estandar iec 60947-2.pdf
TRANSCRIPT
International standardIEC 60947-2Low voltage switchgearPart 2: Circuit-breakers
DBTP83-Fr-03/99
E55
229
0523
87
5310
1
2
Standard IEC 60947-2 Contents
n I. General 3
n 2. Definitions 8
n 3. Circuit-breaker characteristics 10
n 4. Constructional requirements 14
n 5. Specific points (appendices) 21
n 6. Tests 27
n 7. Conclusion 34
3
Standard IEC 60947-2
Standard IEC 60947-2n Came into force in 1989n Takes into account the circuit-breaker main technological upgradesStandard IEC 60947-2n Is internationally recognized and approved
and is applied in the majority of countries (> 100)
General
E55
225
IEC
IEC
UL
CSAIEC
JIS/IEC
IEC
IEC
IEC
4
Standard IEC 60947-2 Generalconstitution
E55
231
IEC60947
IEC60947-1
IEC60 947-2
IEC 60947-3
IEC 60947-4-1
IEC 60947-4-2
IEC 60947-6-2
IEC 60947-7-1 … ...
or
or or or
or or
Standard IEC 60947-2 is part of a set of 7 standards characterizinglow voltage switchgear
Generalrules
Circuit-breakers
SwitchesContactorsand starters
Dimmersand starters
Control andconnectiondevices
Terminalblock
5
Standard IEC 60947-2 GeneralThe scope
« Standard IEC 60947-2 applies to circuit-breakers, the main contactsof which are intended to be connected to circuits, the rated voltage ofwhich does not in exceed 1000 V AC or 1500 DC; … »
The standard applies to circuit-breakers intended for use byexperienced operators.
0359
28a
0416
24
0311
07a
6
Standard IEC 60947-2 GeneralThe scope
Standard IEC 60947-2 contains additional specifications for:n Circuit-breakers suitable for isolationn Residual current devices (appendix B)n Circuit-breakers with electronic protection (appendices J and F)n Circuit-breakers for IT systems (appendix H)
E55
233
7
Standard IEC 60947-2 General
Standard IEC 60947-2 definesn The circuit-breaker classificationo according to utilization category A or Bo according to design type
air circuit-breaker, moulded case circuit-breaker
n The circuit-breaker mechanical and electrical data:size, trip unit, etc.
E55
232
8
Standard IEC 60947-2 DefinitionsCircuit-breaker classification
Utilization category A Utilization category BCircuit-breaker not specifically intended Circuit-breaker specifically intendedfor discrimination for discrimination:n Without an intentional short-time delay n With intentional short-time delay
(adjustable)n Without short time withstand current n With short time withstand current
E55
235
E55
234
9
Standard IEC 60947-2
Extract from appendix K of standard IEC 60947-2Characteristics Ue Rated operational voltagevoltage Ui Rated insulation voltage
Uimp Rated impulse withstand voltagecurrent In Rated current
Ith Conventional free-air thermal currentIthe Conventional enclosed thermal currentIcm Rated short-circuit making capacity
short-circuit Icu Rated ultimate short-circuit breaking capacityIcs Rated service short-circuit breaking capacityIcw Rated short-time withstand currentIr Adjustable overload setting current1.05 x Ir Conventional non-tripping current
trip unit 1.30 x Ir Conventional tripping currentIsd Short time delay tripping setting currentIi Instantaneous tripping setting current
DefinitionsTerminology / Vocabulary
10
Standard IEC 60947-2 Circuit-breaker characteristicsOverload withstand
In (in A rms) = rated currentn Maximum uninterrupted current withstood at ambient temperature, given without abnormal temperature rise
Ir (in A rms) = adjustableoverload setting currentn Ir depends on Inn Ir characterizes the
overload protection
E55
236
11
Standard IEC 60947-2 Circuit-breaker characteristicsShort-circuit withstand
Icu (kA rms) = rated ultimateshort-circuit breaking capacityn This performance expresses
the maximum value of theshort-circuit current that canbe broken by the circuit-breaker
E55
237
12
Standard IEC 60947-2 Circuit-breaker characteristicsShort-circuit withstand
E55
238
Standard IEC 60947-2 introduces anew important performance
Ics (as a % of Icu) = rated serviceshort-circuit breaking capacityn This performance expresses
the suitability of a circuit-breaker toensure fully normal service afterbreaking this current 3 times
n Normal ratio between Ics and Icu
Utilization category A Utilization category B % of Icu % of Icu 25 50 50 75 75 100 100
13
Standard IEC 60947-2 Circuit-breaker characteristicsShort-circuit withstand
Standard IEC 60947-2 introduces anew performance forcategory B circuit-breakers
Icw (in kA rms) = rated short-timewithstand current
n Icw is the maximum short-circuitcurrent that a circuit-breaker canwithstand for a short duration∆t without deterioration ofthese characteristics
n ICW must be at least equal to12 In or 5 kA for In ≤ 2500 A30 kA for In > 2500 A
n The standardized delay time ∆t is: 0.05 - 0.1 - 0.25 - 0.5 - or 1s
E55
239
14
Standard IEC 60947-2 Constructional requirementsIsolation co-ordination
The circuit-breaker, as a safety device, must be able to withstand
n Network overvoltagesthis suitability is characterized by the withstand to the conventionaldielectric test at 2 Ui + 1000 - 1 min at power frequency
n Impulse voltages ( «lightning stroke» simulation)this suitability is characterized by the withstand to the1.2/ 50 µs impulse voltage test of value Uimp
E55
240
15
Standard IEC 60947-2 Constructional requirementsIsolation co-ordination
Uimp (kV peak) = rated impulse withstand voltage
Characterization of Uimp
n Depends on the LV network voltage
n Depends on the position of the circuit-breaker in the LV network
n Depends on altitude: Uimp must be valid up to 2000 mtests carried out at +23 % of value
8
16
Standard IEC 60947-2
Characterization of Uimp
Nominal Applications installation voltage
at the origin of the on the distribution and at loadinstallation/MSB final circuits level
230/400 V 6 4 2.5 400/690 V 8 6 4
Constructional requirementsIsolation co-ordination
E55
243
17
Standard IEC 60947-2 Constructional requirementsIsolation co-ordination
Industrial circuit-breaker Uimp = 8 kVn Tests to be consideredo Uimp + 23 % = 9.8 kV
o standard industrial circuit-breakers and those suitable for isolation
Application of Impulse voltage value impulse voltage Breakers Disconnector BreakersPhase-to-phase 9.8 kV 9.8 kVUp-to-downstream 12.3 kV (*)contacts openPhase-to-earth 9.8 kV 9.8 kV
(*) 14.7 kV for front face class II circuit-breaker as per IEC 61 140
Test between upstreamand downstream
18
Standard IEC 60947-2 Constructional requirementsCircuit-breaker suitable for isolation
Test of isolation suitability
n 3 tests designed to ensure users that a device«suitable for isolation» is not dangerous
o in open position... - even after having eliminated a short-circuit up to Icu - even in the event of overvoltage on the network ... or in closed position
o cannot be declared «open» and/or « padlockable »
19
Standard IEC 60947-2 Constructional requirementsCircuit-breaker suitable for isolation
Leakage current measurement testat 110 % of maximum utilization voltage Uen New device, leakage current < 0.5 mA per pole,n After breaking at Ics, leakage current < 2 mA per pole,n After durability tests, leakage current < 2 mA per pole,n After breaking at Icu, leakage current < 6 mA per pole
Impulse voltage withstandn Uimp = 12 kV (instead of 9.8 kV) between the inlet and the outlet of the
open device(*) 14.7 kV for front face class II circuit-breaker as per IEC 61 140
Mechanical ruggedness test
n Circuit-breaker with a pole held in closed position must not be indicated«open» and/or «lockable» by padlock.
Padlockable in « open » position
Class llenclosure
Class llfront face
Front face class ll
Mechanical ruggedness
20
Standard IEC 60947-2 Constructional requirementsCircuit-breaker/isolator
Marking
n A circuit-breaker that is «suitable for isolation» will display the circuit-breaker/isolator symbol on its front face
E55
246
21
Standard IEC 60947-2 Specific points (appendix A)
n Cascading n Discrimination
Standard IEC 60947-2 recognizes and defines circuit-breakerco-ordination
22
Standard IEC 60947-2 Specific points (appendix B)Residual current device
Standard IEC 60947-2 appendix B defines
n The characteristics of the residual current devices
n The tests and verifications that must be performed on a residual currentdevice
o in order to guarantee the safety of the residual current function
o in order to guarantee the quality of the residual current function(malfunctioning)
23
Standard IEC 60947-2 Specific points (appendix B)Residual current device
Tests and verifications
n Safety of the residual current function
o after breaking at Icu and Ics, no deterioration of the earth leakage protection units,
o correct operation of the function:- in harsh environmental conditions
(damp heat 28-day cycle)14h30 duration(h)
24
Standard IEC 60947-2 Specific points (appendix B)Residual current device
Tests and verifications
n Quality of the residual current function
o no nuisance tripping in the event of:- single-phase overcurrent (standardized tests)- current waves generated by impulse voltage- network capacitance load- in event of an insulation fault with a DC component
(class A),
25
Standard IEC 60947-2 Specific points (appendix F)Circuit-breaker with electronic trip unit
Standard IEC 60947-2 appendices F definesn The additional specifications
for circuit-breakers withelectronic trip unit
n The tests required to guaranteetheir correct operation inrestrictive industrialenvironments
o EMC tests: immunity todisturbances,
o EMC tests: verification ofradiated emission level,
o (very harsh) environmentaltests, dry and damp heat,temperature variationsAfter each test,verification of propertrip unit operation
E55
251
26
Standard IEC 60947-2 Specific points (appendix H)
Circuit-breaker suitable for ITStandard IEC 60947-2n Defines this breaking type
(with a single pole at phase-to-phase voltage)n Stipulates a specific testo the devices not suitable for use with the IT system are marked
with the symbol IT
E55
252
27
Standard IEC 60947-2 Tests
Standard IEC 60947-2 makes provision for complete device testing
Cumulative tests grouped into sequencesn One sample undergoes all the sequence tests
5 Test Sequences + 1 Combined test sequencen All the functions and characteristics are tested
Specific testsn Circuit-breaker suitable for isolationn Residual current device,n Circuit-breaker with electronic trip unit,EMC Testsn etc.
28
Standard IEC 60947-2
Test sequencesCategory A Category B
Icw < Ics Icw = Ics Icw = Ics = IcuSequence 1General operating n n n ncharacteristicsSequence 2Service breaking n ncapacity IcsSequence 3Ultimate breaking n n ncapacity IcuSequence 4Rated short time nwithstand current IcwCombinedtest sequence n nExample NS100 to NS630 C801 to C1251 CM1251 Masterpact
+ Multi 9 Masterpact H2-L1 to 3200 N1-H1
Tests
29
Standard IEC 60947-2
Examplen Sequence 1 and 2Test Circuit-breaker type Tests to be performed in turn Additional tests forsequences Cat. A Cat. B on the same circuit-breaker circuit-breakers declared
Icw Icw Icw suitable for isolation< Ics = Ics = Ics
= IcuSequence 1 1. Verification of tripping thresholds 1. DittoGeneral 2. Dielectric properties 2. Dielectric propertiesoperating 2.1 If an Uimp is declared by the Uimp withstand compulsory:characteristics Manufacturer: Uimp Test phase-to ditto opposite plus between
n phase, phase-to-earth Inlet and Outlet: Uimp + 25 %2.2 If no Uimp is declared and leakage current test
Dielectric test 50 Hz at 2Ui + 1000 (< 0.5 mA per pole at 110 % Ue)3. Mechanical durability 3. Ditto4. Electrical durability 4. Ditto5. Operation in overload at 6 In 5. Ditto6. Dielectric withstand at 2 Ue (min. 1000 V) 6. Ditto + leakage current test
(< 2 mA per pole at 110 % Ue)7. Temperature rise at In 7. Ditto8. Verification of non-drift of 8. Ditto
overload trip unitsSequence 2 1. Three successive current breakings Ics 1. DittoService as per cycle O - 3 mm - CO - 3 mm - CObreaking 2. Verification of suitability for 2. Dittocapacity Ics n operation, achievement of 5 %
of electrical durability3. Dielectric withstand at 2 Ue (50 Hz-1 mm) 3. Ditto + leakage test current
(≤ 2 mA per pole at 110 % Ue)4. Temperature rise at In 4. Ditto5. Verification of non-drift of 5. Ditto
overload trip units
Test sequences
30
Standard IEC 60947-2 Tests
n Tripping curveso all the important points
on the tripping curveare tested
o essential features are tested in realand the hardest conditions
E55
228
31
Standard IEC 60947-2
In «sequence 3» of standardized testsO - t - CO test
Verificationsn Dielectric at 2 Ue (minimum 1000 V) for 1 minute,
NB: for circuit-breaker suitable for isolationtest of leakage I = < 6 mA at 110 % Ue
n Verification of overload trip units at 2 Ir
Standard IEC 60947-2 clarifies the definition of circuit-breakerbreaking capacityThe circuit-breaker must not be «dangerous » after 2 breakings at Icu
Tests Icu
32
Standard IEC 60947-2 Tests Ics
In « sequence 2 » of standardized testsO - t - CO - t - CO test
Verificationsn Dielectric at 2 Ue (minimum 1000 V) for 1 minute,
NB: for circuit-breaker suitable for isolationtest of leakage I ≤ 2 mA at 110 % Ue
n Of suitability to break its nominal current by achieving 5% of electricaldurability
n Of temperature rise at In,n Verification of overload trip units at Ir
The circuit-breaker must be suitable for operation after a short circuitat Ics. This performance is guaranteed 3 times.
The Ics performance represents a « practical » breaking capacity.
33
Standard IEC 60947-2
In « sequence 4 » of standardized testsCategory B circuit-breaker
Verificationsn Device withstand at Icw and ∆t indicated by the manufacturern Of temperature rise at In, after O - t - CO cycle
at Icw at maximum voltagen Dielectric at 2 U 1(minimum 1000 V) for 1 minute,n Overload trip units at 2 Ir
The circuit-breaker must be suitable for operation after a short-circuitat Icw
Tests Icw
34
Standard IEC 60947-2 Conclusion
Standard IEC 60947-2
A standard that adheres to realitySimple, clear choice of circuit-breakersn In and Icu are sufficient to determine the circuit-breaker,
New recognized, defined and tested characteristics / functionsn Suitability for isolation,n Residual current device,n Circuit-breakers with electronic trip unit
Tests representative of the real stresses exerted on a circuit-breakern Ics, etc.n Cumulative tests in sequences,n Tests of all the design characteristics
35
Standard IEC 60947-2
Standard IEC 60947-2
A standard that adheres to realityExamples
o probable Isc very close to o probable Isc less thanprospective Isc: Ics = 100 % Icu prospective Isc: Ics = 50 % IcuNS160N is optimized C60L is optimized
Conclusion
E55
258
E55
234
E55
259
E55
260
1250 kVA
Isc = 29 kA
28 kA
160 A
MSB
Sub-distributionboard
18 kA
8.5 kA
36
Standard IEC 60947-2 Conclusion
A circuit-breaker certified according to Standard IEC 60947-2guarantees a quality device with durable performance of all its safetyfunctions.
E55
256