Highly configurable genset controller designed to handle a wide range of critical and complex parallel applications, including multiple Mains and CHP systems Up to 24 gensets connected on the same bus and Mains parallel application Internal Load sharing, Synchronizer and VAR regulation PLC functions with PID blocks Digital UP/DOWN command for speed governor and AVR Mains and Genset circuit breaker management True RMS readings on generator and mains voltages and currents with additional current measurement for neutral or differential protection (51N) Active, Reactive and Apparent power measurement Frequency and power measurement on Mains input 20 fully programmable digital Input with possibility of additional several Input 16 digital Output + 2 Fixed with possibility of additional several Output Several communication tools (RS232, Insulated RS485, RJ45 Ethernet, USB port) Large graphic display. TFT Colour display available in DST4602Evolution Real Time Clock and Events and data recording Remote control systems KEMA Certification - Guideline BDEW (DE)

Upload: buithuan

Post on 10-Mar-2018

251 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

Highly configurable genset controller designed to handle a wide range of critical and

complex parallel applications, including multiple Mains and CHP systems

Up to 24 gensets connected on the same bus and Mains parallel application

Internal Load sharing, Synchronizer and VAR regulation

PLC functions with PID blocks

Digital UP/DOWN command for speed governor and AVR

Mains and Genset circuit breaker management

True RMS readings on generator and mains voltages and currents with additional current measurement for neutral or differential protection (51N)

Active, Reactive and Apparent power measurement

Frequency and power measurement on Mains input

20 fully programmable digital Input with possibility of additional several Input

16 digital Output + 2 Fixed with possibility of additional several Output

Several communication tools (RS232, Insulated RS485, RJ45 Ethernet, USB port)

Large graphic display. TFT Colour display available in DST4602Evolution

Real Time Clock and Events and data recording

Remote control systems

KEMA Certification - Guideline BDEW (DE)

Page 2: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

DST4602 & DST4602Evolution

are the top products among the

controllers for gensets. They are particularly designed for complex plants, where there is the need of a huge number of settings, functions and parameters aimed at managing the genset and its auxiliary circuits.

DST4602 & DST4602Evolution

are highly configurable genset

controllers for advanced multiple and single synchro/parallel applications. In details, they allow the connection up to 24 gensets on the same bus working in island mode, and even the control of gensets running in synchro/parallel with the mains. Thanks to the high configurable level of the controllers and the PLC inbuilt functions with PID block, DST4602 &

DST4602Evolution

can be well used for CHP power plants

composed by Gas, Diesel Biofule, Dualfuel gensets.

DST4602 & DST4602Evolution

are designed to allow an easy

installation thanks to its internal Load Sharing, Synchronizer and VAR regulation.

DST4602 & DST4602Evolution

include the CAN J1939 interface

used by a wide range of engines (Volvo Penta, Scania, Perkins, MTU, Deutz, Cummins, John Deere, Caterpillar and others) and they can be also used with standard and traditional engines, whose measurements are performed by the embedded analogue interfaces.

DST4602 & DST4602Evolution

can be used together with several

Sices controllers like GC500, GC500Plus/Mains

and DST4601/PX.

In case of multiple gensets in parallel with the mains where the

back synchro is required, DST4602 & DST4602Evolution

can be

interfaced with the common parallel management controller MC100. In that way, any lack is avoided. The adjustable parameters of the controllers allow their use for standard and customized tasks. Parameters are programmed using the free software tool (BoardPRG), which can be freely downloaded thorough Sices website. It is also possible to set them directly by the keyboard of the controllers. The software for setting PLC logic (Plc Editor) is also available for free. The large graphic display is a user-friendly human interface, which is useful for an immediate visualization of measures and alarms coming form the genset. DST4602 has a powerful LCD display whose features are recommended also in critical environmental conditions.

On the other hand, DST4602Evolution

has an enhanced and

impressive 7’’ colour display with TFT technology. It is possible to improve the human interface, using D-MONITOR, a 12’’ touch panel that is the ideal solution for cogeneration (CHP) plants where it is necessary to visualize the thermal circuit of the plant.

DST4602 & DST4602Evolution

offer the storage of the events and

data occurred. This info can be accessed from the front panel and read through the display.

DST4602 & DST4602Evolution

provide several communications

devices/tools for local or remote control. In addition, in case of complex plants like Oil&Gas stations, their inbuilt protections can be increased by using an external protection relay called D-PRO, expanding the functions already included into the controllers.

The MODE selection is available in 2 versions:

With selector key

With push buttons.

Engine START and STOP pushbutton. ACK/MODE (acoustic alarm silencing and other aux. functions). GCB and MCB command using push buttons. LCD CONTRAST DECREASE/INCREASE. Four ARROW keys for LCD display selection mode, window selection, parameter change and other. EXIT, ENTER and SHIFT keys.

Page 3: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

RESET: engine start inhibition, load is forced to be supplied from the Mains. When the engine is running and the selector switch is turned to the 'OFF' position, the engine shutdown sequence activates. Reset of all alarms. Enable parameters change (programming). PROGRAM: access to all programmable parameters. Programming access can be controlled by means of a three level passwords. Some parameters can be changed even if the engine is running. MANUAL: engine manual START and STOP controls are enabled. The Genset protection devices are activated. The starting command is automatically disabled when the engine is running. MCB and GCB pushbuttons are enabled when generator is in operating range. Their function depends on the selected function mode. Manual synchronization can easily accomplished by built-in function. AUTOMATIC: function mode depends on the selected one: Single Prime Mover, Stand-by, Stand-by and Short Time Parallel, Single Parallel to Mains, Multiple Prime Mover, Multiple Parallel to Mains. TEST: Automatic start for testing operations with safety protections enabled. Test can be made unloaded, loaded or in parallel to mains. Upon Mains failure, the load is immediately supplied by the Genset. Parallel application: Parallel to mains application is allowed by the internal power regulator. Soft loading and unloading is automatically performed. Some interface protection is embedded in the board. Multiple prime mover application is allowed by means of CAN interface that allows load sharing. Up to 24 gen-sets can be connected to this bus. Synchronization is done through an internal digital synchronizer, avoiding external and expensive external synchronizers.

Generator Voltages: L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1 True RMS measurement Lx-N max. voltage < 300Vac cat. IV High voltage pulse = 6kV 1.2/50 us Max. measurable voltage = 25.000V (by external TV) Generator Currents: L1, L2, L3, N (*) True RMS measurement Nominal max. current: 5Aac, 1Aac Overload measurable current : 4 x 5Aac (sinusoidal) Internal current transformer Max. nominal current = 6000A (by external TA) (*) Neutral generator current measure (64) or, in alternative used for the measure of the power shared with the mains. Mains Voltage: L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1 True RMS measurement Lx-N max. voltage < 300Vac cat. IV High voltage pulse = 6kV 1.2/50 us Max. measurable voltage = 25.000V (by external TV) Generator and Mains Frequency meter: Resolution = 0.1 Hz Accuracy = ± 50ppm, ±35ppm/°C (typical) Battery Voltmeter: Resolution = 0.1V Oil Pressure Sensor: Settable curve based on sensors available

Water Temperature Sensor: Settable curve based on sensors available Fuel Level Sensor: Settable curve based on sensors available Up to 400 ohm Engine Revolution Counter: By pick-up. Programmable teeth number Same Input can be used by W signal

Active power Reactive power Apparent power Power factor: Total and phase by phase Active and reactive energy counter Hour counter for maintenance/rental Start Counter

Overspeed (12) Incomplete sequence (48) Belt-break Engine temperature warning and alarm Oil pressure warning and alarm Water level warning and alarm Max. power Fuel level

Underfrequency (81U) Overfrequency (81O) Undervoltage (27) Overvoltage (59) Power direction (32) Loss of excitation (Reverse reactive 32RQ) Time dependent overcurrent (51) IDMT Instantaneous overcurrent (50) Synchro-check (25) Phase sequence (47) Current and Voltage unbalance (46/47) Ground Fault Protection (51N or 51GN) as alternative to neutral measure (64). Negative sequence (I2) Phase overcurrent with voltage restraint/control (51V)

For Mains parallel applications there are the following protections: Rate of Change of Frequency (81R ROCOF) Vector shift Undervoltage (27) Overvoltage (59) Underfrequency (81U) Overfrequency (81O)

Page 4: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

New function available for the automatic adjustment of the power output based on the mains frequency value. This feature allows to maintain the safety conditions of the genset in case of the mains frequency drops under acceptable values for the genset. Compliant with BDEW German rules which regulates energy plants connection with the MV and HV. In conformity to the German technical guidance, the calculation for the current "positive sequence I1" has been introduced, adding it to the calculation of the current "negative sequence I2", already included. Real time calculation of active and reactive power and the power factor of the generator for the singles phases. 27T - Low voltage protection time-dependent (BDEW) 27Q - Low Voltage Protection with Directional reactive (BDEW) KEMA Certification

Real time clock calendar: Hour, minute, second, day, month, year (leap year), day of week. Rechargeable Lithium battery available as standard. Gen-set operation can be enabled based on days of the week and time. Test operation can be enabled based on days of the week. Date and time can be remotely adjusted by software. Fast and Slow trend history log: Up to 860 record based on the setup Event history log: Up to 860 record Fuel pump: Board manages a fuel pump by means an external power relays and by 5 input level signals. Auto and Manual operating mode. Maintenance warning: Board issue a warning when the running hours before maintenance are elapsed. Panel Temperature warning: Board issue a warning when panel temperature are approaching a specified temperature. Gen-Set lock function: Gen-Set operation can be remotely disabled. Unlocking requires the supplied password. Internal Alarm Horn: Internal Alarm Horn make easier panel assembling.

N.1 Serial port RS232 with MODBUS RTU protocol N.1 Serial port RS232 or RS485 insulated with MODBUS RTU protocol N.1 Serial port USB for firmware upgrade N.1 Setting for Ethernet interface

Direct GSM and PSTN Modem management Automatic call in case of event Available as option:

IEC 61850 Converter (NEW)

Serial converter RS232/485/USB.

Modem GSM.

REWIND - Module interface for Si.MO.NE using GPRS/SM

and GPS technology.

DANCE - Module interface for Si.MO.NE using Ethernet

technology.

Ethernet interface with MODBUS TCP/RTU protocol

Supervision software SicesSupervisor and SI.MO.NE

Plug-in for SCADA (personalized software) interface

CAN Interface with J1939 SAE Protocol and with MTU specifications.

In case of multiple plants with several gensets connected in synchro/parallel on the same bus, it is possible to set different automatic logics for start/stop gensets, based on the load request. In detail:

Manual setting of the master genset by means of selector

switch on the control panel

Automatic rotation of the Master genset after a fixed time per

day.

Automatic rotation of the Master genset after an elapsed

time.

Automatic selection of working gensets having a matching power with the request on load (NEW) (*)

Automatic start/stop of gensets in order to maintain the

minimum quantity of gensets able to supply the load “ON” (NEW) (*).

(*) Functions available for a max of 5 gensets.

Page 5: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

Load sharing: Load sharing is accomplished in parallel operations by means CAN interface or analogue interface. DST4602 controls the speed regulation in order to have the same percentage power among generator sets. Power modulation: Power regulation is allowed through internal power regulator. For electronic engines a CAN line is available for speed regulation, for traditional engines is however available a proper analogical interface. Reactive power regulation: DST4602 controls AVR directly in order to manage the reactive power. DST4602 is a MULTILANGUAGE DEVICE. The display languages available are: English, Italian, French, German, Spanish and Russian.

N. 20 Digital input (settable) N. 3 Analogical input for engine instruments N. 3 Additional analogical input N. 8 Settable and protected output N. 6 Settable output with relay N. 2 Switch relay for MCB and GCB

Up to 10 DITEL with CPU or 20 DITEL without CPU for a

max. of 160 Binary and settable Input and 160 Binary and settable Output, all of the insulated.

Up to 16 DITHERM/DIGRIN aimed for getting analogical

measures from thermocouples e/o thermoresistance (PT100)

Up to 16 DIVIT aimed for getting analogical measures of

current and/or voltage (0...10mA, 0...20mA, 0...5V, 0...10V)

Up to 8 DANOUT for max. 32 additional analogue output

(insulated) 0...10mA, 0...20mA, 0...5V, 0...10V

Innovative and automatic sequence already built-in DST4602 genset controller that allows to achieve a fast synchronization and paralleling of many gensets comprising in an emergency power station in a maximum time of 9 - 15 sec. (based on the alternator and engine features).

The advanced system called “Fast Paralleling” is an effective solution for those sensitive realities where any mains failure, even for a few seconds, could cause huge problems for the security of people and data and create damages for the production processes (banks, hospitals, data centres, etc…)Using the Fast Paralleling system, gensets are switched on, synchronized and ready to supply the loads in a few seconds from the mains failure signal.

How?

In case of mains failure, Sices genset control panel gets a

signal from the existing ATS in order to start to run the stand-by gensets.

The new operation logic implemented in DST4602 controls the

status of gensets, checking which of them are ready and available to start and take the load.

Gensets start to work all together with the relevant circuit

breakers already closed.

By means of a safety and proper control of speed ramp and

excitation range, gensets are simultaneously brought to the rated conditions.

All gensets are therefore ready and in parallel in 9-15 seconds

max. (based on the engines and alternator types).

The load is supplied by all gensets running in parallel.

If one or more gensets don’t start to work at the first starter,

the control logic opens the relevant alternator circuit breaker. The other gensets can go ahead with the fast starting operations.

The genset that has reached the rated conditions with delay,

can be inserted afterwards making the usual synchro operations.

Supply voltage: 8…33 Vdc Power consumption: typically less than 7W (+5W for display lamp) Rated Genset frequency: 50 or 60 Hz Digital Input: opto-isolated Static Output: 500mA @ 25°C, 360mA @ 50 °C, 20 Apk Relay Outputs: 10A nominal Auxiliary relays Output: 1A 30V

DST4602Evolution

is equipped with a dual processor for

improved response: One processor is aimed for the measures and operation sequences. The other one is aimed for the human interface (display) and for the management of LEDs and buttons. Weight: 1,6kg Overall dimension: 260 (W) x 202 (H) x 86 (D) Overall dimension display: 125(L) x 72(H) mm Panel cut-out: 240(L) x 172(H) mm Panel mounting: by means of stud-bolt Protection Grade: IP54 (front panel, by means of additional keylock protective cap and gasket) EMC: compliant with EN61326-1 Safety: built in compliance with EN61010-1 A tropicalized version for harsh environment is available on demand. DISPLAY Features: DST4602: 240x128 Pixel LCD: transflective with LED backlight Operating temperature: -25 °C to 70 °C Stock temperature: -30 °C to 80 °C

DST4602Evolution

800x450 Pixel TFT, 7’’ Colour display

Operating temperature: -20 °C to 70 °C Stock temperature: -30 °C to 80 °C

Page 6: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

On the left: User interface with display unit to be mounted on the control panel’s door. On the right: Box / Control unit to be mounted into the control panel.

Based on the type of the plant, DST4602 & DST4602Evolution

are available in two versions, differing for the single line

diagrams on the front:

DST4602 & DST4602Evolution

- SPLIT VERSION: Display + Control unit.

In addition it’s possible to choose between the version with Key selector switch or with Push buttons for the MODE selection.

DST4602 & DST4602Evolution

for those plants where it is necessary to control the MCB

(Mains Circuit Breaker) and there is a single genset in

synchro/parallel with the mains (SPtM)

DST4602/P & DST4602PEvolution

for those plants where the genset controller does NOT

directly control the MCB (Mains Circuit Breaker)

MODE SELECTION: with selector key or with Push buttons

Page 7: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

EXPANSION MODULES AND ACCESSORIES

CANBUS ENGINE SAE J1939/MTU

CAN0

CAN1

EXBUS

USB

SICES

SUPERVISOR

BY MEANS OF THE SERIAL PORTS OF THE CONTROLLER IT IS POSSIBLE TO CONNECT:

DST4602Remote MODEM GSM ROUTER GSM

REWIND / DANCE for

GPRS/GSM or

ETHERNET Interface

ANALOGUE MODEM PC

UP TO MAX. 24 GENSETS CONNECTED ON THE SAME BUS

MAX. 20 DITEL (*)

MAX 16 DIGRIN/DITHERM/DIVIT

MAX 8 DANOUT (**)

(*) Max 160 Digital and additional I/O

(**) Max. 32 Analogue additional Output

CAN1

CAN1

SERIAL PORTS 1xRS232 1xRS485

1xRJ45

LOCAL PC for genset controller firmware upgrade

RE

V.0

6

Page 8: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

DST4602 Compact (MASTER)

In really sensitive contests, it is necessary to ensure a safety control of the gensets. Basically, a reliable control is achieved using a “Master unit” that controls the start/stop, the alarms and the engine/generator protec-tions, combined to a “Back-up unit”. The “Master unit” is equipped with a self-diagnostic system (watch dog), able to detect any failure of the controller. After an elapsed and settable time of communication, the “Back-up unit” automatically switches on taking responsibility of the genset process. When the “Master unit” is ON, the “Back-up unit” is OFF and vice-versa. In that way, there is no danger of failed command between the controllers. The redundancy available is defined “warm type”, considering that 6-7 seconds are required before the “Back-up unit” is activated. It is possible to configure the redundancy of the controllers as follows. For each genset: A) 2 x DST4602 compact B) 2 x DST4602 SCM + N.1 DST4602 HMI (display). With the case b) there is one common display (DST4602 HMI) and the backup is done on DST4602 SCM (the internal box).

DST4602Evolution

- HMI

DST4602 Compact (BACK-UP)

DST4602 SCMT (BACK-UP) DST4602 SCMT (MASTER)

Page 9: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

Remote

For each local DST4602 & DST4602Evolution

it is possible to add one or more remote DST4602 controllers, usually called

DST4602Remote.

This solution is usually recommended in case of remote control room where a supervision of the genset from a remote station is necessary. Thanks to this controller it is possible to visualize the measures, parameters and status of a local DST4602, as the Operator is in front of the local controller.

Connection between DST4602 / DST4602Evolution

and DST4602Remote

:

Via RS485 Modbus RTU (max 800mt)

Via Ethernet TCP/IP (max distance 100mt without any hub). If via Ethernet, it iss possible to connect several DST4602Remote

to

one local controller.

Graphic display:

DST4602Remote

is equipped with a powerful 7’’ colour graphic display TFT - 800x480 pixel

Controls:

Selector key: COMMAND DISABLED - COMMAND ENABLED - REMOTE RESET:

○ Command disabled: no operation is allowed

○ Command enable: all operations are allowed

○ Remote reset: reset of alarms/shutdown In order to increase the safety of the system, It is possible to set a password on the local controller and on the remote one. By inserting the proper password, it is possible to enable the command from remote.

Page 10: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

REMOTE START: Push button used to start the genset from remote. The starting is enabled if the selector key of the local controller is in AUTO mode. REMOTE STOP: Push button used to stop the genset from remote. If the genset has been started by the DST4602/RC, pushing the “REMOTE STOP”, the genset stops conclud-

ing the cooling operations. If the genset has been started by the local DST4602, pushing the “REMOTE STOP”, the genset immediately stops without any cooling operations. GCB: Push button for the manual opening/closure of the Genset Circuit Breaker. MCB: Disabled.

DST4602Remote

is equipped with a configurable Output. This Output can be used to connect an external horn or to set up a

communication failure as watch dog.

Remote control room

Eth

ern

et

/ R

S48

5

Eth

ern

et

/ R

S48

5

Eth

ern

et

/ R

S48

5

Eth

ern

et

/ R

S48

5

Page 11: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

In addition or alternatively to the display of the DST4602 & DST4602Evolution

, it is possible to provide Nr.1 Coloured touch panel

called D-MONITOR. It allows a powerful visualization of all measures and statuses of the plant. In addition, in case of CHP Plants, it is possible to customize the graphic, showing the thermic equipment of the circuit.

DST4602 & DST4602Evolution

are interfaced with D-MONITOR via RS485 or via Ethernet Modbus TCP/IP.

Different sizes are available: 7’’ 10’’ 12,1’’ 15,6’’ Additional sizes available on demand.

Page 12: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

MOSE - Venezia Customized control panels for Synchro/parallel gensets supplying the compressors in case of mains failure

ROSETTI OFF-SHORE PLATFORMS Electric control panels for emergency gensets

UDINE Hospital - Emergency power plant comprising 3 Synchro/Parallel gensets

Page 13: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

CHP Plant Electric control panel for biogas genset with MAN engine

Electric control panels for Rental gensets with double voltage and double frequency

CHP plant at Vicenza S. Bortolo Hospital comprising one gas 1584kW genset

Page 14: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

RABIGH II (Saudi Arabia) – Oil refinery

Emergency power plant installed at Rabigh II, a Refining and Petrochemical company based in Saudi Arabia.

Giov Third Railway Crossing Passage - Ac/Av Milano-Genova Line

Production power station comprising 7 Gensets 800kVA + 2 Gensets 410kVA

Page 15: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

Dimensions: DST4602 - SPLIT Version

Page 16: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

Dimensions: DST4602Evolution

- SPLIT Version

Page 17: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

Dimensions: DST4602 & DST4602Evolution

- COMPACT Version

Page 18: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)

Dimensions: DST4602Remote

Page 19: Evolution - SICES is for setting PLC logic ... an external protection relay called D-PRO, ... IDMT Instantaneous overcurrent (50) Synchro-check (25)