RESIDENTIAL VERTICAL CLADDING
Espan 340™ / 470™
RVEP
0800 ROOFNZ (0800 766 369)www.metalcraftgroup.co.nz
Architectural / Specification EnquiriesPh: 09 274 0408
Mobile: 027 603 1096Email: [email protected]
00 / 21 COVER SHEET01 / 21 PARAPET AND BALUSTRADE CAPPING02 / 21 SCUPPER W/ RAINWATER HEAD03 / 21 SOFFIT04 / 21 BUTT WINDOW HEAD05 / 21 BUTT WINDOW SILL06 / 21 BUTT WINDOW JAMB07 / 21 RECESSED WINDOW HEAD08 / 21 RECESSED WINDOW SILL09 / 21 RECESSED WINDOW JAMB10 / 21 METERBOX HEAD11 / 21 METERBOX SILL12 / 21 METERBOX JAMB13 / 21 INTERNAL CORNER14 / 21 EXTERNAL CORNER15 / 21 SOAKER FLASHING16 / 21 CHANGE IN CLADDING17 / 21 CLADDING ABUTMENT18 / 21 BOTTOM OF CLADDING (FLUSH)19 / 21 BOTTOM OF CLADDING (RECESSED)20 / 21 3D WINDOW FLASHINGS21 / 21 3D RAINWATER HEAD
DETAIL LIST
PRE-FINISHED PARAPET CAP FLASHINGNO FIXINGS ON TOP OF FLASHING
PERMEABLE WALL UNDERLAY, SHOWNDASHED
PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER FOR FIXING TOPOF ESPAN™ CLADDING
METALCRAFT ESPAN™VERTICAL CLADDING
WALL FRAMING
CONTINUOUS TIMBER PACKING
MIN
. 5.00°
PROVIDE SEPARATION OF METAL CAPPING ANDTIMBER AS REQUIRED WITH DPC, SHOWNDASHED
CLE
ARAN
CE
3 m
m M
IN
CLE
ARAN
CE
25m
m M
IN
PRE-FINISHED POP RIVET BEDDEDIN SILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
STOPENDS TO WALL CLADDING
COMPRESSIBLE FOAM SEAL. REFERTO MRM CODE OF PRACTICE VERSION2.2 /2012 FOR REQUIRMENT.
20mm HORIZONTAL CAVITY BATTEN
5mm GAP
CLE
A RAN
CE
25m
m M
IN
5mm GAP5mm GAP
MIN
. 5.00 °
ALTERNATIVE OPTION
Z
Z
Z
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)
MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)
MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)
Z
ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE
SITUATION 1
1. LOW, MEDIUM, HIGH WINDZONES, WHERE ROOF PITCH ≥ 10°
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGHWIND ZONE2. LOW, MEDIUM, HIGH WIND ZONESWHERE ROOF PITCH ≤ 10°
MIN. 70mmZ
SITUATION 3
1. FOR ALL ROOF PITCHES INEXTRA HIGH WIND ZONES
MIN. 90mm
ACCEPTABLE SOLUTION AS PER E2/ASI
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
PARAPET AND BALUSTRADE CAPPING
01 / 212018
METALCRAFT ESPAN™ VERTICALCLADDING
METALCRAFT ESPAN™ VERTICALCLADDING PERMEABLE WALL UNDERLAY,
SHOWN DASHED
20mm HORIZONTAL CAVITYBATTEN
WALL FRAMING
CAVITY CLOSER
RETURN MEMBRANE INTORAINWATER HEAD
CONTINUOUS MEMBRANEDRESSED THROUGH BASE ANDUP SIDES OF OPENING WITHUPPER EDGES SEALED AGAINSTCLADDING. RETURN ALONGBACK OF RAINWATERHEAD
RAINWATER HEAD
RETURN MEMBRANEAT END OF LIP
MEMBRANE ON ROOF SUBSTRATE
8g WAFER-TEK SCREW
TRUE ROOF LINE BEHIND
PRE FINISHED SCREW WITHRUBBER WASHER
25RAINWATER HEADOVERFLOW BELOWOPEINING LEVEL,1.5 xCROSS-SECTIONDOWNPIPE DIAMETER
50 mm
SEPARATE BATTEN AND CLADDINGAS REQUIRED WITH DPC
ALTERNATIVE OPTIONMETALCRAFT ESPAN™ CLIP SYSTEMWITH 12G x 16mm WAFERTEK
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
SCUPPER W/ RAINWATER HEAD
02 / 212018
FLY RAFTER
BARGE BOARD
SOFFIT LINING
PURLIN
INTERNAL CEILING LINING
SQUARE STOP CORNICE
EXTRA NOG FOR TOP FIXING OFWALL CLADDING
MIN. 50mm
PERMEABLE WALL UNDERLAY,SHOWN DASHED
WALL FRAMING
METALCRAFT ESPAN™ VERTICALCLADDING
COMPRESSIBLE FOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012 FOR REQUIRMENT.
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
PRE-FINISHED SOFFIT FLASHING
20mm HORIZONTAL CAVITY BATTEN
STOPENDS TO WALL CLADDING
INTERNAL WALL LINING
PRE-FINISHED POP RIVET BEDDEDIN SILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
SEPARATE BATTEN AND CLADDING ASREQUIRED WITH DPC
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER FORFIXING TOP OF ESPAN™ CLADDING
100m
m M
IN
5mm GAP
MIN. 50mm
100m
m M
IN
5mm GAP
ALTERNATIVE OPTION
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
SOFFIT
03 / 212018
PERMEABLE WALL UNDERLAY DRESSED INTOOPENING WITH FLEXIBLE FLASHING TAPEINSTALLED OVER WRAP TO CORNERS AT HEAD
TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING
WINDOW LINTEL FRAMING
PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL
DOUBLE GLAZING WINDOW JOINERY
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
WINDOW HEAD LINER
LINE OF WINDOW JAMB LINER BEHIND
STOPENDS TO HEAD FLASHING
LINE OF JAMB FLASHING BEHIND
EXTRA PERMEABLE WALL UNDERLAYOVER WINDOW HEAD FLASHING, SHOWNDASHED
INTERNAL WALL LINING
STST OR GALV. FLAT HEAD NAIL FORFLASHING
METALCRAFT ESPAN™ VERTICALCLADDING
PERMEABLE WALL UNDERLAY, SHOWNDASHED
METALCRAFT ESPAN™ CLIP SYSTEMWITH 12G x 35mm SCREWS
CAVITY CLOSER AS REQUIRED TO NZBC
MIN
. 10m
m C
OVE
R
SUG
GES
T M
IN. 5
0mm
DIM
ENSI
ON
TO
SU
IT
5mm
GAP
DR
IP E
DG
E TO
CLA
DD
ING
MIN
.15m
m
MIN
.75m
m W
ITH
OU
T H
EM E
DG
E
MIN
.50m
m C
OVE
R
5mm GAP
20mm HORIZONTAL CAVITY BATTEN
5mm
GAP
MIN
. 10m
m C
OVE
R
SUG
GES
T M
IN. 5
0mm
DIM
ENSI
ON
S TO
SU
ITDR
IP E
DG
E TO
CLA
DD
I NG
MIN
. 15m
m
MIN
. 75m
m W
I TH
OU
T H
EM E
DG
E
MIN
. 50m
m C
OVE
R
ALTERNATIVE OPTION
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
BUTT WINDOW HEAD
04 / 212018
STOPENDS TO SILL FLASHING
LINE OF WINDOW JAMB LINER BEHIND
MIN. 8mm PACKER
WINDOW SILL LINER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
PRE-FINISHED WINDOW SILL FLASHING
LINE OF JAMB FLASHING BEHIND
WINDOW SILL SUPPORT BAR
5mm GAP
MIN
.8m
m C
OVE
R
FLEXIBLE FLASHING TAPE OVER PERMEABLEWALL UNDERLAY FOR FULL WIDTH/DEPTH SILL
DOUBLE GLAZING WINDOW JOINERY
5mm
GAP
METALCRAFT ESPAN™ VERTICALCLADDING
PERMEABLE WALL UNDERLAY,SHOWN DASHED STOPENDS TO WALL CLADDING
WALL FRAMING
INTERNAL WALL LINING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER FOR FIXINGTOP OF ESPAN™ WALL CLADDING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW20mm HORIZONTAL CAVITY BATTEN
CO
VER
CLA
DD
ING
60m
m
COMPRESSIBLE FOAM SEAL. REFERTO MRM CODE OF PRACTICEVERSION 2.2 /2012 FORREQUIRMENT.
SEPARATE BATTEN AND CLADDING WITHDPC AS REQUIRED
5mm
GAP
CO
V ER
CLA
DD
ING
60m
m
MIN
. 8m
m C
OVE
R
5mm GAP
5mm GAP
ALTERNATIVE OPTION
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet
- DEPENDING ON ACTUAL SITUATION, A SECONDARY FLASHINGMAY BE REQUIRED. REFER METALCRAFT ROOFING FOR MOREINFORMATION.
1 : 2
BUTT WINDOW SILL
05 / 212018
5mm GAP
MIN.10mm COVER
SUGGEST MIN. 50mm
DIMENSION TO SUIT
PERMEABLE WALL UNDERLAY,SHOWN DASHED
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW SILL LINER BELOW
WINDOW JAMB LINER
TIMBER PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB
20mm JAMB BATTEN
INTERNAL WALL LINING
PRE-FINISHED SECONDARYFLASHING
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
FLEXIBLE FLASHING TAPE OVER PERMEABLEWALL UNDERLAY FOR FULL WIDTH/DEPTHSILL
LINE OF HEAD FLASHING ABOVE
PRE-FINISHED WINDOW JAMBFLASHING
SEPARATE BATTEN AND FLASHINGWITH DPC AS REQUIRED
LINE OF SILL FLASHING BELOW
LINE OF HEAD FLASHING ABOVE
PRE-FINISHED 8g WAFER-TEKSCREW WITH EPDM WASHER
METALCRAFT ESPAN™VERTICAL CLADDING
5mm
GAP
PRE-FINISHED FIXING BRACKET WITH PRE-FINISHED POP RIVET BEDDED IN SILICONEOR PRE-FINISHED 8g WAFER-TEK SCREW
20mm HORIZONTALCAVITY BATTEN
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet
- DEPENDING ON ACTUAL SITUATION, A SECONDARY FLASHINGMAY BE REQUIRED. REFER METALCRAFT ROOFING FOR MOREINFORMATION.
1 : 2
BUTT WINDOW JAMB
06 / 212018
PERMEABLE WALL UNDERLAY DRESSEDINTO OPENING WITH FLEXIBLE FLASHINGTAPE INSTALLED OVER WRAP TO CORNERSAT HEAD
TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING
WINDOW LINTEL FRAMING
PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL
DOUBLE GLAZING WINDOW JOINERY
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
WINDOW HEAD LINER
LINE OF WINDOW JAMB LINER BEHIND
STOPENDS TO HEAD FLASHING
LINE OF JAMB FLASHING BEHINDM
IN. 1
0mm
CO
VER
EXTRA PERMEABLE WALL UNDERLAYOVER WINDOW HEAD FLASHING, SHOWNDASHED
INTERNAL WALL LINING
STST OR GALV. FLAT HEAD NAIL FORFLASHING
METALCRAFT ESPAN™ VERTICALCLADDING
PERMEABLE WALL UNDERLAY, SHOWNDASHED
METALCRAFT ESPAN™ CLIP SYSTEM WITH12G x 35mm SCREWS
CAVITY CLOSER AS REQUIRED TO NZBC
SUG
GES
T M
IN.5
0mm
DIM
ENSI
ON
TO
SU
IT
5mm
GAP
MIN
.75m
m W
ITH
OU
T H
EM E
DG
E
MIN
. 50m
m C
OVE
R
DR
IP E
DG
E TO
CLA
DD
ING
MIN
.15m
m G
AP
20mm HORIZONTAL CAVITY BATTEN
5mm
GAP DR
IP E
DG
E TO
CLA
DD
I NG
MIN
15m
m G
AP
MIN
. 75m
m W
I TH
OU
T H
EM E
DG
E
MIN
. 50m
m C
OVE
R
SUG
GES
T M
IN. 5
0mm
DIM
ENSI
ON
TO
SU
IT
10m
m M
IN C
OVE
R
ALTERNATIVE OPTION
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
RECESSED WINDOW HEAD
07 / 212018
STOPENDS TO SILL FLASHING
LINE OF WINDOW JAMB LINER BEHIND
MIN. 8mm PACKER
WINDOW SILL LINER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
PRE-FINISHED WINDOW SILL FLASHING
LINE OF JAMB FLASHING BEHIND
WINDOW SILL SUPPORT BAR
FLEXIBLE FLASHING TAPE OVER PERMEABLEWALL UNDERLAY FOR FULL WIDTH/DEPTH SILL
DOUBLE GLAZING WINDOW JOINERY
METALCRAFT ESPAN™ VERTICALCLADDING
PERMEABLE WALL UNDERLAY,SHOWN DASHED
STOPENDS TO WALL CLADDINGWALL FRAMING
INTERNAL WALL LINING
SEPARATE BATTEN AND CLADDING WITHDPC AS REQUIRED
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
PRE-FINISHED SECONDARY FLASHING
20mm HORIZONTAL CAVITY BATTEN
PRE-FINISHED SELF DRILLING/TAPPING SCREWWITH RUBBER WASHER FOR FIXING TOP OFESPAN™ CLADDING C
OVE
R C
LAD
DIN
G
60m
m
5mm GAP
5mm
GAP
MIN
. 8m
m C
OVE
R
COMPRESSIBLE FOAM SEAL. REFERTO MRM CODE OF PRACTICE VERSION2.2 /2012 FOR REQUIRMENT.
5mm GAP
CO
VER
CLA
DD
ING
60m
m
5mm
GAP
MIN
. 8m
m C
OVE
R
ALTERNATIVE OPTION
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet
- DEPENDING ON ACTUAL SITUATION, A SECONDARY FLASHINGMAY BE REQUIRED. REFER METALCRAFT ROOFING FOR MOREINFORMATION.
1 : 2
RECESSED WINDOW SILL
08 / 212018
5mm GAP
MIN. 10mm COVER
SUGGEST MIN. 50mm
DIMENSION TO SUIT
PERMEABLE WALL UNDERLAY,SHOWN DASHED
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW SILL LINER BELOW
WINDOW JAMB LINER
TIMBER PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB
20mm JAMB BATTEN
INTERNAL WALL LINING
PRE-FINISHED SECONDARYFLASHING
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
FLEXIBLE FLASHING TAPE OVER PERMEABLEWALL UNDERLAY FOR FULL WIDTH/DEPTHSILL
LINE OF HEAD FLASHING ABOVE
PRE-FINISHED WINDOW JAMBFLASHING
SEPARATE BATTEN AND FLASHINGWITH DPC AS REQUIRED
LINE OF SILL FLASHING BELOW
LINE OF HEAD FLASHING ABOVE
PRE-FINISHED 8g WAFER-TEKSCREW WITH EPDM WASHER
METALCRAFT ESPAN™VERTICAL CLADDING
5mm
GAP
PRE-FINISHED FIXING BRACKET WITH PRE-FINISHED POP RIVET BEDDED IN SILICONEOR PRE-FINISHED 8g WAFER-TEK SCREW
LINE OF SILL FLASHING BELOW
20mm HORIZONTAL CAVITYBATTEN
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet
- DEPENDING ON ACTUAL SITUATION, A SECONDARY FLASHINGMAY BE REQUIRED. REFER METALCRAFT ROOFING FOR MOREINFORMATION.
1 : 2
RECESSED WINDOW JAMB
09 / 212018
PERMEABLE WALL UNDERLAY DRESSEDINTO OPENING WITH FLEXIBLE FLASHINGTAPE INSTALLED OVER WRAP TO CORNERSAT HEAD
TEMPORARY PACKER IF REQUIRED, REMOVEDAFTER FIXING
EXTRA PERMEABLE WALL UNDERLAYOVER WINDOW HEAD FLASHING, SHOWNDASHED
INTERNAL WALL LINING
METERBOX LINTEL FRAMING
METALCRAFT ESPAN™ VERTICALCLADDING
PRE-FINISHED HEAD FLASHING WITH 15° FALL
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
METER BOX
STOPENDS TO HEAD FLASHING
LINE OF JAMB FLASHING BEHIND5m
m G
AP
DR
IP E
DG
E TO
CLA
DD
ING
MIN
. 15m
m G
AP
PRE-FINISHED 'U' BRACKET FIXED TOMETERBOX BEFORE INSTALLATIONMETAL ANGLE TO BE CONTINUOUS
AROUND METER BOX.
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
CAVITY CLOSER AS REQUIRED TO NZBC
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
MIN
.75m
m W
ITH
OU
T H
EM E
DG
E
MIN
.50m
m C
OVE
R
METALCRAFT ESPAN™ CLIP SYSTEM WITH12G x 35mm SCREWS
20mm HORIZONTAL CAVITY BATTEN
MIN
. 15m
m G
AP
ALTERNATIVE OPTION
5mm
GAP
MIN
. 75m
m W
ITH
OU
T H
EM E
DG
E
MIN
. 50m
m C
OVE
R
SEPERATE BETTEN AND CLADDINGAS REQUIRED WITH EPDM
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
METERBOX HEAD
10 / 212018
METALCRAFT ESPAN™ VERTICALCLADDING
PERMEABLE WALL UNDERLAY,SHOWN DASHED
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
MIN. 8mm PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
COMPRESSIBLE FOAM SEAL. REFERTO MRM CODE OF PRACTICEVERSION 2.2 /2012 FORREQUIRMENT.
WALL FRAMING
INTERNAL WALL LINING
LINE OF JAMB FLASHING BEHIND
20mm HORIZONTAL CAVITY BATTEN
FLEXIBLE FLASHING TAPE OVER PERMEABLE WALLUNDERLAY FULL WIDTH/DEPTH SILL
METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.
PRE-FINISHED SILL FLASHING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER FORFIXING TOP OF ESPAN™ CLADDING
STOPENDS TO SILL FLASHING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
METER BOX
STOPENDS TO WALL CLADDING
5mm GAP
5mm gap
ALTERNATIVE OPTION
MIN
.100
mm
MIN
.100
mm
SEPERATE BATTEN AND CLADDING ASREQUIRED WITH EPDM
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet
- DEPENDING ON ACTUAL SITUATION, A SECONDARY FLASHINGMAY BE REQUIRED. REFER METALCRAFT ROOFING FOR MOREINFORMATION.
1 : 2
METERBOX SILL
11 / 212018
METALCRAFT ESPAN™ VERTICALCLADDING
PERMEABLE WALL UNDERLAY, SHOWNDASHED
METER BOX
TIMBER PACKER
20mm JAMB BATTEN
INTERNAL WALL LINING
LINE OF SILL FLASHING BELOW
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
LINE OF HEAD FLASHING ABOVE
PRE-FINISHED JAMB FLASHING FIXED TOMETERBOX BEFORE INSTALLATION
METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB
FLEXIBLE FLASHING TAPE OVERPERMEABLE WALL UNDERLAY FOR FULLWIDTH/DEPTH SILL
LINE OF HEAD FLASHING ABOVE
STST OR GALV. FLAT HEAD NAIL FORFLASHING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEKSCREW
20mm HORIZONTAL CAVITY BATTEN
5mm
GAP
PRE-FINISHED POP RIVET BEDDEDIN SILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
METERBOX JAMB
12 / 212018
METALCRAFT ESPAN™VERTICAL CLADDING
PRE-FINISHED 8g WAFER-TEKSCREW WITH EPDM WASHER
20mm HORIZONTAL CAVITYBATTEN
PRE-FINISHED INTERNALCORNER FLASHING
INTERNAL WALL LINING
PERMEABLE WALLUNDERLAY, SHOWN DASHED
WALL FRAMING
POP RIVET BEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
PRE-FINISHED SECONDARYFLASHING
SEPERATE BATTEN ANDCLADDING WITH DPC ASREQUIRED
5mm GAP
5mm
GAP
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
INTERNAL CORNER
13 / 212018
20mm HORIZONTAL CAVITYBATTEN
METALCRAFT ESPAN™VERTICAL CLADDING
INTERNAL WALL LINING
PRE-FINISHED 8g WAFER-TEK SCREWWITH EPDM WASHER
WALL FRAMING
PRE-FINISHED EXTERNALCORNER FLASHING
PERMEABLE WALL UNDERLAY, SHOWNDASHED
PRE-FINISHEDSECONDARY FLASHING
POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEKSCREW
SEPERATE BATTEN ANDCLADDING WITH DPC ASREQUIRED
5mm
GAP
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
EXTERNAL CORNER
14 / 212018
PERMEABLE WALLUNDERLAY, SHOWNDASHED
METALCRAFT ESPAN™VERTICAL CLADDING
PRE-FINISHED FLAT HEADWAFER-TEK SCREW WITHEPDM WASHER
INTERNAL WALL LINING
SEPARATE BATTEN ANDFLASHING AS REQUIRED WITHDPC
WALL FRAMING
PRE-FINISHED SOAKERFLASHING TO LINE UP WITHWINDOW JAMB ABOVE
20mm HORIZONTAL CAVITYBATTEN
SOAKER FLASHING ONLY REQUIRED TOLINE UP WITH WINDOW JAMB ABOVE.REFER TO MRM CODE OF PRACTICEVERSION 2.2 /2012 FOR REQUIRMENT.
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
SOAKER FLASHING
15 / 212018
METALCRAFT ESPAN™ VERTICALCLADDING
PRE FINISHED SCREWWITH RUBBERWASHER
20mm HORIZONTAL CAVITYBATTEN
FIBRE CEMENT BOARDBY OTHERS
PRE FINISHEDALUMINIUM FLASHING
PERMEABLE WALLUNDERLAY, SHOWNDASHED
INTERNAL WALL LINING
SEPARATE BATTEN AND FLASHING ASREQUIRED WITH DPC
5mm
GAP
MIN. 50mm
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
CHANGE IN CLADDING
16 / 212018
METALCRAFT ESPAN™ VERTICALCLADDING
WALL FRAMING
PRE FINISHED SCREWWITH RUBBERWASHER
CONCRETE WALL BYOTHERS
CONTINUOUS AIR SEAL ONBACKING ROD
DPC
PRE FINISHED ALUMINIUMFLASHING
20mm HORIZONTAL CAVITYBATTEN
PRE-FINISHED POP RIVETBEDDED IN SILICONE
PERMEABLE WALLUNDERLAY, SHOWNDASHED
SEPARATE BATTEN ANDFLASHING AS REQUIREDWITH DPC
INTERNAL WALLLINING
PRE-FINISHEDSECONDARY FLASHING
Mastic bead
5mm
GAP
ALTERNATIVE OPTION
Rawlplug
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
CLADDING ABUTMENT
17 / 212018
PERMEABLE WALL UNDERLAY, SHOWNDASHED
INTERNAL WALL LINING
WALL FRAMING
METALCRAFT ESPAN™VERTICAL CLADDING
PRE-FINISHED NON-PERFORATEDCLOSURE FLASHING WITH 10° FALLPRE-PRIMED SKIRTING
CONCRETE SLAB
MIN
. 50m
m L
AP
VEN
TILA
TIO
N G
AP
3-5m
m
DR
IP E
DG
E TO
CLA
DD
ING
MIN
. 15m
m G
AP
METALCRAFT ESPAN™ CLIP SYSTEMWITH 12G x 35mm SCREWS
STST OR GALV. FLAT HEAD NAIL FORFLASHING
CAVITY CLOSER AS REQUIRED TONZBC
20mm HORIZONTAL CAVITY BATTEN
SEPERATE BATTEN AND CLADDING ASREQUIRED WITH EPDM
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
BOTTOM OF CLADDING (FLUSH)
18 / 212018
PERMEABLE WALL UNDERLAY OVERFLASHING, SHOWN DASHED
INTERNAL WALL LINING
WALL FRAMING
METALCRAFT ESPAN™ VERTICALCLADDING
STST OR GALV. FLAT HEAD NAIL FORFLASHING
PRE-PRIMED SKIRTING
CONCRETE SLAB
METALCRAFT ESPAN™ CLIP SYSTEMWITH 12G x 35mm SCREW
PRE-FINISHED NON-PERFORATEDCLOSURE FLASHING WITH 10° FALL
CAVITY CLOSER AS REQUIRED TONZBC
20mm HORIZONTAL CAVITY BATTEN
SEPERATE BATTEN AND CLADDING ASREQUIRED WITH DPC
3-5m
m V
ENTI
ALTI
ON
GAP
MIN
. 50m
m L
APM
IN. 7
5mm
CO
VER
ALTERNATIVE OPTION
6mm GAPM
IN. 5
0mm
LAP
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet 1 : 2
BOTTOM OF CLADDING (RECESSED)
19 / 212018
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet
3D WINDOW FLASHINGS
20 / 212018
RECESSED WINDOW FLASHINGS
HEAD FLASHING
JAMB FLASHING
SILL FLASHING
ALUMINIUMWINDOWJOINERY
METALCRAFTESPAN™ VERTICALCLADDING
LIP OF DISCHARGE AT LOWEST POINTOF ROOF
DOWNPIPE
OVERFLOW BELOW OPENING LEVEL, 1.5 xCROSS-SECTION AREA OF DOWNPIPE
METALCRAFT ESPAN™ VERTICALCLADDING
EITHER SIDE
50 mm MIN OPENING200 mm MIN
OPE
NIN
G
75 m
m M
IN
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL VERTICAL CLADDING
RVEP
Espan 340 / 470™
- CAVITY SYSTEM FOR VERTICAL CLADDING : 20mm NOMINAL THICK(VERTICALLY DRAINING) HORIZONTAL CAVITY SYSTEM WITH BATTENSAS APPLICABLE TO SUPPORT CLADDINGS & FLASHINGS TO NZBC.
ScaleDate Sheet
3D RAINWATER HEAD
21 / 212018