example_ramping_overcurrent_enu.pdf
TRANSCRIPT
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
1/21
Testing With the RampingTest Module
Practical Example of Use
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
2/21
2
Testing With the Ramping Test Module
Manual Version: Expl_RMP.AE.1 - Year 2011
OMICRON electronics. All rights reserved.
This manual is a publication of OMICRON electronics GmbH.
All rights including translation reserved.
The product information, specifications, and technical data embodied in this manual represent the technical
status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this manual is useful, accurate, up-to-date and
reliable. However, OMICRON electronics does not assume responsibility for any inaccuracies which may be
present.
The user is responsible for every application that makes use of an OMICRON product.
OMICRON electronics translates this manual from the source language English into a number of other
languages. Any translation of this manual is done for local requirements, and in the event of a dispute between
the English and a non-English version, the English version of this manual shall govern.
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
3/21
OMICRON 2011 Page 3 of 21
Preface
This paper describes how to test the pick-up value of the first overcurrent element. This will be explained fordirectional or non directional relays with IDMT or DTOC tripping characteristics. It contains an applicationexample which will be used throughout the paper.
The theoretical background for testing the pick-up value of the 1stelement with the Rampingtest module will
be explained. This paper also covers the definition of the necessary Test Objectsettings as well as theHardware Configurationfor testing the 1
stelement pick-up value of directional or non-directional
overcurrent relays.
Finally the Rampingtest module is used to perform the tests which are needed for testing the pick-up valueof different protection relays:
> non-directional overcurrent protection relays
> directional overcurrent protection relays
> distance protection relays with overcurrent starter function, etc.
Supplements: Sample Control Centerfiles Example_Ramping_OvercurrentDirectional_ENU.occ andExample_Ramping_OvercurrentNonDirectional_ENU.occ (referred to in this document).
Requirements: Test Universe2.40 or later; Rampingand Control Centerlicenses.
Note: The Rampingtest module can also be used for nearly all pick-up functions for current,voltage and frequency protection etc.For testing the 1
stelement pick-up value of overcurrent protection relays the
Pick-up /Drop-off Testtab in the Overcurrenttest module can also be used.
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
4/21
OMICRON 2011 Page 4 of 21
1 Application Example
10.5 kV
200/1
Protection functions
Overcurrent Relay
1stelement (67) / directional characteristic forward (IDMT)
2nd
element (50/51) /
non-directional characteristic (DTOC)
Figure 1: Feeder connection diagram of the application example
Parameter Name Parameter Value Notes
Frequency 50 Hz
VT (primary/secondary) 10500 V / 110 V
CT (primary/secondary) 200 A /1 A
1st
element
IEC Very Inverse Tripping characteristicDirectional Fwd Directional characteristic Forward
300 A Pick-up 1.5 x In CT primary
1.2Time multiplier setting (TD; TMS; P, etc.)(only for IDMT characteristics)
45Relay characteristic angle (only fordirectional protection function)
2nd
element
DTOC Tripping characteristic
600 A Pick-up 3 x In CT primary
100 ms Trip time delay
Table 1: Relay parameters for this example
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
5/21
OMICRON 2011 Page 5 of 21
2 Theoretical Introduction
2.1 Define the Ramps for Testing the Pick-Up Value of the 1stElement
In this example we will use the following time and current tolerances to define the test ramps.
Parameter Name Absolute Relative
Delay time 10ms 1%
Pick-up current 10mA 3%
Drop-off / pick-up value 95%
Angle faults1)
3
1) only necessary for directional overcurrent relays
Table 2: Relay tolerances and technical data (only valid for this example)
Note: The tolerances depend on the relay type. They can be obtained from the technical specificationin the relay manual.
Fault current /AIp
200 300 700 800600500400
Very Inverse (element 1)
DTOC (element 2)
Triptime/s
1.1Ip
0.1
1
10
100
0.01
= Pick-up current tolerances of the element 1 (3%= 1.07IP 1.13IP)
= Pick-up current tolerances of the element 2 (3%)
The pick-up value of this element can only be tested with the Pulse Rampingtest module!
Figure 2: IDMT trip time characteristic from the example (Table 1)with current tolerances
Note: Some relays have an increased pick-up value for IDMT characteristics. For example, the relayused in this example has an actual pick-up value that is 1.1 times higher than the IPsetting.
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
6/21
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
7/21
OMICRON 2011 Page 7 of 21
The following parameters will be tested (seeFigure 3):
1. Pick-up value of the 1stelement (measured)
2. Drop-off value of the 1stelement (measured)
3. Drop-off/pick-up value (calculated)
Faultcurrent
1st element
Test time
Drop-off
ratio
1st element
= Test current
= Measured drop-off value= Measured pick-up value
= Pick-up current tolerances (3%)
Figure 4: Time signal diagram of a pick-up/drop-off test
These three parameters can be tested with the Rampingtest module.
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
8/21
OMICRON 2011 Page 8 of 21
2.2 Structure of the Ramping Test Module
A ramp state is defined as the stepped change of one physical quantity. Several settings can be made in thetest module.
1. With the Set modethe user can decide whether to ramp the output voltages and currents directly, orwhether to ramp calculated values such as symmetrical components, fault values or fault impedances.
2. The Signaltype and the Quantitycan be set to define the values to be ramped. It is possible to ramptwo different signals and quantities at the same time. The signals and quantities that can be chosen aredefined by the Set mode.
3. The beginning and the end of the ramps have to be defined for testing. The Delta, which is the step size,as well as the duration between two steps dtalso have to be defined. The slope d/dtis calculatedautomatically.
4. The analog outputs of the Detail Viewshow the values which are generated by the CMC test set. Thevalues displayed with a grey background are modified by the ramp and, therefore, cannot be edited in thedetail view. The remaining values can be edited freely.
Note:The analog values should be set according to realistic fault values. For example, 180 phase shiftof the currents for phase to phase faults.
5. The trigger which stops the ramp can be set in the Triggertab of the Detail View. This Stop conditionisalso displayed in the Test View. This is explained in more detail in the following section.
Note: The step duration dthas to be set according to the trigger. It must be longer than the triggertime. If the start contact is used, for instance, the step time has to be longer than the startingtime. However, if the trip command is used, then the step time has to be longer than the triptime.
If the unbalanced load protection function (negative sequence) is active, a three phase fault hasto be used for testing.
1
2
3
5
4
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
9/21
OMICRON 2011 Page 9 of 21
Trigger conditions can be specified to control the sequence progression. They may be selected to be:
1. The test object response (e.g., start signal / trip signal)
2. A manual intervention.
The Rampingtest module includes the measurement and calculation of test values. These can be assessedautomatically and added to the report.
Note: The definition of these conditions is explained in more detail in the next chapter.
1
2
Trigger = valid ?
Start State 2
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
10/21
OMICRON 2011 Page 10 of 21
3 Practical Introduction to Testing with the Ramping Test Module
The Rampingtest module can be found on the Start Pageof the OMICRON Test Universe. It can also beinserted into an OCC File (Control Centerdocument).
3.1 Defining the Test Object
Before testing can begin the settings of the relay to be tested must be defined. In order to do that, theTest Objecthas to be opened by double clicking the Test Objectin the OCC file or by clicking theTest Objectbutton in the test module.
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
11/21
OMICRON 2011 Page 11 of 21
3.1.1 Device Settings
General relay settings (e.g., relay type, relay ID, substation details, CT and VT parameters) are entered inthe RIOfunction Device.
Note: The parameters V maxand I maxlimit the output of the currents and voltages to preventdamage to the device under test. These values must be adapted to the respectiveHardware Configurationwhen connecting the outputs in parallel or when using an amplifier.The user should consult the manual of the device under test to make sure that its input ratingwill not be exceeded.
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
12/21
OMICRON 2011 Page 12 of 21
3.2 Global Hardware Configuration for Directional Overcurrent Relays
The global Hardware Configurationspecifies the general input/output configuration of the CMC test set. Itis valid for all subsequent test modules and, therefore, it has to be defined according to the relaysconnections. It can be opened by double clicking the Hardware Configurationentry in the OCC file.
3.2.1 Example Output Configuration for Protection Relays with a Secondary Nominal Current of 1 A
VN
VA
VB
VC
IA
IB
IC
IN
Note: For non-directional overcurrent relays the voltage outputs can be set to .
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
13/21
OMICRON 2011 Page 13 of 21
3.2.2 Example Output Configuration for Protection Relays with a Secondary Nominal Current of 5 A
VN
VA
VB
VC
IB IN
IA IC
Note: Make sure that the rating of the wires is sufficient when connecting the outputs in parallel.
For non-directional overcurrent relays the voltage outputs can be set to .
The following explanations only apply to protection relays with a secondary nominal current of1 A
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
14/21
OMICRON 2011 Page 14 of 21
3.2.3 Analog Outputs
The analog outputs, binary inputs and outputs can all be activated individually in the local HardwareConfigurationof the specific test module (see chapter3.3 ).
3.2.4 Binary Inputs
1. The start and the trip command are connected to binary inputs. BI1 BI10 can be used.
2. For wet contacts adapt the nominal voltages of the binary inputs to the voltage of the circuit breaker tripcommand or select Potential Freefor dry contacts.
3. The binary outputs and the analog inputs etc. will not be used for the following tests.
Start
Trip
1
2
3
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
15/21
OMICRON 2011 Page 15 of 21
3.2.5 Wiring of the Test Set for Directional Overcurrent Relays
Note: The following wiring diagrams are examples only. The wiring of the analog current inputs maybe different if additional protective functions such as sensitive ground fault protection areprovided. In this case INmay be wired separately.
IN
IA
IB
IC
Protection
Relay
VA
VB
VC
Trip
(+)
(-)
Start
(+)
(-)
optional
IN
IA
IB
IC
Protection
Relay
VA
VB
VC
Trip
(+)
(-)
Start
(+)
(-)
optional
Note: For non-directional overcurrent relays the wiring of the voltage outputs is not necessary.
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
16/21
OMICRON 2011 Page 16 of 21
3.3 Local Hardware Configuration for Directional Overcurrent Testing
The local Hardware Configurationactivates the outputs/inputs of the CMC test set for the selected testmodule. Therefore, it has to be defined for each test module separately. It can be opened by clicking theHardware Configurationbutton in the test module.
3.3.1 Analog Outputs
Note: For non-directional overcurrent relays the voltages are already deactivated in the globalHardware Configuration(see chapter3.2 ). Therefore, they will not be visible in this tab.
3.3.2 Binary Inputs
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
17/21
OMICRON 2011 Page 17 of 21
3.4 Defining the Test Configuration
3.4.1 General Approach
Note: In this example an overcurrent relay with an IDMT tripping characteristic and an increased pick-
up value is used (seeTable 1 andFigure 2). Because of this, the nominal trip time for the pick-up current of 1.65 A is approximately 162 s. However, the start signal is not delayed which iswhy the start contact is used as the trigger.
When testing the pick-up and the drop-off values for directional or non-directional overcurrent relays, thefollowing steps are recommended.
Calculation of the Nominal Values:
For testing the pick-up and the drop-off values, the settings (Table 1)as well as the tolerances (Table 2)ofthe overcurrent protection function must be known. Also, it must be known whether there is an increasedpick-up value. From these values the nominal pick-up current, the nominal drop-off current and the absolutetolerances for these currents can be calculated. The calculations for this example are shown below:
Nominal pick-up value: 1.1 IPNominal drop-off value: 0.95 1.1 IPCurrent tolerances: 3% or 10 mA
Nominal value TOL- TOL+
Pick-up 1.65 A 49.5 mA 49.5 mA
Drop-off 1.57 A 47 mA 47 mA
Table 3: Nominal currents and tolerances for this example
Settings in the Test View:
1. As the currents are to be ramped directly, the Set modeshould be Direct.
2. In this example a phase to phase fault will be applied.
Note:If an unbalanced load protection is activated in the relay a three phase fault should be chosenbecause a phase to phase fault could trip the unbalanced load protection instead of the overcurrentprotection.
3. For the overcurrent pick-up the Magnitudeis ramped.
2 3
1
4
5 6 7
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
18/21
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
19/21
OMICRON 2011 Page 19 of 21
Settings in the Detail View:
1. For directional overcurrent relays all three voltages must be set to the nominal voltage.
2. The angles of the currents have to be adapted to the fault type. For example, a phase to phase fault has180 between each fault current. For directional overcurrent relays the angles also have to be adjustedto the directional characteristic.
3. The start contact is chosen as the trigger for this test. If the trip contact is used, the step duration of theramp has to be longer than the trip time (e.g., 1.2 x Trip Time).
Settings in the Measurement view:
4. In this test the pick-up and drop-off currents are measured.
5. The pick-up value will be measured during the upward ramp. The drop-off value during the downwardramp.
6. The pick-up current will be measured when the start signal is activated. The drop-off current will bemeasured when it is deactivated.
7. The nominal values as well as the tolerances (Table 3)have to be set.
8. By dividing the measured drop-off current by the measured pick-up current, the drop-off ratio iscalculated.
9. After testing, the assessment is made automatically and the actual values, as well as the deviation fromthe nominal values, are displayed.
1
2
3
4
5 6 7
8
9
-
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
20/21
OMICRON 2011 Page 20 of 21
3.5 Why it is Not Possible to Use the Ramping Test Module for the 2ndElement
For this example, the General Start signal or the General Trip signal is defined as the trigger condition fortesting the pick-up value of the 1
stelement.
For testing the 2ndelement the General Start signal cannot be used as the trigger condition because it willoperate after the threshold of the 1
stelement is exceeded. This would prevent the test current from reaching
the pick-up value of the 2nd
element (seeFigure 6).
Faultcurrent
Test time
From
To
1st
element
2nd
element
t(1stel.)
= General Trip signal= General Start signal
Figure 6: Time signal view of a ramp during an attempt to test the pick-up value of element 2
Note: The use of the Rampingtest module is only possible if the start signal of the 2nd
element iswired separately. If only a General Trip signal is available, the test will be stopped as soon asthe current of the 1
stelement is exceeded and the trip time t(1
stelement) has elapsed and,
therefore, it will fail.
To test the 2nd
element the Pulse Rampingtest module can be used instead.
Feedback regarding this application is welcome by email [email protected].
mailto:[email protected]:[email protected]:[email protected]:[email protected] -
8/10/2019 Example_Ramping_Overcurrent_ENU.pdf
21/21
OMICRONis an international company serving the electrical power
industry with innovative testing and diagnostic solutions. The application of
OMICRON products provides users with the highest level of confidence in
the condition assessment of primary and secondary equipment on their
systems. Services offered in the area of consulting, commissioning,
testing, diagnosis, and training make the product range complete.
Customers in more than 130 countries rely on the company's ability to
supply leading edge technology of excellent quality. Broad application
knowledge and extraordinary customer support provided by offices in
North America, Europe, South and East Asia, and the Middle East,
together with a worldwide network of distributors and representatives,
make the company a market leader in its sector.
Europe, Middle East, Africa
OMICRON electronics GmbH
Oberes Ried 1
6833 Klaus, Austria
Phone: +43 5523 507-0
Fax: +43 5523 507-999
Asia-Pacific
OMICRON electronics Asia Limited
Suite 2006, 20/F, Tower 2
The Gateway, Harbour City
Kowloon, Hong Kong S.A.R.
Phone: +852 3767 5500
Fax: +852 3767 5400
Americas
OMICRON electronics Corp. USA
12 Greenway Plaza, Suite 1510
Houston, TX 77046, USA
Phone: +1 713 830-4660
+1 800-OMICRON
Fax: +1 713 830-4661