evomax. - storage.googleapis.com · multiple boiler installations 25mm for full details of all...
TRANSCRIPT
EVOMAX.30kWCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
30kW 360 130 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 49
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
Full Load % 89.6
Part Load % 98.4
Seasonal Efficiency % 96.7
Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0
BURNER PRE MIX
Fuel (Type G20) Natural Gas
Fuel Consumption (Nat Gas) m³/h 3.2
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 6-30
Boiler Output (Mean 40°C) kW 6.5-31.54
Boiler Input (Gross cv) kW 33.7
Gas Inlet Size G¾”
Weighted Power Level dB(A) 53
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (31)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 425
Hydraulic Resistance (20°C ∆T) mbar 127
Nominal Flow Rate (11°C ∆T) l/s 0.651
Nominal Flow Rate (20°C ∆T) l/s 0.358
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.07
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 3
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or Open Flue
Flue Gas Volume m³/h 47.6
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 140
B/F Max Counter Pressure Diff Pa 140
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 0.6
Power Consumption watt 126
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 30kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211156
EVOMAX.30kW - LPGCONDENSING - WALL HUNG
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
All dimensions in mm
The following minimum clearances must be maintained for operation and servicing:
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
30kW LPG 360 130 118
FEATURES AND BENEFITS
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 49
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
Full Load % 91.6
Part Load % 99.6
Seasonal Efficiency % 97.2
Min/Max Gas pressure (Nat Gas) mbar 37
BURNER PRE MIX
Fuel (Type G31) LPG Model
Fuel Consumption (Nat Gas) m³/h 1.26
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 6-30
Boiler Output (Mean 40°C) kW 6.4-30.9
Boiler Input (Gross cv) kW 33
Gas Inlet Size G¾”
Weighted Power Level dB(A) 53
NOx Rating/emissions at 0% O2 mg/kWh Class 4 (79)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 425
Hydraulic Resistance (20°C ∆T) mbar 127
Nominal Flow Rate (11°C ∆T) l/s 0.651
Nominal Flow Rate (20°C ∆T) l/s 0.358
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.08
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 3
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or Open Flue
Flue Gas Volume m³/h 46.5
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 140
B/F Max Counter Pressure Diff Pa 140
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 0.6
Power Consumption watt 126
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 30kW LPG
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
WALL HUNG NOx CLASS 4 BIM FLUE VARIANTS
211163
EVOMAX.40kWCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
40kW 360 130 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 49
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
Full Load % 89.6
Part Load % 97.8
Seasonal Efficiency % 96.2
Min/Max Gas pressure (Nat Gas) mbar 17.5 - 20.0
BURNER PRE MIX
Fuel (Type G20) Natural Gas
Fuel Consumption (Nat Gas) m³/h 4.3
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 8-40
Boiler Output (Mean 40°C) kW 8.5-42
Boiler Input (Gross cv) kW 44.9
Gas Inlet Size G¾”
Weighted Power Level dB(A) 53
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (39.1)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 875
Hydraulic Resistance (20°C ∆T) mbar 225
Nominal Flow Rate (11°C ∆T) l/s 0.868
Nominal Flow Rate (20°C ∆T) l/s 0.478
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.09
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 3
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or Open Flue
Flue Gas Volume m³/h 63.4
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 225
B/F Max Counter Pressure Diff Pa 200
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 0.98
Power Consumption watt 207
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 40kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211157
EVOMAX.40kW - LPGCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
40kW LPG 360 130 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 49
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
Full Load % 91.5
Part Load % 99.5
Seasonal Efficiency % 96.7
Min/Max Gas pressure (Nat Gas) mbar 37
BURNER PRE MIX
Fuel (Type G31) LPG Model
Fuel Consumption (Nat Gas) m³/h 1.69
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 8-40
Boiler Output (Mean 40°C) kW 8.3-41.2
Boiler Input (Gross cv) kW 44
Gas Inlet Size G¾”
Weighted Power Level dB(A) 53
NOx Rating/emissions at 0% O2 mg/kWh Class 4 (80)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 875
Hydraulic Resistance (20°C ∆T) mbar 225
Nominal Flow Rate (11°C ∆T) l/s 0.868
Nominal Flow Rate (20°C ∆T) l/s 0.478
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.08
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 3
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or Open Flue
Flue Gas Volume m³/h 62.1
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 225
B/F Max Counter Pressure Diff Pa 200
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 0.98
Power Consumption watt 207
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 40kW LPG
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
WALL HUNG NOx CLASS 4 BIM FLUE VARIANTS
211164
EVOMAX.60kWCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
60kW 360 130 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 60.3
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
Full Load % 89.7
Part Load % 97.9
Seasonal Efficiency % 96.4
Min/Max Gas pressure (Nat Gas) mbar 17.5 - 20.0
BURNER PRE MIX
Fuel (Type G20) Natural Gas
Fuel Consumption (Nat Gas) m³/h 6.4
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 12-60
Boiler Output (Mean 40°C) kW 12.7 - 63.5
Boiler Input (Gross cv) kW 67.4
Gas Inlet Size G¾”
Weighted Power Level dB(A) 52
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (32.3)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 435
Hydraulic Resistance (20°C ∆T) mbar 83
Nominal Flow Rate (11°C ∆T) l/s 1.3
Nominal Flow Rate (20°C ∆T) l/s 0.716
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.14
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 5
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 60kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or 100/150 or Open Flue
Flue Gas Volume m³/h 95.1
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 150
B/F Max Counter Pressure Diff Pa 117
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 0.7
Power Consumption watt 131
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211158
EVOMAX.60kW - LPGCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
60kW LPG 360 130 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 60.3
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
Full Load % 91.7
Part Load % 99.7
Seasonal Efficiency % 96.9
Min/Max Gas pressure (Nat Gas) mbar 37
BURNER PRE MIX
Fuel (Type G31) LPG Model
Fuel Consumption (Nat Gas) m³/h 2.53
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 15-60
Boiler Output (Mean 40°C) kW 15.5 - 62.1
Boiler Input (Gross cv) kW 66
Gas Inlet Size G¾”
Weighted Power Level dB(A) 52
NOx Rating/emissions at 0% O2 mg/kWh Class 4 (83.8)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 435
Hydraulic Resistance (20°C ∆T) mbar 83
Nominal Flow Rate (11°C ∆T) l/s 1.3
Nominal Flow Rate (20°C ∆T) l/s 0.716
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.17
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 5
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 60kW LPG
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or 100/150 or Open Flue
Flue Gas Volume m³/h 93.1
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 150
B/F Max Counter Pressure Diff Pa 117
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 0.7
Power Consumption watt 131
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
WALL HUNG NOx CLASS 4 BIM FLUE VARIANTS
211165
EVOMAX.80kWCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
80kW 360 130 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 60.3
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
SEDBUK 2009 % 89.8
Seasonal Efficiency % 97.2
Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0
BURNER PRE MIX
Fuel (Type G20) Natural Gas
Fuel Consumption (Nat Gas) m³/h 8.7
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 16-80
Boiler Output (Mean 40°C) kW 17.2-84.4
Boiler Input (Gross cv) kW 90.9
Gas Inlet Size G¾”
Weighted Power Level dB(A) 56
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (39.8)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 750
Hydraulic Resistance (20°C ∆T) mbar 180
Nominal Flow Rate (11°C ∆T) l/s 1.736
Nominal Flow Rate (20°C ∆T) l/s 0.955
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.19
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 5
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 80kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or 100/150 or Open Flue
Flue Gas Volume m³/h 128.3
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 312
B/F Max Counter Pressure Diff Pa 260
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 1.4
Power Consumption watt 265
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211159
EVOMAX.80kW - LPGCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
80kW LPG 360 130 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 60.3
Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
SEDBUK 2009 % 90.8
Seasonal Efficiency % 97.7
Min/Max Gas pressure (Nat Gas) mbar 37
BURNER PRE MIX
Fuel (Type G31) LPG Model
Fuel Consumption (Nat Gas) m³/h 3.41
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 20-80
Boiler Output (Mean 40°C) kW 21.2-82.6
Boiler Input (Gross cv) kW 88.9
Gas Inlet Size G¾”
Weighted Power Level dB(A) 56
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (68.0)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar 750
Hydraulic Resistance (20°C ∆T) mbar 180
Nominal Flow Rate (11°C ∆T) l/s 1.736
Nominal Flow Rate (20°C ∆T) l/s 0.955
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.23
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 5
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 80kW LPG
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
FLUE/AIR INLET
Flue Size mm 80/125 Concentric or 100/150 or Open Flue
Flue Gas Volume m³/h 125.4
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 312
B/F Max Counter Pressure Diff Pa 260
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 1.4
Power Consumption watt 265
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211166
EVOMAX.100kWCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
100kW 520 226 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 75.7
Boiler Dimensions mm 850 (H) x 500 (W) x 520 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
SEDBUK 2009 % 89.5
Seasonal Efficiency % 96.7
Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0
BURNER PRE MIX
Fuel (Type G20) Natural Gas
Fuel Consumption (Nat Gas) m³/h 10.8
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 20-100
Boiler Output (Mean 40°C) kW 21.6-103.9
Boiler Input (Gross cv) kW 113.6
Gas Inlet Size G¾”
Weighted Power Level dB(A) 51
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (39.6)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar N/A
Hydraulic Resistance (20°C ∆T) mbar 134
Nominal Flow Rate (11°C ∆T) l/s N/A
Nominal Flow Rate (20°C ∆T) l/s 1.195
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.23
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 7
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 100kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
FLUE/AIR INLET
Flue Size mm 100/150 Concentric or Open Flue
Flue Gas Volume m³/h 160.3
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 220
B/F Max Counter Pressure Diff Pa 220
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 1.8
Power Consumption watt 370
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211160
EVOMAX.120kWCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
120kW 520 226 118
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 75.7
Boiler Dimensions mm 850 (H) x 500 (W) x 520 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
SEDBUK 2009 % 89.4
Seasonal Efficiency % 96.6
Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0
BURNER PRE MIX
Fuel (Type G20) Natural Gas
Fuel Consumption (Nat Gas) m³/h 13.0
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 24-120
Boiler Output (Mean 40°C) kW 26-124.7
Boiler Input (Gross cv) kW 136.4
Gas Inlet Size G¾”
Weighted Power Level dB(A) 54
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (38.8)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar N/A
Hydraulic Resistance (20°C ∆T) mbar 218
Nominal Flow Rate (11°C ∆T) l/s N/A
Nominal Flow Rate (20°C ∆T) l/s 1.43
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.28
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 7
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 120kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
FLUE/AIR INLET
Flue Size mm 100/150 Concentric or Open Flue
Flue Gas Volume m³/h 192.5
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 365
B/F Max Counter Pressure Diff Pa 288
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 1.9
Power Consumption watt 403
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211161
EVOMAX.150kWCONDENSING - WALL HUNG
IDEAL COMMERCIAL BOILERS
PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN
T: 0844 5436060F: 0844 5436181E: [email protected]
IDEALCOMMERCIALBOILERS.COM
DIMENSIONS AND CLEARANCES
The following minimum clearances must be maintained for operation and servicing:
For full details of all configurations & specifications, please refer to the Evomax sales brochure.
BOILER DIM A DIM B DIM C
150kW 610 233 120
Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.
• Largest range of outputs in market (30 – 150 kW)
• Robust & light aluminium silicon alloy heat exchanger
• Up to 110% part load efficiency
• High 5:1 turndown
• Compact – one width & height for easy siting
• Simple controls interface with large backlit display
• Comprehensive range of options
• Designed for easy installation, commissioning and servicing
• Quality product through design, component selection and proving
• NOx <40mg/kWh (Class 5) for all natural gas models
• 5 year parts and labour warranty
FEATURES AND BENEFITS
All dimensions in mm
TOPDEPENDENT ON
FLUE SIZE
SIDES25mm
BELOW300mm
FRONT450mm
CLEARANCE BETWEEN
MULTIPLE BOILER INSTALLATIONS
25mm
TECHNICAL SPECIFICATIONS.
GENERAL
Dry Weight KG 89.75
Boiler Dimensions mm 850 (H) x 500 (W) x 610 (D)
Boiler Clearances mm Front: 450 Side: 25 Below: 300
SEDBUK 2009 % 89.5
Seasonal Efficiency % 96.7
Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0
BURNER PRE MIX
Fuel (Type G20) Natural Gas
Fuel Consumption (Nat Gas) m³/h 16.2
Flame Protection Ionisation
Ignition Spark
Boiler Output (Mean 70°C) kW 30-150
Boiler Output (Mean 40°C) kW 32.5-158
Boiler Input (Gross cv) kW 170.5
Gas Inlet Size G¾”
Weighted Power Level dB(A) 56
NOx Rating/emissions at 0% O2 mg/kWh Class 5 (38.1)
HYDRAULICS
Hydraulic Resistance (11°C ∆T) mbar N/A
Hydraulic Resistance (20°C ∆T) mbar 230
Nominal Flow Rate (11°C ∆T) l/s N/A
Nominal Flow Rate (20°C ∆T) l/s 1.79
Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.35
Min Flow Temperature °C 30
Max Flow Temperature °C 82
Min Working Pressure bar 0.3
Max Working Pressure bar 4
Max Static Head Of Water metres 40.7
Condensate Connection mm 25
High Limit Set Point °C 105 flow, 95 return
Flow & Return Size G1¼”
Water Content litres 9.2
Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.
EVOMAX 150kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE.
*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
FLUE/AIR INLET
Flue Size mm 100/150 Concentric or Open Flue
Flue Gas Volume m³/h 240.7
Flue Gas Temperature 80/60 °C 70
O/F Max Counter Pressure Diff Pa 430
B/F Max Counter Pressure Diff Pa N/A
ELECTRICAL
Electrical Supply 230/240V 50Hz 1 Ph
Current (Max No Pump) amp 1.9
Power Consumption watt 400
Modulating Input V/dc 0-10V or OpenTherm
Fuse Rating amp 4
Controls Voltage V 230 or Low
Insulation Class IP IP20
CONTROL OPERATION
On/Off 0-10V DC Yes
OpenTherm Yes
High Limit Protection Yes
Low Water Protection Yes
Volt Free Common Alarm Yes
Boiler Run Indication Yes
OPTIONAL EXTRAS
Multi Boiler Frame & Header Kits Yes
Modulating Sequencer Kit Yes
Programmable Room Thermostat Kit Yes
Outside Sensor Kit Yes
Tank Sensor Kit Yes
Room Sensor Kit Yes
Safety Interlock Kit Yes
Pump Kit Yes
Universal Sequencer Kit Yes
WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS
211162