15-20 yrs$650+)FEATURE: Convection ovenFEATURE: Self cleaning oven

    MICROWAVE:AGE: 1-5 yrsCONDITION: GoodREPLACEMENT PROBABILITY: Low(average life span = 5-10 yrs)

    DISHWASHER:AGE: 10-15 yrsCONDITION: GoodREPLACEMENT PROBABILITY: High(average life span = 5-12 yrs)

    REFRIGERATOR:AGE: 10-15 yrsCONDITION: GoodREPLACEMENT PROBABILITY: Low(average life span = 15-20 yrs)FEATURE: Ice makerFEATURE: Ice dispenserFEATURE: Water dispenser

    DISPOSER:AGE: 1-5 yrsCONDITION: GoodREPLACEMENT PROBABILITY: Low(average life span = 5-12 yrs)

    OTHER FEATURE(S):Recirculating fan

    IN NI MA m RR FYI

    7.0.B RANGE

    7.1.B RECIRCULATING RANGE HOOD

    7.2.B REFRIGERATOR

    7.3.B DISHWASHER

    7.4.B DISPOSER

    7.5.B MICROWAVE

    7.6.B SINK

    7.7.B COUNTERTOPS/CABINETS

    7.8.B DRAWERS/DOORS

    IN NI MA m RR FYI

    IN= Inspected - OK at inspection, NI= Not Inspected, MA= Major problem, m= Minor problem, RR= Repair or Replace, FYI= For Your Information

    Comments:

    7.2.B Inoperative: Main level kitchen refrigerator ice maker (Picture 1) and water dispenser (Picture 2) - water linedoes not appear to be hooked up

    7.3.B (1) Loose: Dishwasher (Picture 1) - recommend securing to the countertop or cabinet

    7.3.B (2) Continues to cycle at the one minute point and does not automatically shut off: Dishwasher (Picture 2)

    CliEnlighten Home Inspections, LLC

    Page 20 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    21/67

    Minor Discovery Summary

    Enlighten Home Inspections, LLC

    39 Benton CourtSterling, VA 20165

    [email protected](301) 204-2825

    Customer

    Sample Client

    AddressSample Street

    Sample Report VA

    The following items or discoveries indicate that these system(s) or component(s) do not function as intended, adverselyaffect the habitability of the dwelling, appear to warrant further investigation by a specialist, or require subsequentobservation. Generally, this summary includes items that constitute "minor" problems or concerns. A minor problem orconcern is an item or discovery that would cost less than $500.00 to repair or replace. This summary shall not containrecommendations for routine upkeep of a system or component to keep it in proper functioning condition orrecommendations to upgrade or enhance the function, efficiency, or safety of the home. This Summary is not the entirereport. The complete report may include additional information of concern to the customer. It is recommended that the

    customer read the complete report.

    1. STRUCTURE

    1.5 STRUCTURAL STEEL

    Minor problem, Repair or Replace

    Rusted lintels: Multiple windows/doors (Pictures 1, 2) - keep lintels scraped and painted to prevent expansionfrom rusting

    CliEnlighten Home Inspections, LLC

    Page 21 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    22/67

    1. STRUCTURE

    1.5 Picture 1 1.5 Picture 2

    2. EXTERIOR2.1 ROOF DRAINAGE

    Minor problem, Repair or Replace

    Improper drainage/damaged underground drain: Downspouts (Picture 1) - recommend extending downspouts aminimum of 8-10 feet away from the foundation walls, further if possible. Use smooth wall pipe for extensions

    2.1 Picture 1

    2.3 SIDING

    Minor problem, Repair or Replace

    Seal siding at penetration points: Multiple areas (Pictures 1, 2) - recommend sealing all siding penetrations withduct seal

    CliEnlighten Home Inspections, LLC

    Page 22 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    23/67

    2. EXTERIOR

    2.3 Picture 1 2.3 Picture 2

    2.5 MASONRY

    Minor problem, Repair or Replace

    Eroded/cracked/missing mortar: Multiple areas (Pictures 1-16) - point up

    2.5 Picture 1 2.5 Picture 2

    2.5 Picture 3 2.5 Picture 4

    CliEnlighten Home Inspections, LLC

    Page 23 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    24/67

    2. EXTERIOR

    2.5 Picture 5 2.5 Picture 6

    2.5 Picture 7 2.5 Picture 8

    2.5 Picture 9 2.5 Picture 10

    CliEnlighten Home Inspections, LLC

    Page 24 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    25/67

    2. EXTERIOR

    2.5 Picture 11 2.5 Picture 12

    2.5 Picture 13 2.5 Picture 14

    2.5 Picture 15 2.5 Picture 16

    2.6 CHIMNEY(S)

    Minor problem, Repair or Replace

    (1) Missing flue cap and screen: Left chimney (Picture 1), Rear patio fireplace (Picture 2)

    CliEnlighten Home Inspections, LLC

    Page 25 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    26/67

    2. EXTERIOR

    2.6 Picture 1 2.6 Picture 2

    (2) Cracked crown: Right chimney (Picture 3)

    2.6 Picture 3

    2.15 EXTERIOR DRAINAGE

    Minor problem, Repair or Replace

    Ponding/wet areas: Front (Picture 1) - maintain a positive flow of surface water away from foundation walls

    2.15 Picture 1

    CliEnlighten Home Inspections, LLC

    Page 26 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    27/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    28/67

    3. PLUMBING

    3.2 Picture 3

    (3) Clogged/slow drain: Jack and Jill bathroom bathtub (Picture 4), Upper level bathroom sink (Picture 5), Upperlevel bathroom bathtub (Picture 6)

    3.2 Picture 4 3.2 Picture 5

    3.2 Picture 6

    3.3 FAUCET(S)

    Minor problem, Repair or Replace

    CliEnlighten Home Inspections, LLC

    Page 28 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    29/67

    3. PLUMBING

    Faucet leaks: Jack and Jill bathroom shower head (Picture 1), Upper level bathroom shower head (Picture 2)

    3.3 Picture 1 3.3 Picture 2

    3.4 VALVE(S)

    Minor problem, Repair or Replace

    (1) Corroded valve(s): Utility room washer cold water line (Picture 1), Main level kitchen sink ice maker shut-off

    (Picture 2)

    3.4 Picture 1 3.4 Picture 2

    (2) Valves leak: Basement bathroom shower (Picture 3), Entryway bathroom sink cold water handle (Picture 4),

    Jack and Jill bathroom toilet (Picture 5)

    CliEnlighten Home Inspections, LLC

    Page 29 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    30/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    31/67

    3. PLUMBING

    3.5 Picture 1

    3.7 BATHROOM TILE/WALL PROTECTION

    Minor problem, Repair or Replace

    (1) Missing/cracked caulk: Bathtub(s)/shower(s) at the tile and floor (Picture 1)

    3.7 Picture 1

    (2) Cracked tiles: Basement bathroom (Pictures 2, 3)

    3.7 Picture 2 3.7 Picture 3

    CliEnlighten Home Inspections, LLC

    Page 31 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    32/67

    3. PLUMBING

    (3) Cracked grout: Jack and Jill bathroom bathtub tiles (Picture 4)

    3.7 Picture 4

    3.12 HOSE BIBB(S)

    Minor problem, Repair or Replace

    Vacuum breaker(s) missing - All hose bibbs (Picture 1) - can compromise public water supply safety

    3.12 Picture 1

    4(A). ELECTRIC - GARAGE/EXTERIOR

    4.0.A ELECTRIC PANEL

    Minor problem, Repair or Replace

    Improper cover screws: Electric panel (Picture 1) - pointed screws should never be used to secure the panelcover

    CliEnlighten Home Inspections, LLC

    Page 32 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    33/67

    4(A). ELECTRIC - GARAGE/EXTERIOR

    4.0.A Picture 1

    4.3.A CIRCUITS/CABLES

    Minor problem, Repair or Replace

    (1) Missing conduit: Rear patio lighting cables (Picture 1)

    4.3.A Picture 1

    (2) Unprotected connections: Backyard (Picture 2) - all connections should be made in a covered junction box

    4.3.A Picture 2

    CliEnlighten Home Inspections, LLC

    Page 33 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    34/67

    4(A). ELECTRIC - GARAGE/EXTERIOR

    (3) Improper connections: Electric panel buss neutrals (Picture 1) - there should be no more than one neutral perlug.

    4.3.A Picture 3

    4.7.A RECEPTACLES

    Minor problem, Repair or Replace

    Wall plate(s) missing: Garage (Picture 1)

    4.7.A Picture 1

    4.10.A JUNCTION/WORK BOXES

    Minor problem, Repair or Replace

    Missing cover plate(s): Garage junction box (Picture 1), Front door (Picture 2)

    CliEnlighten Home Inspections, LLC

    Page 34 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    35/67

    4(A). ELECTRIC - GARAGE/EXTERIOR

    4.10.A Picture 1 4.10.A Picture 2

    4.11.A LIGHT FIXTURES

    Minor problem, Repair or Replace

    Missing/burned bulb(s): Rear patio ceiling fan (Picture 1), Garage (Picture 2), Front door (Picture 3), Left side(Picture 4)

    4.11.A Picture 1 4.11.A Picture 2

    4.11.A Picture 3 4.11.A Picture 4

    CliEnlighten Home Inspections, LLC

    Page 35 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    36/67

    4(A). ELECTRIC - GARAGE/EXTERIOR

    4.12.A CEILING FAN(S)

    Minor problem, Repair or Replace

    Unbalanced ceiling fan: Rear patio (Picture 1)

    4.12.A Picture 1

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.1.B SUB PANEL

    Minor problem, Repair or Replace

    (1) Improperly terminated cables: Utility room sub panel (Picture 1)

    4.1.B Picture 1

    (2) Loose panel cover: Utility room sub panel (Picture 2)

    CliEnlighten Home Inspections, LLC

    Page 36 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    37/67

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.1.B Picture 2

    4.3.B CIRCUITS/CABLES

    Minor problem, Repair or Replace

    Missing wire clamp: Basement kitchen sink disposer feed wire (Picture 1)

    4.3.B Picture 1

    4.7.B RECEPTACLES

    Minor problem, Repair or Replace

    (1) Wall plate(s) missing: Basement bathroom (Picture 1). Main level middle bedroom closet (Pictures 2, 3), Masterbedroom (Picture 4)

    CliEnlighten Home Inspections, LLC

    Page 37 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    38/67

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.7.B Picture 1 4.7.B Picture 2

    4.7.B Picture 3 4.7.B Picture 4

    (2) Reversed polarity: Basement bathroom (Picture 5), Basement rear right room (Picture 6), Main level kitchen

    (Picture 7), Main level office (Picture 8), Main level hall (Picture 9), Attic front bedroom (Picture 10)

    CliEnlighten Home Inspections, LLC

    Page 38 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    39/67

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.7.B Picture 5 4.7.B Picture 6

    4.7.B Picture 7 4.7.B Picture 8

    4.7.B Picture 9 4.7.B Picture 10

    (3) Ungrounded electrical receptacles: Basement rear right room (Pictures 11, 12)

    CliEnlighten Home Inspections, LLC

    Page 39 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    40/67

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.7.B Picture 11 4.7.B Picture 12

    (4) Loose receptacle(s): Main level kitchen (Picture 13)

    4.7.B Picture 13

    4.9.B SWITCHES/DIMMERS

    Minor problem, Repair or Replace

    (1) Wall plate(s) missing: Utility room (Picture 1)

    4.9.B Picture 1

    CliEnlighten Home Inspections, LLC

    Page 40 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    41/67

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    (2) Defective dimmer: Basement safe room (Pictures 2, 3)

    4.9.B Picture 2 4.9.B Picture 3

    4.11.B LIGHT FIXTURES

    Minor problem, Repair or Replace

    (1) Unprotected closet fixture(s): Multiple closets (Picture 1) - recommend installing a fixture with a protectiveglobe

    4.11.B Picture 1

    (2) Missing/burned bulb(s): Main level middle bedroom closet (Picture 2), Main level hall ceiling fixtures (Picture3)

    CliEnlighten Home Inspections, LLC

    Page 41 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    42/67

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.11.B Picture 2 4.11.B Picture 3

    4.12.B CEILING FAN(S)

    Minor problem, Repair or Replace

    Inadequate clearance: Basement rear right room ceiling fan (Picture 1) - blades should be a minimum of 7' fromthe ground

    4.12.B Picture 1

    5(A). HVAC - UPPER LEVEL

    5.5.A CONDENSATE DRAIN LINE(S)

    Minor problem, Repair or Replace

    Missing cap: Attic AC condensate drain line (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 42 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    43/67

    5(A). HVAC - UPPER LEVEL

    5.5.A Picture 1

    5(B). HVAC - BASEMENT5.0.B COMBUSTION AIR

    Minor problem, Repair or Replace

    Inadequate combustion air: Utility room (Picture 1) - recommend adding a louvered door

    5.0.B Picture 1

    5.4.B FILTER

    Minor problem, Repair or Replace

    Dirty reusable HVAC filter: Utility room in the AC return plenum (Picture 1) - clean

    CliEnlighten Home Inspections, LLC

    Page 43 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    44/67

    5(B). HVAC - BASEMENT

    5.4.B Picture 1

    5.8.B CONDENSATE DRAIN LINE(S)

    Minor problem, Repair or Replace

    Missing cap: AC condensate drain line (Picture 1)

    5.8.B Picture 1

    5.9.B DUCTWORK/PLENUM

    Minor problem, Repair or Replace

    Missing duct insulation: Garage (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 44 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    45/67

    5(B). HVAC - BASEMENT

    5.9.B Picture 1

    6. INTERIOR6.4 DOORS (REPRESENTATIVE NUMBER)

    Minor problem, Repair or Replace

    Doors do not latch/doors rub/bind: Multiple doors (Pictures 1-3) - adjust hardware

    CliEnlighten Home Inspections, LLC

    Page 45 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    46/67

    6. INTERIOR

    6.4 Picture 1 6.4 Picture 2

    6.4 Picture 3

    6.9 ATTIC MOISTURE

    Minor problem, Repair or Replace

    Moisture stains: Attic (Pictures 1, 2), monitor

    6.9 Picture 1 6.9 Picture 2

    6.13 FIRE SEPARATION

    CliEnlighten Home Inspections, LLC

    Page 46 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    47/67

    6. INTERIOR

    Minor problem, Repair or Replace

    Missing fire stop: Garage ceiling (Pictures 1, 2)

    6.13 Picture 1 6.13 Picture 2

    7(A). KITCHEN - BASEMENT

    7.0.A RANGE

    Major problem, Minor problem, Repair or Replace

    (1) Inoperative oven light: Range (Picture 1)

    7.0.A Picture 1

    7.1.A DISPOSER

    Minor problem, Repair or Replace

    Seized: Basement kitchen sink disposer (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 47 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    48/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    49/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    50/67

    7(B). KITCHEN - MAIN LEVEL

    Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Isaac Kieffer

    CliEnlighten Home Inspections, LLC

    Page 50 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    51/67

    MAJOR Discovery Summary

    Enlighten Home Inspections, LLC

    39 Benton CourtSterling, VA 20165

    [email protected](301) 204-2825

    Customer

    Sample Client

    AddressSample Street

    Sample Report VA

    The following items or discoveries indicate that these system(s) or component(s) do not function as intended, adverselyaffect the habitability of the dwelling, appear to warrant further investigation by a specialist, or require subsequentobservation. This summary includes those items that constitute "MAJOR" problems or concerns. A major problem orconcern is any item or discovery that would cost more than $500.00 to repair or replace. This summary shall not containrecommendations for routine upkeep of a system or component to keep it in proper functioning condition orrecommendations to upgrade or enhance the function, efficiency, or safety of the home. This Summary is not the entirereport. The complete report may include additional information of concern to the customer. It is recommended that the

    customer read the complete report.

    1. STRUCTURE

    1.0 FOUNDATION WALLS

    Major problem, Repair or Replace

    Foundation settlement crack(s): Garage (Picture 1) - recommend contacting a licensed structural engineer tofurther evaluate

    CliEnlighten Home Inspections, LLC

    Page 51 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    52/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    53/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    54/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    55/67

    2. EXTERIOR

    (2) SAFETY CONCERN - Loose hand/safety rail: Left side stairs (Picture 4)

    2.8 Picture 4

    2.14 LANDSCAPING

    Major problem, Repair or Replace

    MONETARY CONCERN - Large tree(s) overhanging: Multiple trees (Picture 1) - keep branches trimmed away

    from roof and house

    2.14 Picture 1

    2.17 RETAINING WALL(S)

    Major problem, Repair or Replace

    SAFETY CONCERN - Retaining walls bowed/pulling away from the house: Back left side (Pictures 1, 2) - monitor

    CliEnlighten Home Inspections, LLC

    Page 55 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    56/67

    2. EXTERIOR

    2.17 Picture 1 2.17 Picture 2

    3. PLUMBING

    3.15 GAS PIPE

    Major problem, Repair or Replace

    SAFETY CONCERN - Missing a gas shut-off valve outside of the fireplace: Rear patio (Picture 1), Basement(Picture 2)

    3.15 Picture 1 3.15 Picture 2

    4(A). ELECTRIC - GARAGE/EXTERIOR

    4.2.A CIRCUIT BREAKERS

    Major problem, Repair or Replace

    SAFETY CONCERN - Overfused circuit(s): Electric panel (Picture 1)

    CliEnlighten Home Inspections, LLC

    Page 56 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    57/67

    4(A). ELECTRIC - GARAGE/EXTERIOR

    4.2.A Picture 1

    4.8.A INSTALLATION/OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTER(S)

    Major problem, Repair or Replace

    SAFETY CONCERN - Missing GFCI receptacle(s): Multiple exterior receptacles (Pictures 1-6)

    CliEnlighten Home Inspections, LLC

    Page 57 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    58/67

    4(A). ELECTRIC - GARAGE/EXTERIOR

    4.8.A Picture 1 4.8.A Picture 2

    4.8.A Picture 3 4.8.A Picture 4

    4.8.A Picture 5 4.8.A Picture 6

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.2.B CIRCUIT BREAKERS

    Major problem, Repair or Replace

    CliEnlighten Home Inspections, LLC

    Page 58 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    59/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    60/67

    4(B). ELECTRIC - UTILITY ROOM/INTERIOR

    4.8.B Picture 1 4.8.B Picture 2

    4.8.B Picture 3 4.8.B Picture 4

    CliEnlighten Home Inspections, LLC

    Page 60 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    61/67

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    62/67

    5(B). HVAC - BASEMENT

    5.1.B Picture 1 5.1.B Picture 2

    6. INTERIOR6.10 STEPS, STAIRWAYS, BALCONIES AND RAILINGS

    Major problem, Repair or Replace

    (1) SAFETY CONCERN - Missing hand rail: Entryway stairs (Picture 1) - handrails should be continuous alongthe entire length of the stairs

    6.10 Picture 1

    (2) SAFETY CONCERN - Safety rails do not meet current child safety standards: Upper level stairs (Picture 2) -

    balusters should be spaced a maximum of 4" apart

    CliEnlighten Home Inspections, LLC

    Page 62 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    63/67

    6. INTERIOR

    6.10 Picture 2

    6.11 SMOKE DETECTORS

    Major problem, Repair or Replace

    SAFETY CONCERN - Inoperative smoke detector(s): Main level hall ceiling (Picture 1) - highly recommend onesmoke alarm in the general living space on each level, and one in each bedroom. Any smoke alarm ten or more

    years old needs to be replaced. If the age cannot be determined, it is best to replace the alarm(s)

    6.11 Picture 1

    7(A). KITCHEN - BASEMENT

    7.0.A RANGEMajor problem, Minor problem, Repair or Replace

    (2) SAFETY CONCERN - Anti-tip bracket not installed: Range (Picture 2)

    CliEnlighten Home Inspections, LLC

    Page 63 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    64/67

    7(A). KITCHEN - BASEMENT

    7.0.A Picture 2

    Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Isaac Kieffer

    CliEnlighten Home Inspections, LLC

    Page 64 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    65/67

    General Summary

    Enlighten Home Inspections, LLC

    39 Benton CourtSterling, VA 20165

    [email protected](301) 204-2825

    Customer

    Sample Client

    AddressSample Street

    Sample Report VA

    1. STRUCTURE

    1.7 FOR YOUR INFORMATION

    For Your Information

    For your information: Recommend installing a dehumidifier in the basement

    2. EXTERIOR

    2.20 FOR YOUR INFORMATION

    For Your Information

    For your information: Clean debris from window well(s) to allow water to drain quickly (Picture 1)

    2.20 Picture 1

    CliEnlighten Home Inspections, LLC

    Page 65 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    66/67

    2. EXTERIOR

    3. PLUMBING

    3.9 PIPES AND FITTINGS

    For Your Information

    For your information: Freeze vulnerable pipes - Rear hose bibb (Picture 1)

    3.9 Picture 1

    3.16 FOR YOUR INFORMATION

    For Your Information

    (1) For your information: Recommend installing a washer pan with a drain

    (2) For your information: Recommend installing No Burst orFlood Chek washer hoses

    (3) For your information: Recommend installing a solid aluminum dryer vent instead of the foil vent (Picture 1)

    3.16 Picture 1

    5(A). HVAC - UPPER LEVEL

    5.10.A FOR YOUR INFORMATION

    For Your Information

    CliEnlighten Home Inspections, LLC

    Page 66 of Sample Street

  • 7/30/2019 Enlighten Home Inspections, LLC - Sample Website Report

    67/67

    5(A). HVAC - UPPER LEVEL

    For your information: Recommend contacting a licensed AC technician to service the unit once a year in the

    spring

    5(B). HVAC - BASEMENT

    5.17.B FOR YOUR INFORMATION

    For Your Information(1) For your information: Recommend contacting a licensed HVAC technician to service the heating and A/Cunits twice a year

    (2) For your information: Recommend cleaning the reusable HVAC filter every 30 days of operational use

    6. INTERIOR

    6.14 LEAD PAINT

    For Your Information

    For your information: Any structure built prior to 1978 likely contains lead based paint

    6.15 FOR YOUR INFORMATIONFor Your Information

    (1) For your information: Recommend contacting a licensed chimney sweep to clean and inspect the flues

    (2) For your information: Recommend installing at least one carbon monoxide detector on every level and withinten feet of every bedroom