experiences in integrating pv and other dg to the power …€¢ minimum load to generation ratio...
TRANSCRIPT
Experiences in Integrating PV and Other DG to the Power System
(Radial Distribution Systems)
Prepared by:
Philip Barker
Founder and Principal Engineer Nova Energy Specialists, LLC
Schenectady, NY
Phone (518) 346-9770
Website: novaenergyspecialists.com
E-Mail: [email protected]
Presented at:
Utility Wind Interest Group (UWIG) 6th Annual Distributed Wind/Solar Interconnection Workshop
February 22-24, 2012
Golden, CO
1 Prepared by Nova Energy Specialists, LLC
Topics
• Discussion of Distribution and Subtransmission Factors Considered in Basic DG integration Studies
• Useful Ratios for Screening Analysis of DG Impacts
• Review of Some System Impacts:
– Voltage Issues
– Fault Current Issues
– Islanding Issues
– Ground Fault Overvoltage Issues
• Summary and Conclusions of PV Experiences
Prepared by Nova Energy Specialists, LLC 2
Prepared by Nova Energy Specialists, LLC 3
12.47 kV
Subtransmission Line
Substation
Transformer
LTC
DG
Distribution
Feeder
Rotating Machine or
Inverter based DG
Step Up
Transformer
Subtransmission
Source
Bulk
System
Reclosing and
Relay Settings
Primary Feeder
Point of Connection
(POC)
Other Substations
with Load and DG
Customer
Site Load
Adjacent
Feeders
Voltage Regulator
Discussion of
Some Factors to
Consider in DG
Integration
Regulator and
LTC Settings
Capacitor
Alt. Feed
Alt. Feed
Other load and
DG scattered on
feeder
Type of
Grounding
Prime mover or
energy source
characteristics
Some Useful Penetration Ratios for Screening Analysis
• Minimum Load to Generation Ratio (this is the annual minimum load on the relevant power system section divided by the aggregate DG capacity on the power system section)
• Stiffness Factor (the available utility fault current divided by DG
rated output current in the affected area)
• Fault Ratio Factor (also called SCCR) (available utility fault current divided by DG fault contribution in the affected area) (Note: also called Short Circuit Contribution Ratio: SCCR)
• Ground Source Impedance Ratio (ratio of zero
sequence impedance of DG ground source relative to utility ground source impedance at point of connection)
NREL Workshop on High Penetration PV: Defining High Penetration PV – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC
Note: all ratios above are based on the aggregate DG sources on the system area of interest where appropriate
Prepared by Nova Energy Specialists, LLC 4
Minimum Load to Generation Ratio (MLGR)
• Try to use the annual minimum load (don’t just assume 1 week of measurements gives the minimum)
Prepared by Nova Energy Specialists, LLC 5
Time (up to 1 year is ideal)
Minimum
Load
Peak Load
Weekend
Weekdays
Annual Minimum Load
False Minimum
Name of Ratio
What is Ratio useful for? (Note: these ratios are intended for distribution and subtransmission system impacts of DG for the types of impacts described below.)
Suggested Penetration Level Ratios(1)
Very Low Penetration
(Very low probability of any issues)
Moderate Penetration
(Low to minor probability of issues)
Higher Penetration(4) (Increased probability
of serious issues.
Minimum Load to
Generation Ratio
[MLGR](2)
• MLGR used for Ground Fault Overvoltage Suppression Analysis (use ratios shown when DG is not effectively grounded)
>10 Synchronous Gen.
10 to 5 Synchronous Gen.
Less than 5 Synchronous Gen.
>6 Inverters(3)
6 to 3 Inverters(3)
Less than 3 Inverters(3)
• MLGR used for Islanding Analysis (use ratios 50% larger than shown when minimum load characteristics are not well defined or if significant load dropout is a concern during sags.)
>4 4 to 2 Less than 2
Notes: 1. Ratios are meant as guides for radial 4-wire multigrounded neutral distribution system DG applications and are calculated based on aggregate DG on relevant power system sections
2. “Minimum load” is the lowest annual load on the line section of interest (up to the nearest applicable protective device). Presence of power factor correction banks that result in a surplus
of VARs on the “islanded line section of interest” may require slightly higher ratios than shown to be sure overvoltage is sufficiently suppressed.
3. Inverters are inherently weaker sources than rotating machines therefore this is why a smaller ratio is shown for them than rotating machines
4. If DG application falls in this “higher penetration” category it means some system upgrades/adjustments are likely needed to avoid power system issues.
NREL Workshop on High Penetration PV: Defining High Penetration PV – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC
Some Helpful Screening Thresholds the Author Uses in His Studies
Prepared by Nova Energy Specialists, LLC 6
Type of Ratio
What is it useful for? (Note: these ratios are intended for distribution and subtransmission system impacts of DG for the types of impacts described below.)
Suggested Penetration Level Ratios(1)
Very Low Penetration
(Very low probability of any issues)
Moderate Penetration
(Low to minor probability of issues)
Higher Penetration(3) (Increased probability
of serious issues.
Fault Ratio Factor
(ISCUtility/ISCDG)
• Overcurrent device coordination • Overcurrent device ratings >100 100 to 20
Less than 20
Ground Source Impedance
Ratio(2)
• Ground fault desensitization • Overcurrent device coordination
and ratings >100 100 to 20
Less than 20
Stiffness Factor
(ISCUtililty/IRatedDG)
• Voltage Regulation (this ratio is a good indicator of voltage influence. Wind/PV have higher ratios due to their fluctuations. Besides this ratio, may need to check for current reversal at upstream regulator devices.)
>100 PV/Wind
100 to 50 PV/Wind
Less than 50 PV/Wind
> 50 Steady Source
50 to 25 Steady Source
Less than 25 Steady Source
Notes: 1. Ratios are meant as guides for radial 4-wire multigrounded neutral distribution system DG applications and are calculated based on aggregate DG on relevant power system sections
2. Useful when DG or it’s interface transformer provides a ground source contribution. Must include effect of grounding step-up transformer and/or accessory ground banks if present.
3. If DG application falls in this “higher penetration” category it means some system upgrades/adjustments are likely needed to avoid power system issues.
NREL Workshop on High Penetration PV: Defining High Penetration PV – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC
Screening Ratios (Continued)
Prepared by Nova Energy Specialists, LLC 7
NREL Workshop on High Penetration PV: Defining High Penetration PV – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC
What Does it Mean if it Falls Into the Higher Penetration Category?
• If the DG application falls into these higher penetration categories , then a detailed study is generally recommended and may lead to the need for mitigation
Prepared by Nova Energy Specialists, LLC 8
In addition to the ratios discussed in the prior slides, also check for:
• Reverse power flow at any voltage regulator or transformer LTC bank: if present, check compatibility of the controls and settings of regulator controls.
• Check line drop compensation interaction: if employed by any upstream regulator, do a screening calculation of the voltage change seen at the regulator with the R and X impedance settings actually employed at the regulator. Generally, if ΔV < 1% seen by the regulator controller calculated for the full rated power change of DG, then line drop compensation effects and LTC cycling is not usually an issue.
• Capacitor Banks: if significant VAR surplus on a possible islanded area study for potential impact
• Fast Reclosing Dead Times: if less than 5 seconds (especially those less than 2 seconds) consider the danger of reclosing into live island.
Prepared by Nova Energy Specialists, LLC 9
Caveats for Use of the Ratios & Checks
• Ratios we have discussed on preceding slides are only guides for establishing when distribution and subtransmission system effects of DG become “significant” to the point of requiring more detailed studies and/or potential mitigation options.
• They must be applied by knowledgeable engineers that understand the context of the situation and the exceptions where the ratios don’t work
• It requires a lot more than just these slides here to do this topic justice. We have omitted a lot of details due to the short presentation format so this is just meant as a brief illustration of these issues.
NREL Workshop on High Penetration PV: Defining High Penetration PV – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC
Prepared by Nova Energy Specialists, LLC 10
Voltage Regulation & Variation Issues
• Steady State Voltage (ANSI C84.1 voltage limits)
• Voltage Excursions and LTC Cycling
• Voltage Flicker
• Line Drop Compensator Interactions
• Reverse Power Interactions
• Regulation Mode Compatibility Interactions
Prepared by Nova Energy Specialists, LLC 11
High Voltage Caused by Too Much DG at End of Regulation Zone
SUBSTATION
Voltage
Distance
Heavy Load No DG
Heavy Load (DG High Output)
End
ANSI C84.1 Lower Limit (114 volts)
Light Load (DG at High Output) ANSI C84.1 Upper
Limit (126 volts)
CosRSinXIVDG
LTC Large DG exports large amounts of power up feeder
IDG
Feeder (with R and X)
IEEE 1547 trip Limit (132 Volts)
Prepared by Nova Energy Specialists, LLC 12
DG current
at angle
Impact of Distributed Generation on Line Drop Compensation
Vo
ltag
e
Distance
Heavy Load No DG
Heavy Load with DG
End
ANSI C84.1 Lower Limit (114 volts)
Light Load No DG
SUBSTATION LTC
Large DG (many MW)
DG Supports most of feeder load
Exporting DG “shields” the substation LTC controller from seeing the feeder current. The LTC sees less current than there is and does not boost voltage adequately.
CT
Line drop compensator LTC Controller
Prepared by Nova Energy Specialists, LLC 13
ANSI C84.1 Upper Limit (114 volts)
Voltage Regulator Reverse Mode Confused by DG Reverse Power
SUBSTATION LTC
Reverse Power Flow Due to DG
Supplementary Regulator with Bi-
Directional controls
Normally Closed
Recloser
R
R
Normally Open
Recloser
DG
Supplementary regulator senses reverse power and erroneously assumes that auto-loop has operated – it attempts to regulate voltage on the substation side of the supplementary regulator
What happens? Since the feeder is still connected to the substation, the line regulator once it is forced into the reverse mode will be attempting to regulate the front section of the feeder. To do this can cause the supplementary regulator to “runaway” to either its maximum or minimum tap setting to attempt to achieve the desired set voltage. This in turn could cause dangerously high or low voltage on the DG side of the regulator. This occurs because the source on DG side of regulator is voltage following (not aiming to a particular voltage set point) and is weak compared to the substation source.
Prepared by Nova Energy Specialists, LLC 14
Fluctuating Output of a Photovoltaic Power Plant
Prepared by Nova Energy Specialists, LLC 15
1 2 3 4 5 6 7 8 9
Days
CosRSinXIVDG
System Impedance
DG Starting Current and DG Running current
fluctuations DG
ΔIDG
Infinite Source R X
V
Flicker Voltage Example
The GE Flicker Curve
(IEEE Standard 141-1993 and 519-1992) Flicker Screening: Using the voltage drop screening formula to estimate the ΔV for a given DG current change (ΔIDG). Then plot ΔV on the flicker curve using expected time period between fluctuations
Realize that this is a basic screening concept. For situations where there might be more significant dynamic interactions with other loads, or utility system equipment, a dynamic simulation with a program such as EMTP or PSS/E may be required to verify if flicker will be visible.
Prepared by Nova Energy Specialists, LLC 16
A Conservative Quick Screen for PV Flicker (Not as accurate as IEEE 1453 method but easy and quick for PV)
Prepared by Nova Energy Specialists, LLC 17
Pe
rce
nt V
olta
ge
Ch
an
ge
(
V%
)
Adjusted Borderline of Visibility Curves for PV: This
curve used/developed by NES represents a conservative
modification to the regular IEEE flicker visibility curve. This
curve for PV is meant to capture the fact that PV is not
square modulation, and is based on cloud ramping rates,
and possible LTC interactions causing flicker.
IEEE 519-1992 Borderline of Irritation Curve
519 Visibility
Curve x 2.0
519 Irritation
Curve x
1.25X
Adjusted Borderline of Irritation Curve for PV: This curve used/developed by
NES represents a conservative modification to the regular IEEE flicker irritation
curve. This curve for PV is meant to capture the fact that PV is not square
modulation, and is based on cloud ramping rates, and possible LTC interactions
causing flicker.
IEEE 519-1992 Borderline of Visibility Curve
This is the IEEE 519-1992 flicker
curve, but with two new adjusted
curves added by NES to
conservatively approximate PV
flicker thresholds.
While the IEEE 1453 method based
on Pst, Plt is still the most
technically robust approach and
should allow best results in tight
situations, it is the author’s view that
this adjusted IEEE 519-1992 curve
approach shown here can serve as
a cruder but easier alternative
method to facilitate quick screens.
Note that for PV, the regular IEEE
519-1992 curves are generally too
conservative from a flicker visibility
perspective due to the fact that PV
fluctuations are more rounded rather
than square.
PV Flicker Experiences
• Use of IEEE 1453 method is a technically very robust screening methodology for flicker when very accurate threshold levels need to be determined
• However, a suggested modified GE flicker curve can work well for PV as a conservative tool for simple screening when less accuracy is required
• It is the author’s experience that other voltage problems (LTC cycling, ANSI limits, etc.) related to PV become problematic at lower capacity thresholds than flicker – flicker is one of the last concerns to arise
Prepared by Nova Energy Specialists, LLC 18
Some DG Fault Current Issues
• Impact of current on breaker, fuse, recloser, coordination. Affect on directional devices and impedance sensing devices.
• Increase in fault levels (interrupting capacity of breakers on the utility system)
• Nuisance trips due to “backfeed” fault current
• Distribution transformer rupture issues
• Impact on temporary fault clearing/deionization
Prepared by Nova Energy Specialists, LLC 19
Fault Currents of Rotating Machines
Separately-Excited Synchronous Generator
2 to 4 times rated current
Faul
t Cur
rent
Time
Subtransient Period
Envelope
Transient Period
Envelope Steady State Period
Envelope
Faul
t Cur
rent
Time
Subtransient Period
Envelope
Transient Period
Envelope Steady State Period
Envelope
4-10 times rated current
Induction Machine
Current decays to essentially zero
Current Decay Envelope
37%
Transient Time Constant
Time
100%
Fau
lt C
urr
ent
4-10 times rated current
Prepared by Nova Energy Specialists, LLC 20
Pre-fault Fault Current Worst case i
t
Fault Current Contributions of Inverters
Note: The exact nature and duration of the fault contribution from an inverter is much more difficult to predict than a rotating machine. It is a function of the inverter controller design, the thermal protection functions for the IGBT and the depth of voltage sag at the inverter terminals. In the worst case if fault contributions do continue for more than ½ cycle, they are typically no more than 1 to 2 times the inverter steady state current rating.
Best Case: May last only a few milliseconds (less than ½ cycle) for many typical PV, MT and fuel cell inverters
Typical Worst Case: may last for up to the IEEE 1547 limits and be up to 200% of rated current
Irated
Prepared by Nova Energy Specialists, LLC 21
Fault Current Impacts: Nuisance trips, fuse coordination issues, transformer rupture issues, etc.
Recloser B
13.2 kV
115 kV
Recloser A
DG
Adjacent Feeder
Fault Case 1
Fault Contribution from DG Might Trip The Feeder
Breaker and Recloser
(Nuisance trip)
Iutility
IDG
Prepared by Nova Energy Specialists, LLC 22
Fault Case 2
Utilit
y
DG U
tilit
y
DG
Fault Case 3
The good news is that PV is
much less likely than
conventional rotating DG to
cause issues since inverter fault
contributions are smaller! Fault Contribution from DG Might Interfere with Fuse Saving or Exceed
Limits of a Device Transformer Rupture Limits (fault magnitude)
The Author’s Experiences Related to PV Fault Levels
• In doing many projects, I have observed that fault current problems associated with PV in most cases are not an issue due to the low currents injected by the inverter (about 1-2 per unit of rating).
• In general, only the largest PV (or large PV aggregations) can cause enough fault current to even begin to worry current impacts (there are some special exceptions).
• As PV capacity grows on a circuit, voltage problems usually arise well before fault currents become an issue. A circuit without voltage problems is not likely to have fault current problems due to PV.
Prepared by Nova Energy Specialists, LLC 23
Unintentional DG Islanding Issues
Recloser B (Normally Open)
13.2 kV
115 kV
Recloser A
DG
Adjacent Feeder
The recloser has tripped on its first instantaneous shot, now the DG must trip before a fast reclose is attempted by the utility
Islanded Area
• Incidents of energized downed conductors can increase (safety)
• Utility system reclosing into live island may damage switchgear and loads
• Service restoration can be delayed and will become more dangerous for crews
• Islands may not maintain suitable power quality
• Damaging overvoltages can occur during some conditions
Prepared by Nova Energy Specialists, LLC 24
Islanding Protection Methods of DG
Passive Relaying Approach (Voltage and frequency windowing relay functions: 81o, 81u, 27, 59 – if conditions leave window then unit trips)
Active Approach (instability induced voltage or frequency drift coupled and/or actively perturbed system impedance measurement or other active parameter measurement) (UL-1741 utility interactive inverters)
Communication Link Based Approach (use of direct transfer trip [DTT] or other communications means)
Prepared by Nova Energy Specialists, LLC 25
Islanding and PV Inverters
• Inverters typically have very effective active anti-islanding protection.
• Unfortunately, the IEEE 1547 and UL-1741 islanding protection requirements (2 second response time) are not compatible with high speed utility reclosing practices used at many utilities
• If minimum load is nearly matched to generation then provisions such as DTT and/or live line reclose blocking may be needed, especially with high speed reclosing situations.
Prepared by Nova Energy Specialists, LLC 26
Screening for Islanding Issues
Prepared by Nova Energy Specialists, LLC 27
Start
Is the annual minimum load on any
“Islandable” section at least twice the rated DG
capacity?
Is the DG an Inverter Based
Technology Certified Per
UL1741 Non-IslandingTest?
Islanding Protection May Need
Careful Examination and
Possible Enhancement
Islanding Protection is
Adequate
Yes
No
Yes
Yes
No
No Is the reclosing dead time on the “Islandable”
section ≥ 5 seconds?
Is the DG equipped with at least passive relaying-
based islanding protection?
No
Is the mix of (number of and
capacity) inverters and other
converters and capacitors on the
“Islandable” section within
comfortable limits of the UL1741
algorithms?
No
Yes
Yes
Ground Fault Overvoltage
Ground Fault Overvoltage can result in serious damaging overvoltage on the unfaulted phases. It can be up to roughly 1.73 per unit of the pre-fault voltage level.
Neutral
Vcn
Van
Vbn
Before the Fault
Neutral
Voltage Increases on Van, Vbn
Vbn
Van
Vcn
During the Fault
Neutral and earth return path
Phase A
Phase B
Phase C
Source Transformer (output side)
Fault Vbn
Van
Vcn
X1, X2 R1, R2
X0 R0
Voltage swell during ground fault
V(t)
(t)
Prepared by Nova Energy Specialists, LLC 28
X1, X2
X1, X2 R1, R2
R1, R2
IEEE Effective Grounding
• Effective grounding is achieved when the source impedance has the following ratios:
Ro/X1 < 1
Xo/X1 < 3
• Effective grounding limits the L-G voltage on the unfaulted phases to roughly about 1.25-1.35 per unit of nominal during the fault
• With ungrounded source, the voltage could be as high as 1.82 per unit.
ideally grounded system
Vbn
Van
Vcn
Effectively grounded system
Ungrounded system
N
N
N 1.82 VLN
Prepared by Nova Energy Specialists, LLC 29
Voltage
includes 5%
regulation
factor
Generator Step-Up Transformer Grounding Issues
delta Neutral
Neutral
Low Voltage Side
(DG facility)
wye
wye wye
Neutral grounding of
generator on low side of
transformer does not impact
grounding condition on high
side
*IMPORTANT: Generator
neutral must be
connected to the
neutral/ground of the
transformer to establish
zero sequence path to
high side
Neutral wye *neutral is not connected
then the source acts as
an ungrounded source
even though transformer
is grounded-wye to
grounded-wye
Acts as grounded
source feeding out to
system only if
generator neutral is
tied to the transformer
grounded neutral
Acts as ungrounded
source feeding out to
system only if generator
neutral is not connected
to transformer grounded
neutral*
Acts as grounded
source feeding out
to system
C N
A
B
Gen.
C
C N
A
B
Gen.
C
C N
A
B
Gen.
C
Distribution Transformer
wye
High Voltage Side (to Utility Distribution System Primary)
Prepared by Nova Energy Specialists, LLC 30
Generator Step-Up Transformer Grounding Issues – Continued
delta Neutral
Low Voltage Side
(DG facility)
wye
Neutral grounding of
generator on low side of
transformer does not impact
grounding condition on high
side
Acts as ungrounded
source feeding out
to system
C N
A
B
Gen.
C
Distribution Transformer
High Voltage Side (to Utility Distribution System Primary)
delta
Acts as
ungrounded
source feeding out
to system
Neutral grounding of
generator on low side of
transformer does not impact
grounding condition on high
side
C N
A
B
Gen.
C delta
delta wye Neutral grounding at generator
on low side of transformer does
not impact grounding condition
on high side
Acts as
ungrounded
source feeding out
to system
C N
A
B
Gen.
C
Floating Neutral
No connection to
Transformer Neutral
Prepared by Nova Energy Specialists, LLC 31
PV Inverter – Neutral Is Typically Not Effectively Grounded
Prepared by Nova Energy Specialists, LLC 32
Building Neutral
A
A
B
C
Utility Distribution Transformer 480V
277V
Delta
12,470V
Wye
B
C
Wye has high resistance neutral grounding or is essentially ungrounded
Three Phase Inverter with Internal Isolation Transformer all inside an enclosure – a typical arrangement
Safety Ground
Enclosure bond to safety ground
Neutral
Neutral Terminal
Usually bonded to earth ground at main service panel
per NEC but this does not make it effectively
grounded if inverter transformer is not so
Ground Fault Overvoltage Issues
Prepared by Nova Energy Specialists, LLC 33
Need enough load on this island with respect aggregate DG at all connected distribution substations to suppress overvoltage – otherwise special solutions are needed!
12.47 kV Line
DG Site 1
Ground Fault
Feeder Breaker
Utility System Bulk Source
Load Load Load
Need enough load on this island with respect aggregate DG at distribution level to suppress overvoltage – otherwise effective grounding or other solutions are needed!
Transformer Acts as ungrounded source (not effectively grounded)
Substation transformer acts as grounded source with respect to 12.47 feeder suppressing ground fault overvoltage on distribution until feeder breaker opens. But it acts as an ungrounded source when feeding backwards into subtransmission!
Neutral is Ungrounded or High Z Grounded
Transformer acts as ungrounded source or acts as high Z grounded source (if generator neutral is not grounded or high z grounded)
DG Site 2
Subtransmission (46kV)
Subtransmission source transformer acts as grounded source suppressing ground fault overvoltage on subtransmission until subtransmission breaker opens.
Ground Fault
Distribution SubstationDG
DGDistribution Substation
Load
Load
Distribution Substation
Subtransmission Breaker
Solutions to Ground Fault Overvoltage (any one of these alone will work)
• Effectively ground the DG if possible (But be careful since too much effectively grounded DG can desensitize relaying and cause other issues. Also, see note 1 with regard to subtransmission impacts of distribution effective grounding of DG.)
• If DG is not effectively grounded make sure to maintain a minimum load to aggregate generation ratio >5 for rotating DG and >3 for inverter generation
• Don’t separate the feeder from the substation grounding source transformer until sufficient non-effectively grounded DG is “cleared” from the feeder (e.g. use a time coordinated DTT method.)
• Use grounding transformer banks at strategic point(s) on feeder.
Prepared by Nova Energy Specialists, LLC 34
Note 1: On subtransmission since the distribution substations usually feed in through delta (high-side)
windings, effective grounding of DG at the distribution level does not make it effectively grounded with
respect to subtransmission level.
How Load Reduces Ground Fault Overvoltage
Neutral
Vcg
Vag
Vbg
Before the Fault
12.47 kV Feeder
Load
Impedance of DG
Source, its transformer
and connecting leads
Ground Fault (phase C)
Open Breaker Utility Source
Neutral
Voltage Increases on Vag, Vbg
Vbg Vcg=0
During Ground Fault (light load)
Neutral
Voltage does not rise much on Vag, Vbg because the overall size of the triangle has been reduced (phase to phase voltage has dropped)
Vbg
During Ground Fault (heavy load)
X
R
Vag
Vcg=0
Vag
Prepared by Nova Energy Specialists, LLC 35
For inverters the
excessive load will
also trigger fast
shutdown to protect
transistors
Grounding Transformer Impedance Sizing
Prepared by Nova Energy Specialists, LLC 36
1
3
1
0
1
0
pv
groundbank
pv
groundbank
X
R
X
X
IEEE Effective Grounding Definition
7.0
2
1
0
1
0
pv
groundbank
pv
groundbank
X
R
X
X
Engineering Targets to Provide Effective
Grounding with Reasonable Margin Assume inverter X1 is 30% for generic worst case 30% is not the actual impedance since the inverter impedance varies due to controller dynamics and operating state. But 30% is a conservative number that factors worst case conditions whether the inverter is a current controlled or voltage controlled PV source. A higher number can be used for some inverters, but care should be exercised if using a higher value (especially if it exceeds 50%).
Utility
Primary
Feeder
X1PV = 30%
Xt=5%
Utility Source
Grounding
Transformer
Bank
X0groundbank, R0groundbank
Open
Inverter
Ground Transformer Sizing/Rating
• Must be sized such that: – X0/X1 and R0/X1 ratios are
satisfied with some margin (see the targets prior slide)
– Bank must be able to handle fault currents and steady state zero sequence currents without exceeding damage limits
– Bank must not desensitize the utility ground fault relaying or impact ground flow currents too much
– Bank may need alarming or interlock trip of DG if bank trips off.
Prepared by Nova Energy Specialists, LLC 37
Zero Sequence Current Divider
Grounding Transformer Path
Utility Source Path
I0 utility
I0 Total
I0 Ground transformer
Ferroresonance and Load Rejection Overvoltage with DG
Conditions to Avoid: Islanded State (Feeder Breaker open) Generator Rating > minimum load on island Excessive Capacitance on island
Reliable and fast anti-islanding protection that clears DG from line before island forms is a good defense against this type of ferroresonant condition! Reasonably high MLGR avoids it too.
EMTP Simulation of Ferroresonant Overvoltage
Unfaulted Phase Voltage
Load rejection, ground fault and
resonance related overvoltage
Breaker Opens (island forms)
Normal Voltage
Prepared by Nova Energy Specialists, LLC 38
Waveform shown is Rotating
Machine Type Overvoltage
Outcomes of PV Projects (0.1 to 5 MW) the Author Has Been Involved With in Various Locations
Prepared by Nova Energy Specialists, LLC 39
Type of Issue Typical Experience (over 30 projects studied)
Voltage Regulation Interactions
Most have not required changes to the regulator or regulation settings and no special mitigation. A few projects have required regulator setting changes to reduce the chance of LTC cycling or ANSI C84.1 voltage violations. The largest sites studied are considering reactive compensation to mitigate LTC cycling and voltage variations.
Fault Current Interactions
No sites except one caused enough additional fault current to impact coordination or device ratings in a significant manner.
Islanding Interactions
For islanding protection, roughly 1/3rd of the sites have required something special beyond the standard UL-1741 inverter with default settings. Some required more sensitive inverter settings or adjustments to utility reclosing dead time. A few have needed a radio based or hardwired DTT and/or live line reclose blocking added.
Ground Fault Overvoltage
About 1/3rd of the sites need some form of mitigation – usually a grounding transformer bank, a grounded inverter interface, or a time coordinated DTT
Harmonics No sites have required any special provisions for harmonics yet
Other Some sites are considering operating in power factor mode producing VARs to provide reactive power support. One site had a capacitor concern.
Conclusions
• PV and other types of DG today are being successfully interconnected on distribution feeders all over the country. In many cases the impacts are not enough to cause worrisome effects.
• However, the size of projects is growing, especially now that many large commercial and FIT type projects are being considered at the distribution level. Also, the ongoing aggregation effects as PV becomes more widely adopted is leading to more substantial impacts.
• Many projects can still be screened using simple methods, but increasingly, more detailed analytical methods are becoming necessary.
Prepared by Nova Energy Specialists, LLC 40
Conclusions (continued)
• The “relative size” of the PV (or DG) compared to the power system to which it is connected plays the key role in system impact effects. Key factors that gauge the relative size include:
– The MLGR, FRF (SCCR), Stiffness Factor, and GSIR
– The ratios will usually need to be gauged based on aggregate DG in a zone or region of concern
• The settings of utility voltage regulation equipment and feeder overcurrent devices and system designs also play a key role.
• The “absolute size” and “project class” (e.g. FIT, net metered) play a role only in that this impacts the scope and criticality of the project and may trigger certain regulatory requirements.
Prepared by Nova Energy Specialists, LLC 41