ex lighting installation: hazardous areas - zone 1 / … · your partner for safety since 1961...

94
YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT TUBE LAMPS Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D LIGHTING FIXTURES ATEX 94/9/EC GOST-R (RTR / RTN) GOST-K EXECUTION II 2 G Ex d IIC T5/T4 II 2 D Ex tD A21 T100°C / T135°C 1Ex d IIC T5/T4 DIP A21 TA (100…135)°C 1Ex d IIC T5/T4 DIP A21 TA (100…135)°C INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 PROTECTION DEGREE IP66 IP66 IP66 CERTIFICATE REF. ISSEP 02 ATEX 043 POCC IT. ГБ05.B02536 No. 07/43-269 RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1 ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96) ГОСТ Р МЭК 61241-3-99 ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002 EMERGENCY UNIT ATEX 94/9/EC GOST-R (RTR / RTN) GOST-K EXECUTION II 2 G Ex d IIC T6 II 2 D Ex d tD A21 T85°C 1Ex d IIC T6 DIP A21 TA T85°C 1Ex d IIC T6 DIP A21 TA T85°C INSTALLATION ZONA 1 / 2 - ZONA 21 / 22 ZONA 1 / 2 - ZONA 21 / 22 ZONA 1 / 2 - ZONA 21 / 22 PROTECTION DEGREE IP66 IP66 IP66 CERTIFICATE REF. INERIS 08 ATEX 018 POCC IT. ГБ05.B02537 No. 07/43-269 RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61241-1; ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96) ГОСТ Р МЭК 61241-3-99 ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002 Mechanical characteristics Body marine grade copper free aluminium (control gear & emergency unit) Tubes high-temperature resistant borosylicate glass tube Painting external epoxy powders grey RAL-9006 colour Screws external stainless steel Gaskets nbr rubber Reflectors white stove enamelled sheet steel Cable entry 3/4” NPT size threaded Electrical characteristics Power supply elettronic ballast 220V/240v - 50/60Hz (p.f.corrected - cos ρ ≥ 0,98) Lampholders bi-pin G13 cap Internal wiring high-temperature resistant silicon rubber insulation cables Emergency unit emergency unit composed of inverter charger and ni-cd battery pack 4A/h 6V. autonomy from 60 to 120min. Led power-on indicating lamp provided Feam Catalogue 01 - 1 ON REQUEST ACCESSORIES: • Pole mounting kit complete with stainless steel hardware • Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware • Wall/Structure mounting kit complete with stainless steel hardware • Galvanized steel wire protection guard • Stainless steel wire protection guard • Stainless steel reflectors • External painting colour on request • Electronic ballast with voltage supply different than standard • Ni-Cd Battery pack 7A/h 6V for Emergency Unit with Autonomy more than 150min

Upload: trinhtu

Post on 29-Jul-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVF

EVF

Ex Lighting

LIGHTING FIXTURES FOR FLUORESCENT TUBE LAMPS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

LIGHTING FIXTURESATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T5/T4 II 2 D Ex tD A21 T100°C / T135°C

1Ex d IIC T5/T4 DIP A21 TA (100…135)°C

1Ex d IIC T5/T4 DIP A21 TA (100…135)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. ISSEP 02 ATEX 043 POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

EMERGENCY UNITATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T6 II 2 D Ex d tD A21 T85°C

1Ex d IIC T6 DIP A21 TA T85°C

1Ex d IIC T6 DIP A21 TA T85°C

INSTALLATION ZONA 1 / 2 - ZONA 21 / 22 ZONA 1 / 2 - ZONA 21 / 22 ZONA 1 / 2 - ZONA 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INERIS 08 ATEX 018 POCC IT. ГБ05.B02537 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61241-1;

ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Mechanical characteristicsBody marine grade copper free aluminium (control gear & emergency unit)Tubes high-temperature resistant borosylicate glass tubePainting external epoxy powders grey rAl-9006 colourScrews external stainless steelGaskets nbr rubberreflectors white stove enamelled sheet steelCable entry 3/4” NPT size threaded

Electrical characteristicsPower supply elettronic ballast 220v/240v - 50/60hz (p.f.corrected - cos ρ ≥ 0,98)lampholders bi-pin G13 capInternal wiring high-temperature resistant silicon rubber insulation cablesEmergency unit emergency unit composed of inverter charger and ni-cd battery pack 4A/h 6v. autonomy from 60 to 120min. Led power-on indicating lamp provided

Feam Catalogue 01 - 1

ON REqUEST ACCESSORIES: • Pole mounting kit complete with stainless steel hardware• Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware • Wall/Structure mounting kit complete with stainless steel hardware • Galvanized steel wire protection guard

• Stainless steel wire protection guard• Stainless steel reflectors• External painting colour on request• Electronic ballast with voltage supply different than standard • Ni-Cd Battery pack 7A/h 6V for Emergency Unit with Autonomy more than 150min

Page 2: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVF

C

D

A

3/4”B

DA

3/4”B

C

B

A

8MA 8MA

8MA 8MA

EVF18ELME 1 x 18W T5 T 100°C G13 1 x 3/4” 4.8 V - 4Ah 2h C T4 T 135°C 1 x 1/2”

EVF36ELME 1 x 36W T5 T 100°C G13 1 x 3/4” 4.8 V - 4Ah 2h C T4 T 135°C 1 x 1/2”

EVF58ELME 1 x 58W T5 T 100°C G13 1 x 3/4” 4.8 V - 4Ah 2h C T4 T 135°C 1 x 1/2”

EVF18ELBE 2 x 18W T5 T 100°C G13 1 x 3/4” 4.8 V - 4Ah 2h D T4 T 135°C 1 x 1/2”

EVF36ELBE 2 x 36W T5 T 100°C G13 1 x 3/4” 4.8 V - 4Ah 2h D T4 T 135°C 1 x 1/2”

EVF58ELBE 2 x 58W T5 T 100°C G13 1 x 3/4” 4.8 V - 4Ah 2h D T4 T 135°C 1 x 1/2”

EVF18EL 1 x 18W T5 T 100°C G13 2 x 3/4” - - A T4 T 135°C

EVF36EL 1 x 36W T5 T 100°C G13 2 x 3/4” - - A T4 T 135°C

EVF58EL 1 x 58W T5 T 100°C G13 2 x 3/4” - - A T4 T 135°C

EVF18BEL 2 x 18W T5 T 100°C G13 2 x 3/4” - - B T4 T 135°C

EVF36BEL 2 x 36W T5 T 100°C G13 2 x 3/4” - - B T4 T 135°C

EVF58BEL 2 x 58W T5 T 100°C G13 2 x 3/4” - - B T4 T 135°C

2 - Feam Catalogue 01

Ex Lighting

EVF Technical data

EVF Technical features

Reference details

EMERGENCY FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 220V/240V - 50/60Hz

FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 220V/240V - 50/60Hz

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE ENTRY EMERGENCY

UNIT AUTONOMY DETAIL

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

EVF18EL 1000 96 95 602 4,50 2 x 3/4” A

EvF36El 1600 96 95 1202 5,70 2 x 3/4” A

EVF58EL 1900 96 95 1490 7,00 2 x 3/4” A

EVF18BEL 1000 200 95 602 9,00 2 x 3/4” B

EVF36BEL 1600 200 95 1202 12,20 2 x 3/4” B

EVF58BEL 1900 200 95 1490 14,70 2 x 3/4” B

Page 3: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVF

45

170

45 45108

170

156

156

100

100

50

128

45°

3/4”

273

273

12845°

50

100

50

C

D

A

3/4”

3/4”1 - 1/2”

B

C

DA

3/4”B

C

D

1 - 1/2”

3/4”

EVF18ELME 1000 222 379 602 10,00 1 x 3/4” / 1 x 1/2” C

EVF36ELME 1600 222 379 1202 12,00 1 x 3/4” / 1 x 1/2” C

EVF58ELME 1900 222 379 1490 14,00 1 x 3/4” / 1 x 1/2” C

EVF18ELBE 1000 287 265 602 16,00 1 x 3/4” / 1 x 1/2” D

EVF36ELBE 1600 287 265 1202 19,00 1 x 3/4” / 1 x 1/2” D

EVF58ELBE 1900 287 265 1490 21,00 1 x 3/4” / 1 x 1/2” D

Feam Catalogue 01 - 3

Ex Lighting

EVF Technical features

EVF Installation and mounting details

Wall/structure mountingPole mounting

Assemblig detail with pole (typical)

Pendant mountingCeiling mountingtype 2type 1

type 3 type 4

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

Page 4: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVF EVF18BEL EVF36BEL EVF58BEL

4 - Feam Catalogue 01

Ex Lighting

EVF Polar diagrams – photometric data

EVF On request accessories

GABBIAEVFF18 18W SIZE GALVANIZED STEEL WIRE PROTECTION GUARD GALVANIZED STEELGABBIAEVFF36 36W SIZE GALVANIZED STEEL WIRE PROTECTION GUARD GALVANIZED STEELGABBIAEVFF58 58W SIZE GALVANIZED STEEL WIRE PROTECTION GUARD GALVANIZED STEELGABBIAEVFF18IX 18W SIZE STAINLESS STEEL WIRE PROTECTION GUARD STAINLESS STEELGABBIAEVFF36IX 36W SIZE STAINLESS STEEL WIRE PROTECTION GUARD STAINLESS STEELGABBIAEVFF58IX 58W SIZE STAINLESS STEEL WIRE PROTECTION GUARD STAINLESS STEELD18IX 18W SIZE STAINLESS STEEL REFLECTOR STAINLESS STEELD36IX 36W SIZE STAINLESS STEEL REFLECTOR STAINLESS STEELD58IX 58W SIZE STAINLESS STEEL REFLECTOR STAINLESS STEEL20301.0151 SINGLE LAMP CEILING MOUNTING KIT C/W HARDWARE TYPE 1 ALUM. LIGHT ALLOY20301.0152 TWIN LAMP CEILING MOUNTING KIT C/W HARDWARE TYPE 1 ALUM. LIGHT ALLOY20301.0153 SINGLE LAMP POLE MOUNTING KIT (SIZE 1” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL20301.0155 SINGLE LAMP POLE MOUNTING KIT (SIZE 1 1/2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL20301.0156 TWIN LAMP POLE MOUNTING KIT (SIZE 1 1/2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL20301.0157 SINGLE LAMP POLE MOUNTING KIT (SIZE 2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL20301.0158 TWIN LAMP POLE MOUNTING KIT (SIZE 2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL20302.0128 SINGLE LAMP WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 GALVANIZED STEEL20302.0128 TWIN LAMP WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 GALVANIZED STEEL20301.0165 SINGLE LAMP PENDANT MOUNTING KIT C/W HARDWARE TYPE 2 GALVANIZED STEEL20301.0165 TWIN LAMP PENDANT MOUNTING KIT C/W HARDWARE TYPE 2 GALVANIZED STEEL

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

CODE DESCRIPTION INSTALLATION MATERIAL

Page 5: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVACEVAC

ON REqUEST ACCESSORIES: •Ceiling mounting AISI 316L stainless steel kit complete with stainless steel hardware •Pendant mounting AISI 316L stainless steel kit complete with stainless steel hardware •Pole mounting kit 1” – 1 1/2” – 2” dia. complete with stainless steel hardware•Wall/Structure mounting kit complete with stainless steel hardware •Galvanized steel wire protection guard•Stainless steel wire protection guard

•White stove enamelled aluminium reflectors •Stainless steel reflectors •External painting colour on request•Control gear with voltage supply different than standard •Threaded cable entry different than standard

Mechanical characteristicsBody marine grade copper free aluminium (control gear & lamp body)

Globe high-temperature resistant borosylicate glass

Painting external epoxy powders grey rAl-9006 colour

Screws external stainless steel

Gaskets silicon rubber

Cable entry 3/4” NPT size threaded

Installation swivel bracket AISI 316L stainless steel

Electrical characteristicsPower supply (prc) conventional ballast 230V - 50Hz (p.f. corrected - cos ρ ≥ 0,95)

Lampholders porcelain E27/E40 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

LIGHTING FIXTURES FOR INCANDESCENT AND DISCHARGE LAMPS

LIGHTING FIXTURE / CONTROL GEARATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T6/T2 II 2 D Ex tD A21 T80°C / T290°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0054X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Feam Catalogue 01 - 5

Ex Lighting

Page 6: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

6 - Feam Catalogue 01

Ex Lighting

EVAC Technical data

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

LAMPHOLDER SIZE CABLE ENTRY SIZE DETAIL

LIGHTING FIXTURE FOR HALOGEN LAMP - POWER SUPPLY 230V-50Hz

LIGHTING FIXTURE FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V-50Hz

LIGHTING FIXTURE FOR METAL HALIDE LAMP - POWER SUPPLY 230V-50Hz

LIGHTING FIXTURE FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V-50Hz

LIGHTING FIXTURE FOR BLENDED LIGHT LAMP - POWER SUPPLY 230V-50Hz

EvAC101 100 W T4 T 130°C E-27 1 x 3/4" A

EvAC100 100 W T4 T 130°C E-27 2 x 3/4" B

EvAC201 200 W T4 T3

T 130°C T 195°C E-27 1 x 3/4" A

EvAC200 200 W T4 T3

T 130°C T 195°C E-27 2 x 3/4" B

EvAC301 300 W T4 T3

T 130°C T 195°C E-40 1 x 3/4" A

EvAC300 300 W T4 T3

T 130°C T 195°C E-40 2 x 3/4" B

EvAC501 500 W T3 T 195°C E-40 1 x 3/4" A

EvAC500 500 W T3 T 195°C E-40 2 x 3/4" B

EvAC100-E20 25 W 20 W

T5 T4

T 95°C T 130°C E-14 + Ba-15s 2 x 3/4" B

EvAC101-100h 100 W T4 T 130°C E-27 1 x 3/4" A

EvAC100-100h 100 W T4 T 130°C E-27 2 x 3/4" B

EvAC201-150h 150 W T1 T 130°C E-27 1 x 3/4" A

EvAC200-150h 150 W T2 T 130°C E-27 2 x 3/4" B

EvAC301-250h 250 W T4 T3

T 130°C T 195°C E-27 1 x 3/4" A

EvAC300-250h 250 W T4 T3

T 130°C T 195°C E-27 2 x 3/4" B

EVAC101-80HG 80 W T4 T 130°C E-27 2 x 3/4” / 1 x 1-1/2” C

EvAC201-125hG 125 W T3 T 195°C E-27 2 x 3/4” / 1 x 1-1/2” C

EvAC301-250hG 250 W T3 T 195°C E-40 2 x 3/4” / 1 x 1-1/2” C

EvAC501-250hG 250 W T4 T 130°C E-40 2 x 3/4” / 1 x 1-1/2” C

EvAC501-400hG 400 W T3 T 195°C E-40 2 x 3/4” / 1 x 1-1/2” C

EVAC101-100MH 100 W T4 T 130°C E-27 2 x 3/4" / 1 x 1-1/2" C

EVAC301-150MH 150 W T4 T3

T 130°C T 195°C E-27 2 x 3/4" / 1 x 1-1/2" C

EVAC301-250MH 250 W T3 T 195°C E-40 2 x 3/4" / 1 x 1-1/2" C

EVAC501-400MH 400 W T3 T 195°C E-40 2 x 3/4" / 1 x 1-1/2" C

EvAC101-70hPNA 70 W T4 T 130°C E-27 2 x 3/4" / 1 x 1-1/2" C

EvAC301-150hPNA 150 W T4 T 130°C E-40 2 x 3/4" / 1 x 1-1/2" C

EvAC301-250hPNA 250 W T3 T2

T 195°C T 290°C E-40 2 x 3/4" / 1 x 1-1/2" C

EvAC501-400hPNA 400 W T3 T 195°C E-40 2 x 3/4" / 1 x 1-1/2" C

EVAC201-160MLL 160 W T3 T 195°C E-27 2 x 3/4" / 1 x 1-1/2" A

EVAC200-160MLL 160 W T3 T 195°C E-27 2 x 3/4" / 1 x 1-1/2" B

EVAC301-250MLL 250 W T3 T 195°C E-40 2 x 3/4" / 1 x 1-1/2" A

EVAC300-250MLL 250 W T3 T 195°C E-40 2 x 3/4" / 1 x 1-1/2" B

LIGHTING FIXTURE FOR INCANDESCENT LAMP - POWER SUPPLY 230V-50Hz

Page 7: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

B C

3/4”

DE

A

80 6060Ø

8.5

180200

80 6016

3

A

ED

B C

2X3/4”

A

DE

B C

200

30

Ø10

2828

192

5

1-1/2”

A B

C

EVAC101 150 270 240 145 280 3,50 1 x 3/4” A

EVAC100 150 270 240 145 280 3,50 2 x 3/4” B

EVAC201 175 290 270 170 345 4,00 1 x 3/4” A

EVAC200 175 290 270 170 345 4,00 2 x 3/4” B

EVAC301 200 390 330 190 402 7,00 1 x 3/4” A

EVAC300 200 390 330 190 402 7,00 2 x 3/4” B

EVAC501 260 420 395 255 515 10,00 1 x 3/4” A

EVAC500 260 420 395 255 515 10,00 2 x 3/4” B

EvAC101-..hG EVAC101-..HPNA 225 545 515 145 280 9,00 2 x 3/4” CEVAC101-..MH

1 x 1-1/2”

EVAC201-..HG 225 565 545 170 345 9,50 2 x 3/4” C 1 x 1-1/2”EvAC301-..hG EVAC301-..HPNA 225 665 640 190 402 12,00 2 x 3/4” CEVAC301-..MH

1 x 1-1/2”

EvAC501-..hG EVAC501-..HPNA 225 695 670 255 515 15,50 2 x 3/4” CEVAC501-..MH

1 x 1-1/2”

Feam Catalogue 01 - 7

Ex Lighting

EVAC Technical features

Reference details Reference details

Reference details

CODE A [mm] B [mm] C [mm] Ø D [mm] Ø E [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

CODE A [mm] B [mm] C [mm] Ø D [mm] Ø E [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Page 8: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

237

180

58283

275

54

16

8 - Feam Catalogue 01

Ex Lighting

EVAC Installation and mounting detailsCeiling mounting

Pendant mounting

Wall/structure mounting

type 1

type 2

type 3

Page 9: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

EVAC125HG EVAC150HPS EVAC100MH

25°

25°

Feam Catalogue 01 - 9

Ex Lighting

EVAC Installation and mounting details

EVAC Polar diagrams – photometric data

Pole mounting / Assemblig detail with pole (typical)

SEAlING FITTINGS

SEAlING FITTINGS

POlEPOlE

Page 10: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

EVAC250HG-D EVAC400HPS-D EVAC400MH-D

CODE DESCRIPTION INSTALLATION MATERIAL

10 - Feam Catalogue 01

EVAC Polar diagrams – photometric data

EVAC On request accessories

20302.0070 EVAC 100 / 101 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUMININIUM20302.0071 EVAC 200 / 201 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUMININIUM20302.0072 EVAC 300 / 301 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUMININIUM20302.0073 EVAC 500 / 501 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUMININIUM20302.0025 EvAC 100 / 101 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl20302.0026 EvAC 200 / 201 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl20302.0027 EvAC 300 / 301 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl20302.0028 EVAC 500 / 501 SIZE STAINLESS STEEL REFLECTOR STAINLESS STEEL20302.0074 EVAC 100 / 101 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0075 EVAC 200 / 201 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0076 EVAC 300 / 301 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0077 EVAC 500 / 501 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0037 EVAC 100 / 101 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0038 EVAC 200 / 201 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0039 EVAC 300 / 301 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0040 EVAC 500 / 501 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0078 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 AISI 316l STAINlESS STEEl 20302.0079 WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 AISI 316l STAINlESS STEEl20302.0082 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 AISI 316l STAINlESS STEEl

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Ex Lighting

Page 11: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVAC

-FL

EVAC-FL

LIGHTING FIXTURES FOR FLUORESCENT LAMPS

Ex Lighting

ON REqUEST ACCESSORIES: •Ceiling mounting AISI 316L stainless steel kit complete with stainless steel hardware •Pendant mounting AISI 316L stainless steel kit complete with stainless steel hardware •Pole mounting kit 1” – 1 1/2” – 2” dia. complete with stainless steel hardware•Wall/Structure mounting kit complete with stainless steel hardware •Galvanized steel wire protection guard•Threaded cable entry different than standard

•Stainless steel wire protection guard•White stove enamelled aluminium reflectors •Stainless steel reflectors •External painting colour on request•Electronic ballast with voltage supply different than standard

Mechanical characteristicsBody marine grade copper free aluminium (control gear & lamp body)

Globe high-temperature resistant borosylicate glass

Painting external epoxy powders grey rAl-9006 colour

Screws external stainless steel

Gaskets silicon rubber

Cable entry 3/4” NPT size threaded

Installation swivel bracket AISI 316L stainless steel

Electrical characteristicsPower supply (prc) elettronic ballast 220V/240V - 50/60Hz (p.f.corrected - cos ρ ≥ 0,98)

lampholders porcelain E27 size - plastic 2G10 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

Feam Catalogue 01 - 11

LIGHTING FIXTURE / CONTROL GEARATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T6/T2 II 2 D Ex tD A21 T80°C / T290°C

1Ex d IIC T6 X DIP A21 TA (80)°C

1Ex d IIC T6 X DIP A21 TA (80)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0054X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Page 12: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

-FL

180

200

6080

∅8.5

80 6060

3

16

B C

3/4”

DE

A

80 6060

Ø 8.5

180200

80 6016

3

A

180

200

6080

∅8.5

80 6060

3

16

ED

B C

2X3/4”

Ø10

5

200

30

19228

28

A

DE

B C

200

30

Ø10

2828

192

5

1-1/2”

A B

C

EVAC101-15FL 1 x 15W T6 T 80°C E-27 1 x 3/4” A

EVAC100-15FL 1 x 15W T6 T 80°C E-27 2 x 3/4” B

EVAC201-23FL 1 x 23W T6 T 80°C E-27 1 x 3/4” A

EVAC301-218FL 2 x 18W T6 T 80°C 2G-10 2 x 3/4” C

EVAC301-318FL 3 x 18W T6 T 80°C 2G-10 2 x 3/4” C

EVAC501-236FL 2 x 36W T6 T 80°C 2G-10 2 x 3/4” C

EVAC501-336FL 3 x 36W T6 T 80°C 2G-10 2 x 3/4” C

EVAC101-15FL 150 270 235 145 280 3,5 1 x 3/4” A

EVAC100-15FL 150 270 235 145 280 3,5 4 x 3/4” B

EVAC201-23FL 175 270 255 170 345 4 1 x 3/4” A

EVAC301-218FL 225 605 590 190 395 12 2 x 3/4” C

EVAC301-318FL 225 605 590 190 395 12 2 x 3/4” C

EVAC501-236FL 225 648 620 255 515 15,5 2 x 3/4” C

EVAC501-336FL 225 648 620 255 515 15,5 2 x 3/4” C

12 - Feam Catalogue 01

Ex Lighting

EVAC-FL Technical data

EVAC-FL Technical features

LIGHTING FIXTURES FOR FLUORESCENT LAMPS - POWER SUPPLY 220V/240V - 50/60Hz

CODE A [mm] B [mm] C [mm] Ø D [mm] Ø E [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details Reference details

Reference details

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

LAMPHOLDER SIZE

CABLE ENTRY SIZE DETAIL

Page 13: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

-FL

237

180

58283

275

54

16

Feam Catalogue 01 - 13

EVAC-FL Installation and mounting detailsCeiling mounting

Pendant mounting

Wall/structure mounting

type 1

type 2

type 3

Ex Lighting

Page 14: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVAC

-FL

25°

25°

14 - Feam Catalogue 01

EVAC-FL Installation and mounting detailsPole mounting

EVAC-FL On request accessories

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

20302.0070 EVAC 100 / 101 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.20302.0071 EVAC 200 / 201 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.20302.0072 EVAC 300 / 301 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.20302.0073 EVAC 500 / 501 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.20302.0025 EvAC 100 / 101 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl20302.0026 EvAC 200 / 201 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl20302.0027 EvAC 300 / 301 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl20302.0028 EVAC 500 / 501 SIZE STAINLESS STEEL REFLECTOR STAINLESS STEEL20302.0074 EVAC 100 / 101 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0075 EVAC 200 / 201 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0076 EVAC 300 / 301 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0077 EVAC 500 / 501 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL20302.0037 EVAC 100 / 101 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0038 EVAC 200 / 201 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0039 EVAC 300 / 301 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0040 EVAC 500 / 501 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL20302.0078 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 AISI 316l STAINlESS STEEl 20302.0079 WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 AISI 316l STAINlESS STEEl 20302.0082 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 AISI 316l STAINlESS STEEl

SEAlING FITTINGS

SEAlING FITTINGS

POlEPOlE

CODE DESCRIPTION INSTALLATION MATERIAL

Ex Lighting

Page 15: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVP-

100

EVP-100

Feam Catalogue 01 - 15

PORTABLE LIGHTING FIXTURES FOR INCANDESCENT LAMPS

Ex Lighting

ON REqUEST ACCESSORIES:• External painting colour on request

Mechanical characteristicsBody marine grade copper free aluminium (control gear & lamp body)

Globe high-temperature resistant borosylicate glass

Painting external epoxy powders grey rAl-9006 colour

Screws external stainless steel

Gaskets silicon rubber

Cable entry Nickel plated brass cable gland 1/2” NPT (armoured cable)

Electrical characteristicsPower supply 12 ÷ 230V AC/DC

lampholders E27 porcelain

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 /22 (Dusts) Classification: Group II - Category 2G 2D

LIGHTING FIXTUREATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T4/T2 II 2 D Ex tD A21 T130°C

1Ex d IIC T4 (T5…T2) X DIP A21 TA (130)°C

1Ex d IIC T4 (T5…T2) X DIP A21 TA (130)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0054X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1

ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Page 16: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVP-

100

A

B

ØD

C

A

16 - Feam Catalogue 01

Ex Lighting

EVP-100 Technical data

EVP-100 Technical features

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

LAMPHOLDER SIZE

CABLE ENTRY SIZE DETAIL

CODE A [mm] B [mm] C [mm] Ø D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

LIGHTING FIXTURE FOR INCANDESCENT LAMP - POWER SUPPLY 230V-50Hz

Reference details

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

EVP-100 395 257 287 150 4,00 CABLE GLAND 1/2” NPT A

EVP-100 100 W T4 T 130°C E-27 CABLE GLAND 1/2” NPT A

Page 17: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

AWLAWL

Feam Catalogue 01 - 17

Ex Lighting

ON REqUEST ACCESSORIES: • Galvanized steel wire protection guard• Stainless steel wire protection guard• Aircraft Warning Lights and control panel support manufactured in according to customer specification

• External painting colour on request• Threaded cable entry different than standard

Electrical characteristicsLampholders porcelain E27 size Internal wiring high-temperature resistant silicon rubber insulation cablesTerminals suitable up to 4mm/sq cablesMedium intensity flashing obstruction light 1450 / 2000 cd intensity (over than 45mt distance)low intensity steady obstruction light 30 cd intensity (less than 45mt distance)Construction single awl - twin awl (1 main + 1 spare) in according to ICAO directive

Mechanical characteristicsBody marine grade copper free aluminium Globe high-temperature resistant borosylicate glass Fresnel len shock proof acrilyc material suitable for high temperaturesPainting external epoxy powders grey rAl-9006 colourScrews external stainless steelGaskets silicon rubberCable entry 3/4” NPT size threaded

AIRCRAFT WARNING LIGHTS AND A.W.L. CONTROL PANELS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

OBSTRUCTION LIGHTING FIXTUREATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T6/T2 II 2 D Ex tD A21 T80°C / T290°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0054X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

CONTROL PANELATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION

II 2 G Ex d IIB+H2 T6...T3 II 2 D Ex tD A21 T85°C ÷ T150°C

II 2 G Ex d IIC T6/T2 II 2 D Ex tD A21 T80°C / T290°C

1Ex d IIB+H2 T6…T3 DIP A21 TA 85°C ÷ 150°C 1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

1Ex d IIB+H2 T6…T3 DIP A21 TA 85°C ÷ 150°C 1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

PROTECTION DEGREE ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22PROTEZIONE MECCANICA IP66 IP66 IP66

ICAO IN ACCOrDING TO ICAO DIrECTIvE ANNEX 14

RULES OF COMPLIANCEEN 60079-0; EN 60079-1; EN 60079-11; EN 61241-0;

EN 61241-1

ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Page 18: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

AWL

D

ØC ØC

B

A

AB

ØC

180200

A B

EVAC201-F 430 415 200 - 4,50 1 x 3/4” A

EVAC200-F 430 415 200 - 4,50 4 x 3/4” A

EVAC201-XF 280 260 176 - 4,50 1 x 3/4” C

EVAC200-XF 280 260 176 - 4,00 4 x 3/4” C

EVAC201-XFR-24V 280 260 176 - 4,00 1 x 3/4” C

EVAC201-F2R 790 415 200 475 9,00 1 x 3/4” B

EVAC201-XF2R 630 260 176 453 8,00 1 x 3/4” D

EVAC301-25R 345 322 197 - 7,00 1 x 3/4” C

EVAC300-25R 345 322 197 - 7,00 4 x 3/4” C

18 - Feam Catalogue 01

Ex Lighting

AWL Technical data

CODE LAMP TYPE TEMPERATURE

CLASS (GAS)

TEMPERATURE CLASS

(DUSTS)

FLASHING [x/min.]

LAMPHOLDERCABLE ENTRY SIZE

DETAIL

AWL Technical featuresCODE A [mm] B [mm] Ø C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

EVAC201-F 100W INCANDESCENT T4 T 130°C - E-27 1 x 3/4” A

EVAC200-F 100W INCANDESCENT T4 T 130°C - E-27 4 x 3/4” A

EVAC201-XF 6J XENOFLASH T6 T 80°C 65 ± 10 E-27 1 x 3/4” C

EVAC200-XF 6J XENOFLASH T6 T 80°C 65 ± 10 E-27 4 x 3/4” C

EVAC201-XFR-24V 6J XENOFLASH T6 T 80°C 65 ± 10 E-27 1 x 3/4” C

EVAC201-F2R 2 x 100W INCAND. T4 T 130°C - E-27 1 x 3/4” B

EVAC201-XF2R 2 x 6J XENOFLASH T6 T 80°C 65 ± 10 E-27 1 x 3/4” D

EVAC301-25R 40W INCANDESCENT T4 T 130°C - E-27 1 x 3/4” C

EVAC300-25R 40W INCANDESCENT T4 T 130°C - E-27 4 x 3/4” C

Page 19: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

AWL

B A

180200

ØC

ØC

B

A

ØC

DC D

FRESNEL XENOFLASH

ROTALLARM MULTI-LED

Feam Catalogue 01 - 19

Ex Lighting

Aircraft warning lights models

Reference details

AWL Technical features

Page 20: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

AWL

08 09

0201AUT. MAN.

OFF

ON

OFF

ON

OFF

ON

03

04 05 06

12

07

OFF

ON

OFF

ON

OFF

ON

OFF

ON

13 14 15

>>

10

OFF

ON

18

11

OFF

ON

1916 17

01

OFF

ON AUT. MAN.

0302

0504 06 07

>>

EX d

20 - Feam Catalogue 01

Ex Lighting

AWL Control panels

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

WEATHERPROOF IP66

BREATHER vAlvE TYPE ECD

INSTRUMENT HOUSING WITH PhOTOElECTrIC CEll

BREATHER vAlvE TYPE ECDE

INSTRUMENT HOUSING WITH PhOTOElECTrIC CEll

CODE DESCRIPTION MATERIAL

20302.0075 EVAC 200 / 201 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0076 EVAC 300 / 301 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0038 EVAC 200 / 201 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL

20302.0039 EVAC 300 / 301 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL

20302.0078 STRUCTURE MOUNTING KIT C/W HARDWARE AISI 316l STAINlESS STEEl

1030.00055 RED FRESNEL LEN Ø155mm PLASTIC

1030.00186 ORANGE FRESNEL LEN Ø155mm PLASTIC

1030.00211 GREEN FRESNEL LEN Ø155mm PLASTIC

1030.00213 WHITE FRESNEL LEN Ø155mm PLASTIC

EVAC On request accessories

Page 21: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

MIO

L -

LIO

L

MIOL - LIOL

Ex Lighting

Feam Catalogue 01 - 21

ON REqUEST ACCESSORIES: •Stainless steel wire protection guard•Aircraft Warning Lights and control panel support manufactured in according to customer specification

•External painting colour on request•Threaded cable entry different than standard•Control panel with simultaneous or catenary multilight flashing system

Electrical characteristics

APPLY TO:

Optical characteristics

Mechanical characteristics

MEDIUM INTENSITY AND LOW INTENSITY MULTILED SYSTEM AIRCRAFT WARNING LIGHTS

OBSTRUCTION WARNING LIGHTSATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T6/T2 II 2 D Ex tD A21 T80°C / T290°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 SAFE ArEA

ZONE 1 / 2 - ZONE 21 / 22 SAFE ArEA

ZONE 1 / 2 - ZONE 21 / 22 SAFE ArEA

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0054X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1

ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

INTERNATIONAL REGULATIONS COMPLIANCY FOR VISUAL AIDS

ICAO International Standards and Recommended Practices: Aerodromes - Annex 14 - Volume 1 - 4th Edition (November 2004)

Charapter 6 : Medium Intensity Type B Flashing obstacle light MIOL-B Charapter 6 : Low Intensity Type A-B Steady burning obstacle light LIOL-A / LIOL-B

FAA Advisor Circular AC150/5345-43F E.B.#67 - Lamp type MIOL-B / LIOL-A / LIOL-B

lEDs separate groups with individual led protection system - lED technology stalilized by constant current generatorConsumption LIOL-B = 4,8W (single and dual) / MIOL-B = 30W (single) - 60W (dual)Medium intensity (MIOL) flashing light with intensity 2000 cd (+/-25%) flashing 40 flash/minute Low intensity (lIOl) steady burning with intensity 32 cd (flashing on request)

Realization single group lEDs system with own reflector dual groups lEDs system, each group with own reflector (1 main + 1 reserve)

FLARE - AIRPORT - STACKS - HIGH BUILDINGS - CHIMNEYS - TOWER CRANE - PIPELINES - BRIDGES - RADIO AND TELEVISION TOWERS TRANSMISSION LINES - WIND TURBINES - RADAR - and so on

Horizontal beam radiation 360° (MIOL / LIOL) Vertical beam radiation lIOl = between 5° and 10° / MIOL = 3°Efficency > 91% - pfc factor 0,99Expetancy life long life time - more than 10 years

Body Marine grade copper free aluminium

Globe High-temperature resistant borosylicate glass (zone 1/2 - 21/22 version) Transparent polycarbonate U/V resistant (safe area version)

Painting External epoxy powders grey rAl-9006 colourScrews External stainless steelGaskets Silicon rubberCable Entry 3/4" NPT size threaded

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) - Safe area Classification: Group II - Category 2G 2D

Page 22: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

MIO

L -

LIO

L

YOUR PARTNER FOR SAFETY

Since 1961

315

(FIX

ING)

DO NOT

NON

ENERGISEDTENSIONE

WHILE

SOTTO

OPENAPRIRE

N O N A P R

I RE

SO

TT

OT

EN

SIONEOPE

N

NOTDO

WH

ILE

EN

ER

G I S E D

MIOL LIOL260

768

310

270275

(FIXING)

A MIOL LIOLB

DO NOT

NON

ENERGISEDTENSIONE

WHILE

SOTTO

OPENAPRIRE

N O N A P R

I RE

SO

TT

OT

EN

SIONEOPE

N

NOTDO

WH

ILE

EN

ER

G I S E D

MIOL LIOL150

445

115,5

135,5

151

(FIX

ING)

(FIXING)

22 - Feam Catalogue 01

MIOL - LIOL Technical data

MIOL - LIOL Technical featuresReference details Reference details

lIOl-A-S > 10 cd x 1 rED FIXED -Ex-d T6 T80°C 1 x 3/4" B

IP66 - - 2 x 3/4" D

lIOl-A-D > 10 cd x 2 rED FIXED -Ex-d T6 T80°C 1 x 3/4" B

IP66 - - 2 x 3/4" D

LIOL-B-S > 32 cd x 1 rED FIXED -Ex-d T6 T80°C 1 x 3/4" B

IP66 - - 2 x 3/4" D

LIOL-B-D > 32 cd x 2 rED FIXED -Ex-d T6 T80°C 1 x 3/4" B

IP66 - - 2 x 3/4" D

MIOL-A-S = 20.000 cd x 1 WHITEFlAShING 40 IP66 - - 2 x 3/4" C

MIOL-A-D = 20.000 cd x 2 WHITEFlAShING 40 IP66 - - 2 x 3/4" C

MIOL-B-S = 2.000 cd x 1 rEDFlAShING 40

Ex-d T6 T80°C 1 x 3/4" A

IP66 - - 2 x 3/4" C

MIOL-B-D = 2.000 cd x 2 rEDFlAShING 40

Ex-d T6 T80°C 1 x 3/4" A

IP66 - - 2 x 3/4" C

MIOL-C-S = 2.000 cd x 1 rED FIXED -Ex-d T6 T80°C 1 x 3/4" A

IP66 - - 2 x 3/4" C

MIOL-C-D = 2.000 cd x 2 rED FIXED -Ex-d T6 T80°C 1 x 3/4" A

IP66 - - 2 x 3/4" C

LOW INTENSITY OBSTRUCTION WARNING LIGHTS

MEDIUM INTENSITY OBSTRUCTION WARNING LIGHTS

CODE LED LAMP GROUP

VISUAL AIDS TYPES

FLASHING[x/min.]

EXECUTION TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

CABLE ENTRIES DETAIL

Ex Lighting

Page 23: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

MIO

L -

LIO

L

C MIOL LIOLD

MIOL LIOL

660MIOL LIOL

320

400

191

410

MIOL LIOL150

200

240

Feam Catalogue 01 - 23

Ex Lighting

MIOL - LIOL Technical featuresReference details Reference details

MIOL - LIOL Main rules for aircraft warning lightsMAIN RULES FOR VISUAL AIDS ICAO Annex 14 - Aerodromes Vol. 1 - Chapter 6 / 10 (July 2004)

• The marking and/or lighting of obstacles is intended to reduce hazards to aircraft by indicating the presence of the obstacles (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.1)

• Marking (red-orange/white painting) is used for day time• Marking may be ommitted when the obstacle is lighted

• A fixed obstacle above a horizontal surface should be marked and, if the aerodrome is used at night, lighted.. (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.1.4)

• A system of preventive maintenance of visual aids shall be employed to ensure lighting and marking system reliability (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 10.4.2)

• The reliability of installed lighting equipments shold not less than one year (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 10.4.6)

• The number and arrangement of Low, Medium or High Intensity Obstacle Lights , at each level to be marked, shall be such that the object is indicated from every angle in azimuth

• Where a light is shielded in any direction by another, additional light shall be provided (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.22)

• The number of lights needed for each level depends on the outside diameter of the obstacle• The top lights should be placed sufficiently below the top, so as to minimize contamination by smoke, powders, and so on.. (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.12)

AWL TYPES (Aircraft Warning Lights) LIOL-A / B Low Intensity Obstacle Lights on fixed objects, Type-A / Type-B, shall be steady burning RED lights(ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.23) MIOL-A Medium Intensity Obstacle Lights on fixed objects, Type-A , shall be flashing WHITE lights MIOL-B Medium Intensity Obstacle Lights on fixed objects, Type-B , shall be flashing RED lights MIOL-C Medium Intensity Obstacle Lights on fixed objects, Type-C , shall be steady burning RED lights(ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.30) MIOL-A / MIOL-B Medium Intensity Obstacle Lights Type-A / Type-B, located on an obstacle, shall be flash simultaneously (ICA: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.32)

HIOL-A / B High Intensity Obstacle Lights on fixed objects, Type-A / Type-B, shall be flashing WHITE lights(ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.33) HIOL-A High Intensity Obstacle Lights Type-A, located on an obstacle, shall be flash simultaneously (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.35) HIOL-B High Intensity Obstacle Lights Type-B, indicating the presence of tower supporting overhead wires, an others.. shall be flash sequentially (ICAO: Aerodromes - Annex 14 - Vol. 1 - Ch. 6.3.36)

Page 24: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

MIO

L -

LIO

L

> 45 m

> 150 m

24 - Feam Catalogue 01

MIOL - LIOL Indicative diagram to obstruction light selectionOBSTACLE ELEVATION

LIOL-A

MIOL-B + LIOL-B

LIOL-B

MIOL-C

YES

YES NO

NO

NO YES

YES

VERTICAL

EXTENDED

NO

MIOL - LIOL Polar diagrams – photometric data

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

MIOL - LIOL On request accessories

20302.0074 EVAC 100 / 101 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0077 EVAC 500 / 501 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0037 EVAC 100 / 101 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL

20302.0040 EVAC 500 / 501 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL

CONTROL PANEL WITH SIMULTANEOUS OR CATENARY MULTILIGHT FLASHING SYSTEM ALUMINIUM / PAINTED STEEL

LIOL 32cd - POLAR MIOL 2000cd - POLARLIOL 32cd - CARTESIAN MIOL 2000cd - CARTESIAN

LEGEND

(1) Painted obstacle in acc. to ICAO directive

LIOL-A Low intensity obstruction light - TYPE A

LIOL-B Low intensity obstruction light - TYPE B

MIOL-A Medium intensity obstruction light - TYPE A

MIOL-B Medium intensity obstruction light - TYPE B

MIOL-C Medium intensity obstruction light - TYPE C

HIOL-A High intensity obstruction light - TYPE AHIOL-B High intensity obstruction light - TYPE B

DUAL HIOL-A/B DAY: HIOL-A

+ NIGHT: MIOL-B

DUAL HIOL-A/C DAY: HIOL-A

+ NIGHT: MIOL-C

HIOL-A DAY: HIOL-A

NIGHT: HIOL-A

DUAL MIOL-A/B

DAY: MIOL-A + NIGHT: MIOL-B

DUAL MIOL-A/C DAY: MIOL-A

+ NIGHT: MIOL-C

MIOL-A DAY: MIOL-A

NIGHT: MIOL-A

STRUCTURE TYPE

MARKED STRUCTURE (1)

MARKED STRUCTURE (1)

CODE DESCRIPTION MATERIAL

Ex Lighting

VH Planes VH Planes VH Planes VH Planes

H Angles H Angles

Flux 76.52 Im

Maximum 69.78 cd

Position H=-35.00 V=5.00

Efficiency: 100.00%

asymmetric VH

Flux 76.52 Im

Maximum 69.78 cd

Position H=-35.00 V=5.00

Efficiency: 100.00%

asymmetric VH

Flux 1864.58 Im

Maximum 4301.23 cd

Position H=80.00 V=-90.00

Efficiency: 100.00%

asymmetric VH

Flux 1864.58 Im

Maximum 4301.23 cd

Position H=80.00 V=-90.00

Efficiency: 100.00%

asymmetric VH

Page 25: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

SFD

ESFDE

Feam Catalogue 01 - 25

FLOODLIGHTS FOR HALOGEN AND DISCHARGE LAMPS

Ex Lighting

ON REqUEST ACCESSORIES: • External painting colour on request• Control gear with voltage supply different than standard • Threaded cable entry different than standard

Mechanical characteristicsBody marine grade copper free aluminium

Diffuser tempered front glass

Support adjustable type hot dip galvanized steel

reflector internal polished aluminium

Painting external epoxy powders grey rAl-9006 colour

Screws external stainless steel

Gaskets silicon rubber

Cable entry 3/4” NPT size threaded

Electrical characteristicsPower supply conventional ballast 230v - 50hz (p.f.corrected - cos ρ ≥ 0,95)

lampholders porcelain E40 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

FLOODLIGHT / PROJECTORATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d / Ex de IIB T3/T2 II 2 D Ex tD A21 T200°C / T229°C

1Ex de IIB T6 (T3…T2) DIP A21 TA (200…230) °C

1Ex de IIB T6 (T3…T2) DIP A21 TA (200…230) °C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INERIS 01 ATEX 0018 POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Page 26: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

E

SFD250HPS SFD400MH SFD500IA

B

110 110110 110

A F C

D

E

2 x ISOM20 2 x ISOM20

A

SFDE250MH 250 W T4 T 200°C E-40 2 x ISO-M20 A

SFDE400MH 400 W T3 T 200°C E-40 2 x ISO-M20 A

SFDE150HPNA 150 W T4 T 200°C E-40 2 x ISO-M20 A

SFDE250HPNA 250 W T4 T 200°C E-40 2 x ISO-M20 A

SFDE400HPNA 400 W T3 T 200°C E-40 2 x ISO-M20 A

SFDE500IA 500 W T2 T 229°C E-40 2 x ISO-M20 A

SFDE150HPNA 485 425 290 270 504 88 25,00 2 x ISO-M20 ASFDE250HPNA 485 425 290 270 504 88 25,00 2 x ISO-M20 ASFDE400HPNA 485 425 290 270 504 88 25,00 2 x ISO-M20 ASFDE250MH 485 425 290 270 504 88 25,00 2 x ISO-M20 ASFDE400MH 485 425 290 270 504 88 25,00 2 x ISO-M20 ASFDE500 IA 485 425 290 270 504 88 21,00 2 x ISO-M20 A

26 - Feam Catalogue 01

Ex Lighting

SFDE Technical data

SFDE Technical features

CODE POWER LAMP

TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

LAMPHOLDER SIZE

CABLE ENTRY SIZE DETAIL

FLOODLIGHTS FOR HALOGEN LAMP - POWER SUPPLY 230V-50Hz

FLOODLIGHTS FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V-50Hz

FLOODLIGHTS FOR METAL HALIDE LAMP - POWER SUPPLY 230V-50Hz

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Reference details

CODE A [mm] B [mm] C [mm] D [mm] E [mm] F [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Page 27: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

RCD

ERCDE

Feam Catalogue 01 - 27

Ex Lighting

ON REqUEST ACCESSORIES:• External painting colour on request• Control gear with voltage supply different than standard • Threaded cable entry different than standard

Electrical characteristicsPower supply conventional ballast 230V - 50Hz (p.f.corrected - cos ρ ≥ 0,95)Lampholders porcelain E40 sizeInternal wiring high-temperature resistant silicon rubber insulation cablesTerminals suitable up to 4mm/sq cables

Mechanical characteristicsBody marine grade copper free aluminium Diffuser tempered front glassSupport adjustable type hot dip galvanized steelReflector internal polished aluminiumPainting external epoxy powders grey rAl-9006 colourScrews external stainless steelGaskets silicon rubberCable entry 3/4” NPT size threaded

FLOODLIGHTS FOR INCANDESCENT AND DISCHARGE LAMPS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

FLOODLIGHT / PROJECTORATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T4/T3/T2 II 2 D Ex tD A21 T135°C/T160°C T200°C/T230°C

1Ex d IIC T4/T3/T X DIP A21 TA 200°C,

DIP A21 TA (135, 160, 200, 230)°C

1Ex d IIC T4/T3/T2 X DIP A21 TA (135, 160, 200, 230)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 03 ATEX 0004 X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

CONTROL GEARATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T6/T2 II 2 D Ex tD A21 T80°C/T290°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

1Ex d IIC T6 (T5…T2) X DIP A21 TA (80…290)°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0054X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Page 28: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

RCD

E

rECDE500 250hPNA 250 W T4 T 135°C E-40 3x3/4” BrECDE500 400hPNA 400 W T3 T 200°C E-40 3x3/4” B

RECDE500 250HG 250 W T3 T 160°C E-40 3x3/4” B RECDE500 400HG 400 W T3 T 200°C E-40 3x3/4” B

A B

220

1x3/4”1x3/4”

CC 220

220

B

B

A

A

D

RCDE250MH RCDE250HG RCDE250HPS

RECDE500 500 W T3 T 200°C E-40 1x3/4” A

RECDE500 500 W T2 T 230°C E-40 1x3/4” A

RECDE500 250MH 250 W T4 T 135°C E-40 3x3/4” BRECDE500 400MH 400 W T3 T 200°C E-40 3x3/4” B

RECDE500 542 378 376 - 21,00 1 x 3/4” ARECDE500 250HG 542 378 406 700 29,00 3 x 3/4” BRECDE500 250HPNA 542 378 406 700 29,50 3 x 3/4” BRECDE500 400HG 542 378 406 700 31,00 3 x 3/4” BRECDE500 400HPNA 542 378 406 700 31,50 3 x 3/4” BRECDE500 250MH 542 378 406 700 26,50 3 x 3/4” BRECDE500 400MH 542 378 406 700 31,50 3 x 3/4” B

Ex Lighting

RCDE Technical data

RCDE Technical features

FLOODLIGHTS FOR METAL HALIDE LAMP - POWER SUPPLY 230V-50Hz

FLOODLIGHTS FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V-50Hz

FLOODLIGHTS FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V-50Hz

FLOODLIGHTS FOR BLENDED LIGHT LAMP - POWER SUPPLY 230V-50Hz

FLOODLIGHTS FOR INCANDESCENT LAMP - POWER SUPPLY 230V-50Hz

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

LAMPHOLDER SIZE

CABLE ENTRY SIZE DETAIL

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

28 - Feam Catalogue 01

2x3/4”with PLG2

Page 29: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVO

- E

VT -

TLF

EVO - EVT - TLF

Feam Catalogue 01 - 29

Ex Lighting

ON REqUEST ACCESSORIES:• External painting colour on request• Threaded cable entry different than standard

Electrical characteristicsPower supply standard voltage 230v - 50hz lampholders porcelain E27 sizeInternal wiring high-temperature resistant silicon rubber insulation cables

Mechanical characteristicsBody marine grade copper free aluminium Diffuser borosilicate frontal glass (EvT)Diffuser tempered frontal glass (EvO - TlF)Painting external epoxy powders grey rAl-9006 colourScrews external stainless steelGaskets silicon rubberCable entry 3/4” NPT size threaded Protection guard galvanized wire steel (EVT ONLY)

LIGHTING FIXTURES FOR INCANDESCENT LAMPS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

PORTHOLE LIGHTING FIXTURE (EVO)

ATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T3, II 2 D Ex tD A21 T200°C 1Ex d IIC T3 X, DIP A21 TA 200°C 1Ex d IIC T3 X, DIP A21 TA 200°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0039 X POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

LIGHTING FIXTURE (EVT)

ATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIC T4, II 2 D Ex tD A21 T135°C 1Ex d IIC T4, DIP A21 TA 135°C 1Ex d IIC T4, DIP A21 TA 135°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INErIS 01 ATEX 0040 POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1 ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

LIGHTING FIXTURE (TLF)

ATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d / Ex de IIB T3 II 2 D Ex tD A21 T200°C

1Ex d IIB T3, 2Ex de IIB T3 DIP A21 TA 200°C

1Ex d IIB T3, 2Ex de IIB T3 DIP A21 TA 200°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP65 IP65 IP65

CERTIFICATE REF. INErIS 01 ATEX 0026 POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1 ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Page 30: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVO

- E

VT -

TLF

1 x 3/4”

ØC

A

B

2 x 3/4”

B C

A

C

ØA

B

2 x 3/4”

A

C

B

EVO100 Ø140 185 Ø162 2,00 1 x 3/4” A

EVT100 Ø233 180 155 4,00 2 x 3/4” B

TLF100 309 127 165 3,00 2 x 3/4” C

EVO100 100 W T3 T 200°C E-27 1x3/4” A

EVT100 100 W T4 T135°C E-27 2x3/4” B

TLF100 100 W T3 T 200°C E-27 2x3/4” C

30 - Feam Catalogue 01

Ex Lighting

EVO – EVT - TLF Technical data

EVO – EVT - TLF Technical features

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

CODE LAMP TEMPERATURE CLASS

(GAS) TEMPERATURE CLASS

(DUSTS) LAMPHOLDER

SIZECABLE ENTRY

SIZEDETAIL

LIGHTING FIXTURE FOR INCANDESCENT LAMP - POWER SUPPLY 230V-50Hz

CODE A [mm] B [mm] C [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

Page 31: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EXLEXL

Feam Catalogue 01 - 31

Ex Lighting

ON REqUEST ACCESSORIES:• External painting colour on request• Electronic ballast with voltage supply different than standard

• Threaded cable entry different than standard• Self-adhesive green label with EXIT sign (language on request)

Mechanical characteristicsBody marine grade copper free aluminium Diffuser high-temperature resistant borosylicate glass Painting external epoxy powders grey rAl-9006 colourScrews external stainless steelreflectors white stove enamelled sheet steelCable entry 3/4” NPT size threaded c/w cable gland

Electrical characteristicsPower supply elettronic ballast 220V/240V - 50/60Hz (p.f.corrected - cos ρ ≥ 0,98)lampholders bi-pin G5 cap (fluorescent lamp only)Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cablesEmergency unit emergency unit with inverter charger and Ni-Cd battery pack see technical features for more details

LIGHTING FIXTURES FOR HIGH EFFICENCY LED LAMPS AND FLUORESCENT TUBE LAMPS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

· EXL08E / EXL08ESA - 8W fluorescent lamp: emergency light intensity is 40% of light intensity with networking power supply· EXL08LE - with high brightness LEDs (350mA -4.8 W): emergency light intensity is 100% of light intensity with networking power supply

Functional characteristics

Remarks

LIGHTING FIXTUREATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex d IIB T6 II 2 D Ex tD A21 T85°C

1Ex d IIB T6, 1Exd [ia/ib] IIB T6, DIP A21 TA 85°C

1Ex d IIB T6, 1Exd [ia/ib] IIB T6, DIP A21 TA 85°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. IMQ 09 ATEX 020 POCC IT. ГБ05.B02537 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1

ГОСТ Р 51330.9-99 (МЭК 660079-10-95) ГОСТ Р 51330.13-99 (МЭК 660079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

· EXL08ESA (Always ON - Maintained): 8W fluorescent lamp and electronic ballast 230V AC and emergency unit 3.6 V - 2Ah for an autonomy of 2 hours 3.6 V - 4Ah for an autonomy 3 hours

· EXL08E (Emergency only - Maintained): 8W fluorescent lamp and emergency unit 3.6 V - 2Ah with autonomy 3 hours· EXL08L (Network only - Not Maintained): with high brightness LEDs (350mA - 4,8 W) Supply from 120V to 240V AC / DC· EXL08LE (Emergency only - Maintained): with high brightness LEDs (350mA - 4,8 W) 220/240V AC and emergency unit 6V - 2Ah for an

autonomy of 3 hours complete with charge status monitor LED system (RED: battery under charging – GREEN: battery loaded)

Page 32: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EXL

EXL-08 EXL-08L EXL2-08L

E

3/4"

C A

D

B

A

EXL08 380 170 125 370 125 8,00 1 x 3/4” AEXL08E-3 380 170 125 370 125 8,00 1 x 3/4” AEXL08ESA-3 380 170 125 370 125 8,00 1 x 3/4” AEXL08L 380 170 125 370 125 8,00 1 x 3/4” AEXL08LE 380 170 125 370 125 8,00 1 x 3/4” AEXL208L 380 170 125 370 125 8,00 1 x 3/4” A

EXL08 220 ÷ 240V AC 8 W - T6 T 85°C - -EXL08E-3 220 ÷ 240V AC 8 W - T6 T 85°C 3,6V - 4A/h 3hEXL08ESA-3 220 ÷ 240V AC 8 W - T6 T 85°C 3,6V - 4A/h 3h

EXL08L 120 ÷ 240V AC/DC 4,8 W 350 T6 T 85°C - -EXL08LE 220 ÷ 240V AC 4,8 W 350 T6 T 85°C 3,6V - 2A/h 3hEXL208L 120 ÷ 240V AC/DC 9,16 W 350 T6 T 85°C - -

32 - Feam Catalogue 01

EXL Technical data

EXL Technical features

CODE POWER SUPPLY LAMP mA (LED) TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

EMERGENCY UNIT AUTONOMY

LIGHTING FIXTURES FOR FLUORESCENT TUBE LAMPS

LIGHTING FIXTURES FOR HIGH EFFICENCY LED LAMPS

CODE A [mm] B [mm] C [mm] D [mm] E [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

EXL On request accessoriesCODE DESCRIPTION MATERIAL

2070.00088 SELF-ADHESIVE GREEN “EXIT” LABEL POLYESTER

Ex Lighting

Page 33: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVG

EVG

Feam Catalogue 01 - 33

ON REqUEST ACCESSORIES:•Pole mounting kit complete with stainless steel hardware•Ceiling mounting kit complete with stainless steel hardware

•Pendant mounting kit complete with stainless steel hardware •Wall/Structure mounting kit complete with stainless steel hardware •Electronic ballast with voltage supply different than standard

Electrical characteristicsPower supply elettronic ballast 220v/240v - 50/60hz (p.f.corrected - cos ρ ≥ 0,98)lampholders bi-pin G13 capInternal wiring high-temperature resistant silicon rubber insulation cablesTerminals suitable up to 6mm/sq cablesSafety feature “end of life” switching-off system in according to EN 60079-7 rulesEmergency unit emergency unit composed of inverter charger and Ni-Cd battery pack 7A/h 6v autonomy up to 180 min. Advantages see table “advantage features”

Mechanical characteristicsBody glass fibre reinforced polyester resindiffuser U/V resistant polycarbonate - hinged to bodysafety closing operated by triangular keygaskets EPDM rubber suitable for high temperatures and resistant to enviroments conditionsinternal reflector white polyester highly refractor diffusercable entry ISO-Metric thread c/w plastic cable glands and stopping plug

Ex Lighting

LIGHTING FIXTURES FOR FLUORESCENT TUBE LAMPS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

18W LIGHTING FIXTURE 36W LIGHTING FIXTUREATEX 94/9/EC GOST-R (RTR / RTN) ATEX 94/9/EC

EXECUTION II 2 G Ex edq IIC T4 II 2 D Ex tD A21 T 80°C

2Ex edq IIC T4 (T6) DIP A21 TA 80°C

II 2 G Ex edq IIC T4 II 2 D Ex tD A21 T 80°C

AMBIENT TEMPERATURE -20°C ÷ +60°C -20°C ÷ +60°C -20°C ÷ +55°C

PROTECTION DEGREE IP66 IP66 IP66/64

CERTIFICATE REF. PTB 97 ATEX 2223 POCC DE. ГБ05.B01788 PTB 07 ATEX 2040

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1

ГОСТ Р 51330.9-99 (МЭК 660079-10-95) ГОСТ Р 51330.13-99 (МЭК 660079-14-96)

ГОСТ Р МЭК 61241-3-99

EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1

58W LIGHTING FIXTURE LIGHTING FIXTURES WITH EMERGENCY UNIT ONLY

ATEX 94/9/EC GOST-R (RTR / RTN) ATEX 94/9/EC

EXECUTION II 2 G Ex edq IIC T4 II 2 D Ex tD A21 T 90°C

2Ex edq IIC T4 (T6) DIP A21 TA 90°C

II 2 GD Ex edq IIC T4 T80°C

AMBIENT TEMPERATURE -20°C ÷ +60°C -20°C ÷ +60°C -20°C ÷ +55°C

PROTECTION DEGREE IP66 IP66 IP66/64

CERTIFICATE REF. PTB 97 ATEX 2225 POCC DE. ГБ05.B01788 PTB 05 ATEX 2066

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1

ГОСТ Р 51330.9-99 (МЭК 660079-10-95) ГОСТ Р 51330.13-99 (МЭК 660079-14-96)

ГОСТ Р МЭК 61241-3-99

EN 60079-0; EN 60079-1; EN 61241-0; EN 61242-1

Page 34: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

EVG

YOUR PARTNER FOR SAFETY

Since 1961

SH-21EVG 786 160 214 600 10,00 3 x ISO-M25 A

SH-41EVG 1355 150 226 716 13,00 3 x ISO-M25 A

SH-61EVG 1696 160 214 800 16,00 3 x ISO-M25 A

SH-22EVG 786 160 214 600 10,50 3 x ISO-M25 A

SH-42EVG 1355 150 226 716 13,50 3 x ISO-M25 A

SH-62EVG 1696 160 214 800 16,50 3 x ISO-M25 A

SH-22EVG-E 913 160 221 600 9,40 2 x ISO-M25 B

SH-42EVG-E 1523 160 221 800 12,80 2 x ISO-M25 B

A

D

C

B

A

D

C

BSH-21EVG 1 x 18W T4 (Ta = -20°C / +60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 - - A

SH-41EVG 1 x 36W T4 (Ta = -20°C / +60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 - - A

SH-61EVG 1 x 58W T4 (Ta = -20°C / +60°C) T 90°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 - - A

SH-22EVG 2 x 18W T4 (Ta = -20°C / +60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 - - A

SH-42EVG 2 x 36W T4 (Ta = -20°C / +60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 - - A

SH-62EVG 2 x 58W T4 (Ta = -20°C / +60°C) T 90°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 - - A

SH-22EVG-E 2 x 18W T4 (Ta = -20°C / +60°C) T 80°C (Ta = -20°C / +60°C) G13 2 x ISO-M25 6 V - 7 A/h 3h B

SH-42EVG-E 2 x 36W T4 (Ta = -20°C / +60°C) T 80°C (Ta = -20°C / +60°C) G13 2 x ISO-M25 6 V - 7 A/h 3h B

A

B

34 - Feam Catalogue 01

Ex Lighting

EVG Technical data

EVG Technical featuresCODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V-50/60Hz

EMERGENCY FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V-50/60Hz

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE ENTRY EMERGENCY

UNIT AUTONOMY DETAIL

Page 35: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVG

50

45°

100

100

SH-21EVG SH-22EVG SH-41EVG

Feam Catalogue 01 - 35

Ex Lighting

EVG Installation and mounting details

EVG Polar diagrams – photometric data

Wall/structure mountingPole mounting

Assemblig detail with pole (typical)type 3 type 4

type 1 type 2Ceiling mounting Pendant mounting

Page 36: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVG

SH-42EVG SH-61EVG SH-62EVG

36 - Feam Catalogue 01

Ex Lighting

EVG Polar diagrams – photometric data

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

EVG with emergency unit

EVG On request accessoriesCODE DESCRIPTION INSTALLATION MATERIAL

20301.0162 POLE MOUNTING KIT (SIZE 2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20301.0163 POLE MOUNTING KIT (SIZE 1 1/2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20301.0165 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 STAINLESS STEEL

20302.0121 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 GALVANIZED STEEL

20302.0128 WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 GALVANIZED STEEL

LIGHTING FIXTURES AND EMERGENCY UNIT ELECTRICAL DESIGN AND SPECIAL FEATURES Microprocessor (PlC) “END-OF lIFE” switching-off system at the end of life a fluorescent tube lamp is safely switched off (according to iec eN-60079-7 stds)Multi-function led Multi-function led indcator with coded indication of the functions, status and potential failures of the electronic device and of the batteriesMonitoring Special signal whenever there is a e.o.l. situation (led red flashing ) Automatic weekly functions test Automatic annual 2/3 times operating period test Function and operating period test can be done manually also

Maintenance Quick replacement of battery set even in explosive atmosphere presence

Electrical disconnection whenever the batteries box is opened

24h max recharging time (in according to EN-60598-2-22)

Safety Highest degree of safety in case of lamp failure during the emergency light operation

In case of lamp failure during emergency operation the second tube lamp will automatically take over the emergency operation (two lamps version only)

Page 37: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

e191

- e1

92

e191 - e192

Feam Catalogue 01 - 37

Ex Lighting

ON REqUEST ACCESSORIES:•Recessed mounting kit EB182 series complete with stainless steel hardware•Stainless steel sheet body •Electronic ballast with voltage supply different than standard

FLUORESCENT LIGHTING FIXTURES FOR CEILING OR RECESSED INSTALLATION

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

Mechanical characteristicsBody sheet steel white coloured rAl 9016

Diffuser safety toughened impact resistant tempered glass hinged to body

Safety closing central locking system operated by 5mm allen key - hinges on opposite side

Gaskets EPDM rubber suitable for high temperatures and resistant to enviroments conditions

Internal reflector high anodized purest aluminium

Cable entry ISO-metric thread c/w plastic cable glands and stopping plug

Electrical characteristicsPower supply dual channel elettronic ballast 220v/240v-50/60hz (p.f.corrected - cos ρ ≥ 0,98) - DC

lampholders bi-pin G13 cap

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 6mm/sq cables

Isolating switch switching off all poles when lighting fitting is opened showing the actual position by optical indicator

Safety feature “END OF LIFE” switching-off system in according to EN 60079-7 rules

LIGHTING FIXTUREATEX 94/9/EC GOST-R (RTR / RTN)

EXECUTION II 2G Ex edq IIC T4 II 2D Ex tD A21 T 80°C

2Ex edq IIC T4, 2Ex eq II T4, DIP A21 TA 80°C

AMBIENT TEMPERATURE-20°C ÷ +60°C (e191… - e192... surface/recessed in suspend. ceiling)

-20°C ÷ +50°C (e191… recessed mount. insulated) -20°C ÷ +40°C (e192... recessed mount. insulated)

-20°C ÷ +40°C

PROTECTION DEGREE IP65 IP65

CERTIFICATE REF. IBExU 04 ATEX 1062 POCC DE. ГБ05.B01788

RULES OF COMPLIANCE EN 50014 +A1 +A2; EN 50017; EN 50018; EN 50019; EN 50281-1-1

ГОСТ Р 51330.9-99 (МЭК 660079-10-95) ГОСТ Р 51330.13-99 (МЭК 660079-14-96)

ГОСТ Р МЭК 61241-3-99

Page 38: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

e191

- e1

92e1

91-

e192

e19121 1 x 18W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19122 2 x 18W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19141 1 x 36W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19142 2 x 36W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19161 1 x 58W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19162 2 x 58W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19223 3 x 18W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19224 4 x 18W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19243 3 x 36W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19244 4 x 36W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19263 3 x 58W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19264 4 x 58W T4 (Ta = -20°C ÷ 40/50/60°C) T 80°C (Ta = -20°C / +60°C) G13 3 x ISO-M25 A

e19121 720 82 368 600 404 10,00 3 x ISO-M25 A

e19122 720 82 368 600 404 10,00 3 x ISO-M25 A

e19141 1330 82 368 1200 404 15,50 3 x ISO-M25 A

e19142 1330 82 368 1200 404 15,50 3 x ISO-M25 A

e19161 1630 82 368 1400 404 18,00 3 x ISO-M25 A

e19162 1630 82 368 1400 404 18,00 3 x ISO-M25 A

e19223 720 82 500 600 536 18,50 3 x ISO-M25 A

e19224 720 82 500 600 536 18,50 3 x ISO-M25 A

e19243 1330 82 500 1200 536 25,50 3 x ISO-M25 A

e19244 1330 82 500 1200 536 25,50 3 x ISO-M25 A

e19263 1630 82 500 1400 536 28,50 3 x ISO-M25 A

e19264 1630 82 500 1400 536 28,50 3 x ISO-M25 A

B

E

C

D

A

Ø9

A

38 - Feam Catalogue 01

Ex Lighting

e191 - e192 Technical data

e191 - e192 Lighting fixture technical features

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE ENTRY DETAIL

FLUORESCENT LIGHTING FIXTURES - POWER SUPPLY 220-240V-50/60Hz - DC

Lighting fixture Reference details

CODE A [mm] B [mm] C [mm] D [mm] E [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Page 39: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

e191

- e1

92

EB182-18 e19121 388 740 786 93 300 434 82 9

e19122 388 740 786 93 300 434 82 9

EB182-36 e19141 388 1350 1396 98 400 434 82 9

e19142 388 1350 1396 98 400 434 82 9

EB182-58 e19161 388 1650 1696 48 400 434 82 9

e19162 388 1650 1696 48 400 434 82 9

EB192-18 e19223 520 740 786 93 300 566 82 9

e19224 520 740 786 93 300 566 82 9

EB192-36 e19243 520 1350 1396 96 400 566 82 9

e19244 520 1350 1396 96 400 566 82 9

EB192-58 e19263 520 1650 1696 48 400 566 82 9

e19264 520 1650 1696 48 400 566 82 9

e191-42 e192-43 e192-44

BA

C

E E E

G

DD

h

F

Feam Catalogue 01 - 39

Ex Lighting

e191 - e192 Recessed frame technical featuresCODE LUMINARIE TYPE A [mm] B [mm] C [mm] D [mm] E [mm] F [mm] G [mm] H [mm]

Recessed frame Reference details

e191 - e192 Polar diagrams – photometric data

Page 40: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

e191

- e1

92

e191-22 e191-23 e191-64

40 - Feam Catalogue 01

e191 - e192 Polar diagrams – photometric data

e191 - e192 On request accessories

CODE DESCRIPTION MATERIAL

EB182-18 RECESSED FRAME FOR LIGHTING FIXTURE 1x18W AND 2x18W PAINTED SHEET STEEL

EB182-36 RECESSED FRAME FOR LIGHTING FIXTURE 1x36W AND 2x36W PAINTED SHEET STEEL

EB182-58 RECESSED FRAME FOR LIGHTING FIXTURE 1x58W AND 2x58W PAINTED SHEET STEEL

EB192-18 RECESSED FRAME FOR LIGHTING FIXTURE 3x18W AND 4x18W PAINTED SHEET STEEL

EB192-36 RECESSED FRAME FOR LIGHTING FIXTURE 3x36W AND 4x36W PAINTED SHEET STEEL

EB192-58 RECESSED FRAME FOR LIGHTING FIXTURE 3x58W AND 4x58W PAINTED SHEET STEEL

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Ex Lighting

Page 41: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

AVF

AVF

Feam Catalogue 01 - 41

Ex Lighting

ON REqUEST ACCESSORIES: • Pole mounting kit complete with stainless steel hardware• Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware

• Wall/Structure mounting kit complete with stainless steel hardware • Electronic ballast with voltage supply different than standard• AUTOTEST electronic system for emergency unit

Mechanical characteristicsBody galss fibre reinforced polyester resin self-extinguishing acc. to UL94Diffuser U/V resistant polycarbonate - hinged to body Safety closing operated by hexagonal keyGaskets EPDM 60 rubber suitable for high temperatures and resistant to enviroments conditionsInternal reflector white stove enamelled sheet aluminumCable entry ISO-Metric complete with cable glands and plug

Electrical characteristicsPower supply elettronic ballast 220V/240V 50/60Hz (p.f. corrected - cos ρ ≥ 0,98)Lampholders bi-pin G13 capInternal wiring high-temperature resistant silicon rubber insulation cablesTerminals suitable up to 6mm/sq cablesSafety feature EEx de safety switch

INCREASED SAFETY LIGHTING FIXTURES FOR BI-PIN FLUORESCENT LAMPS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

LIGHTING FIXTUREATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex ed IIC T5 II 2 D Ex tD A21 T70°C

2Ex ed IIC T5 DIP A21 TA 70°C

2Ex ed IIC T5 DIP A21 TA 70°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. KEMA 01 ATEX 2069 POCC IT. ГБ05.B02536 No. 07/43-269

RULES OF COMPLIANCE EN 60079-0; EN 60079-1; EN 60079-7; EN 61241-1

ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

EMERGENCY UNITATEX 94/9/EC GOST-R (RTR / RTN) GOST-K

EXECUTION II 2 G Ex ed IIC T6 II 2 D Ex tD A21 T85°C

1Ex ed IIB T6 DIP A21 TA 85°C

1Ex ed IIB T6 DIP A21 TA 85°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. IMQ 08 ATEX 026X POCC IT. ГБ05.B02537 No. 07/43-269

RULES OF COMPLIANCE EN 60070-0; EN 60079-7; EN 61241-0; EN 61241-1;

ГОСТ Р 51330.9-99 (МЭК 60079-10-95) ГОСТ Р 51330.13-99 (МЭК 60079-14-96)

ГОСТ Р МЭК 61241-3-99

ГОСТ Р 51330.0 / 1 / 8 / 14-99 ГОСТ Р МЭК 61241-1-1-2002

Page 42: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

AVF

AVF 118 1 x 18W T5 T 70°C G13 3 x M20 x 1,5 - - A

AVF 136 1 x 36W T5 T 70°C G13 3 x M20 x 1,5 - - A

AVF 218 2 x 18W T5 T 70°C G13 3 x M20 x 1,5 - - A

AVF 236 2 x 36W T5 T 70°C G13 3 x M20 x 1,5 - - A

AVF 118-E 1 x 18W T5 T 70°C G13 2 x M20 x 1,5 4.8 V - 4Ah 3h B

AVF 136-E 1 x 36W T5 T 70°C G13 2 x M20 x 1,5 4.8 V - 4Ah 3h B

AVF 218-E 2 x 18W T5 T 70°C G13 2 x M20 x 1,5 4.8 V - 4Ah 3h B

AVF 236-E 2 x 36W T5 T 70°C G13 2 x M20 x 1,5 4.8 V - 4Ah 3h B

D

B

C

8MA 8MA

A

8MA

D

B

C

8MA 8MA

A

8MA

AVF 118 730 215 160 400 6,00 3 x M20 x 1,5 A

AVF 136 1340 215 160 450 6,50 3 x M20 x 1,5 A

AVF 218 730 215 160 400 7,00 3 x M20 x 1,5 A

AVF 236 1340 215 160 450 7,50 3 x M20 x 1,5 A

AVF 118-E 925 215 280 400 11,00 2 x M20 x 1,5 B

AVF 136-E 1535 215 280 450 11,50 2 x M20 x 1,5 B

AVF 218-E 925 215 280 400 12,00 2 x M20 x 1,5 B

AVF 236-E 1535 215 280 450 12,50 2 x M20 x 1,5 B

A

B

42 - Feam Catalogue 01

FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V 50/60Hz

EMERGENCY FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V 50/60Hz

Ex Lighting

AVF Technical data

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE

ENTRYEMERGENCY

UNIT AUTONOMY DETAIL

AVF Technical featuresCODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

Page 43: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

AVF

50

45°

100

100

AVF218 AVF136 AVF236

Feam Catalogue 01 - 43

Ex Lighting

AVF Installation and mounting details

AVF Polar diagrams – photometric data

Wall/structure mountingPole mounting

Assemblig detail with pole (typical)type 3 type 4

type 1 type 2Ceiling mounting Pendant mounting

Page 44: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

AVF

ON ON ON ON ON ON ON ON ON

ON ON ON ON ON ON ON ON ON

OFF OFF OFF OFF OFF OFF OFF OFF OFF

ON ON ON OFF ON ON ON OFF ON

ON OFF ON OFF ON OFF ON OFF ON

ON ON OFF ON ON OFF ON ON OFF

ON OFF ON OFF ON OFF ON OFF ON

ON OFF ON OFF ON OFF ON OFF ON

ON ON ON ON ON ON ON ON ON

44 - Feam Catalogue 01

Ex Lighting

AVF with emergency unit (design and special features)

CODE DESCRIPTION INSTALLATION MATERIAL

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

AVF On request accessories

Multicolor LED indicator in standard working (continuous led light)

Multicolor LED indicator during test opetarion (intermittent led light)

Multicolor LED indicator during batteries recharging phase

GENERALITY:

The controller unit system permits to manage in AUTOTEST the verify of emergency unit working This system allows the emergency working of every fluorescent tube lamps (NON maintened working) The check and the control system has been realized by proper microprocessor which perform the following tests : - continuous test on the battery charger working, on the operation of the battery, and on presence of voltage supply - duration test in emergency working (every 3 months) with check of battery charge - test of emergency working (weekly) with check of right lamp operation

Every information concerning the checks can be managed singly or tranmitted by “remote control system” in order to manage complete illumination system test in centralized way.

Regular operation

Failed battery performance check

Lack of main power supply

Lack of battery

Performing lamp test

Performing battery pack test

Failed lamp test

24 hours

After 24 hours

20301.0162 POLE MOUNTING KIT (SIZE 2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20301.0163 POLE MOUNTING KIT (SIZE 1 1/2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20301.0165 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 STAINLESS STEEL

20302.0121 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 GALVANIZED STEEL

20302.0128 WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 GALVANIZED STEEL

AUTOTEST ELECTRONIC SYSTEM - -

Page 45: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

SFD

qL

SFDqL

Feam Catalogue 01 - 45

Ex Lighting

ON REqUEST ACCESSORIES:•Power supply 90 ÷ 120V AC/DC (55/85W only)

Mechanical characteristicsBody marine grade copper free aluminum

Diffuser tempered front glass

Support steel bracket with rotation-proof system

Reflector anodized and polished 99,85 pure aluminum internal optic

Painting thermosetting polyester powder resistant to atmospheric agents and corrosion grey RAL 9006 colour

Screws stainless steel

Gaskets pure silicon heat resistance

Cable entry ISO-Metric complete with nikel plated brass cable gland M20

Electrical characteristics Power supply 180 ÷ 230V DC / 180 ÷ 277V AC x 165W - 55W - 85W

Lamp long life induction lamp (60.000 hours)

Terminals suitable up to 4mm/sq cables

FLOODLIGHT PROJECTORS FOR INDUCTION LAMPS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D

FLOODLIGHT ATEX 94/9/EC

EXECUTION II 2G Ex eq II T3 II 2D Ex tD A21 T 200°C

AMBIENT TEMPERATURE -40°C ÷ +40°C -40°C ÷ +60°C

PROTECTION DEGREE IP66

CERTIFICATE REF. IMQ 09 ATEX 014X

RULES OF COMPLIANCE EN 60079-0; EN 60079-5; EN 60079-7; EN 61241-0; EN 61241-1

Page 46: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

qL

SFDQL-55JB 430 460 545 260 8,50 2 x ISO M20 A

SFDQL-85JB 430 460 545 260 8,70 2 x ISO M20 A

SFDQL-165JB 430 460 545 260 9,50 2 x ISO M20 A

SFDQL-55 430 460 545 180 8,00 1 x PCE M20 B

SFDQL-85 430 460 545 180 8,20 1 x PCE M20 B

SFDQL-165 430 460 545 180 9,00 1 x PCE M20 B

SFDQL-55JB 55W T3 (Ta = -40°C / +60°C) T 200°C 2 x ISO M20 A

SFDQL-85JB 85W T3 (Ta = -40°C / +60°C) T 200°C 2 x ISO M20 A

SFDQL-55 55W T3 (Ta = -40°C / +60°C) T 200°C 1 x PCE M20 B

SFDQL-85 85W T3 (Ta = -40°C / +60°C) T 200°C 1 x PCE M20 B

SFDQL-165JB 165W T3 (Ta = -40°C / +40°C) T 200°C 2 x ISO M20 A

SFDQL-165 165W T3 (Ta = -40°C / +40°C) T 200°C 1 x PCE M20 B

INDUCTION LAMPwww.feam-ex.com

SFDQL0722

165W 85W 55W

180÷230V DC180÷277V AC90÷120V AC/DC

II 2G Ex eq II T3

IMQ 08 ATEX 014XII 2D Ex tD A21 IP 66 T200° C

55W-85W Ta -40° C / +60° C

165W Ta -40° C / +40° C

120°

A D

155 155

2 X ISO M20

B

C

A

46 - Feam Catalogue 01

Ex Lighting

SFDqL Technical data

SFDqL Technical features

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) CABLE ENTRY SIZE DETAIL

FLOODLIGHT FOR INDUCTION LAMP - POWER SUPPLY 220V/240V 50/60Hz - 220V/240V DC - 120V AC/DC

FLOODLIGHT FOR INDUCTION LAMP - POWER SUPPLY 220V/240V 50/60Hz - 220V/240V DC

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

Page 47: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

qL

SFDqL55 SFDqL85 SFDqL165

SFDQLINDUCTION LAMP

www.feam-ex.com

0722

165W 85W 55W

180÷230V DC180÷277V AC90÷120V AC/DC

II 2G Ex eq II T3

IMQ 08 ATEX 014XII 2D Ex tD A21 IP 66 T200° C

55W-85W Ta -40° C / +60° C

165W Ta -40° C / +40° C

120°

A D

155 155

1 X PCE M20

B

C

B

Ex Lighting

SFDqL Technical features

SFDqL Polar diagrams – photometric data

Reference details

Feam Catalogue 01 - 47

Page 48: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

qL

20303.0099 20303.0100

SFDqL On request accessories

Ex Lighting

20303.0099 PROTECTION GRID ALUMINUM

20303.0100 POLE ADAPTER - DIA. 40÷60mm PAINTED STEEL

48 - Feam Catalogue 01

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Protection grid Pole adapter

CODE DESCRIPTION MATERIAL

Page 49: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVSNEVSN

Feam Catalogue 01 - 49

Ex Lighting

ON REqUEST ACCESSORIES:• Pole mounting kit complete with stainless steel hardware• Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware• Wall/Structure mounting kit complete with stainless steel hardware

• Electronic ballast with voltage supply different than standard• Ex-de safety switch• AUTOTEST electronic system for emergency unit

Mechanical characteristicsBody glass fibre reinforced polyester resin

Diffuser U/V resistant polycarbonate - hinged to body

Safety closing stainless steel hooks with safety device

Gaskets EPDM 60 rubber suitable for high temperatures and resistant to enviroments conditions

Internal reflector white stove enamelled sheet steel

Cable entry complete with PVC cable gland

Electrical characteristicsPower supply dual channel electronic ballast 220/240V 50/60Hz (cos ρ ≥ 0,98)

Lampholders bi-pin G13 cap

Terminals suitable up to 6mm/sq cables

Installation: hazardous areas - Zone 2 (Gases) - Zone 22 (Dusts) Classification: Group II - Category 3G 3D

LIGHTING FIXTURES FOR FLUORESCENT TUBE LAMPS

LIGHTING FIXTURE EMERGENCY UNIT

ATEX 94/9/EC ATEX 94/9/EC

EXECUTION II 3 G Ex nA II T6/T5 II 3 D Ex tD A22 T85°C/T100°C

II 2 G Ex ed IIC II 2 D Ex tD A21 T85°C

AMBIENT TEMPERATURE - -40°C ÷ +55°C

INSTALLATION ZONE 2 - ZONE 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP65 IP66

CERTIFICATE REF. IMQ 08 ATEX 008X IMQ 08 ATEX 026X

RULES OF COMPLIANCE EN 60079-0; EN 60079-15; EN 61241-0; 61241-1 EN 60070-0; EN 60079-7; EN 61241-0; EN 61241-1

Page 50: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVSN

EVSN118EL 667 90 98 420 1,75 1 x PG 13,5 A

EVSN136EL 1276 90 98 775 2,45 1 x PG 13,5 A

EVSN158EL 1576 90 98 1070 3,10 1 x PG 13,5 A

EVSN218EL 667 155 102 455 2,10 1 x PG 13,5 A

EVSN236EL 1276 155 102 770 3,90 1 x PG 13,5 A

EVSN258EL 1576 155 102 1055 5,20 1 x PG 13,5 A

C

BA

DA

T6 T 85°C

EVSNE118EL 1 x 18W T5 T100°C G13 1 x PG 13,5 4,8V - 4Ah 3h B

T4 T135°C

T6 T 85°C

EVSNE136EL 1 x 36W T5 T100°C G13 1 x PG 13,5 4,8V - 4Ah 3h B

T4 T135°C

EVSNE158EL 1 x 58W T5 T100°C G13 1 x PG 13,5 4,8V - 4Ah 3h B

T6 T 85°C

EVSNE218EL 2 x 18W T5 T100°C G13 1 x PG 13,5 4,8V - 4Ah 3h B

T4 T135°C

T6 T 85°C

EVSNE236EL 2 x 36W T5 T100°C G13 1 x PG 13,5 4,8V - 4Ah 3h B

T4 T135°C

EVSNE258EL 2 x 58W T5 T100°C G13 1 x PG 13,5 4,8V - 4Ah 3h B

T6 T 85°C

EVSN118EL 1 x 18W T5 T100°C G13 1 x PG 13,5 - - A

T4 T135°C

T6 T 85°C

EVSN136EL 1 x 36W T5 T100°C G1 1 x PG 13,5 - - A

T4 T135°C

EVSN158EL 1 x 58W T5 T100°C G13 1 x PG 13,5 - - A

T6 T 85°C

EVSN218EL 2 x 18W T5 T100°C G13 1 x PG 13,5 - - A

T4 T135°C

T6 T 85°C

EVSN236EL 2 x 36W T5 T100°C G13 1 x PG 13,5 - - A

T4 T135°C

EVSN258EL 2 x 58W T5 T100°C G13 1 x PG 13,5 - - A

50 - Feam Catalogue 01

Ex Lighting

EVSN Technical data

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE ENTRY WITH

CABLE GLANDEMERGENCY

UNIT AUTONOMY DETAIL

EVSN Technical featuresCODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V-50Hz

EMERGENCY FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V-50Hz

Page 51: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVSN

EVSNE118EL 842 90 120 420 2,75 1 x PG 13,5 B

EVSNE136EL 1451 90 120 775 3,45 1 x PG 13,5 B

EVSNE158EL 1751 90 120 1070 4,10 1 x PG 13,5 B

EVSNE218EL 842 155 120 455 3,10 1 x PG 13,5 B

EVSNE236EL 1451 155 120 770 4,90 1 x PG 13,5 B

EVSNE258EL 1751 155 120 1055 6,20 1 x PG 13,5 B

50

45°

100

100

C

BA

DB

Feam Catalogue 01 - 51

Ex Lighting

EVSN Technical features

EVSN Installation and mounting details

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Wall/structure mountingPole mounting

Assemblig detail with pole (typical)type 3 type 4

type 1 type 2Ceiling mounting Pendant mounting

Reference details

Page 52: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVSN

EVS218 EVS236 EVS258

EVS118 EVS136 EVS158

52 - Feam Catalogue 01

Ex Lighting

EVSN Polar diagrams – photometric data

EVSN On request accessoriesCODE DESCRIPTION INSTALLATION MATERIAL

20302.0122 POLE MOUNTING KIT (SIZE 1 1/2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20302.0123 POLE MOUNTING KIT (SIZE 2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20302.0125 POLE MOUNTING KIT (SIZE 1” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20301.0165 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 STAINLESS STEEL

20303.0091 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 GALVANIZED STEEL

20303.0092 WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 GALVANIZED STEEL

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Page 53: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

SFD

NSFDN

Feam Catalogue 01 - 53

Ex Lighting

ON REqUEST ACCESSORIES: • Control gear with voltage supply different than standard • Threaded cable entry different than standard

Mechanical characteristicsBody marine grade copper free aluminum

Diffuser tempered front glass

Support steel bracket with rotation-proof system

Reflector anodized and polished 99,85 pure aluminum internal optic

Painting thermosetting polyester powder resistant to atmospheric agents and corrosion grey RAL 9006 colour

Screws stainless steel

Gaskets pure silicon heat resistance

Cable entry complete with cable gland

Internal optic (S) symmetric optic - (A)asymmetric optic - (C) concentrating beam optic

Electrical characteristicsPower supply conventional ballast 230V - 50Hz (P.F. CORRECTED - cos ρ ≥ 0,95)

Lampholders porcellain E40 / E27 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

Installation: hazardous areas - Zone 2 (Gases) - Zone 22 (Dusts) Classification: Group II - Category 3G 3D

FLOODLIGHTS FOR DISCHARGE LAMPS

FLOODLIGHT

ATEX 94/9/EC

EXECUTION II 3 G Ex nr II T3 II 3 D Ex tD A22 T200°C

AMBIENT TEMPERATURE -20°C ÷ +60°C

PROTECTION DEGREE IP66

CERTIFICATE REF. IMQ 08 ATEX 019

RULES OF COMPLIANCE EN 60079-0; EN 60079-15; EN 61241-0; 61241-1

Page 54: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

N

SFDN#250HG-(1) 544 461 430 180 8,80 1 x PCE M20 A

SFDN#400HG-(1) 544 461 430 180 9,10 1 x PCE M20 A

SFDN#150MH-(1) 544 461 430 180 9,50 1 x PCE M20 A

SFDN#250MH-(1) 544 461 430 180 9,70 1 x PCE M20 A

SFDN#400MH-(1) 544 461 430 180 11,00 1 x PCE M20 A

SFDN#150HPNA-(1) 544 461 430 180 10,50 1 x PCE M20 A

SFDN#250HPNA-(1) 544 461 430 180 11,10 1 x PCE M20 A

SFDN#400HPNA-(1) 544 461 430 180 12,30 1 x PCE M20 A

SFDN#250HG-(1) 250 W T3 (Ta = -20°C / +60°C) T 200°C E-40 1 x PCE M20 A

SFDN#400HG-(1) 400 W T3 (Ta = -20°C / +60°C) T 200°C E-40 1 x PCE M20 A

SFDN#150MH-(1) 150 W T3 (Ta = -20°C / +60°C) T 200°C E-27 1 x PCE M20 A

SFDN#250MH-(1) 250 W T3 (Ta = -20°C / +60°C) T 200°C E-40 1 x PCE M20 A

SFDN#400MH-(1) 400 W T3 (Ta = -20°C / +60°C) T 200°C E-40 1 x PCE M20 A

SFDN#150HPNA-(1) 150 W T3 (Ta = -20°C / +60°C) T 200°C E-40 1 x PCE M20 A

SFDN#250HPNA-(1) 250 W T3 (Ta = -20°C / +60°C) T 200°C E-40 1 x PCE M20 A

SFDN#400HPNA-(1) 400 W T3 (Ta = -20°C / +60°C) T 200°C E-40 1 x PCE M20 A

54 - Feam Catalogue 01

Ex Lighting

SFDN Technical data

SFDN Technical features

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

LAMPHOLDER SIZE

CABLE ENTRY WITH CABLE GLAND DETAIL

FLOODLIGHT FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V 50Hz

FLOODLIGHT FOR METAL HALIDE LAMP - POWER SUPPLY 230V 50Hz

FLOODLIGHT FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V 50Hz

(1) INTERNAL OPTICAL BEAM: (S) SYMMETRIC BEAM - (A) ASYMMETRIC BEAM - (C) CONCENTRATING BEAM SAMPLE: SFDN#400MH-S = FLOODLIGHT 400W METAL HALIDE WITH SYMMETRIC OPTICAL BEAM

(1) INTERNAL OPTICAL BEAM: (S) SYMMETRIC BEAM - (A) ASYMMETRIC BEAM - (C) CONCENTRATING BEAM SAMPLE: SFDN#400MH-S = FLOODLIGHT 400W METAL HALIDE WITH SYMMETRIC OPTICAL BEAM

Page 55: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

N

SFDN

Tamb -20° C / +60° C

Ex nR II T3Ex tD A22 IP 66 T200°C

DO NOT OPEN WHILE ENERGIZEDTOGLIERE TENSIONE PRIMA DI APRIRE

IMQ 09 ATEX 019

FLOODLIGHT TYPE

AS

IK10

SM

CT

0.206m˛

www.feam-ex.com

400W HPNA250W HPNA150W HPNA

400W MH250W MH150W MH

240V 50HZ230V 50Hz

277 60Hz220V 60Hz

II 3 GD

120°

C D

155 155

B

A

SFDN#250HPNA-S SFDN#250HPNA-A SFDN#250HPNA-C

A

Feam Catalogue 01 - 55

Ex Lighting

SFDN Technical features

SFDN Polar diagrams – photometric data

Reference details

Page 56: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

N SFDN#400MH-S SFDN#400MH-A SFDN#400MH-C

20303.0099 20303.0100

56 - Feam Catalogue 01

Ex Lighting

SFDN Polar diagrams – photometric data

SFDN On request accessories

CODE DESCRIPTION MATERIAL

20303.0099 PROTECTION GRID ALUMINIUM

20303.0100 POLE ADAPTER FOR DIA 40÷60MM PAINTED STEEL

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Protection grid Pole adapter

Page 57: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EVSAEVSA

Feam Catalogue 01 - 57

Weatherproof Lighting

ON REqUEST ACCESSORIES: • Pole mounting kit complete with stainless steel hardware• Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware

• Wall/Structure mounting kit complete with stainless steel hardware • Electronic ballast with voltage supply different than standard• Emergency Group

Mechanical characteristics Body glass fibre reinforced polyester resin

Diffuser U/V resistant polycarbonate - hinged to body

Safety closing stainless steel hooks

Gaskets EPDM 60 rubber suitable for high temperatures and resistant to enviroments conditions

Internal reflector white stove enamelled sheet steel

Cable entry complete with PVC cable gland

Electrical characteristicsPower supply dual channel electronic ballast 220/240V 50/60Hz (cos ρ ≥ 0,98)

Lampholders bi-pin G13 cap

Terminals suitable up to 6mm/sq cables

Installation: Safe Area Insulation Class: I EVSA

WEATHERPROOF FLUORESCENT LIGHTING FIXTURES

LIGHTING FIXTURE

CEI / EN

EXECUTION INDUSTRIAL WEATHERPROOF

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP65

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1; EN 60598-2-1

Page 58: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVSA

EVSA118EL 667 90 98 420 1,75 1 x PG 13,5 A

EVSA136EL 1276 90 98 775 2,45 1 x PG 13,5 A

EVSA158EL 1576 90 98 1070 3,10 1 x PG 13,5 A

EVSA218EL 667 155 102 455 2,10 1 x PG 13,5 A

EVSA236EL 1276 155 102 770 3,90 1 x PG 13,5 A

EVSA258EL 1576 155 102 1055 5,20 1 x PG 13,5 A

EVSA118EL-E 667 90 98 420 1,75 1 x PG 13,5 A

EVSA136EL-E 1276 90 98 775 2,45 1 x PG 13,5 A

EVSA158EL-E 1576 90 98 1070 3,10 1 x PG 13,5 A

EVSA218EL-E 667 155 102 455 2,10 1 x PG 13,5 A

EVSA236EL-E 1276 155 102 770 3,90 1 x PG 13,5 A

EVSA258EL-E 1576 155 102 1055 5,20 1 x PG 13,5 A

EVSA118EL 1 x 18W - - G13 1 x PG 13,5 - - A

EVSA136EL 1 x 36W - - G13 1 x PG 13,5 - - A

EVSA158EL 1 x 58W - - G13 1 x PG 13,5 - - A

EVSA218EL 2 x 18W - - G13 1 x PG 13,5 - - A

EVSA236EL 2 x 36W - - G13 1 x PG 13,5 - - A

EVSA258EL 2 x 58W - - G13 1 x PG 13,5 - - A

EVSA118EL-E 1 x 18W - - G13 1 x PG 13,5 4,8V - 4Ah 3h A

EVSA136EL-E 1 x 36W - - G13 1 x PG 13,5 4,8V - 4Ah 3h A

EVSA158EL-E 1 x 58W - - G13 1 x PG 13,5 4,8V - 4Ah 3h A

EVSA218EL-E 2 x 18W - - G13 1 x PG 13,5 4,8V - 4Ah 3h A

EVSA236EL-E 2 x 36W - - G13 1 x PG 13,5 4,8V - 4Ah 3h A

EVSA258EL-E 2 x 58W - - G13 1 x PG 13,5 4,8V - 4Ah 3h A

A

C

BA

D

58 - Feam Catalogue 01

Weatherproof Lighting

EVSA Technical data

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER

CABLE ENTRY WITH CABLE

GLAND

EMERGENCY UNIT AUTONOMY DETAIL

EVSA Technical featuresCODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V-50Hz

EMERGENCY FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 230V-50Hz

Page 59: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVSA

EVS118 EVS136 EVS158

50

45°

100

100

Feam Catalogue 01 - 59

Weatherproof Lighting

EVSA Installation and mounting details

EVSA Polar diagrams – photometric data

Wall/structure mountingPole mounting

Assemblig detail with pole (typical)type 3 type 4

type 1 type 2Ceiling mounting Pendant mounting

Page 60: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EVSA

EVS218 EVS236 EVS258

60 - Feam Catalogue 01

Weatherproof Lighting

EVSA Polar diagrams – photometric data

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

EVSA On request accessories

CODE DESCRIPTION INSTALLATION MATERIAL

20302.0122 POLE MOUNTING KIT (SIZE 1 1/2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20302.0123 POLE MOUNTING KIT (SIZE 2” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20302.0125 POLE MOUNTING KIT (SIZE 1” DIA.) C/W HARDWARE TYPE 4 GALVANIZED STEEL

20301.0165 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 STAINLESS STEEL

20303.0091 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 GALVANIZED STEEL

20303.0092 WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 3 GALVANIZED STEEL

Page 61: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

SFD

ASFDA

Feam Catalogue 01 - 61

Weatherproof Lighting

Installation: Safe Area Insulation Class: I

WEATHERPROOF FLOODLIGHTS FOR DISCHARGE LAMPS

ON REqUEST ACCESSORIES: • Control gear with voltage supply different than standard • Threaded cable entry different than standard• Ready for serial configuration through a second cable gland• Internal optic definition under the symbol (S - A - C) to be added to the product code

Mechanical characteristics Body marine grade copper free aluminum

Diffuser tempered front glass

Support steel bracket with rotation-proof system

Reflector anodized and polished 99,85 pure aluminum internal optic

Painting thermosetting polyester powder resistant to atmospheric agents and corrosion grey RAL 9006 colour

Screws stainless steel

Gaskets pure silicon heat resistance

Cable entry complete with cable gland

Internal optic (S) symmetric optic - (A)asymmetric optic - (C) concentrating beam optic

Electrical characteristicsPower supply conventional ballast 230V - 50Hz (P.F. CORRECTED - cos ρ ≥ 0,95)

Lampholders porcellain E40 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

FLOODLIGHT

CEI / EN

EXECUTION INDUSTRIAL WEATHERPROOF

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP66

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1; EN 60598-2-5

Page 62: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

A

SFDA#250HG-(1) 544 461 430 180 8,80 1 x PCE M20 A

SFDA#400HG-(1) 544 461 430 180 9,10 1 x PCE M20 A

SFDA#150MH-(1) 544 461 430 180 9,50 1 x PCE M20 A

SFDA#250MH-(1) 544 461 430 180 9,70 1 x PCE M20 A

SFDA#400MH-(1) 544 461 430 180 11,00 1 x PCE M20 A

SFDA#150HPNA-(1) 544 461 430 180 10,50 1 x PCE M20 A

SFDA#250HPNA-(1) 544 461 430 180 11,10 1 x PCE M20 A

SFDA#400HPNA-(1) 544 461 430 180 12,30 1 x PCE M20 A

SFDA#250HG-(1) 250 W - - E-40 1 x PCE M20 A

SFDA#400HG-(1) 400 W - - E-40 1 x PCE M20 A

SFDA#150MH-(1) 150 W - - E-27 1 x PCE M20 A

SFDA#250MH-(1) 250 W - - E-40 1 x PCE M20 A

SFDA#400MH-(1) 400 W - - E-40 1 x PCE M20 A

SFDA#150HPNA-(1) 150 W - - E-40 1 x PCE M20 A

SFDA#250HPNA-(1) 250 W - - E-40 1 x PCE M20 A

SFDA#400HPNA-(1) 400 W - - E-40 1 x PCE M20 A

62 - Feam Catalogue 01

Weatherproof Lighting

SFDA Technical data

SFDA Technical features

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS)

LAMPHOLDER SIZE

CABLE ENTRY WITH CABLE

GLANDDETAIL

FLOODLIGHT FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V 50Hz

FLOODLIGHT FOR METAL HALIDE LAMP - POWER SUPPLY 230V 50Hz

FLOODLIGHT FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V 50Hz

(1) INTERNAL OPTICAL BEAM: (S) SYMMETRIC BEAM - (A) ASYMMETRIC BEAM - (C) CONCENTRATING BEAM SAMPLE: SFDA#400MH-S = FLOODLIGHT 400W METAL HALIDE WITH SYMMETRIC OPTICAL BEAM

(1) INTERNAL OPTICAL BEAM: (S) SYMMETRIC BEAM - (A) ASYMMETRIC BEAM - (C) CONCENTRATING BEAM SAMPLE: SFDA#400MH-S = FLOODLIGHT 400W METAL HALIDE WITH SYMMETRIC OPTICAL BEAM

Page 63: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

A

SFDA

Tamb -20° C / +60° C

DO NOT OPEN WHILE ENERGIZEDTOGLIERE TENSIONE PRIMA DI APRIRE

FLOODLIGHT TYPE

AS

IK10

SM

CT

0.206m˛

www.feam-ex.com

400W HPNA250W HPNA150W HPNA

400W MH250W MH150W MH

240V 50HZ230V 50Hz

277 60Hz220V 60Hz

120°

C D

155 155

B

A

SFDA#250HPNA-S SFDA#250HPNA-A SFDA#250HPNA-C

A

1 X PCE M20

Feam Catalogue 01 - 63

SFDA Technical features

SFDA Polar diagrams – photometric data

Reference details

Weatherproof Lighting

Page 64: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SFD

A SFDA#400MH-S SFDA#400MH-A SFDA#400MH-C

20303.0099 20303.0100

64 - Feam Catalogue 01

Weatherproof Lighting

SFDA Polar diagrams – photometric data

SFDA On request accessories

CODE DESCRIPTION MATERIAL

20303.0099 PROTECTION GRID ALUMINIUM

20303.0100 POLE ADAPTER FOR DIA 40÷60MM PAINTED STEEL

Protection grid Pole adapter

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Page 65: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EWNEWN

LIGHTING FIXTURE

ATEX 94/9/EC

EXECUTION II 3 G Ex nr II T3 II 3 D Ex tD A22 T200°C

INSTALLATION ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60079-0; EN 60079-15; EN 61241-0; EN 61241-1

Feam Catalogue 01 - 65

Ex Lighting

Installation: hazardous areas - Zone 2 (Gases) - Zone 22 (Dusts) Classification: Group II - Category 3G 3D

ON REqUEST ACCESSORIES: • Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware • Pole mounting 25° kit 1 1/2” dia. complete with stainless steel hardware• Wall/Structure mounting kit complete with stainless steel hardware • Galvanized steel wire protection guard• Stainless steel wire protection guard

• White stove enamelled aluminium reflectors • White stove enamelled aluminium reflectors inclined 30°• Stainless steel AISI 316L reflectors • External painting colour on request• Control gear with voltage supply different than standard • Threaded cable entry different than standard

Mechanical characteristics Body marine grade copper free aluminium (control gear & lamp body)

Globe high-temperature resistant borosylicate glass

Painting external epoxy powders grey rAl-9006 colour

Screws external stainless steel

Gaskets silicon rubber

Electrical characteristicsPower supply conventional ballast 230v - 50hz (p.f.corrected - cos ρ ≥ 0,95)

lampholders porcelain E27/E40 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

LIGHTING FIXTURES FORDISCHARGE LAMPS

Page 66: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EWN

EWN2 280 430 415 145 280 8,50 A

EWN3 280 510 480 190 402 9,50 A

EWN5 280 570 545 255 515 10,00 A

ØA

CB

ØDØE

A

EWN2-80HG 80 W T3 T 200°C E-27 A

EWN2-125HG 125 W T3 T 200°C E-27 A

EWN3-250HG 250W T3 T 200°C E-40 A

EWN5-400HG 400 W T3 T 200°C E-40 A

EWN2-70MH 70 W T3 T 200°C E-27 A

EWN2-100MH 100 W T3 T 200°C E-27 A

EWN2-150MH 150 W T3 T 200°C E-27 A

EWN3-175MH 175 W T3 T 200°C E-40 A

EWN3-250MH 250 W T3 T 200°C E-40 A

EWN5-400MH 400 W T3 T 200°C E-40 A

EWN2-70HPNA 70 W T3 T 200°C E-27 A

EWN3-100HPNA 100 W T3 T 200°C E-27 A

EWN3-150HPNA 150 W T3 T 200°C E-40 A

EWN3-250HPNA 250 W T3 T 200°C E-40 A

EWN5-400HPNA 400 W T3 T 200°C E-40 A

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER SIZE DETAIL

CODE A [mm] B [mm] C [mm] Ø D [mm] Ø E [mm] WEIGHT [Kg] DETAIL

LIGHTING FIXTURE FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V 50Hz

LIGHTING FIXTURE FOR METAL HALIDE LAMP - POWER SUPPLY 230V 50Hz

LIGHTING FIXTURE FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V 50Hz

66 - Feam Catalogue 01

Ex Lighting

Reference details

EWN Technical data

EWN Technical features

Page 67: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EWN

3/4”

3/4” 3/4”

1”

25°

45°

90°

Feam Catalogue 01 - 67

Ex Lighting

EWN Installation and mounting detailsCeiling mounting

Wall/structure mounting

Pole mounting 25°

Pendant mountingtype 1

type 3

type 4

type 2

Universal mounting inst. with adjustable brackettype 5

Page 68: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EWN

EWN250HG-D EWN400HPS-D EWN400MH-D

68 - Feam Catalogue 01

Ex Lighting

EWN Polar diagrams – photometric data

EWN On request accessories

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

20302.0070 EVAC 100 / 101 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.

20302.0072 EVAC 300 / 301 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.

20302.0073 EVAC 500 / 501 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.

20302.0025 EvAC 100 / 101 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl AISI 316l

20302.0027 EvAC 300 / 301 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl AISI 316l

20302.0028 EVAC 500 / 501 SIZE STAINLESS STEEL REFLECTOR STAINLESS STEEL AISI 316L

20302.0133 EVAC 100 / 101 SIZE STAINLESS STEEL REFLECTOR INCLINED 30° WHITE STOVE ENAMELLED ALUM.

20302.0031 EVAC 300 / 301 SIZE STAINLESS STEEL REFLECTOR INCLINED 30° WHITE STOVE ENAMELLED ALUM.

EVAC 500 / 501 SIZE STAINLESS STEEL REFLECTOR INCLINED 30° WHITE STOVE ENAMELLED ALUM.

20302.0074 EVAC 100 / 101 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0076 EVAC 300 / 301 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0077 EVAC 500 / 501 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0037 EVAC 100 / 101 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL AISI 316L

20302.0039 EVAC 300 / 301 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL AISI 316L

20302.0040 EVAC 500 / 501 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL AISI 316L

20303.0108 2” DIA.SIZE POLE MONTING KIT C/W HARDWARE TYPE 4 ALUMININIUM

20303.0107 1-1/2” DIA.SIZE POLE MONTING KIT C/W HARDWARE TYPE 4 ALUMININIUM

20303.0106 1” DIA.SIZE POLE MONTING KIT C/W HARDWARE TYPE 4 ALUMININIUM

20303.0104 WALL MOUNTING KIT C/W HARDWARE TYPE 3 ALUMININIUM

20303.0103 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 ALUMININIUM

20303.0102 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 ALUMININIUM

20303.0105 UNIVERSAL MOUNTING INST. WITH ADJUSTABLE BRACKET C/W HARDWARE TYPE 5 STAINlESS STEEl AISI 316l

CODE DESCRIPTION INSTALLATION MATERIAL

Page 69: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

EW

EW

Feam Catalogue 01 - 69

Weatherproof Lighting

Installation: Safe Area Insulation Class: I

WEATHERPROOF LIGHTING FIXTURES

ON REqUEST ACCESSORIES: • Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware • Pole mounting 25° kit 1 1/2” dia. complete with stainless steel hardware• Wall/Structure mounting kit complete with stainless steel hardware • Galvanized steel wire protection guard• Stainless steel wire protection guard

• White stove enamelled aluminium reflectors • White stove enamelled aluminium reflectors inclined 30°• Stainless steel AISI 316L reflectors • External painting colour on request• Control gear with voltage supply different than standard • Threaded cable entry different than standard

Mechanical characteristics Body marine grade copper free aluminium (control gear & lamp body)

Globe high-temperature resistant borosylicate glass

Painting external epoxy powders grey rAl-9006 colour

Screws external stainless steel

Gaskets silicon rubber

Electrical characteristicsPower supply conventional ballast 230v - 50hz (p.f.corrected - cos ρ ≥ 0,95)

lampholders porcelain E27/E40 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

LIGHTING FIXTURE

CEI / EN

EXECUTION INDUSTRIAL WEATHERPROOF

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP66

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1; EN 60598-2-1

Page 70: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EW

EW2-80HG 80 W - - E-27 A

EW2-125HG 125 W - - E-27 A

EW3-250HG 250W - - E-27 A

EW5-400HG 400 W - - E-40 A

EW2-70MH 70 W - - E-27 A

EW2-100MH 100 W - - E-27 A

EW2-150MH 150 W - - E-27 A

EW3-175MH 175 W - - E-40 A

EW3-250MH 250 W - - E-40 A

EW5-400MH 400 W - - E-40 A

EW2-70HPNA 70 W - - E-27 A

EW3-150HPNA 150 W - - E-40 A

EW3-250HPNA 250 W - - E-40 A

EW5-400HPNA 400 W - - E-40 A

ØA

CB

ØDØE

A

EW2 280 430 415 145 280 8,50 A

EW3 280 510 480 190 402 9,50 A

EW5 280 570 545 255 515 10,00 A

70 - Feam Catalogue 01

Weatherproof Lighting

EW Technical data

LIGHTING FIXTURE FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V 50Hz

LIGHTING FIXTURE FOR METAL HALIDE LAMP - POWER SUPPLY 230V 50Hz

LIGHTING FIXTURE FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V 50Hz

Reference details

EW Technical featuresCODE A [mm] B [mm] C [mm] Ø D [mm] Ø E [mm] WEIGHT [Kg] DETAIL

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER SIZE DETAIL

Page 71: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EW

3/4”

3/4” 3/4”

1”

25°

45°

90°

Feam Catalogue 01 - 71

Weatherproof Lighting

EW Installation and mounting detailsCeiling mounting

Wall/structure mounting

Pole mounting 25°

Pendant mountingtype 1

type 3

type 4

type 2

Universal mounting inst. with adjustable brackettype 5

Page 72: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

EW

EW250HG-D EW400HPS-D EW400MH-D

72 - Feam Catalogue 01

Weatherproof Lighting

EW Polar diagrams – photometric data

EW On request accessories

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

CODE DESCRIPTION INSTALLATION MATERIAL20302.0070 EVAC 100 / 101 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.

20302.0072 EVAC 300 / 301 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.

20302.0073 EVAC 500 / 501 SIZE STANDARD REFLECTOR WHITE STOVE ENAMELLED ALUM.

20302.0025 EvAC 100 / 101 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl AISI 316l

20302.0027 EvAC 300 / 301 SIZE STAINlESS STEEl rEFlECTOr STAINlESS STEEl AISI 316l

20302.0028 EVAC 500 / 501 SIZE STAINLESS STEEL REFLECTOR STAINLESS STEEL AISI 316L

20302.0133 EVAC 100 / 101 SIZE STAINLESS STEEL REFLECTOR INCLINED 30° WHITE STOVE ENAMELLED ALUM.

20302.0031 EVAC 300 / 301 SIZE STAINLESS STEEL REFLECTOR INCLINED 30° WHITE STOVE ENAMELLED ALUM.

EVAC 500 / 501 SIZE STAINLESS STEEL REFLECTOR INCLINED 30° WHITE STOVE ENAMELLED ALUM.

20302.0074 EVAC 100 / 101 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0076 EVAC 300 / 301 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0077 EVAC 500 / 501 SIZE STANDARD PROTECTION GUARD GALVANIZED STEEL

20302.0037 EVAC 100 / 101 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL AISI 316L

20302.0039 EVAC 300 / 301 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL AISI 316L

20302.0040 EVAC 500 / 501 SIZE STAINLESS STEEL PROTECTION GUARD STAINLESS STEEL AISI 316L

20303.0108 2” DIA.SIZE POLE MONTING KIT C/W HARDWARE TYPE 4 ALUMININIUM

20303.0107 1-1/2” DIA.SIZE POLE MONTING KIT C/W HARDWARE TYPE 4 ALUMININIUM

20303.0106 1” DIA.SIZE POLE MONTING KIT C/W HARDWARE TYPE 4 ALUMININIUM

20303.0104 WALL MOUNTING KIT C/W HARDWARE TYPE 3 ALUMININIUM

20303.0103 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 2 ALUMININIUM

20303.0102 CEILING MOUNTING KIT C/W HARDWARE TYPE 1 ALUMININIUM

20303.0105 UNIVERSAL MOUNTING INST. WITH ADJUSTABLE BRACKET C/W HARDWARE TYPE 5 STAINlESS STEEl AISI 316l

Page 73: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

M40

0M400

Feam Catalogue 01 - 73

Waterproof Lighting

LIGHTING FIXTURE

CEI/IEC

EXECUTION INDUSTRIAL WEATHERPROOF

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP66 (optic group) IP66 (control gear box)

CERTIFICATE REF. -

RULES OF COMPLIANCE CEI / EN 60598-1

ON REqUEST ACCESSORIES:• Electronic ballast with voltage supply different than standard• Insulation class II• Angle/wall installation bracket• Pole adapter - dia. 40 mm

Mechanical characteristicsBody die-cast aluminum

Diffuser tempered glass 4mm thickness

Anchorage cured poles Ø45-60mm (Ø40 with adapter)

Reflector CUT-OFF optic - anodized and polished 99,85 pure aluminum

Painting thermosetting polyester powder resistant to atmospheric agents and corrosion grey RAL 7038/7039 colour

Screws stainless steel

Gaskets silicon rubber gasket running oround the body

Cable entry from pole

Electrical characteristicsPower supply conventional ballast 230V - 50Hz (P.F. CORRECTED - cos ρ ≥ 0,95)

Lampholders porcellain E27 - E40 size

Internal wiring high-temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

Installation: Safe Area Insulation Class: I

STREET LIGHTING FIXTURES

Page 74: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

M40

0

M400-125HG 125 W - - E-27 A

M400-250HG 250 W - - E-40 A

M400-400HG 400 W - - E-40 A

M400-70MH 70 W - - E-27 A

M400-100MH 100 W - - E-27 A

M400-150MH 150 W - - E-27 A

M400-250MH 250 W - - E-40 A

M400-400MH 400 W - - E-40 A

M400-70HPNA 70 W - - E-27 A

M400-100HPNA 100 W - - E-40 A

M400-150HPNA 150 W - - E-40 A

M400-250HPNA 250 W - - E-40 A

M400-400HPNA 400 W - - E-40 A

M400-125HG 719 224 387 228 10,20 A

M400-250HG 719 224 387 228 11,50 A

M400-400HG 719 224 387 228 12,90 A

M400-70MH 719 224 387 228 10,40 A

M400-100MH 719 224 387 228 10,40 A

M400-150MH 719 224 387 228 11,70 A

M400-250MH 719 224 387 228 11,70 A

M400-400MH 719 224 387 228 13,00 A

M400-70HPNA 719 224 387 228 10,50 A

M400-100HPNA 719 224 387 228 10,50 A

M400-150HPNA 719 224 387 228 11,70 A

M400-250HPNA 719 224 387 228 13,00 A

M400-400HPNA 719 224 387 228 14,30 A

74 - Feam Catalogue 01

Waterproof Lighting

M400 Technical data

M400 Technical features

LIGHTING FIXTURE FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V 50Hz

LIGHTING FIXTURE FOR METAL HALIDE LAMP - POWER SUPPLY 230V 50Hz

LIGHTING FIXTURE FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V 50Hz

CODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] DETAIL

CODE LAMP TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER SIZE DETAIL

Page 75: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

M40

0

B

A

DC

M400-250HG M400-400HG M400-250HPS

A

Feam Catalogue 01 - 75

Waterproof Lighting

M400 Polar diagrams – photometric data

Reference details

M400 Technical features

Page 76: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

M40

0 M400-400HPS M400-250MH M400-400MH

20303.0099 20303.0100

76 - Feam Catalogue 01

M400 Polar diagrams – photometric data

Waterproof Lighting

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

M400 On request accessories

CODE DESCRIPTION MATERIAL

20303.0099 ANGLE/WALL INSTALLATION BRACKET ALUMINIUM

20303.0100 POLE ADAPTER - DIA. 40÷60MM PAINTED STEEL

Angle/wall installation bracket Pole adapter - dia. 40 mm

Page 77: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

OFF

ICE

OFFICE

Feam Catalogue 01 - 77

Indoor Lighting

Mechanical characteristics Body sheet steel

Optical diff transparent methacrilate diffuser - white panted metal sheet frame

Optical par “Darklight” - preanodised 99.85 aluminium double parabolic with 4u oxidation layer antiglare and antiridescent

Painting epoxy-polyester powder coated in white

Gasket anti-age cellular structure

Electrical characteristicsPower supply electronic ballast 220/240V 50/60Hz p.f. corrected (cos ρ ≥ 0,98)

Lampholders bi-pin G13 cap

Internal wiring high temperature resistant silicon rubber insulation cables

Terminals suitable up to 4mm/sq cables

Installation: Safe Area Insulation Class: I

CEILING LIGHTING FIXTURES

ON REqUEST ACCESSORIES: • Electronic ballast with voltage supplì different than standard• Emergency unit with charger and battery pack

LIGHTING FIXTURE

EXECUTION INDOOr lIGhTING

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP20 / IP40

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1

Page 78: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

OFFICE-PAR-218 OFFICE-PAR-236 OFFICE-PAR-418

C

A B

OFF

ICE

A

78 - Feam Catalogue 01

Indoor Lighting

OFFICE Technical data

OFFICE Technical featuresCODE A [mm] B [mm] C [mm] FIXING [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

(1) OPTICAL / DIFFUSER: PAR = DARKLIGHT - DIFF= TRANSPARENT METHACRILATE

CODE LAMP TYPE

TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE ENTRY DETAIL

FLUORESCENT LIGHTING FIXTURES WITH DARKLIGHT OPTICAL - POWER SUPPLY 230V-50Hz

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Reference details

OFFICE-(1)-136 1225 180 90 1023 x 90 3,80 CABLE GLAND Ø20mm A

OFFICE-(1)-158 1525 180 90 1323 x 90 4,90 CABLE GLAND Ø20mm A

OFFICE-(1)-218 618 306 90 414 x 130 3,30 CABLE GLAND Ø20mm A

OFFICE-(1)-236 1225 306 90 1023 x 130 6,20 CABLE GLAND Ø20mm A

OFFICE-(1)-258 1525 306 90 1323 x 130 8,00 CABLE GLAND Ø20mm A

OFFICE-(1)-418 618 610 90 414 x 496 5,70 CABLE GLAND Ø20mm A

OFFICE-PAR-136 1 x 36W - - G13 CABLE GLAND Ø20mm A

OFFICE-PAR-158 1 x 58W - - G13 CABLE GLAND Ø20mm A

OFFICE-PAR-218 2 x 18W - - G13 CABLE GLAND Ø20mm A

OFFICE-PAR-236 2 x 36W - - G13 CABLE GLAND Ø20mm A

OFFICE-PAR-258 2 x 58W - - G13 CABLE GLAND Ø20mm A

OFFICE-PAR-418 4 x 18W - - G13 CABLE GLAND Ø20mm A

OFFICE-DIFF-218 2 x 18W - - G13 CABLE GLAND Ø20mm A

OFFICE-DIFF-236 2 x 36W - - G13 CABLE GLAND Ø20mm A

OFFICE-DIFF-418 4 x 18W - - G13 CABLE GLAND Ø20mm A

FLUORESCENT LIGHTING FIXTURES WITH METHACRILATE DIFFUSER - POWER SUPPLY 230V-50Hz

Page 79: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

SECU

RLU

X

SECURLUX

Feam Catalogue 01 - 79

Weatherproof Lighting

ON REqUEST ACCESSORIES: • Pole mounting kit complete with stainless steel hardware• Pendant mounting kit complete with stainless steel hardware• Wall/structure mounting kit complete with stainless steel hardware• Electronic ballast with voltage supply different than standard • Steel protection cage

Mechanical characteristics Body extruded aluminum, type UNI 9006T, 2,5mm thick; 15 ÷ 20 micron axidation thikness

Diffuser transparent ribbed polycarbonate, 2,2mm thick

Screws stainless steel

Gaskets EPDM rubber suitable for high temperatures and resistant to enviroments conditions

Reflector sheet steel polyurethane powder coated in white, ready for electrical components housing

Cable Entry PG16 complete with poliamyde cable gland

Locking top edges black self-extinguishing polycarbonate

ANTI-VANDALIC LIGHTING FIXTURES FOR FLUORESCENT TUBE LAMPS

Electrical characteristicsPower supply electronic ballast 220/240V 50/60Hz p.f. corrected (cos ρ ≥ 0,98)

Lampholders bi-pin G13 cap

Terminals suitable up to 4mm/sq cables

Installation: Safe Area Insulation Class: I

LIGHTING FIXTURE

CEI / EN

EXECUTION INDUSTRIAL WATERPROOF

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP66

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1

Page 80: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SECU

RLU

X

SECURLUX-118 1 x 18W - - G13 1 x PG16 A

SECURLUX-136 1 x 36W - - G13 1 x PG 16 A

SECURLUX-158 1 x 58W - - G13 1 x PG 16 A

SECURLUX-218 2 x 18W - - G13 1 x PG 16 A

SECURLUX-236 2 x 36W - - G13 1 x PG 16 A

SECURLUX-258 2 x 58W - - G13 1 x PG 16 A

SECURLUX-118 660 135 145 10,00 1 x PG16 A

SECURLUX-136 1270 135 145 13,00 1 x PG16 A

SECURLUX-158 1570 135 145 17,00 1 x PG16 A

SECURLUX-218 660 135 145 10,50 1 x PG16 A

SECURLUX-236 1270 135 145 13,50 1 x PG16 A

SECURLUX-258 1570 135 145 17,50 1 x PG16 A

5010

0

100

45°

C

1xPG16

B A

A

80 - Feam Catalogue 01

Weatherproof Lighting

SECURLUX Technical data

SECURLUX Technical features

SECURLUX Installation and mounting details

CODE LAMP TYPE

TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE ENTRY DETAIL

FLUORESCENT LIGHTING FIXTURES FOR SINGLE, TWIN LAMPS - POWER SUPPLY 230V-50/60Hz

CODE A [mm] B [mm] C [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

Reference details

Pendant mounting Wall/structure mountingtype 1 type 2

Page 81: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SECU

RLU

X

SECURLUX 118 SECURLUX 218 SECURLUX 113

type 3

Feam Catalogue 01 - 81

Weatherproof Lighting

SECURLUX Installation and mounting details

SECURLUX Polar diagrams – photometric data

Pole mounting Assemblig detail with pole (typical)

Page 82: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

SECU

RLU

X

SECURLUX 236 SECURLUX 158 SECURLUX 258

82 - Feam Catalogue 01

SECURLUX Polar diagrams – photometric data

SECURLUX On request accessories

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Weatherproof Lighting

CODE DESCRIPTION INSTALLATION MATERIAL20302.0122 POLE MOUNTING KIT (SIZE 1 1/2” DIA.) C/W HARDWARE TYPE 3 GALVANIZED STEEL

20302.0123 POLE MOUNTING KIT (SIZE 2” DIA.) C/W HARDWARE TYPE 3 GALVANIZED STEEL

20302.0125 POLE MOUNTING KIT (SIZE 1” DIA.) C/W HARDWARE TYPE 3 GALVANIZED STEEL

20301.0165 PENDANT MOUNTING KIT C/W HARDARE AND EYE-BOLTS TYPE 1 STAINLESS STEEL

20303.0092 WALL/STRUCTURE MOUNTING KIT C/W HARDWARE TYPE 2 GALVANIZED STEEL

Page 83: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

KRO

NO

S SA

T

KRONOS SAT

Feam Catalogue 01 - 83

Waterproof Lighting

ON REqUEST ACCESSORIES: • Galvanized steel wire protection guard• Electronic device for aux halogen lamp• Control gear with voltage supply different than standard

Mechanical characteristicsHousing die-casting aluminium complete with stainless steel safety chains

Diffuser plane tempered glass resistant to shocks and thermal shocks, coupled with stainless steel clips and secured with a security chain

Painting thermosetting polyester powder resistant to atmospheric agents and corrosion

Reflector anodized and polished 99,85 pure aluminum

Cable entry cable gland M20 IP68 tear proof

Electrical characteristicsPower supply conventional ballst 230V - 50Hz p.f. corrected (cos ρ ≥ 0,95)

Lampholders ceramic E27 / E40

Internal wiring 1,5mm/sq silicon cables with glass sheat

INDUSTRIAL REFLECTORS FOR DISCHARGE LAMPS

INDUSTRIAL REFLECTORS

CEI / EN

EXECUTION WEATHERPROOF

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP65

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1; EN 60598-2-5

Installation: safe area Insulation class: I

Page 84: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

KRO

NO

S SA

T

KRONOS-125MBF 125 W - - E-27 M20 A

KRONOS-250MBF 250 W - - E-40 M20 A

KRONOS-400MBF 400 W - - E-40 M20 A

KRONOS-150JM 150 W - - E-27 M20 A

KRONOS-250JM 250 W - - E-40 M20 A

KRONOS-400JM 400 W - - E-40 M20 A

KRONOS-125MBF 535 265 550 295 4,62 M20 A

KRONOS-250MBF 535 265 550 295 5,03 M20 A

KRONOS-400MBF 535 265 550 295 6,35 M20 A

KRONOS-150JM 535 265 550 295 5,22 M20 A

KRONOS-250JM 535 265 550 295 5,17 M20 A

KRONOS-400JM 535 265 550 295 6,50 M20 A

KRONOS-150SAP 535 265 550 295 5,22 M20 A

KRONOS-250SAP 535 265 550 295 6,57 M20 A

KRONOS-400SAP 535 265 550 295 7,76 M20 A

ØD

ØC

AB

A

KRONOS-400MBF KRONOS-250SAP KRONOS-400JM

KRONOS-150SAP 150 W - - E-40 M20 A

KRONOS-250SAP 250 W - - E-40 M20 A

KRONOS-400SAP 400 W - - E-41 M20 A

84 - Feam Catalogue 01

Waterproof Lighting

KRONOS SAT On request accessories

KRONOS SAT Technical data

KRONOS SAT Technical features Reference details

INDUSTRIAL REFLECTORS FOR MERCURY VAPOUR LAMPS - POWER SUPPLY 230V-50Hz

INDUSTRIAL REFLECTORS FOR METAL HALIDE LAMPS - POWER SUPPLY 230V-50Hz

CODE LAMP TYPE

TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE GLAND DETAIL

CODE DESCRIPTION MATERIAL930000.480 PROTECTION GRID Ø480 GALVANIZED STEEL

CLA ELECTRONIC SWITCHING DEVICE FOR AUXILIARY LAMP -

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

INDUSTRIAL REFLECTORS FOR HIG PRESSURE SODIUM LAMPS - POWER SUPPLY 230V-50Hz

CODE A [mm]

B [mm]

ØC [mm]

ØD [mm]

WEIGHT [Kg] CABLE GLAND DETAIL

Page 85: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

GEN

IUS

GENIUS

Feam Catalogue 01 - 85

Waterproof Lighting

ON REqUEST ACCESSORIES:• Pole mounting kit complete with stainless steel hardware• Pendant mounting kit complete with stainless steel hardware• Wall/structure mounting kit complete with stainless steel hardware• Emergency unit complete with inverter charger and Ni-Cd 4,8V 4A/h battery pack• Electronic ballast with voltage supply different than standard

Mechanical characteristicsBody & frame seamless AISI-3104 stainless steel one piece deep drawn

Diffuser transparent tempered flat glass 5mm thick. with silicon rubber gasket

Screws stainless steel

Gaskets EPDM rubber suitable for high temperatures and resistant to enviroments conditions

Reflector internal in die-fold steel, epoxy powders white coloured coated equiped with security strings

Cable entry PG 13,5 complete with poliamyde cable gland

Closing hooks stainless steel with screw-held spring lock latches and anti-vandal device

Electrical characteristicsPower supply electronic ballast 230V - 50/60Hz p.f. corrected (cos ρ ≥ 0,98)

Lampholders bi-pin G13 cap

Terminals suitable up to 4mm/sq cables

Installation: safe area Insulation class: I

LIGHTING FIXTURES FOR FLUORESCENT TUBE LAMPS

LIGHTING FIXTURE

CEI / EN

EXECUTION INDUSTRIAL WATERPROOF

AMBIENT TEMPERATURE -40°C ÷ +70°C

PROTECTION DEGREE IP65

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1; EN 60598-2-1

Page 86: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

GEN

IUS

GENIUS-118 700 220 90 480 12,50 1 x PG 13,5 A

GENIUS-136 1310 220 90 1090 15,50 1 x PG 13,5 A

GENIUS-158 1610 220 90 1390 18,50 1 x PG 13,5 A

GENIUS-218 700 220 90 480 13,00 1 x PG 13,5 A

GENIUS-236 1310 220 90 1090 16,00 1 x PG 13,5 A

GENIUS-258 1610 220 90 1390 19,00 1 x PG 13,5 A

GENIUS-318 700 220 90 1090 13,50 1 x PG 13,5 A

GENIUS-336 1310 220 90 1390 16,50 1 x PG 13,5 A

GENIUS-118 1 x 18W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

GENIUS-136 1 x 36W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

GENIUS-158 1 x 58W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

GENIUS-218 2 x 18W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

GENIUS-236 2 x 36W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

GENIUS-258 2 x 58W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

GENIUS-318 3 x 18W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

GENIUS-336 3 x 36W - - G13 1 x PG 13.5 4,8V - 4A/h 3h A

C

D

B

1 x PG 13,5

A

A

86 - Feam Catalogue 01

Waterproof Lighting

GENIUS Technical data

GENIUS Technical featuresCODE A [mm] B [mm] C [mm] D [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

CODE LAMP TYPE TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE

ENTRYEMERG.UNIT

(ON REqUEST)AUTONOMY

(EMERG.UNIT) DETAIL

FLUORESCENT LIGHTING FIXTURES FOR SINGLE, TWIN, AND THREE LAMPS - POWER SUPPLY 230V-50/60Hz

Reference details

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

Page 87: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

ESOESO

Feam Catalogue 01 - 87

Waterproof Lighting

ON REqUEST ACCESSORIES: • Adhesive labels (with various symbols) according to European standards 92/58

Mechanical characteristicsBody techno polymer thermo resistant and anti shok, flame resistant chemical and atmospheric agents

Diffuser transparent ribbed polycarbonate, 2,2mm thick

Electrical characteristicsPower supply electronic ballast 230V - 50Hz p.f. corrected (cos ρ ≥ 0,98)

Lampholders bi-pin G5 cap

Battery pack Ni-Cd high temperature 1,5Ah - time to recharge 12h - autonomy 1h / 3h

Optical signal luminors indicator for power presence and correct recharging

Self-diagnosis circuit (ATD) execute automatic functioning tests; a red flashing light indicate eventual wrong operations

Installation: safe area Insulation class: I

EXIT EMERGENCY LIGHTING FIXTURE

LIGHTING FIXTURE

CEI / EN

EXECUTION INDUSTRIAL WEATHERPROOF

AMBIENT TEMPERATURE -

PROTECTION DEGREE IP40

CERTIFICATE REF. -

RULES OF COMPLIANCE EN 60598-1 + A1; EN 60598-2-1

Page 88: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

ESO

ESO 8-NA 365 50 180 3,00 Ø20mm A

ESO 8-NA/3 365 50 180 3,20 Ø20mm A

ESO 8-NS 365 50 180 3,00 Ø20mm A

ESO 8-NS/3 365 50 180 3,20 Ø20mm A

ESO 8-NA ATD 365 50 180 3,20 Ø20mm A

ESO 8-NA/3 ATD 365 50 180 3,50 Ø20mm A

ESO 8-NS ATD 365 50 180 3,20 Ø20mm A

ESO 8-NS/3 ATD 365 50 180 3,50 Ø20mm A

ESO 8-NA 1 x 8W - - G5 Ø20mm 2.4 V - 1.5Ah 1h A

ESO 8-NA/3 1 x 8W - - G5 Ø20mm 6 V - 1.5Ah 3h A

ESO 8-NS 1 x 8W - - G5 Ø20mm 2.4 V - 1.5Ah 1h A

ESO 8-NS/3 1 x 8W - - G5 Ø20mm 6 V - 1.5Ah 3h A

ESO 8-NA ATD 1 x 8W - - G5 Ø20mm 3.6 V - 1.5Ah 1h A

ESO 8-NA/3 ATD 1 x 8W - - G5 Ø20mm 3.6 V - 4Ah 3h A

ESO 8-NS ATD 1 x 8W - - G5 Ø20mm 3.6 V - 1.5Ah 1h A

ESO 8-NS/3 ATD 1 x 8W - - G5 Ø20mm 3.6 V - 4Ah 3h A

C

A B

A

88 - Feam Catalogue 01

ESO Technical data

ESO Technical features

CODE LAMP TYPE

TEMPERATURE CLASS (GAS)

TEMPERATURE CLASS (DUSTS) LAMPHOLDER CABLE ENTRY EMERG.UNIT

(ONREqUEST)AUTONOMY

(EMERG.UNIT) DETAIL

FLUORESCENT LIGHTING FIXTURES FOR SINGLE LAMP - POWER SUPPLY 230V-50/60Hz

FLUORESCENT LIGHTING FIXTURES FOR SINGLE LAMP - POWER SUPPLY 230V-50/60Hz - SELF DIAGNOSTIC VERSION

Reference details

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

CODE A [mm] B [mm] C [mm] WEIGHT [Kg] CABLE ENTRY DETAIL

REMAKS: Always ON - Maintained “NA”: lighting fixtures light-on and working in emergency also Emergency only - Maintained “NS”: lighting fixtures light-off and working in emergency only

Waterproof Lighting

Page 89: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

TORR

I e P

ALI

Feam Catalogue 01 - 89

Ex Lighting

HIGH MAST TOWERS & LIGHTING POLES FOR HAZARDOUS AREA

The utility of the high masts with mobile crown in lighting large areas, is universally recognised. It , in fact, represents the best answer either from the lighting environmental, maintenance point of view. Lighting high masts undertakes an irreplaceable part in designing modern lighting plant of large areas, having the approval of engineers who consider more and more difficult to find personnel for carrying out maintenance, disposed to climb to a certain height. Furthermore, the possibility of lighting large areas (interchanges, parking areas etc....) with few lighting sources of considerable height, without particular maintenance costs, makes FEAM high masts with mobile crown particularly profitable in the economy of the whole plant.. Our actual range, designed in standard elements suitable to guarantee maximum safety levels, with explosion proof floodlights for zone 1 and zone 2.

LIGHTING STUDY ON REqUEST

Installation: hazardous areas - Zone 1/2 (Gases) - Zone 21/22 (Dusts) - Safe Area

LIGHTING MASTS WITH MOBILE CROWN FOR EXPLOSION PROOF FLOODLIGHS EEX D IIB T3 IP65

MOVEMENT DETAIL

MO

TOR

CRU

CK

TOWERS

Page 90: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

TORR

I e P

ALI

90 - Feam Catalogue 01

Ex Lighting

Lighting poles

Installation: hazardous areas - Zone 2 (Gases) - Zone 22 (Dusts) - Safe Area

Designed and manufactured according to national and European standard, FEAM lighting columns, are manufactured in 3 different types: • Conical columns with circular section • Stepped columns from welded tubes • Columns with octagonal and polygonal section

Normally provided with standard works for the electric wiring according to the standard, they may be personalised with particular works upon request. Furthermore a complete range of accessories such as brackets, cross arms, make them suitable to the most different needs. All columns are protected against corrosion by means of hot galvanisation.

LIGHTING COLUMNS FOR EXPLOSION PROOF CONNECTION BOX, LIGHTING FIXTURES AND FLOODLIGHTS

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

POLES

Page 91: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

ACCE

SSO

RI

AB

R

A

ØD

30°

R

B

ØD

30°

R

A

B

A

ØD

45°

R

ØC

FIGURA A FIGURA B FIGURA C FIGURA D

ØC

ØD

ØCØC

AB

R

A

ØD

30°

R

B

ØD

30°

R

A

B

A

ØD

45°

R

ØC

FIGURA A FIGURA B FIGURA C FIGURA D

ØC

ØD

ØCØC

AB

R

A

ØD

30°

R

B

ØD

30°

R

A

B

A

ØD

45°

R

ØC

FIGURA A FIGURA B FIGURA C FIGURA D

ØC

ØD

ØCØC

AB

R

A

ØD

30°

R

B

ØD

30°

R

A

B

A

ØD

45°

R

ØC

FIGURA A FIGURA B FIGURA C FIGURA D

ØC

ØD

ØCØC

A B C D

Feam Catalogue 01 - 91

Ex Lighting

Installation: hazardous areas - Zone 1 / 2 (Gases) Zone 21 /22 (Dusts) - Safe Area ACCESSORIES

FASTENING ACCESSORIES, LIGHTING POLES

POLES Technical featuresCODE A [mm] B [mm] ØC [mm] ØD R MATERIAL DETAIL

PAL041 1900 1650 1-1/2” - 500 GALVANIZED STEEL A

PAL042 500 1650 1-1/2” - 500 GALVANIZED STEEL A

PAL855 2700 1650 2-1/2” 1-1/2” 500 GALVANIZED STEEL D

PAS043 700 - 1” - 250 GALVANIZED STEEL B

PAS856 3000 500 2-1/2” 1” 250 GALVANIZED STEEL C

PAS857 2000 700 1-1/2” 1” 250 GALVANIZED STEEL COther poles are supplied according to customer’s requestMaterials: stainless steel on request

Reference details

Clamp

U-Bolts

Poles

Page 92: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

ACCE

SSO

RI

r

r

E

F

92 - Feam Catalogue 01

U-BOLTS Technical features

Ex Lighting

CLAMP Technical featuresReference details

Reference details

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.

GF1 1/2” 10 GALVANIZED STEEL E

GF2 3/4” 12 GALVANIZED STEEL E

GF3 1” 15 GALVANIZED STEEL E

GF4 1-1/4” 20 GALVANIZED STEEL E

GF5 1-1/2” 22,5 GALVANIZED STEEL E

GF6 2” 27,5 GALVANIZED STEEL E

GF7 2-1/2” 35 ALUMINUM E

GF8 3” 45 ALUMINUM E

GF10 4” 60 ALUMINUM E

GH1 1/2” 10 GALVANIZED STEEL F

GH2 3/4” 12 GALVANIZED STEEL F

GH3 1” 15 GALVANIZED STEEL F

GH4 1-1/4” 20 GALVANIZED STEEL F

GH5 1-1/2” 22,5 GALVANIZED STEEL F

GH6 2” 27,5 GALVANIZED STEEL F

GH7 2-1/2” 35 GALVANIZED STEEL F

GH8 3” 45 GALVANIZED STEEL F

GH10 4” 60 GALVANIZED STEEL F

With nuts and washer Materials: stainless steel on request

CODE Ø CONDUIT R MATERAL DETAIL

CODE Ø CONDUIT R MATERAL DETAIL

Page 93: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

CALC

OLO

ILLU

MIN

OM

ETRI

CO

Feam Catalogue 01 - 93

Ex Lighting

LIGHTING CALCULATION FOR EXTERNAL AND INTERNAL AREAS

Our technical staff offers its services in planning lighting installation, with photometric graphs and lighting data outputs in full according to Customer requirements.

A well-organized software system is available to calculate the luminance level and the lighting distribution.This system will help you to plan the right and best position of FEAM luminaries in your project. It is enough you to inform us about the required illumination level: FEAM will present you the lighting project quickly.

Using a proper software , our technical staff is able to insert FEAM lighting fixtures into a project and produce a virtual image of the area, which shows the real illuminating effect.

Lighting calculation of example

LIGHTING CALCULATION

Installation: hazardous areas - Zone 1 / 2 (Gases) Zone 21 / 22 (Dusts) - Safe Area

Lighting layout software for internal and external areas available by our office lighting calculation service for lighting installation to right and best position of luminaires in your project.

Page 94: Ex Lighting Installation: hazardous areas - Zone 1 / … · YOUR PARTNER FOR SAFETY Since 1961 Explosion Proof Electrical Equipment EVF EVF Ex Lighting LIGHTING FIXTURES FOR FLUORESCENT

YOUR PARTNER FOR SAFETY

Since 1961

CALC

OLO

ILLU

MIN

OM

ETRI

CO

94 - Feam Catalogue 01

Ex Lighting

Lighting calculation examples

REMARK:Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.