Event Notification ModuleTM

Installation GuideVersion 7.0

63220-083-03A108/2012

Event Notification Module 63220-083-03A108/2012

© 2012 Schneider Electric. All Rights Reserved.2

Notices

StruxureWare, StruxureWare Power Monitoring, PowerLogic, Citect, and Schneider Electric are either trademarks or registered trademarks of Schneider Electric in France, the USA, and other countries. All other trademarks are property of their respective owners.

63220-083-03A1 08/2012

© 2012 Schneider Electric. All Rights Reserved. 3

Safety Information

Important InformationRead these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

Please NoteElectrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

DANGERDANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNINGWARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.

CAUTIONCAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.

NOTICE, is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.

Table of Contents 63220-083-03A108/2012

© 2012 Schneider Electric. All Rights Reserved4

Introduction ..................................................................................................5

Requirements ..............................................................................................5

Upgrade from Active Pager Module or Event Notification Solution ..............6

Standalone Installation ................................................................................7

Database Server Installation .....................................................................17

Application Server Installation ...................................................................25

63220-083-03A1 Event Notification Module08/2012 Introduction

© 2012 Schneider Electric All Rights Reserved 5

Introduction

Event Notification Module (ENM) installation is one step in the commissioning of a system. The ENM installer allows for a great deal of flexibility including both local and remote database instances. To facilitate remote installation, the installer provides three install paths:

Complete Installation: The Event Notification Module and the SQL database will reside on the same server host. The user selects an SQL instance on the local machine for the install to configure the database server.

Database Server: Installs the database components on the target database server for Event Notification Module.

Application Server: The user must select the target database server, but only the application components will be installed. The user must install the database server first.

Requirements

Note the following system requirements when installing or using Event Management solutions.

NOTE: For server systems where SQL Server will also be installed, refer to the SQL requirements to ensure the system can support both SQL and ENM.

Hardware:

Software:

Component Minimum Requirement

Processor Quad CoreMemory 4 GBHard Drive 150 GBNetwork

Component Required

Operating System Windows 7 64-bit or 32-bitWindows Server 2008 SP2Windows Server 2008 R2

SQL Server MS SQL Server 2008 or 2008 R2Language EnglishOther Internet Information Services Version 7.0 or higher

.NET Version 4.0Internet Explorer 8 (In Compatibility Mode)

Event Notification Module 63220-083-03A1Upgrade from Active Pager Module or Event Notification Solution 08/2012

© 2012 Schneider Electric All Rights Reserved6

Upgrade from Active Pager Module or Event Notification Solution

ENM was previously called Active Pager Module (APM 6.3) or Event Notification Solution (ENS 6.4). The APM 6.3 and ENS 6.4 applications were installed on systems with the following configuration:

Windows 2008, SQL 2005 Express, IONE 6.0 SP1

To upgrade a system from APM 6.3 or ENS 6.4 to ENM 7.0, follow these steps:

1. Detach the APM database PLES_APM, if the customer wants to preserve this database.2. Detach the History database PLES_AEHistory, if the customer wants to preserve the

historical data.3. Uninstall APM and Alarm Sentry or ENS.

4. Upgrade SQL Express 2005 to SQL 2008 Standard or R2.5. After successfully upgrading SQL server, attach the PLES_APM and PLES_AEHistory

databases if they were saved.6. (Optional) Upgrade IONE 6.0 SP1 to SPM 7.0 or SPM 7.0.1.7. On the ENM installer disc, browse to the LegacyCleanup folder.

8. Run the LegacyCleanup.bat file. This utility deletes any files left behind after uninstalling APM and Alarm Sentry.

9. Start the ENM installer and follow the install steps based on the desired setup type:• Standalone - Refer to “Standalone Installation” on page 7.• Database Server - Refer to “Database Server Installation” on page 17.• Application Server - Refer to “Application Server Installation” on page 25.

63220-083-03A1 Event Notification Module08/2012 Standalone Installation

© 2012 Schneider Electric All Rights Reserved 7

Standalone Installation

Follow these steps if you are installing the ENM application and the database on the same server.

1. Insert the ENM Installation disc. The Event Notification Module installation screen appears.

2. Under Installs, click Event Notification Module to start the installation. The installation wizard appears.You can also start the installation by browsing the files on the disc and running Setup.exe.

Event Notification Module 63220-083-03A1Standalone Installation 08/2012

© 2012 Schneider Electric All Rights Reserved8

3. License Agreement: Click on I Agree to proceed

4. Setup Type: Select Event Notification Module – Complete and click Next.

63220-083-03A1 Event Notification Module08/2012 Standalone Installation

© 2012 Schneider Electric All Rights Reserved 9

5. File Destination: Click Next to install ENM in the default location. You can select a different folder, if desired. You will be prompted to create a new folder if this is a new install.

NOTE: To select a different install location, click the browse button with 3 dots.

Event Notification Module 63220-083-03A1Standalone Installation 08/2012

© 2012 Schneider Electric All Rights Reserved10

6. Database Server: The local database instance is selected by default. The format displayed is “machine name\database instance”; please ensure it is correct. Enter the Username and Password login credentials associated with the database and click Next.

NOTE: If you enter the wrong credentials, an error appears.

63220-083-03A1 Event Notification Module08/2012 Standalone Installation

© 2012 Schneider Electric All Rights Reserved 11

7. Citect Credentials: Enter the credentials for PowerLogic SCADA if this component is part of the server configuration.

8. Database Maintenance Credentials: Enter the Windows administrator login credentials associated with the machine that ENM is being installed.

The username and password credentials get verified in the screen that follows.

Event Notification Module 63220-083-03A1Standalone Installation 08/2012

© 2012 Schneider Electric All Rights Reserved12

9. Check System: The ENM installer verifies if the requirements are met. If there are any issues, the installer notifies you to correct the issue.

The installer verifies these items:

• Operating System• Previous ENM installs• SQL Server version• Local SQL instance• SQL Server connection• ASP.NET• Database maintenance credentials• SQL Mixed Mode Authentication

63220-083-03A1 Event Notification Module08/2012 Standalone Installation

© 2012 Schneider Electric All Rights Reserved 13

10. Ready to Configure: The configuration choices are displayed before being installed. Please ensure that all items are correct before proceeding.

• Click Back to correct any items.• Click Install to continue. The Copy Files screen appears and the ENM files are

copied to the machine:

Event Notification Module 63220-083-03A1Standalone Installation 08/2012

© 2012 Schneider Electric All Rights Reserved14

11. Advosol OPC Core Component: When prompted, accept the license agreement for Advosol OPC Core Component. Click Next and complete the installation. This component must be installed.

Configure System: The selected configuration settings are applied.

If any errors occurred, the “Configuration failed” message appears. Resolve the issues as follows:

• Select the configuration step that failed and click Open Log to diagnose the error.

63220-083-03A1 Event Notification Module08/2012 Standalone Installation

© 2012 Schneider Electric All Rights Reserved 15

• Click the Try Again link to complete that part of the installation.

Configuration Complete: After the ENM installer finishes configuring the system, the “Configuration Complete” message appears.

Event Notification Module 63220-083-03A1Standalone Installation 08/2012

© 2012 Schneider Electric All Rights Reserved16

12. Complete: The Complete page appears after the install is successful.

• Click the Installation Log link to view details recorded for the installation process. • Click Close to finish.

The StruxureWare Solutions shortcut is added to the Windows Desktop.

Refer to the Event Notification Module 7.0 User Guide for instructions to configure and use ENM.

63220-083-03A1 Event Notification Module08/2012 Database Server Installation

© 2012 Schneider Electric All Rights Reserved 17

Database Server Installation

Distributed installation requires two machines: the Database server and Application Server. The ENM database is installed on the Database Server and ENM components are installed on the Application Server.

NOTE: For a distributed system, install the Database Server before the Application Server.

1. Start the install by running the Setup.exe.2. License Agreement: Click I Agree to continue.

Event Notification Module 63220-083-03A1Database Server Installation 08/2012

© 2012 Schneider Electric All Rights Reserved18

3. Setup Type: Select “Database Server” and click Next.

63220-083-03A1 Event Notification Module08/2012 Database Server Installation

© 2012 Schneider Electric All Rights Reserved 19

4. File Destination: Click Next to install ENM in the default location. You can select a different folder, if desired.

You will be prompted to create a new folder if it’s a new install.

5. Database Server: The local database instance is selected by default. The format is “machine name\database instance”; please ensure it is correct. Enter the Username and Password login credentials associated with the database and click Next.

Event Notification Module 63220-083-03A1Database Server Installation 08/2012

© 2012 Schneider Electric All Rights Reserved20

6. Citect Credentials: Enter the credentials for PowerLogic SCADA if this component is part of the server configuration.

7. Database Maintenance Credentials: Enter the Windows administrator login credentials associated with the machine that ENM is being installed.

The username and password credentials get verified in the screen that follows.

63220-083-03A1 Event Notification Module08/2012 Database Server Installation

© 2012 Schneider Electric All Rights Reserved 21

8. Check System: The ENM installer verifies if the requirements are met. If there are any issues, the installer notifies you to correct the issues.

The installer verifies the following items:

• Operating System• SQL Server version• Local SQL instance• SQL Server connection• Database maintenance credentials• SQL Mixed Mode Authentication

Event Notification Module 63220-083-03A1Database Server Installation 08/2012

© 2012 Schneider Electric All Rights Reserved22

9. Ready to Configure: The configuration choices are displayed before being installed. Please ensure that all items are correct before proceeding.

• Click Back to correct any items.• Click Install to continue. The Copy Files screen appears. The ENM files are copied to

the machine:

10. Configure System: The selected configuration settings are applied.If any errors occurred, the “Configuration failed” message appears. Resolve the issues as follows:

• Select the configuration step that failed and click Open Log to diagnose the error.

63220-083-03A1 Event Notification Module08/2012 Database Server Installation

© 2012 Schneider Electric All Rights Reserved 23

• Click the Try Again link to complete that part of the installation.

11. Configuration Complete: If successful the following screen appears.

Event Notification Module 63220-083-03A1Database Server Installation 08/2012

© 2012 Schneider Electric All Rights Reserved24

12. Complete: The Complete screen appears after the install is successful.

• Click the Installation Log link to view details recorded for the installation process. • Click Close to finish.

63220-083-03A1 Event Notification Module08/2012 Application Server Installation

© 2012 Schneider Electric All Rights Reserved 25

Application Server Installation

NOTE: For a distributed system, install the Database Server before the Application Server.

1. Start the ENM installer on the Application Server.2. License Agreement: Click I Agree to continue.

3. Setup Type: Select “Application Server” and click Next.

Event Notification Module 63220-083-03A1Application Server Installation 08/2012

© 2012 Schneider Electric All Rights Reserved26

4. File Destination: Click Next to install in the default location. You can select a different folder, if desired. You will be prompted to create a new folder if this is a new install.

5. Click Yes to create the new folder.

6. Database Server: The local database instance is selected by default. The format displayed is “machine name\database instance”; please ensure it is correct. Enter the Username and Password login credentials associated with the database and click Next.

63220-083-03A1 Event Notification Module08/2012 Application Server Installation

© 2012 Schneider Electric All Rights Reserved 27

7. Database Maintenance Credentials: Please enter Windows administrator login credentials associated with the machine that ENM is being installed.

The username and password credentials get verified in the screen that follows.

8. Check System: The ENM installer verifies if the requirements are met. If there are any issues, the installer notifies you to correct the issues.

The installer verifies the following items:

• Operating System• SQL Server connection• Database maintenance credentials

Event Notification Module 63220-083-03A1Application Server Installation 08/2012

© 2012 Schneider Electric All Rights Reserved28

9. Ready to Configure: The configuration choices are displayed before being installed. Please ensure that all items are correct before proceeding.

• Click Back to correct any items.• Click Install to continue. The Copy Files screen appears and the ENM files are

copied to the machine:

63220-083-03A1 Event Notification Module08/2012 Application Server Installation

© 2012 Schneider Electric All Rights Reserved 29

10. Advosol OPC Core Components: When prompted, accept the license agreement for Advosol OPC Core Component. Click Next and complete the installation. This component must be installed.

Configure System: The selected configuration settings are applied. After the ENM installer finishes configuring the system, the “Configuration Complete” message appears.

If any errors occurred, the “Configuration failed” message appears. Resolve the issues as follows:

• Select the configuration step that failed and click Open Log to diagnose the error.• Click the Try Again link to complete that part of the installation.

Event Notification Module 63220-083-03A1Application Server Installation 08/2012

© 2012 Schneider Electric All Rights Reserved30

11. Complete: The Complete screen appears after the install is successful.

• Click the Installation Log link to view details recorded for the installation process.• Click Close to finish.

The StruxureWare Solutions shortcut is added to the Windows Desktop.

Refer to the Event Notification Module 7.0 User Guide for instructions to configure and use ENM.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

63220-083-03A1 08/2012

© Schneider Electric All Rights Reserved.

Schneider Electric295 Tech Park Drive, Suite 100LaVergne, TN 37086 USA

For technical support:[email protected](00) + 1 250 544 3010

Contact your local Schneider Electric sales representative for assistance or go towww.schneider-electric.com

Event Notification ModuleTM 7.0

Installation Guide