example_ramping_overcurrent_enu.pdf

Upload: oscar-ordonez-velasquez

Post on 02-Jun-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    1/21

    Testing With the RampingTest Module

    Practical Example of Use

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    2/21

    2

    Testing With the Ramping Test Module

    Manual Version: Expl_RMP.AE.1 - Year 2011

    OMICRON electronics. All rights reserved.

    This manual is a publication of OMICRON electronics GmbH.

    All rights including translation reserved.

    The product information, specifications, and technical data embodied in this manual represent the technical

    status at the time of writing and are subject to change without prior notice.

    We have done our best to ensure that the information given in this manual is useful, accurate, up-to-date and

    reliable. However, OMICRON electronics does not assume responsibility for any inaccuracies which may be

    present.

    The user is responsible for every application that makes use of an OMICRON product.

    OMICRON electronics translates this manual from the source language English into a number of other

    languages. Any translation of this manual is done for local requirements, and in the event of a dispute between

    the English and a non-English version, the English version of this manual shall govern.

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    3/21

    OMICRON 2011 Page 3 of 21

    Preface

    This paper describes how to test the pick-up value of the first overcurrent element. This will be explained fordirectional or non directional relays with IDMT or DTOC tripping characteristics. It contains an applicationexample which will be used throughout the paper.

    The theoretical background for testing the pick-up value of the 1stelement with the Rampingtest module will

    be explained. This paper also covers the definition of the necessary Test Objectsettings as well as theHardware Configurationfor testing the 1

    stelement pick-up value of directional or non-directional

    overcurrent relays.

    Finally the Rampingtest module is used to perform the tests which are needed for testing the pick-up valueof different protection relays:

    > non-directional overcurrent protection relays

    > directional overcurrent protection relays

    > distance protection relays with overcurrent starter function, etc.

    Supplements: Sample Control Centerfiles Example_Ramping_OvercurrentDirectional_ENU.occ andExample_Ramping_OvercurrentNonDirectional_ENU.occ (referred to in this document).

    Requirements: Test Universe2.40 or later; Rampingand Control Centerlicenses.

    Note: The Rampingtest module can also be used for nearly all pick-up functions for current,voltage and frequency protection etc.For testing the 1

    stelement pick-up value of overcurrent protection relays the

    Pick-up /Drop-off Testtab in the Overcurrenttest module can also be used.

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    4/21

    OMICRON 2011 Page 4 of 21

    1 Application Example

    10.5 kV

    200/1

    Protection functions

    Overcurrent Relay

    1stelement (67) / directional characteristic forward (IDMT)

    2nd

    element (50/51) /

    non-directional characteristic (DTOC)

    Figure 1: Feeder connection diagram of the application example

    Parameter Name Parameter Value Notes

    Frequency 50 Hz

    VT (primary/secondary) 10500 V / 110 V

    CT (primary/secondary) 200 A /1 A

    1st

    element

    IEC Very Inverse Tripping characteristicDirectional Fwd Directional characteristic Forward

    300 A Pick-up 1.5 x In CT primary

    1.2Time multiplier setting (TD; TMS; P, etc.)(only for IDMT characteristics)

    45Relay characteristic angle (only fordirectional protection function)

    2nd

    element

    DTOC Tripping characteristic

    600 A Pick-up 3 x In CT primary

    100 ms Trip time delay

    Table 1: Relay parameters for this example

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    5/21

    OMICRON 2011 Page 5 of 21

    2 Theoretical Introduction

    2.1 Define the Ramps for Testing the Pick-Up Value of the 1stElement

    In this example we will use the following time and current tolerances to define the test ramps.

    Parameter Name Absolute Relative

    Delay time 10ms 1%

    Pick-up current 10mA 3%

    Drop-off / pick-up value 95%

    Angle faults1)

    3

    1) only necessary for directional overcurrent relays

    Table 2: Relay tolerances and technical data (only valid for this example)

    Note: The tolerances depend on the relay type. They can be obtained from the technical specificationin the relay manual.

    Fault current /AIp

    200 300 700 800600500400

    Very Inverse (element 1)

    DTOC (element 2)

    Triptime/s

    1.1Ip

    0.1

    1

    10

    100

    0.01

    = Pick-up current tolerances of the element 1 (3%= 1.07IP 1.13IP)

    = Pick-up current tolerances of the element 2 (3%)

    The pick-up value of this element can only be tested with the Pulse Rampingtest module!

    Figure 2: IDMT trip time characteristic from the example (Table 1)with current tolerances

    Note: Some relays have an increased pick-up value for IDMT characteristics. For example, the relayused in this example has an actual pick-up value that is 1.1 times higher than the IPsetting.

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    6/21

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    7/21

    OMICRON 2011 Page 7 of 21

    The following parameters will be tested (seeFigure 3):

    1. Pick-up value of the 1stelement (measured)

    2. Drop-off value of the 1stelement (measured)

    3. Drop-off/pick-up value (calculated)

    Faultcurrent

    1st element

    Test time

    Drop-off

    ratio

    1st element

    = Test current

    = Measured drop-off value= Measured pick-up value

    = Pick-up current tolerances (3%)

    Figure 4: Time signal diagram of a pick-up/drop-off test

    These three parameters can be tested with the Rampingtest module.

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    8/21

    OMICRON 2011 Page 8 of 21

    2.2 Structure of the Ramping Test Module

    A ramp state is defined as the stepped change of one physical quantity. Several settings can be made in thetest module.

    1. With the Set modethe user can decide whether to ramp the output voltages and currents directly, orwhether to ramp calculated values such as symmetrical components, fault values or fault impedances.

    2. The Signaltype and the Quantitycan be set to define the values to be ramped. It is possible to ramptwo different signals and quantities at the same time. The signals and quantities that can be chosen aredefined by the Set mode.

    3. The beginning and the end of the ramps have to be defined for testing. The Delta, which is the step size,as well as the duration between two steps dtalso have to be defined. The slope d/dtis calculatedautomatically.

    4. The analog outputs of the Detail Viewshow the values which are generated by the CMC test set. Thevalues displayed with a grey background are modified by the ramp and, therefore, cannot be edited in thedetail view. The remaining values can be edited freely.

    Note:The analog values should be set according to realistic fault values. For example, 180 phase shiftof the currents for phase to phase faults.

    5. The trigger which stops the ramp can be set in the Triggertab of the Detail View. This Stop conditionisalso displayed in the Test View. This is explained in more detail in the following section.

    Note: The step duration dthas to be set according to the trigger. It must be longer than the triggertime. If the start contact is used, for instance, the step time has to be longer than the startingtime. However, if the trip command is used, then the step time has to be longer than the triptime.

    If the unbalanced load protection function (negative sequence) is active, a three phase fault hasto be used for testing.

    1

    2

    3

    5

    4

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    9/21

    OMICRON 2011 Page 9 of 21

    Trigger conditions can be specified to control the sequence progression. They may be selected to be:

    1. The test object response (e.g., start signal / trip signal)

    2. A manual intervention.

    The Rampingtest module includes the measurement and calculation of test values. These can be assessedautomatically and added to the report.

    Note: The definition of these conditions is explained in more detail in the next chapter.

    1

    2

    Trigger = valid ?

    Start State 2

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    10/21

    OMICRON 2011 Page 10 of 21

    3 Practical Introduction to Testing with the Ramping Test Module

    The Rampingtest module can be found on the Start Pageof the OMICRON Test Universe. It can also beinserted into an OCC File (Control Centerdocument).

    3.1 Defining the Test Object

    Before testing can begin the settings of the relay to be tested must be defined. In order to do that, theTest Objecthas to be opened by double clicking the Test Objectin the OCC file or by clicking theTest Objectbutton in the test module.

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    11/21

    OMICRON 2011 Page 11 of 21

    3.1.1 Device Settings

    General relay settings (e.g., relay type, relay ID, substation details, CT and VT parameters) are entered inthe RIOfunction Device.

    Note: The parameters V maxand I maxlimit the output of the currents and voltages to preventdamage to the device under test. These values must be adapted to the respectiveHardware Configurationwhen connecting the outputs in parallel or when using an amplifier.The user should consult the manual of the device under test to make sure that its input ratingwill not be exceeded.

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    12/21

    OMICRON 2011 Page 12 of 21

    3.2 Global Hardware Configuration for Directional Overcurrent Relays

    The global Hardware Configurationspecifies the general input/output configuration of the CMC test set. Itis valid for all subsequent test modules and, therefore, it has to be defined according to the relaysconnections. It can be opened by double clicking the Hardware Configurationentry in the OCC file.

    3.2.1 Example Output Configuration for Protection Relays with a Secondary Nominal Current of 1 A

    VN

    VA

    VB

    VC

    IA

    IB

    IC

    IN

    Note: For non-directional overcurrent relays the voltage outputs can be set to .

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    13/21

    OMICRON 2011 Page 13 of 21

    3.2.2 Example Output Configuration for Protection Relays with a Secondary Nominal Current of 5 A

    VN

    VA

    VB

    VC

    IB IN

    IA IC

    Note: Make sure that the rating of the wires is sufficient when connecting the outputs in parallel.

    For non-directional overcurrent relays the voltage outputs can be set to .

    The following explanations only apply to protection relays with a secondary nominal current of1 A

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    14/21

    OMICRON 2011 Page 14 of 21

    3.2.3 Analog Outputs

    The analog outputs, binary inputs and outputs can all be activated individually in the local HardwareConfigurationof the specific test module (see chapter3.3 ).

    3.2.4 Binary Inputs

    1. The start and the trip command are connected to binary inputs. BI1 BI10 can be used.

    2. For wet contacts adapt the nominal voltages of the binary inputs to the voltage of the circuit breaker tripcommand or select Potential Freefor dry contacts.

    3. The binary outputs and the analog inputs etc. will not be used for the following tests.

    Start

    Trip

    1

    2

    3

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    15/21

    OMICRON 2011 Page 15 of 21

    3.2.5 Wiring of the Test Set for Directional Overcurrent Relays

    Note: The following wiring diagrams are examples only. The wiring of the analog current inputs maybe different if additional protective functions such as sensitive ground fault protection areprovided. In this case INmay be wired separately.

    IN

    IA

    IB

    IC

    Protection

    Relay

    VA

    VB

    VC

    Trip

    (+)

    (-)

    Start

    (+)

    (-)

    optional

    IN

    IA

    IB

    IC

    Protection

    Relay

    VA

    VB

    VC

    Trip

    (+)

    (-)

    Start

    (+)

    (-)

    optional

    Note: For non-directional overcurrent relays the wiring of the voltage outputs is not necessary.

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    16/21

    OMICRON 2011 Page 16 of 21

    3.3 Local Hardware Configuration for Directional Overcurrent Testing

    The local Hardware Configurationactivates the outputs/inputs of the CMC test set for the selected testmodule. Therefore, it has to be defined for each test module separately. It can be opened by clicking theHardware Configurationbutton in the test module.

    3.3.1 Analog Outputs

    Note: For non-directional overcurrent relays the voltages are already deactivated in the globalHardware Configuration(see chapter3.2 ). Therefore, they will not be visible in this tab.

    3.3.2 Binary Inputs

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    17/21

    OMICRON 2011 Page 17 of 21

    3.4 Defining the Test Configuration

    3.4.1 General Approach

    Note: In this example an overcurrent relay with an IDMT tripping characteristic and an increased pick-

    up value is used (seeTable 1 andFigure 2). Because of this, the nominal trip time for the pick-up current of 1.65 A is approximately 162 s. However, the start signal is not delayed which iswhy the start contact is used as the trigger.

    When testing the pick-up and the drop-off values for directional or non-directional overcurrent relays, thefollowing steps are recommended.

    Calculation of the Nominal Values:

    For testing the pick-up and the drop-off values, the settings (Table 1)as well as the tolerances (Table 2)ofthe overcurrent protection function must be known. Also, it must be known whether there is an increasedpick-up value. From these values the nominal pick-up current, the nominal drop-off current and the absolutetolerances for these currents can be calculated. The calculations for this example are shown below:

    Nominal pick-up value: 1.1 IPNominal drop-off value: 0.95 1.1 IPCurrent tolerances: 3% or 10 mA

    Nominal value TOL- TOL+

    Pick-up 1.65 A 49.5 mA 49.5 mA

    Drop-off 1.57 A 47 mA 47 mA

    Table 3: Nominal currents and tolerances for this example

    Settings in the Test View:

    1. As the currents are to be ramped directly, the Set modeshould be Direct.

    2. In this example a phase to phase fault will be applied.

    Note:If an unbalanced load protection is activated in the relay a three phase fault should be chosenbecause a phase to phase fault could trip the unbalanced load protection instead of the overcurrentprotection.

    3. For the overcurrent pick-up the Magnitudeis ramped.

    2 3

    1

    4

    5 6 7

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    18/21

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    19/21

    OMICRON 2011 Page 19 of 21

    Settings in the Detail View:

    1. For directional overcurrent relays all three voltages must be set to the nominal voltage.

    2. The angles of the currents have to be adapted to the fault type. For example, a phase to phase fault has180 between each fault current. For directional overcurrent relays the angles also have to be adjustedto the directional characteristic.

    3. The start contact is chosen as the trigger for this test. If the trip contact is used, the step duration of theramp has to be longer than the trip time (e.g., 1.2 x Trip Time).

    Settings in the Measurement view:

    4. In this test the pick-up and drop-off currents are measured.

    5. The pick-up value will be measured during the upward ramp. The drop-off value during the downwardramp.

    6. The pick-up current will be measured when the start signal is activated. The drop-off current will bemeasured when it is deactivated.

    7. The nominal values as well as the tolerances (Table 3)have to be set.

    8. By dividing the measured drop-off current by the measured pick-up current, the drop-off ratio iscalculated.

    9. After testing, the assessment is made automatically and the actual values, as well as the deviation fromthe nominal values, are displayed.

    1

    2

    3

    4

    5 6 7

    8

    9

  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    20/21

    OMICRON 2011 Page 20 of 21

    3.5 Why it is Not Possible to Use the Ramping Test Module for the 2ndElement

    For this example, the General Start signal or the General Trip signal is defined as the trigger condition fortesting the pick-up value of the 1

    stelement.

    For testing the 2ndelement the General Start signal cannot be used as the trigger condition because it willoperate after the threshold of the 1

    stelement is exceeded. This would prevent the test current from reaching

    the pick-up value of the 2nd

    element (seeFigure 6).

    Faultcurrent

    Test time

    From

    To

    1st

    element

    2nd

    element

    t(1stel.)

    = General Trip signal= General Start signal

    Figure 6: Time signal view of a ramp during an attempt to test the pick-up value of element 2

    Note: The use of the Rampingtest module is only possible if the start signal of the 2nd

    element iswired separately. If only a General Trip signal is available, the test will be stopped as soon asthe current of the 1

    stelement is exceeded and the trip time t(1

    stelement) has elapsed and,

    therefore, it will fail.

    To test the 2nd

    element the Pulse Rampingtest module can be used instead.

    Feedback regarding this application is welcome by email [email protected].

    mailto:[email protected]:[email protected]:[email protected]:[email protected]
  • 8/10/2019 Example_Ramping_Overcurrent_ENU.pdf

    21/21

    OMICRONis an international company serving the electrical power

    industry with innovative testing and diagnostic solutions. The application of

    OMICRON products provides users with the highest level of confidence in

    the condition assessment of primary and secondary equipment on their

    systems. Services offered in the area of consulting, commissioning,

    testing, diagnosis, and training make the product range complete.

    Customers in more than 130 countries rely on the company's ability to

    supply leading edge technology of excellent quality. Broad application

    knowledge and extraordinary customer support provided by offices in

    North America, Europe, South and East Asia, and the Middle East,

    together with a worldwide network of distributors and representatives,

    make the company a market leader in its sector.

    Europe, Middle East, Africa

    OMICRON electronics GmbH

    Oberes Ried 1

    6833 Klaus, Austria

    Phone: +43 5523 507-0

    Fax: +43 5523 507-999

    [email protected]

    Asia-Pacific

    OMICRON electronics Asia Limited

    Suite 2006, 20/F, Tower 2

    The Gateway, Harbour City

    Kowloon, Hong Kong S.A.R.

    Phone: +852 3767 5500

    Fax: +852 3767 5400

    [email protected]

    Americas

    OMICRON electronics Corp. USA

    12 Greenway Plaza, Suite 1510

    Houston, TX 77046, USA

    Phone: +1 713 830-4660

    +1 800-OMICRON

    Fax: +1 713 830-4661

    [email protected]