exhaust hood presentation1 (2)

Upload: luis-gabriel-bautista

Post on 14-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    1/49

    NFPA 96 and Building Code Requirements

    for Commercial Kitchen Hood Systems

    Presentation for the Sevier County Fire Code and

    Building Code Officials

    Presented by Roger Griffith, PE

    Griffith Engineering, Jefferson City, TN

    April 21, 2004

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    2/49

    Course Outline

    Problem Areas

    General Requirements

    Hoods Exhaust Ducts

    Fans

    Fire Suppression System

    Code Changes NFPA 96

    International Mechanical Code (IMC)

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    3/49

    GENERAL REQUIREMENTS

    Where are commercial hoods required?

    NFPA 96: Cooking equipment used in processes

    producing smoke and grease-laden vapors shallbe equipped with

    NFPA 96 A-1-1 intended to includeresidential cooking equipment where used forpurposes other than residential family use

    SMC gives exceptions for domestic equipmentinstalled in dwelling units and ovens do not heatfood above 2120F.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    4/49

    Clearances

    18 inches to combustible material

    3 inches to limited-combustible material

    0 inches to noncombustible material

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    5/49

    Exceptions

    When the hood is listed for lesser clearances

    If the combustible materialis protected asfollows:

    28 gage sheet metal spaced out 1 inch onnoncombustible spacers 9 inch clearance tocombustible material

    22 gage sheet metal on 1 inch mineral wool bats orceramic fiber blanket reinforced with wire mesh or

    equivalent spaced out 1 inch on noncombustible spacers 3 inch clearance to combustible material

    Reduced clearance to limited-combustible materials tozero clearance where protected by noncombustiblematerials or materials listed for the purpose of reducingclearance, and acceptable to the AHJ.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    6/49

    9 inch clearance reduction

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    7/49

    3 inch clearance reduction

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    8/49

    Clearances

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    9/49

    Clearances

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    10/49

    Duct Clearances

    Protection methods for ducts to reduceclearances shall be applied to the

    combustible or limited-combustibleconstruction, not to the duct itself.

    Exception: Field applied grease duct

    enclosures and factory-built grease ductenclosures

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    11/49

    Field Applied Protection

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    12/49

    Duct Enclosures

    Field applied grease duct enclosure: Alisted system evaluated for reduced

    clearances and as an alternative to aduct with its fire-rated enclosure.

    Factory-built grease duct enclosure: Alisted factorybuilt grease ductenclosure system evaluated forreduced clearances to combustiblesand as an alternative to a duct with its

    fire-rated enclosure.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    13/49

    EXHAUST HOODS

    Type 1: Hoods designed for greaseexhaust applications

    Type 2: Hoods designed for heatand steam removal and othernongrease applications. (NFPA 96does not cover)

    NFPA 96: 2-1, 1998 Edition

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    14/49

    Exhaust Hoods

    Hoods shall be constructed of 18 gagesteel or 20 gage stainless.

    All seams, joints, and penetrations ofthe hood enclosure that direct andcapture grease-laden vapors and

    exhaust gases shall have a liquidtightcontinuous weld external weld.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    15/49

    Hood Integrity

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    16/49

    Exhaust Hood

    Hoods must be sized and configured toprovide for the capture and removal of

    grease-laden vapors. Size:

    Configuration:

    Backshelf/Proximity Hoods

    Short-Circuit Hoods Face Discharge Makeup Hoods

    Exhaust Only Hoods w/Supply Plenums

    NFPA 96: 2-2, 1998 Edition

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    17/49

    Short Circuit Hoods

    Hood performance is principallydependent upon net exhaust.

    Net exhaust = Total exhaustinternal makeup

    Large airflows are required highfirst cost & operating cost.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    18/49

    Backshelf Hood

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    19/49

    Face Discharge Makeup

    Hood Originally designed

    for non-air-

    conditionedkitchens

    Makeup airbecomes load to

    kitchen HVAC

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    20/49

    Exhaust Only Hood Cross

    Section

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    21/49

    Exhaust OnlyHood w/Supply

    Plenum

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    22/49

    Hood w/Supply Plenums

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    23/49

    Fire Dampers at Hoods

    Fire dampers are installed in supply airconnections where they penetrate the

    hood. Fire dampers are not installed in

    exhaust ducts.

    Fire dampers are not required insupply plenums that are isolated fromthe continuously welded shell.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    24/49

    Filters and Baffles

    They are required!

    They must be 18 inches from cooking

    surface. (Hoods above char-broilers must be4 ft above the cooking surface).

    Filters must be installed at an angle of notless than 45 degrees

    Filters must be easily accessible andremovable for cleaning.

    NFPA 96: Ch.3, 1998 Edition

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    25/49

    EXHAUST DUCTS

    Ducts can not pass through fire wallsor fire partitions.

    Ducts cannot have dips or traps.

    Clearances must be maintained.

    Ducts must be 16 gage steel or 18

    gage stainless.

    Seams and joints shall have liquidtight external welds.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    26/49

    Openings in Exhaust Ducts

    Location At changes of direction For damper cleaning and inspection At both sides of inline fans

    Construction On horizontal ducts20x20; if size is not possible, provide

    openings large enough for cleaning every 12 feet. Access openings shall be of the same material and thickness

    as the duct. Access panels shall have a gasket or sealant that is rated for

    15000

    F and shall be grease tight. Enclosure openings are required to reach access panels.They shall be protected by approved self-closing firedoors.

    NFPA 96: 4-3, 1998 Edition

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    27/49

    Exhaust Ducts Exterior

    Fasteners cannot penetrate duct walls.

    Ducts must be painted or be

    constructed of stainless steel.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    28/49

    Exhaust Ducts Interior

    Enclosures must be provided forbuildings more than one story, and

    when penetrating a rated floor /ceilingassembly.

    Enclosure shall be sealed around the

    duct at the bottom.Exception: Field applied or factory

    applied grease duct enclosures.NFPA 96: 4-7, 1998 Edition

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    29/49

    Clearances at Enclosures

    18 to combustible construction 6 to noncombustible or limited-combustible

    construction Clearances may be reduced with field

    applied or factory applied grease ductenclosures.

    Multiple ducts are not permitted in a single

    enclosure

    (SMC only requires 6 clearance)

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    30/49

    Rooftop Terminations

    Maintain 10 feet clearance to adjacentbuildings, property lines, and air

    intakes, or locate exhaust 3 feet aboveair intakes.

    Ductwork must extend 18 above

    roof.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    31/49

    Fans

    Fans must be listed for commercialcooking equipment.

    Rooftop Fans Rooftop fans must be hinged.

    Exhaust outlet must be 40 inches above

    roof. Termination must have a grease trap.

    Safe access must be provided to the fan

    for inspection and cleaning

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    32/49

    Fans

    Wall Termination Fans

    Wall must be noncombustible

    Maintain a minimum of 10 feet clearance fromoutlet to adjacent buildings, property lines,grade level, combustible construction, electricalequipment, air intakes or operable windows.

    Air intakes or operable windows above exhaustshall be 10 feet plus 0.25 feet for each 1 degreefrom horizontal.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    33/49

    Airflow

    Air flow has traditionally been 1500 ft/minminimum. This is changing with the newer

    codes. Air volumes should be of sufficient level to

    capture and remove grease-laden cookingvapors.

    Makeup air shall prevent negative pressuresfrom exceeding 0.02 wc in the cookingarea.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    34/49

    Fire Suppression Systems

    Automatic fireextinguishing

    systems must be inaccordance with

    NFPA 12 - CO2 NFPA 13 Wet

    NFPA 17 DryChemical

    NFPA 17A WetChemical

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    35/49

    Ansul System

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    36/49

    Pyrochem System

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    37/49

    Fire Suppression Systems

    Exhaust fans must continue to operate after theextinguishing system has been activated. Fans donot have to be started upon activation of the

    extinguishing system. Makeup air supplied internally to the hood must be

    shut off when fire suppression system activates.

    All sources of fuel and electric power that produceheat to all equipment requiring protection by that

    system shall automatically shut off upon activationof any extinguishing system.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    38/49

    Fire Suppression Systems

    A means of manual activation must be provided inthe path of egress. (SMC requires it to be from 10-20 feet of hood.)

    An audible alarm or visible indicator shall beprovided.

    If fire alarm system is installed in building, it shallbe activated.

    If electric power is required to operate the firesuppression system, it shall have a backup powersupply or all sources of fuel shall automatically shutoff when the system is inoperable.

    Portable fire extinguishers

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    39/49

    Fire Suppression System

    Inspection and Servicing Systems are required to be inspected every 6

    months by properly trained and qualified

    persons.All devices, actuators, detectors, andcomponents shall be checked for properoperation.

    Fusible links and automatic sprinkler heads shall

    be replaced at least annually, or morefrequently. If required, certificates of inspection and

    maintenance shall be forwarded to the AHJ.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    40/49

    Cleaning and Inspection

    The entire system shall be inspected byproperly trained and certified personnel. Quarterly high volume operations (24 hour,

    charbroiling) Semi-annually moderate volume

    Annually low-volume (churches)

    During inspection if the system is found to

    be contaminated with grease, the entiresystem shall be cleaned by properly trainedand certified personnel.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    41/49

    Cleaning and Inspection

    Hoods, ducts, fans, etc. shall becleaned as needed to prevent them

    from becoming heavily contaminatedwith grease.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    42/49

    Code Updates

    NFPA 96

    International Mechanical Code

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    43/49

    Revisions to NFPA 96

    Minimum Air Velocity through a greaseduct

    1,500 ft/min (1998 edition) 1,200 ft/min (2001 edition)

    500 ft/min (Errata 96-01-01 to 2001

    edition in January 2002

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    44/49

    NFPA 96 2001

    Protection shall be provided on thewall down to the floor or to

    noncombustible material. Horizontal duct support systems shall

    be designed for weight of duct plus800 lbs. at any point.

    Penetrations to ducts and hoods shallbe listed.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    45/49

    NFPA 96 2001

    A minimum of 5 feet horizontalclearance from fan to combustible

    material.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    46/49

    NFPA 2004 under review

    Chapter 15, Down Draft ApplianceVentilation Systems

    A new section requiring a 20 x 20 openingfor personal entry for duct cleaning

    A requirement for factory-built ductenclosures and duct-wrapped grease duct

    systems to be listed in accordance with UL2221, Tests of Fire Resistive Duct Enclosure

    Assemblies.

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    47/49

    International MechanicalCode

    2000 Code

    Performance Test

    Net Exhaust 2003 Code

    Capture and Containment Test

    Net Exhaust

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    48/49

    Capture and ContainmentTest

    Adjust and verify all exhaust and makeupairflows.

    Operate equipment at cooking conditions

    Verify capture and containment with smokepuffers

    Verify pressurization, and adjust if

    necessary Building positive to outdoors, kitchen negative todining

  • 7/29/2019 Exhaust Hood Presentation1 (2)

    49/49

    Capture and ContainmentTest