equipment fundamentals: heat exchangers€¦ · heat exchanger –example 3 heat 291,800 lb/hr cold...

70
Equipment Fundamentals: Heat Exchangers Chapter 3

Upload: others

Post on 02-May-2020

16 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Equipment Fundamentals: Heat Exchangers

Chapter 3

Page 2: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Topics

Equipment – heat exchangers▪ Combines information about

fluid flow & heat transfer across internal boundaries

▪ Considerations

• When do I need to know the specifics of the heat exchange configuration?

• How is the heat transfer coefficient related to the outlet temperatures?

• What is an approach temperature?

Fundamentals of heat transfer & exchange

▪ Heat transfer across boundaries

• Conduction

• Convection

• Radiation

▪ Coupled with internal energy changes

• Sensible heat effects

• Phase change

2

Page 3: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Topics

Fundamentals of heat transfer & exchange

▪ Heat transfer across boundaries

• Conduction

• Convection

• Radiation

▪ Coupled with internal energy changes

• Sensible heat effects

• Phase change

▪ Area-averaged temperature difference

Equipment – heat exchangers▪ Combines information about

fluid flow & heat transfer across internal boundaries

▪ Considerations

• When do I need to know the specifics of the heat exchange configuration?

• How is the heat transfer coefficient related to the outlet temperatures?

• What is an approach temperature?

3

Page 4: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2017 John Jechura ([email protected])

Fundamentals

Page 5: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Transfer – Modes of heat transfer

Conduction

▪ Flow of heat through material with no bulk movement of the material itself

▪ Usually thought of through solid, but can also be through a stagnant fluid

▪ For a flat sold:

▪ Through a circular pipe:

▪ Through a sphere:

5

−=

hot coldT TQ

kA x

( )( )

= −

2

lnhot cold

o i

Qk T T

L D D

( )

= −

+

2

1 1 hot cold

i o

Q k T T

D D

Page 6: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Transfer – Modes of heat transfer

Convection

▪ Flow of heat associated with fluid movement – natural & forced convection

Radiation

▪ Heat transferred via electromagnetic radiation

6

( )= −hot cold

Qh T T

A

( )

( )( ) ( )

= −

= + + −

4 4

2 2

hot cold

hot cold hot cold hot cold

QT T

A

T T T T T T

Page 7: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchangers – Some Basics

Focus is on the system to have heat flow from the hot fluid(s) to the cold fluid(s) usually without direct contact

▪ Use bulk flow parameters to relate the heat conduction across the flow barrier to the change in energy of the hot & cold fluids

▪ Account for the series of resistances to heat transfer between the hot & cold fluids

Heat exchangers

▪ Heat to & from flowing fluids through impermeable barrier(s)

▪ Driving force for heat through barriers is the temperature difference between the two fluids on opposite sides of the barrier

▪ Relate the heat effects in the flowing fluids to the change in enthalpy

• Often this can be related to the difference in the inlet & outlet temperatures for the fluids

7

( ) ( )

( ) ( )

= − = −

= − = −

, , , , , ,

, , , , , ,

ˆ ˆˆ ˆ for constant

ˆ ˆˆ ˆ for constant

H H H in H out H H p H H in H out p H

C C C out C in C C p C C out C in p C

Q m H H Q m C T T C

Q m H H Q m C T T C

Page 8: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchangers – Some Basics▪ Relate the heat across

the barrier to the temperature difference across the barrier

▪ It can be shown that for many typical configurations the AREA AVERAGED temperature difference is the LMTD (Log Mean Temperature Difference)

8

( )( ) ( )( ) ( )− − −

= −

,0 ,0 ,1 ,1

,0 ,0

,1 ,1

where

ln

H C H C

LM LM

H C

H C

T T T TQ UA T T

T T

T T

x

TH,in TH,out

TC,inTC,out

TH(x)

TC(x)

( )( ) ( ) = − = −

AREA AVERAGED

/h c h c

d Q LU T T Q UA T T

dx

Page 9: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchangers – Some Basics

LMTD is a prescribed calculation – calculating the LMTD from the procedure is always correct.

LMTD is appropriate for use as the area averaged temperature difference when temperature vs. heat released/absorbed is a straight line

▪ 1-1 co-current & counter-current flow and …

▪ Both hot & cold sides have a constant heat or …

▪ Only pure component phase change on one side or the other (no subcooling and/or superheating)

9

( ) ( )

( )

( )

( )( ) ( )

( ) ( )

− + = =

1 2

1 2 1 2

1

2

and lim2

lnT T

T T T TLMTD LMTD

T

T

Page 10: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Transfer – Some Basics

Heat exchangers – Co-Current vs. Counter-Current vs. Cross-Current flows

▪ Counter-current flow allows the outlet temperatures to approach more closely to the inlet temperature of the other fluid

▪ Cross-current flow is complicated & requires knowledge of the actual flow patterns

Heat exchangers – Industrial Heat Exchangers

▪ Industrial heat exchangers have a combination of heat transfer through multiple barriers and a combination of counter-current & co-current flow

• LMTD must be “corrected” to give the actual area-averaged temperature difference (i.e., driving force) – this is the source for one type of “F” factor

10

Co-Current Counter-Current Cross-Current

Page 11: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

145°F

C2+ NGL Feed291,800 lb/hr

80°F

??? F

C3+ Bottoms191,600 lb/hr

240°F

Heat Exchanger – Example 1

Heat 291,800 lb/hr cold C2+ NGL feed from 80oF to 105oF using 191,600 lb/hrhot C3+ bottoms @ 240oF

▪ Assume only sensible heat effects

• C2+ NGL feed heat capacity – 0.704 Btu/lb F

• C3+ Bottoms heat capacity – 0.830 Btu/lb F

Determine

▪ C3+ Bottoms outlet temperature

▪ Exchanger duty

▪ (UA) for the exchanger

11

Page 12: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

Exchanger duty & C3+ Bottoms outlet temperature determined from energy balance around exchanger

Determination of UA requires configuration information

▪ 1-1 counter-current flow 1-1 co-current flow

12

( ) ( )( )( )

( )( )

, , ,

o, ,

,

ˆ 291800 0.704 145 80 13,353,000 Btu/hr

13353000240 155.8 F

ˆ 191600 0.828

c p c c out c in

h out h in

h p h

Q m C T T

QT T

m C

= − = − =

= − = − =

( )( ) ( )

( )

o

o

240 145 155.8 8085.1 F

240 145ln

155.8 80

13353000 Btu157,000

85.1 hr F

LMTD

LMTD

T

QUA

T

− − − = =

= = =

( )( ) ( )

( )

o

o

240 80 155.8 14555.4 F

240 80ln

207.7 105

13353000 Btu241,000

55.4 hr F

LMTD

LMTD

T

QUA

T

− − − = =

= = =

Page 13: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

Determination of UA requires configuration information

▪ 1-2 (1 shell & 2 tube passes) combines both counter & co-current flow

The fluid in the shell pass transfers heat separately to the two tube banks

13

Ref: GPSA Data Book, 13th ed.

1-2 Co & Counter-Flow

Page 14: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

▪ 1-2 exchanger calculations require a configuration correction to relate temperatures to the UA

▪ Does not include crossflow effects across the tubes

14

( )( )( )

2

12

2

11 ln

1

2 1 11 ln

2 1 1

PR

RPF

P R RR

P R R

− + −

= − + − + −

− + + +

Ref: GPSA Data Book, 13th ed.

Ref: Kern, Process Heat Transfer, McGraw-Hill, 1965

Page 15: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

▪ 1-2 exchanger

15

( )( ) ( )

( )

( )

o

2

2

o

240 145 155.8 8085.1 F

240 145ln

155.8 80

145 800.4

240 80

240 155.81.3

145 80

0.86 (from chart)

13353000 Btu182,500

0.86 85.1 hr F

LMTD

LMTD

T

P

R

F

QUA

F T

− − − = =

−= =

−= =

=

=

= =

Ref: GPSA Data Book, 13th ed.

Page 16: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

16

Page 17: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

Representation of temperature profiles with combined flow becomes more complicated.

17

Page 18: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

??? F

C2+ NGL Feed291,800 lb/hr

80°F

??? F

C3+ Bottoms191,600 lb/hr

240°F

Heat Exchanger – Example 2

Heat 291,800 lb/hr cold C2+ NGL feed starting from 80oF using 191,600 lb/hrhot C3+ bottoms @ 240oF. Drive the exchanger to a 10oF approach temperature

▪ For 1-1 Counter-Current flow, what are the outlet temperatures?

• The C2+ NGL Feed is either heated to 230oF (approach on the hot inlet side) or …

• the C3+ Bottoms is cooled to 90oF (approach on the cold inlet side)

▪ Assume only sensible heat effects

• C2+ NGL feed heat capacity – 0.704 Btu/lb F

• C3+ Bottoms heat capacity – 0.830 Btu/lb F

Determine

▪ The outlet temperature that is not controlled by the approach

▪ Exchanger duty

▪ (UA) for the exchanger

18

Page 19: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 2

Exchanger duty & “other” outlet temperature determined from energy balance around exchanger

▪ If the hot side inlet has the approach temperature

This has a temperature crossover – this is not the controlling side!

▪ If the cold side inlet has the approach temperature:

19

( ) ( )( )( )

( )( )

o, ,

, , ,

o, ,

,

10 90 F

ˆ 191600 0.828 240 90 23,797,000 Btu/hr

2379700080 195.8 F

ˆ 291800 0.704

h out c in

h p h h in h out

c out c in

c p c

T T

Q m C T T

QT T

m C

= + =

= − = − =

= + = + =

( ) ( )( )( )

( )( )

o, ,

, , ,

o, ,

,

10 230 F

ˆ 291800 0.704 230 80 30,814,000 Btu/hr

30814000240 45.8 F

ˆ 191600 0.828

c out h in

c p c c out c in

h out h in

h p h

T T

Q m C T T

QT T

m C

= − =

= − = − =

= − = − =

Page 20: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 2

Determination of UA for 1-1 Counter-Current flow using the cold & hot outlet temperatures of 195.8oF & 90oF, respectively

20

( )( ) ( )

( )

o

o

240 195.8 90 8023.0 F

240 195.8ln

90 80

23797000 Btu1,035,000

23.0 hr F

LMTD

LMTD

T

QUA

T

− − − = =

= = =

195.8°F

C2+ NGL Feed291,800 lb/hr

80°F

90°F

C3+ Bottoms191,600 lb/hr

240°F

Page 21: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 3

Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current heat exchanger from Example #1 designed with 25% excess heat transfer area (UA=196,000 Btu/hr oF)

▪ Assume only sensible heat effects

• C2+ NGL feed heat capacity – 0.704 Btu/lb F

• C3+ Bottoms heat capacity – 0.830 Btu/lb F

Determine

▪ Both outlet temperatures

▪ Exchanger duty

Need to couple all three equations relating heat exchanger duty find the three unknowns

21

??? F

C2+ NGL Feed291,800 lb/hr

80°F

??? F

C3+ Bottoms191,600 lb/hr

240°F

Page 22: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 3

Even though it looks like you’ll have to solve the three equations in an iterative manner, it can be shown that the heat transfer duty is:

In the limiting case where the mCp terms are equal:

22

( )( ), ,

, ,

, ,

, ,

1 1 1 where exp for

1H in C in

C p C H p H

C p C H p H

C p C H p H

T TQ UA m C m C

m C m Cm C m C

− −= − −

, ,, , if

1

H in C inC p C H p H

p

T TQ m C m C

UA

mC

−= =

+

??? F

C2+ NGL Feed291,800 lb/hr

80°F

??? F

C3+ Bottoms191,600 lb/hr

240°F

Page 23: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 3

Even though it looks like you’ll have to solve the three equations in an iterative manner, it can be shown that the heat transfer duty is:

So:

23

( )( )

( )( )

o, ,

,

o, ,

,

14924000240 145.9 F

ˆ 191600 0.828

1492400080 152.6 F

ˆ 291800 0.704

h out h in

h p h

c out c in

c p c

QT T

m C

QT T

m C

= − = − =

= + = + =

( )( ), ,

, ,

, ,

, ,

1 1 1 where exp for

1H in C in

C p C H p H

C p C H p H

C p C H p H

T TQ UA m C m C

m C m Cm C m C

− −= − −

( )( )( ) ( )( )

( )( )

( )( ) ( )( )

1 1exp 196000 0.7548

291800 0.704 191600 0.828

0.7548 1 240 8014,924,000 Btu/hr

0.7548 1

291800 0.704 191600 0.828

Q

= − =

− −= =

152.6°F

C2+ NGL Feed291,800 lb/hr

80°F

145.9°F

C3+ Bottoms191,600 lb/hr

240°F

Page 24: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchange with Phase Change

Can get significant heat exchange with little to no change in temperature

24

Ref: GPSA Data Book, 13th ed.

ΔT = 0 ΔT = 340

Page 25: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 4

Condense 10,000 lb/hr saturated vapor propane at 120oF using 95oF air. Figure a 10oF approach temperature, so heat the air up to 110oF.

▪ Needed physical properties

• Air heat capacity – 0.24 Btu/lb F

• Propane heat of vaporization @ 120oF – 1,236 Btu/lb

Determine

▪ Exchanger duty

▪ Flow rate of air needed

▪ Exchanger UA

25

Page 26: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 4

Duty determined from the propane energy balance. No sensible heat effect.

Air flowrate from its energy balance:

Calculate UA knowing the terminal temperatures

26

( ) ( )( )= = =

−−, , ,

12,360,0003,430,000 lb/hr

ˆ 0.24 110 95c

p c c out c in

Qm

C T T

( )( )= = =10000 1236 12,360,000 Btu/hrh vap

Q m

( )( ) ( )

( )

− − − = =

= = =

o

o

120 110 120 9516.4 F

120 110ln

120 95

12360000 Btu755,000

16.4 hr F

LMTD

LMTD

T

QUA

T

Page 27: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 4

Calculating the UA is essentially the same as when there is no phase change since the temperature profiles with heat release are still straight lines. The hot stream’s profile just happens to be a constant temperature.

27

Page 28: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 5

Condense 10,000 lb/hr propane vapor that is superheated to 160oF (but still with 120oF vapor pressure) using 95oF air heated up to 110oF.

▪ Needed physical properties

• Air heat capacity – 0.24 Btu/lb F

• Propane vapor heat capacity – 0.52 Btu/lb F

• Propane heat of vaporization @ 120oF – 1236 Btu/lb

Determine

▪ Exchanger duty

▪ Flow rate of air needed

▪ Exchanger UA

28

Page 29: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 5

Duty determined from the propane balance. Combine sensible heat & latent heat effects

Air flowrate from its energy balance:

Just using terminal temperatures gives an incorrect result!

29

( ) ( )( )= = =

−−, , ,

125,680,00034,900,000 lb/hr

ˆ 0.24 110 95c

p c c out c in

Qm

C T T

( ) ( ) ( ) ( )

( )

= + − = + −

= +

=

, , ,ˆ 10000 1236 0.52 160 120

10000 1236 20.8

125,680,000 Btu/hr

h vap p c h in h BPQ m C T T

( )( ) ( )

( )

− − − = = = = =

o

o

160 110 120 95 125680000 Btu36.1 F 3, 480,000

160 110 36.1 hr F ln

120 95

LMTD

LMTD

QT UA

T

Page 30: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 5

Calculating the UA is more complicated than just using the terminal temperatures since there is a drastic break in the temperature profile for the condensing propane

30

Page 31: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 5

Determine the intermediate air temperature between the sensible & latent heat zones

Calculate the UA values for the two zones

The total UA is the sum of these two contributions.

31

( )( ) ( )

( )

− − − = =

= = =

o

o

120 109.8 120 9516.5 F

120 109.8ln

120 95

123600000 Btu3, 420,000

36.1 hr F

LMTD

LMTD

T

QUA

T

( )( )

= =

= + = + = o

, ,

,

123,600,000 Btu/hr

123,600,00095 109.8 F

ˆ 34,900,000 0.24

cond h vap

cond

c mid c in

c p c

Q m

QT T

m C

( )( ) ( )

( )

− − − = =

= = =

o

o

160 110 120 109.825.0 F

160 110ln

120 109.8

2080000 Btu83,000

25.0 hr F

LMTD

LMTD

T

QUA

T

Page 32: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 6

Can we condense 10,000 lb/hr propane vapor that is superheated to 160oF (but still with 120oF vapor pressure) using 95oF air heated up to 140oF? This still gives an apparent 20oF approach temperature?

The answer is NO! It is not apparent from the terminal temperatures but there is an internal pinch point to the temperature profiles & there would be a temperature crossover. The air’s outlet temperature is constrained by this internal pinch point.

32

Page 33: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 6

More air flow is needed to accomplish this cooling. Using a 10oF internal approach temperature shows that the air’s outlet temperature is constrained to 112.5oF. The required air mass flow would be calculated accordingly.

33

Page 34: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Transfer – Some Basics

Thermal resistances are added when in series▪ Can be combined into an overall heat transfer coefficient

▪ Across a flat plate (i.e., constant cross sectional area)

▪ For radial heat transfer (e.g., through the wall of a tube) must also take into account the change is area with respect to radius

• Overall heat transfer coefficient must also be related to a reference area / diameter

34

= + +1 1 1

i o

L

U h k h

= + +

= + + = + +

1 1 1

1 1 1 1 2 1ln

o o i i ave o o

o o o o o

o i i ave o i i i o

L

U A h A kA h A

A L A D D D

U h A k A h h D k D h

Page 35: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Transfer – Correlations for Film Coefficients

Flow in tubes with no phase change

When there is a significant difference between wall & bulk fluid

Stirred liquids, heat transfer from coil …

… from tank jacket

35

= =

0.40.8

0.8 0.4

Nu Re Pr0.023 0.023

pChD D v

N N Nk k

= =

0.14 0.140.330.8

0.8 0.33

Nu Re Pr0.023 0.023

pb b

w w

ChD D vN N N

k k

= =

0.14 0.140.62 0.332

0.62 0.33

Nu Re, Pr0.9 0.9

pb bi i

i

w w

CN DhDN N N

k k

= =

0.14 0.140.67 0.332

0.66 0.33

Nu Re, Pr0.36 0.36

pb bi i

i

w w

CN DhDN N N

k k

Page 36: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Typical Overall Heat Transfer Coefficients

Heat transfer coefficients are drastically different for conditions of boiling and/or condensation versus when there is sensible heat change.

▪ Bubbles break up the films along the wall

▪ Also dependent upon the temperature difference across the wall

36

Fundamentals of Natural Gas Processing, 2nd ed., Kidnay, Parrish, &

McCartney, 2011

Ref: GPSA Data Book, 13th ed.

Page 37: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Typical Overall Heat Transfer Coefficients

37

Ref: GPSA Data Book, 13th ed.

Fundamentals of Natural Gas Processing, 2nd ed., Kidnay,

Parrish, & McCartney, 2011

Page 38: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Typical Fouling Factors

Add these resistances to the reciprocal of the “clean” overall heat transfer coefficient

38

Ref: GPSA Data Book, 13th ed.

Page 39: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2017 John Jechura ([email protected])

Equipment

Page 40: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Gas Processing Applications

Common heat exchangers▪ Shell and Tube

▪ Kettle reboiler

▪ Aerial coolers

▪ Plate Frame

▪ Plate-Fin (Brazed Aluminum)

▪ Hairpin

▪ Tank Heaters

40

http://www.alfalaval.com/globalassets/images/media/stories/crude-oil-

refinery/ppi00393_compabloc-brazil_640x360.jpg

Page 41: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Shell & Tube Heat ExchangersWorkhorses of the gas processing industry

Shell side

▪ Baffles used in the shell side to minimize channeling

Tube side

▪ Manifolds allow for even distribution of fluids into the tubes & collection/mixing of fluids out of the tubes

▪ Multiple tube passes make it easier to pull the tube bundle for maintenance/cleaning and…

▪ … have better allowance for thermal expansion effects

41

Fig. 3.6, Fundamentals of Natural Gas Processing, 2nd ed., Kidnay, Parrish, &

McCartney, 2011

Page 42: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Shell and Tube Heat Exchangers (Types)

42

Ref: GPSA Data Book, 13th ed.

Page 43: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Shell and Tube Heat Exchangers (Selection)

43

Ref: GPSA Data Book, 13th ed.

Page 44: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Kettle Reboiler

Shell & tube heat exchanger with the tubes submerged in boiling liquid on the shell side

▪ Main resistance to heat transfer is on the tube side since boiling is occurring on the shell side

44

Fig. 3.7, Fundamentals of Natural Gas Processing, 2nd ed., Kidnay, Parrish, & McCartney, 2011

Page 45: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Plate Frame Heat Exchangers

Positives

▪ Low cost

▪ Compact – high area per weight & volume

▪ Can get very close approach temperatures (5oF or lower)

▪ Can be disassembled to clean

Negative considerations

▪ Limited maximum allowable working pressure

▪ Susceptible to plugging

45

http://www.cheresources.com/content/articles/heat-transfer/plate-heat-exchangers-preliminary-design

Fig. 3.9, Fundamentals of Natural Gas Processing, 2nd

ed., Kidnay, Parrish, & McCartney, 2011

Page 46: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Tank Heaters

Integrated into existing equipment (i.e., tanks or vessels)

46

https://www.chromalox.com/en/global/case-studies/pocket-heater-reduces-costs-and-downtime

Ref: GPSA Data Book, 13th ed.

Page 47: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Air-Cooled Exchangers – Fundamentals

Air cooled exchangers cool fluids with ambient air▪ Seasonal variation can greatly impact performance

Utilize finned tube in increase heat transfer surface area

47

www.hudsonproducts.com www.hudsonproducts.com

Page 48: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Aerial Coolers

Fans either push air through (forced draft) or pull air through (induced draft) tube bundle

▪ Can control the air flow rate either with a variable speed motor or with louviers

48

Fig. 3.8, Fundamentals of Natural Gas Processing, 2nd ed., Kidnay, Parrish, & McCartney, 2011

http://spxcooling.com/products/detail/air-cooled-heat-exchangers

Page 49: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Aerial Cooler Design Considerations

Typically a small number of diameter tubes (e.g., 1in OD) with fins on the air side (e.g., 1/2 or 5/8 in)

Design considerations

▪ Process side – pressure drop for flow inside of tubes

▪ Air side

• Required air flow

o May need high air flow to preventtemperature crossover, but…

o High air flow gives higher pressure drop & fan power

▪ Mechanical considerations

• Total number of tubes

• Tube layout: number of passes, numberof rows, pitch

• Bay size: typically 45 ft X 15 ft max

49

Ref: GPSA Data Book, 14th ed.

Page 50: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Air-Cooled Exchangers – Types

Forced Draft:

Advantages:

▪ Slightly lower horsepower

▪ Better maintenance accessibility

▪ Easily adaptable for warm air recirculation

▪ Most common in gas industry

Induced Draft:

Advantages

▪ Better distribution of air

▪ Less possibility of air recirculation

▪ Less effect of sun, rain, or hail

▪ Increased capacity in the event of fan failure

50

Page 51: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Air-Cooled Exchanger – Thermal Design(∆ Temperature – CMTD Figs 10-8 & 9)

F ~ 1.0for 3+

Over/UnderPasses

Page 52: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2017 John Jechura ([email protected])

Summary

Page 53: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Summary

Common types of heat exchangers used in the gas processing industry

▪ Shell & tube

▪ Kettle reboiler

▪ Air cooled exchangers

▪ Plate Frame

▪ Plate-Fin (Brazed Aluminum)

▪ Hairpin

▪ Tank Heaters

Heat exchange basics▪ Coupling of fluid energy balances

with heat transfer across barrier

▪ Common heat exchanger configurations

▪ Typical heat transfer coefficients

▪ Example process calculations involving heat exchangers

53

Page 54: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2017 John Jechura ([email protected])

Supplemental Slides

Page 55: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

LMTD as Area-Averaged Temperature Difference

If the temperature curves are linearly related to the duty then the temperature difference will also be linearly related to duty

Can put into differential form of heat transfer equation & integrate

55

( )( ) ( )

( )( ) ( ) − −

= + =1 0 1 0

0

T T T TT T q d T dq

Q Q

( )( ) ( )

( ) ( )

( ) ( ) ( )

( )

( )

( ) ( ) ( )

( )

( )

( ) ( ) ( ) ( )

( )

( )

( )

= = −

− =

− =

− − = = =

1

0

1 0

1 0

1 0

0

1 0 1 01

0 1

0

ln

ln

T A

T

LM

Qdq U T da d T U T da

T T

T Td TU da

T Q

T Td TU da

T Q

T T T TTU A Q UA UA T

T Q T

T

Page 56: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Shell & Tube Heat Exchangers

56

http://www.apiheattransfer.com/Product/54/Type-ST-U-Tube-Shell-Tube-Heat-Exchangers

Page 57: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

145 F

C2+ NGL Feed291,800 lb/hr

80 F

??? F

C3+ Bottoms191,600 lb/hr

240 F

Heat Exchanger – Example 7

Heat 291,800 lb/hr cold C2+ NGL feed from 80oF to 160oF using 191,600 lb/hrhot C3+ bottoms @ 240oF

▪ Assume only sensible heat effects

• C2+ NGL feed heat capacity – 0.704 Btu/lb F

• C3+ Bottoms heat capacity – 0.828 Btu/lb F

Determine

▪ C3+ Bottoms outlet temperature

▪ Exchanger duty

▪ (UA) for the exchanger

57

Page 58: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 7

Exchanger duty & C3+ Bottoms outlet temperature determined from energy balance around exchanger

Determination of UA requires configuration information

▪ 1-1 counter-current flow 1-1 co-current flowcannot be done – crossover!

58

( ) ( )( )( )

( )( )

= − = − =

= − = − =

, , ,

o

, ,

,

ˆ 291800 0.704 160 80 16,434,000 Btu/hr

16434000240 136.4 F

ˆ 191600 0.828

c p c c out c in

h out h in

h p h

Q m C T T

QT T

m C

( )( ) ( )

( )

− − − = =

= = =

o

o

240 160 136.4 8067.5 F

240 160ln

136.4 80

16434000 Btu243,000

67.5 hr F

LMTD

LMTD

T

QUA

T

Page 59: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 7

1-2 exchanger

59

( )( ) ( )

( )

( )

− − − = =

−= =

−= =

=

=

= =

o

2

2

o

240 160 136.4 8067.5 F

240 160ln

136.4 80

160 800.5

240 80

240 136.41.3

160 80

0.51 (from chart)

16434000 Btu477, 400

0.51 67.5 hr F

LMTD

LMTD

T

P

R

F

QUA

F T

Ref: GPSA Data Book, 13th ed.

Page 60: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 7

Correction factor below 0.8. Try 2-4 exchanger

60

( )( ) ( )

( )

( )

− − − = =

−= =

−= =

=

=

= =

o

2

2

o

240 160 136.4 8067.5 F

240 160ln

136.4 80

160 800.5

240 80

240 136.41.3

160 80

0.925 (from chart)

16434000 Btu263,200

0.925 67.5 hr F

LMTD

LMTD

T

P

R

F

QUA

F T

Ref: GPSA Data Book, 13th ed.

Page 61: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Cooling Tower Principles

Evaporative cooling (Psychrometry)

▪ Dry Bulb versus Wet Bulb Temperature

• Contact dry air with water

• Saturation of air (vaporization of some water) takes energy

• Air is cooled below ambient – to “Wet Bulb” temperature

▪ Takes advantage of air below 100% humidity

• Wet Bulb MUST be lower than Dry Bulb temperature

61

Page 62: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Cooling Tower Principles

Evaporative cooling (Psychrometry)

▪ Wet bulb and dry bulb data for various locations around the world Fig 11-3

62

Page 63: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Example:How cold can you get?

Air temperature: 95°F

RH = 65%

Temperature with cooling tower?

Temperature with air cooler?

Wet bulb=84°F

Page 64: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Cooling Towers – Mechanical Induced Draft

64

www.rjdesjardins.com

www.iklimnet.com

Page 65: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Cooling Towers – Mechanical Forced Draft

65

Towertechinc.com

Page 66: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Cooling Towers – Wet Surface Air Cooler

66

www.niagarablower.com

Page 67: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

145°F

C2+ NGL Feed291,800 lb/hr

80°F

??? F

C3+ Bottoms191,600 lb/hr

240°F

Heat Exchanger – Example 1

Heat 291,800 lb/hr cold C2+ NGL feed from 80oF to 105oF using 191,600 lb/hrhot C3+ bottoms @ 240oF

▪ Assume only sensible heat effects

• C2+ NGL feed heat capacity – 0.704 Btu/lb F

• C3+ Bottoms heat capacity – 0.830 Btu/lb F

Determine

▪ C3+ Bottoms outlet temperature

▪ Exchanger duty

▪ (UA) for the exchanger

▪ Does the flow configuration in a 1-2 exchanger make a difference?

67

Page 68: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

Determination of UA requires configuration information

▪ 1-2 (1 shell & 2 tube passes) combines both counter & co-current flow

Four possible flow configurations

68

Hot Stream on Shell Side Cold Stream on Shell Side

Page 69: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 1

Four possible flow configurations – all have the same exit temperatures but different internal profiles

69

Page 70: Equipment Fundamentals: Heat Exchangers€¦ · Heat Exchanger –Example 3 Heat 291,800 lb/hr cold C2+ NGL feed from 80oF using 191,600 lb/hr hot C3+ bottoms @ 240oF. 1-1 Counter-Current

Updated: January 29, 2019Copyright © 2019 John Jechura ([email protected])

Heat Exchanger – Example 7

I thought you said temperature crossovers weren’t possible????

70