extcat-fm200!

15
Page 14 tyco Fire & Security Tyco Electronic Product Group Product Code 300.205.001 FM200 FM200 Equipment & Components - Standard Agent FM200 systems are configured around a range of containers specifically charged with the appropriate quantity of FM200. Containers are manufactured to meet the requirements of British, European or US D.O.T. standards as follows: Applicable Standards BS5045 Part 2 - Welded EEC/84/525 - Seamless EEC/84/527 - Welded DOT 4BW 500/DOT 4BW (HSE) 34.5 - Welded * Containers manufactured to BS5045 Part 2 will be supplied if available. Where these are not available an alternative (EEC or DOT) will be supplied as appropriate. FM200 Containers - LPCB Approved FM200 (HFC 227ea) is known chemically as Heptafluoropropane. FM200 is a colourless gas which is liquified under pressure for storage. Like Halon 1301 it has a low toxicity level and is super- pressurised with Nitrogen to 24.8bar (360psi). It rapidly extinguishes most commonly found fires through a combination of chemical and physical mechanisms. FM200 contains no bromine or chlorine and therefore has zero Ozone Depleting Potential (ODP). The atmospheric lifetime of FM200 is between 31 and 42 years which along with its’ ODP presents a long term solution to fire protection requirements. FM200 has been found to be less toxic than Halon 1301, which makes it safe for use in the fully automatic mode in occupied areas. Typically FM200 requires a design concentration of 7.5%, which is well below the 9% No Observable Adverse Effect Level (NOAEL). The NOAEL for Halon 1301 is only 5% (the same as the design concentration). Container Dia (mm) Ht to Valve Outlet Tare Weight Max FM200 Size (l) (A) (mm) (B) (Kg) Weight (Kg) 6.5 (BS) 222 300 9 6.5 6.5 (EC) 222 335 9 6.5 8 254 304 15 8 13 (BS) 222 495 12 13 13 (EC) 222 520 12 13 16 254 502 19 16 25.5 (BS/EC) 222 830 17 25.5 32 254 833 26 32 40 267 975 65 40 52 (BS) 406 580 49 52 52 (EC) 406 605 49 52 52 (DOT) 406 595 49 52 80 267 1785 108 80 106 (BS) 406 1021 72 106 106 (EC) 406 1040 72 106 106 (DOT) 406 1020 72 106 147 (BS) 406 1354 90 147 147 (EC) 406 1370 90 147 147 (DOT) 406 1360 90 147 180 (BS) 406 1634 106 180 180 (DOT) 406 1640 106 180 All dimensions/tare weights are approximate due to manufacturing tolerances FM200 Container Assembly Container Size Diameter BS5045 Pt.2* EEC/84/525 EEC/84/527 DOT 6.5 Litre 222 mm 303.205.001 n/a 303.205.009 n/a 8 Litre 254 mm n/a n/a n/a 303.205.015 13 Litre 222 mm 303.205.002 n/a 303.205.010 n/a 16 Litre 254 mm n/a n/a n/a 303.205.016 25.5 Litre 222 mm 303.205.003 n/a 303.205.011 n/a 32 Litre 254 mm n/a n/a n/a 303.205.017 40 Litre 267 mm n/a 303.205.025 n/a n/a 52 Litre 406 mm 303.205.004 n/a 303.205.012 303.205.018 80 Litre 267 mm n/a 303.205.024 n/a n/a 106 Litre 406 mm 303.205.005 n/a 303.205.013 303.205.019 147 Litre 406 mm 303.205.006 n/a 303.205.014 303.205.020 180 Litre 406 mm 303.205.007 n/a n/a 303.205.021 FM200 Container Label

Upload: asifaliabid

Post on 09-Nov-2015

212 views

Category:

Documents


55 download

DESCRIPTION

fm 200

TRANSCRIPT

  • Page 14

    tyco Fire &Security

    Tyco ElectronicProduct Group

    Product Code300.205.001FM200

    FM200 Equipment & Components - Standard

    Agent

    FM200 systems are configured around a range ofcontainers specifically charged with theappropriate quantity of FM200. Containers aremanufactured to meet the requirements of British,European or US D.O.T. standards as follows:Applicable StandardsBS5045 Part 2 - WeldedEEC/84/525 - SeamlessEEC/84/527 - WeldedDOT 4BW 500/DOT 4BW (HSE) 34.5 - Welded

    * Containers manufactured to BS5045 Part 2 willbe supplied if available. Where these are notavailable an alternative (EEC or DOT) will besupplied as appropriate.

    FM200 Containers - LPCB Approved

    FM200 (HFC 227ea) is known chemically asHeptafluoropropane. FM200 is a colourless gaswhich is liquified under pressure for storage. LikeHalon 1301 it has a low toxicity level and is super-pressurised with Nitrogen to 24.8bar (360psi). Itrapidly extinguishes most commonly found firesthrough a combination of chemical and physicalmechanisms.

    FM200 contains no bromine or chlorine andtherefore has zero Ozone Depleting Potential(ODP). The atmospheric lifetime of FM200 isbetween 31 and 42 years which along with itsODP presents a long term solution to fireprotection requirements.FM200 has been found to be less toxic than Halon1301, which makes it safe for use in the fullyautomatic mode in occupied areas.

    Typically FM200 requires a design concentrationof 7.5%, which is well below the 9% NoObservable Adverse Effect Level (NOAEL). TheNOAEL for Halon 1301 is only 5% (the same asthe design concentration).

    Container Dia (mm) Ht to Valve Outlet Tare Weight Max FM200Size (l) (A) (mm) (B) (Kg) Weight (Kg)6.5 (BS) 222 300 9 6.56.5 (EC) 222 335 9 6.58 254 304 15 813 (BS) 222 495 12 1313 (EC) 222 520 12 1316 254 502 19 1625.5 (BS/EC) 222 830 17 25.532 254 833 26 3240 267 975 65 4052 (BS) 406 580 49 5252 (EC) 406 605 49 5252 (DOT) 406 595 49 5280 267 1785 108 80106 (BS) 406 1021 72 106106 (EC) 406 1040 72 106106 (DOT) 406 1020 72 106147 (BS) 406 1354 90 147147 (EC) 406 1370 90 147147 (DOT) 406 1360 90 147180 (BS) 406 1634 106 180180 (DOT) 406 1640 106 180

    All dimensions/tare weights are approximate due to manufacturing tolerances

    FM200 Container Assembly

    Container Size Diameter BS5045 Pt.2* EEC/84/525 EEC/84/527 DOT6.5 Litre 222 mm 303.205.001 n/a 303.205.009 n/a8 Litre 254 mm n/a n/a n/a 303.205.01513 Litre 222 mm 303.205.002 n/a 303.205.010 n/a16 Litre 254 mm n/a n/a n/a 303.205.01625.5 Litre 222 mm 303.205.003 n/a 303.205.011 n/a32 Litre 254 mm n/a n/a n/a 303.205.01740 Litre 267 mm n/a 303.205.025 n/a n/a52 Litre 406 mm 303.205.004 n/a 303.205.012 303.205.01880 Litre 267 mm n/a 303.205.024 n/a n/a106 Litre 406 mm 303.205.005 n/a 303.205.013 303.205.019147 Litre 406 mm 303.205.006 n/a 303.205.014 303.205.020180 Litre 406 mm 303.205.007 n/a n/a 303.205.021

    FM200 Container Label

    ext2.qxd 13/02/01 17:01 Page 14

  • Page 15

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The solenoid actuator is used to electricallyoperate the container valve and is operated at24Vd.c. (Power Consumption - 4.8 Watts).It is fitted directly onto the top of the containervalve by means of a knurled swivel couplingwhich enables the unit to be positioned aspreferred for electrical connection.When fitting it is only necessary for the unit to behand tight.The solenoid actuator is normally fitted to thecontainer designated as the Master. Theactuator is an electro-mechanical device whichwhen energised causes the central pin to move

    downwards opening the schrader valve in thecontainer valve.The central pin must be in the retracted positionbefore the solenoid actuator is fitted, otherwisethe container valve will be operated and thecontents discharged.The power lead fitted with a DIN plug forconnecting to the solenoid is to be orderedseparately (P/C 304.001.001).

    Product Code304.205.00124V Solenoid actuator

    Solenoid Actuator - Standard

    The Flameproof solenoid actuator is BASEEFAapproved to Ex d IIB requirements and isoperated at 24Vd.c. (Power Consumption - 11.2Watts).The CENELEC/BASEEFA Approved Explosionproof version is available to order to meet EEx dIIC requirements.The solenoid actuator is fitted to a schraderassembly on the side of the valve body by meansof a brass swivel nut. It is designed to beremovable from the schrader assembly. As therewill be pressure in the brass swivel nut, uponremoval of the solenoid the pressure will bereleased. A pop will be heard at the time ofremoval. It is essential that the schrader assembly

    is not dislodged or removed as this will cause animmediate and potentially hazardous discharge ofFM200. It is recommended that at the time ofremoval all slave containers are disconnectedfrom the Master.NOTE: Earlier versions of this actuator were notdesigned to be removable from the containervalve and no attempt must be made to do sowhilst the container is pressurised, otherwise thiswill result in immediate and potentially hazardousdischarge of FM200.

    Product Code304.205.00224V Solenoid actuator (BASEEFA)

    Solenoid Actuator - Flameproof

    The local manual actuator is used to mechanicallyoperate the system at the container position.When fitting it is only necessary for the unit to behand-tight.Accidental manual release is prevented by meansof a steel safety pin. The steel safety pin must beremoved to allow the use of the local manualactuator.After removing the safety pin, manual operation iscaused by depressing the strike knob.

    The unit is designed so that it may be fitteddirectly onto the top of the container

    Product Code304.205.003Local manual actuator

    Local Manual Actuator

    Product Code304.001.001Solenoid lead

    FM200 Solenoid Lead

    Union AdaptorThe union adaptor is used to enable pipework tobe easily connected to and disconnected fromthe FM200 container valve outlet adaptor. It isavailable in two sizes, 25mm and 50mm.One end is provided with a parallel female threadto provide a compatible joint to the containeroutlet adaptor. The other end is provided with afemale NPT thread to enable pipework to beconnected. A swivel joint makes disconnecting

    containers from the pipework straightforward.It is recommended that the joint to the containervalve adaptor is made using PTFE tape.

    Product Codes309.002.01125mm (1) Union adaptor309.002.01250mm (2) Union adaptor

    The pneumatic actuator is used where containeroperation is required by means of gas pressurefrom the system master container, remote manualrelease unit or from a pilot container. When fittingit is only necessary for the unit to be hand tight.The unit is designed so that it may be fitteddirectly onto the top of the container valve or beused in conjunction with a solenoid actuator, inwhich case it fits directly on top of the solenoidactuator.

    A minimum pressure of 4 bar is required toensure satisfactory operation.Connection to the actuator is 1/4 B.S.P.

    Product Code304.205.004Pneumatic actuator

    Pneumatic Actuator

    ext2.qxd 13/02/01 17:02 Page 15

  • Page 16

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The Pressure Switch is normally mounted on aconnection in the pneumatic actuation tubing andmay be used to provide an electrical indication ofrelease of FM200 or to perform ventilation shut-downs or other interlock functions.The pressure switch requires to be manually resetfollowing operation.A minimum pressure of 3 bar is required toensure satisfactory operation. Connection to thepressure switch may be either 1/2 NPT (male) or1/8 NPT (female).

    Product Code305.205.002Gas released pressure switch

    Pressure Switch - Standard

    The Flameproof Pressure Switch is BASEEFAApproved to meet Ex d IIB requirements.The Pressure Switch requires to be manuallyreset following operation.A minimum pressure of 2 bar is required toensure satisfactory operation. Connection to thepressure switch is 1/4 NPT (female).A CENELEC/BASEEFA approved explosion proofversion is available to order to meet EEx d IICrequirements.

    Product Code305.205.003Gas released pressure switch (BASEEFA)

    Pressure Switch - Flameproof

    The Supervisory Pressure Switch is an optionalitem that is factory fitted at the time of order andis used to continuously monitor the containerpressure.In the event of the container pressure fallingbelow 18 bar the switch will operate to provide anelectrical signal.The operating pressure is factory set and noadjustments may be carries out on site.

    Product Code305.205.001Supervisory pressure switch

    Supervisory Pressure Switch

    The T528 Manual Release Unit is used whereremote mechanical manual release of the FM200system is required.The unit comprises of a box with a hinged yellowlid which is held in the closed position by twofrangible washers. Inside the unit is a red barwhich is to be connected to a wire rope runthrough a system of conduit and corner pulleys tothe Remote Manual Actuator.Operation of the FM200 system using the T528 isa two stage action. Firstly the hinged lid is pulleddownwards towards the operator. This action willbreak the frangible washers and expose the redoperating bar. System operation is caused bypulling hard on the red bar. System discharge willoccur immediately.

    Technical SpecificationNet Weight: 0.9Kg

    Product Code526.001.018T528 Mechanical manual release unit

    T528 Manual Release Unit

    The Remote Manual Actuator may be used tooperate the FM200 container from a remoteposition using the T528 mechanical manualrelease unit which is connected to the remotemanual actuator by wire rope run in conduit.A shear strap is fitted to help guard againstaccidental release. Operation is caused bymoving the lever through 90o, which will break theshear strap. The steel safety pin will preventoperation and is to be removed uponcommissioning of the system.

    A pneumatic actuation port is provided to allowthe unit to double as a manual and pneumaticactuator.The unit is designed so that it may be fitteddirectly onto the top of the container valve or beused in conjunction with a solenoid actuator, inwhich case it fits directly on top of the solenoidactuator. When fitting it is only necessary for theswivel nut to be hand tightened.Product Code304.205.005Remote manual actuator (mechanical)

    Remote Manual Actuator (Mechanical)

    ext2.qxd 13/02/01 17:02 Page 16

  • Page 17

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The Discharge Nozzles are available in a 180o and360o pattern and are designed to uniformlydistribute FM200 throughout the hazard area. The 180o type has seven ports and the 360o typehas eight ports.For Pre-Engineered systems the nozzles areavailable pre-drilled in three sizes.Engineered nozzles are available in seven sizesand are drilled with the specific designrequirement.

    Where the size of any hazard enclosuredetermines that one nozzle does not providesufficient coverage the hazard should betheoretically sub divided into appropriately sizedmodules.Nozzles are provided in aluminium as standard,but are available in brass or stainless steel toorder.

    FM200 Nozzles - Engineered: Aluminium

    NOZZLE TYPE PRODUCT CODEPre-Engineered Engineered

    10mm (180o) Not Available 310.205.02215mm (180o) Not Available 310.205.01120mm (180o) Not Available 310.205.02425mm (180o) 310.205.001 310.205.01232mm (180o) Not Available 310.205.02640mm (180o) 310.205.003 310.205.01350mm (180o) 310.205.005 310.205.01410mm (360o) Not Available 310.205.02315mm (360o) Not Available 310.205.01520mm (360o) Not Available 310.205.02525mm (360o) 310.205.002 310.205.01632mm (360o) Not Available 310.205.02740mm (360o) 310.205.004 310.205.01750mm (360o) 310.205.006 310.205.018

    180o Nozzle

    360o Nozzle

    9 metres

    9 metres

    Nozzle Coverage

    Thread Size 10mm NPT 15mm NPT 20mm NPT 25mm NPT 32mm NPT 40mm NPT 50mm NPTA 25.0mm 29.0mm 35.0mm 41.0mm 50.0mm 60.0mm 76.0mmB 33.5mm 41.0mm 47.0mm 52.0mm 62.0mm 68.0mm 89.0mm

    Discharge Nozzles

    A BASEEFA Approved Supervisory PressureSwitch (P/C 305.205.004) is available to meet theEx d IIB requirements.A CENELEC/BASEEFA Approved explosion proofversion is available to order to meet EEx d IICrequirements.Both the Flameproof and Explosion proofversions are variations on the Flameproof andExplosion proof gas discharged pressureswitches.It is recommended that the Flameproof andExplosion proof switches are wall mountedadjacent to the container.Connection to the switch is 1/4 NPT (female).

    To fit the Flameproof or Explosion proof switchrequires connecting pneumatic actuation tubingbetween the supervisory pressure switch port onthe valve and the supervisory pressure switch.This process involves removing the plug from thesupervisory pressure switch port in the valve andquickly connecting the actuation tubing. Uponremoval of the plug it is normal for a smallquantity of gas to leak. It is critical that allconnections are gas tight otherwise the containerwill gradually lose its charge.Product Code305.205.004Supervisory pressure switch (BASEEFA)

    Supervisory Pressure Switch - BASEEFA/CENELEC

    The Container Brackets are designed to securelyfix a single container to a wall or supportingstructure.The brackets are of a design that allows them tobe wall mounted. They comprise of a steelcruciform section which is fixed to the wall orsupporting structure and a steel strap used tofirmly secure the container to the bracket. A lug atthe bottom of the vertical back section is used tosupport the weight of the container. The strap isfixed around the container to the horizontal backsection using nuts and bolts.

    Product Codes311.205.0016.5 litre container bracket assembly311.205.00213 litre container bracket assembly311.205.00325.5 litre container bracket assembly

    FM200 Container Brackets (Welded Containers) - 6.5/13/25.5 Litre

    SEE DETAIL A

    DETAIL A

    PRESENT ONLYON BRACKETASSEMBLY311.205.003 HOLE DIA 11.5 (TYP)

    6.5/13/25.5 LITRE CONTAINER BRACKET

    PRODUCT CODE DIM A311.205.001 172311.205.002 375311.205.003 715

    ext2.qxd 13/02/01 17:04 Page 17

  • Page 18

    tyco Fire &Security

    Tyco ElectronicProduct Group

    Manifolds are designed to enable all thecontainers in a row to be connected to thesupply pipe and may be used in multi containerapplications or in main and reserve systems.All manifolds are pressure tested at the works to90 bar.All Product Code Numbers include the manifoldand Check Valves.

    ManifoldsType Product Code

    65mm x 2 port 307.205.01265mm x 3 port 307.205.01365mm x 4 port 307.205.01480mm x 2 port 307.205.00180mm x 3 port 307.205.00280mm x 4 port 307.205.00380mm x 5 port 307.205.011

    100mm x 2 port 307.205.004100mm x 3 port 307.205.005100mm x 4 port 307.205.006100mm x 5 port 307.205.007100mm x 6 port 307.205.008150mm x 3 port 307.205.009150mm x 4 port 307.205.010150mm x 5 port 307.205.015150mm x 6 port 307.205.016150mm x 7 port 307.205.017150mm x 8 port 307.205.018150mm x 9 port 307.205.019150mm x 10 port 307.205.020

    The Container Brackets are designed to securelyfix a single container to a wall or supportingstructure. The containers are to be floor mountedonly.The bracket assembly comprises a steel strap,steel channel section and two spring nuts andbolts.Product Code311.205.00452-180 litre container bracket assembly

    FM200 Container Brackets (Welded Containers) - 52/106/147/180 Litre

    52/106/147/180 LITRE CONTAINER BRACKET

    The container brackets are designed to securelyfix a single container to a wall or supportingstructure. The containers are to be floor mountedonly.The bracket assembly comprises two steel straps,steel channel section (400mm long) and nut andbolt.

    Product Code311.205.013Container brackets 8/16/32 litre containers

    FM200 Container Brackets (Welded Containers) - 8/16/32 Litre

    The bracket is designed to securely fix containersto a wall or supporting structure. It comprises of asection of steel channel and a universal clamp.The steel channel sections are fixed securely tothe wall or supporting structure. The universalclamp has a special slotted section which allowseach half to be fitted into the steel channel. Thetwo halves are clamped together in positionaround the container using a nut and bolt.

    Product CodesSL 93841Container strap - 267mmSL 93852Single container wall rack

    FM200 Container Brackets (Seamless Containers)

    210

    Manifold

    65/80/100mm NPT (both ends)

    50mm Check Valve

    ext2.qxd 13/02/01 17:04 Page 18

  • Page 19

    tyco Fire &Security

    Tyco ElectronicProduct Group

    Product Codes308.002.0016mm Kunifer tube308.002.0026mm Half hard copper tube309.010.0026mm x 1/8 NPT stud coupling309.010.0036mm x 1/4 NPT stud coupling309.011.0016mm Straight coupling309.013.0016mm Equal tee

    FM200 Actuation Ancillaries

    308.002.001

    309.013.001

    309.010.002

    309.010.003

    309.011.001

    The Door Caution Plate (no lock-off) providesinstructions to personnel who may enter an areaprotected with FM200.This version of the caution plate is used when it ispermitted to leave the system on automaticcontrol even while the area is occupied.One plate is to be fixed to all entrance doors intoan FM200 protected area.Four 4mm fixing holes are provided.

    Technical SpecificationDimensions: 210 x 210 mm

    Product Code314.205.002Door caution plate (no lock off)

    Door Caution Plate - No Lock-Off

    The Manual Release Caution Plate providesinstructions to personnel on the use of manualcontrols.One plate is to be fixed adjacent to all positionsfrom where FM200 can be released manually.Four 4mm fixing holes are provided.Technical SpecificationDimensions: 210 x 75 mm

    Product Code314.205.003Manual release plate

    Manual Release Caution Plate

    The Door Caution Plate (lock-off) providesinstructions to personnel who may enter an areaprotected with FM200.This version of the caution plate is used when it isnecessary to instruct personnel to place thesystem on manual control before entering theprotected area.One plate is to be fixed to all entrance doors intoan FM200 protected area.Four 4mm fixing holes are provided.

    Technical SpecificationDimensions: 210 x 210 mm

    Product Code314.205.001Door caution plate (lock off)

    Door Caution Plate - Lock Off

    The flexible Discharge Hose connects thecontainer to the check valve on the manifold.A swivel fitting at the end of the hose allows easeof installation.NOTE: The purpose of the 32mm hose is toprevent excessive pressure loss experiencedwhen using a 25mm hose from the 25mm FM200container valve. Connection to the 25mmcontainer valve is by means of a 32mm x 25mmadaptor included as part of the 32mm hoseassembly.

    Product Codes306.205.00132mm flexible discharge hose306.205.00250mm flexible discharge hose

    Discharge Hoses

    Manifold support brackets are designed toprovide a firm fixing of the manifold to a wall orsupporting structure. Two brackets are requiredfor each manifold used.

    Product Codes311.205.01565mm Manifold support bracket311.205.01080mm Manifold support bracket

    311.205.011100mm Manifold support bracket311.205.012150mm Manifold support bracket

    FM200 Manifold Support Brackets

    ext2.qxd 13/02/01 17:05 Page 19

  • Page 20

    tyco Fire &Security

    Tyco ElectronicProduct Group

    Typical Container Arrangement

    KITS - Master Containers (Solenoid Operated)In order to assist in the ordering of correctcomponents to form the FM200 system a numberof kits are available to cover the most popularrange of containers.Each kit comprises the FM200 container, bracket,

    solenoid, solenoid lead, manual actuator,pressure switch, actuation tubing/fittings andmanual caution plate.The kit excludes items which are specific to aindividual enclosure such as FM200, supervisory

    pressure switches, door caution plates, nozzles,pipework, fittings, fixings and any special itemssuch as distribution valves.

    KITS - Slave Containers (Pneumatically Operated)Each kit comprises the FM200 container, bracket,pneumatic actuator and actuation tubing/fittingsand manual caution plate.The kit excludes items which are specific to anindividual enclosure such as FM200, supervisory

    pressure switches, door caution plates, nozzles,pipework, fittings, fixings and any special itemssuch as distribution valves.

    Description Kit No. Weight6.5 Litre Solenoid operated container assy 901.505.048 13 Kgs13 Litre Solenoid operated container assy 901.505.049 16 Kgs25.5 Litre Solenoid operated container assy 901.505.050 22 Kgs52 Litre Solenoid operated container assy 901.505.051 48 Kgs106 Litre Solenoid operated container assy 901.505.052 69 Kgs147 Litre Solenoid operated container assy 901.505.053 84 Kgs180 Litre Solenoid operated container assy 901.505.054 98 Kgs

    KITS - Master Containers (Solenoid Operated)

    Description Kit No. Weight6.5 Litre Pneumatically operated container assy 901.505.041 10 Kgs13 Litre Pneumatically operated container assy 901.505.042 14 Kgs25.5 Litre Pneumatically operated container assy 901.505.043 19 Kgs52 Litre Pneumatically operated container assy 901.505.044 46 Kgs106 Litre Pneumatically operated container assy 901.505.045 67 Kgs147 Litre Pneumatically operated container assy 901.505.046 82 Kgs180 Litre Pneumatically operated container assy 901.505.047 96 Kgs

    KITS - Master Containers (Solenoid Operated)

    Reference Description1 FM200 Container Assembly2 Container Bracket3 Container Nameplate4 Pressure Gauge5 Solenoid Actuator6 Local Manual Actuator6a Safety Pin7 Supervisory Pressure Switch*8 Pneumatic Actuator9 Pressure Switch10 Discharge Nozzle11 Manual Release Caution Plate12 Container Design Details13 Discharge Pipework14 Pneumatic Actuation Tubing15 Junction Box

    * Optional or variable equipment - not included inthe standard kits.

    ext2.qxd 13/02/01 17:05 Page 20

  • The solenoid actuator is fitted to a schraderassembly on the side of the valve body by meansof a brass swivel nut. It is designed to beremovable from the schrader assembly. As therewill be pressure in the brass swivel nut, uponremoval of the solenoid the pressure will bereleased. A pop will be heard at the time ofremoval. It is essential that the schrader assemblyis not dislodged or removed as this will cause animmediate and potentially hazardous discharge ofFM200.

    Product Code304.205.00824V Solenoid actuator (side mounted)

    Solenoid Actuator - Side Mounted (UL)

    Page 21

    tyco Fire &Security

    Tyco ElectronicProduct Group

    Product Code300.205.001FM200

    FM200 Equipment & Components - UL ListedAgent

    Systems are configured around a range ofcontainers specifically charged with theappropriate quantity of FM200. Containers aremanufactured to meet the requirements ofDOT4BW500 / DOT4BW(HSE)34.5.

    Product Codes303.205.0158 Litre container assembly303.205.01616 Litre container assembly303.205.01732 Litre container assembly303.205.01852 Litre container assembly303.205.019106 Litre container assembly

    303.205.020147 Litre container assembly303.205.021180 Litre container assembly

    FM200 Containers - Dot (UL)

    The solenoid actuator is used to electricallyoperate the container valve. The solenoid isoperated at 24Vd.c. (Power Consumption - 4.8Watts).It is fitted directly onto the top of the containervalve by means of a knurled swivel couplingwhich enables the unit to be positioned aspreferred for electrical connection.When fitting it is only necessary for the unit to behand tight.The solenoid actuator is normally fitted to thecontainer designated as the Master. Theactuator is an electro-mechanical device which

    when energised causes the central pin to movedownwards opening the schrader valve in thecontainer valve.The central pin must be in the retracted positionbefore the solenoid actuator is fitted, otherwisethe container valve will be operated and thecontents discharged.The power lead fitted with a DIN plug forconnecting to the solenoid is to be orderedseparately (P/C 304.001.001).Product Code304.205.00824V Solenoid actuator

    Solenoid Actuator - Stackable (UL)

    The local manual actuator is used to mechanicallyoperate the system at the container position.When fitting it is only necessary for the unit to behand-tight.Accidental manual release is prevented by meansof a steel safety pin. The steel safety pin must beremoved to allow the use of the local manualactuator.After removing the safety pin, manual operation iscaused by depressing the strike knob.The unit is designed so that it may be fitteddirectly onto the top of the container

    Product Code304.205.003Local manual actuator

    Local Manual Actuator

    Label fitted to containers on UL listed systems

    ext2.qxd 13/02/01 17:06 Page 21

  • Page 22

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The container brackets are designed to securelyfix a single container to a wall or supportingstructure. The containers are to be floor mountedonly.The bracket assembly comprises two steel straps,steel channel section (400mm long) and nut andbolt.

    Product Codes311.205.0138-32 litre Container bracket assembly311.205.01452-180 litre Container bracket assembly

    FM200 Container Brackets (UL)

    Product Codes306.205.003Flexible pilot hose 1/4 BSP swivel female309.013.003Male tee 1/4 BSPP x 1/4 BSPT309.013.004Male elbow 1/4 BSPT x 1/4 BSPP309.013.0051/4 BSPT x 1/4 BSPP adaptor

    FM200 Actuation Ancillary (UL)

    The Supervisory Pressure Switch is an optionalitem that is Factory fitted at the time of order andis used to continuously monitor the containerpressure.In the event of the container pressure fallingbelow 18 bar the switch will operate to provide anelectrical signal.The operating pressure is factory set and noadjustments may be carries out on site.

    Product Code305.205.006Supervisory pressure switch

    Supervisory Pressure Switch (UL)

    The pneumatic actuator is used where containeroperation is required by means of gas pressurefrom the system master container, remote manualrelease unit or from a pilot container. When fittingit is only necessary for the unit to be hand tight.The unit is designed so that it may be fitteddirectly onto the top of the container valve or beused in conjunction with a solenoid actuator, inwhich case it fits directly on top of the solenoidactuator.A minimum pressure of 4 bar is required toensure satisfactory operation.Connection to the actuator is 1/4 B.S.P.

    Product Code304.205.004Pneumatic actuator

    Solenoid Actuator - Pneumatic Actuator (UL)

    309.013.005

    309.013.003309.013.004

    306.205.003

    The Pressure Switch is normally mounted on aconnection in the pneumatic actuation tubing andmay be used to provide an electrical indication ofrelease of FM200 or to perform ventilation shut-downs or other interlock functions.The pressure switch requires to be manually resetfollowing operation.A minimum pressure of 3 bar is required toensure satisfactory operation. Connection to thepressure switch may be either 1/2 NPT (male) or1/8 NPT (female).

    Product Code305.205.007Gas released pressure switch

    Gas Released Pressure Switch (UL)

    ext2.qxd 13/02/01 17:07 Page 22

  • Page 23

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The Discharge Nozzles are available in a 180o and360o pattern and are designed to uniformlydistribute FM200 throughout the hazard area. The 180o type has seven ports and the 360o typehas eight ports.Nozzles are available in seven sizes and aredrilled with the specific design requirement. Where the size of any hazard enclosuredetermines that one nozzle does not providesufficient coverage the hazard should betheoretically sub divided into appropriately sizedmodules.Nozzles are provided in brass as standard, butare available in stainless steel to order.

    Product Codes310.205.02810mm x 180/360 Degree (state which)310.205.02915mm x 180/360 Degree (state which)310.205.03020mm x 180/360 Degree (state which)310.205.03125mm x 180/360 Degree (state which)310.205.03232mm x 180/360 Degree (state which)310.205.03340mm x 180/360 Degree (state which)310.205.03450mm x 180/360 Degree (state which)

    FM200 Nozzles: Engineered: Brass (UL)

    FM200 Manifolds (UL)

    The flexible Discharge Hose connects thecontainer to the check valve on the manifold.A swivel fitting at the end of the hose allows easeof installation.NOTE: The purpose of the 32mm hose is toprevent excessive pressure loss experiencedwhen using a 25mm hose from the 25mm FM200container valve. Connection to the 25mmcontainer valve is by means of a 32mm x 25mmadaptor included as part of the 32mm hoseassembly.

    Product Codes306.205.00132mm Flexible discharge hose306.205.00250mm Flexible discharge hose

    Discharge Hoses

    FM200 Manifold Support Brackets

    Manifolds are designed to enable all thecontainers in a row to be connected to thesupply pipe and may be used in multi containerapplications or in main and reserve systems.All manifolds are pressure tested at the works to90 bar.All Product Code Numbers include the manifoldand Check Valves.

    Type Product Code65mm x 2 port 307.205.01265mm x 3 port 307.205.01365mm x 4 port 307.205.01480mm x 2 port 307.205.00180mm x 3 port 307.205.00280mm x 4 port 307.205.00380mm x 5 port 307.205.011100mm x 2 port 307.205.004100mm x 3 port 307.205.005100mm x 4 port 307.205.006100mm x 5 port 307.205.007100mm x 6 port 307.205.008150mm x 3 port 307.205.009150mm x 4 port 307.205.010150mm x 5 port 307.205.015150mm x 6 port 307.205.016150mm x 7 port 307.205.017150mm x 8 port 307.205.018150mm x 9 port 307.205.019150mm x 10 port 307.205.020

    Manifold

    65/80/100mm NPT (both ends)

    50mm Check Valve

    Manifold support brackets are designed toprovide a firm fixing of the manifold to a wall orsupporting structure. Two brackets are requiredfor each manifold used.

    Product Codes311.205.01565mm Manifold support bracket311.205.01080mm Manifold support bracket

    311.205.011100mm Manifold support bracket311.205.012150mm Manifold support bracket

    ext2.qxd 13/02/01 17:07 Page 23

  • Page 24

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The Door Caution Plate (no lock-off) providesinstructions to personnel who may enter an areaprotected with FM200.This version of the caution plate is used when it ispermitted to leave the system on automaticcontrol even while the area is occupied.One plate is to be fixed to all entrance doors intoan FM200 protected area.Four 4mm fixing holes are provided.Technical SpecificationDimensions: 210 x 210 mm

    Product Code314.205.002Door caution plate (no lock off)

    FM200 Door Caution Plate - No Lock-Off (UL)

    The Door Caution Plate (lock-off) providesinstructions to personnel who may enter an areaprotected with FM200.This version of the caution plate is used when it isnecessary to instruct personnel to place thesystem on manual control before entering theprotected area.One plate is to be fixed to all entrance doors intoan FM200 protected area.Four 4mm fixing holes are provided.Technical SpecificationDimensions: 210 x 210 mm

    Product Code314.205.001Door caution plate (lock off)

    FM200 Door Caution Plate - Lock Off (UL)

    The Manual Release Caution Plate providesinstructions to personnel on the use of manualcontrols.One plate is to be fixed adjacent to all positionsfrom where FM200 can be released manually.Four 4mm fixing holes are provided.Technical SpecificationDimensions: 210 x 75 mm

    Product Code314.205.003Manual release plate

    FM200 Manual Release Caution Plate (UL)

    ext2.qxd 13/02/01 17:07 Page 24

  • Page 25

    The standard container is 67 Litre nominalcapacity with a 45Kg fill of Carbon Dioxide.Containers are manufactured to the EC directiveEEC/84/525 and the complete assembly consistsof:. CO2 Container. CO2 Valve & Syphon Tube. Valve Protection Cap. 45 Kgs CO2

    The container valve is fitted with a burst disk rated to operate at 190 bar.Containers are painted signal red and are provided with a label providinghandling and maintenance instructions.Product Codes303.200.01145Kg Container assy complete with solenoid and CO2303.200.01245Kg Container assy complete with CO2

    Carbon Dioxide Equipment & ComponentsContainers EC

    Container DetailsWater Capacity 67.0 Litres (nominal)CO2 Capacity 45KgLength 1507mm +/- 10mmOutside Diameter 267mmMax. Working Pressure 194 BarTest Pressure 250 BarNominal Tare Weight 76.9KgNominal Gross Weight 122Kg

    The Local Manual/Pneumatic Actuator may beused to operate the CO2 container by means of alocal mechanical action or by pneumatic means.The actuator is fitted directly onto the top of thecontainer valve and is retained by a steel locatingclip. A grub screw in the front of the containervalve may be tightened to secure the actuator inthe preferred orientation.

    Accidental manual release is prevented by meansof a steel safety pin. The steel safety pin must beremoved to allow the use of the operating lever.After removing the safety pin manual operation iscaused by moving the operating lever through105o.A maximum force of approximately 3kgf isrequired to operate the actuator.Pneumatic operation is possible by means ofactuation ports in the main body of the actuator.At normal storage conditions ie 20oCapproximately 8.5 bar is required.Two ports are provided at 180o to each other. Oneport is used as an inlet port and the other as anoutlet port. Interconnection between adjacentactuators is by means of 3/16 pilot hoses. (Eitherport can be used as the inlet/outlet ports). Noport must be left open ie. depending on thelayout required, manual bleed valves, pilot hosesor pneumatic actuation plugs may be fitted. To

    connect the 3/16 pilot hose to the inlet/outletports of the actuator requires the use of 3/16 x1/8 adaptor (P/C 309.017.005). These adaptorsmust not be omitted as this could cause thesystem operation to fail. For remote manualactuation the actuator is fitted with a shear strapin place of the steel safety pin. This must bespecified at time of order.When operated the actuator latches to keep thecontainer valve open. The knurled reset plungermust be pulled to reset the actuator afteroperation.Technical SpecificationNet Weight: 0.4Kg

    Product Code302.200.026Manual/pneumatic actuator

    Local Manual/Pneumatic Actuator (Type D)

    The Pneumatic Actuator may be used to operateslave containers by means of pressure from apilot container or from the system mastercontainer.The actuator is fitted directly onto the top of the

    container valve and is retained by a steel locatingclip. A grub screw in the front of the containervalve may be tightened to secure the actuator inthe preferred orientation.Pneumatic operation is through actuation ports inthe main body of the actuator. A minimumoperating pressure of 31 bar is required at acontainer pressure of 200 bar. At normal storageconditions ie. 20oC approximately 8.5 bar isrequired.Two ports are provided at 180o to each other. Oneport is used as an inlet port and the other as anoutlet port. Interconnection between adjacentactuators is by means of 3/16 pilot hoses (Eitherport can be used as the inlet/outlet ports). Noport must be left open ie. depending on the

    layout required, manual bleed valves, pilot hosesor pneumatic actuation plugs may be fitted. Toconnect the 3/16 pilot hose to the inlet/outletports of the actuator requires the use of 3/16 x1/8 adaptor (P/C 309.017.005). These adaptorsmust not be omitted as this could cause thesystem operation to fail.When operated the actuator latches to keep thecontainer valve open. The knurled reset plungermust be pulled to reset the actuator afteroperation.Technical SpecificationNet Weight: 0.3KgProduct Code302.200.027Double slave actuator

    Pneumatic Actuator (Type D)

    The 374mm Pilot Hose is used to take pilotpressure from one pneumatic actuator to the nextin the container bank.The 527mm Pilot Hose is used to take pilotpressure from the type D check valve to the firstslave container in the container bank and alsobetween the end actuators of the front and backrow on double row systems.NOTE: Adaptors are required to correctly connectthe hoses to the local manual/pneumatic actuatoror pneumatic actuator.

    Each end is fitted with a 3/16 Enots (male) swivelfitting. A minimum bend radius of 75mm must beallowed.Technical SpecificationNet Weight: 0.04Kg (374mm)

    0.05Kg (527mm)Product Codes306.200.0033/16 x 527mm Pilot hose306.200.0043/16 x 374mm Pilot hose

    PIlot Hoses (527mm & 374mm)

    306.200.003

    306.200.004

    tyco Fire &Security

    Tyco ElectronicProduct Group

    ext2.qxd 13/02/01 17:07 Page 25

  • Page 26

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The Manifold Check Valve allows for thetemporary removal of a container from the systemand is the means to connect the flexibledischarge hose to the manifold. It may also beused as an adaptor between the pipework andthe end of the flexible discharge hose on singlecontainer systems.The manifold check valve is not designed to givecomplete sealing, but will prevent a substantialloss of CO2 should the system discharge with a

    container removed. The check valve is designedfor use in the vertical position and one checkvalve is used for each container connected to themanifold.Technical SpecificationNet Weight: 0.1Kg

    Product Code302.200.014Manifold check valve

    Manifold Check Valve

    A variety of pneumatic actuation fittings areavailable to connect the various actuation hosesand devices.Product Codes309.017.0043/16 x 1/4 Adaptor309.017.0053/16 x 1/8 Adaptor309.005.0093/16 Nipple

    Pneumatic Actuation Fittings

    The Manual Vent Valve serves two functions.Firstly, it acts to relieve a gradual pressure buildup occurring, perhaps as a result of a leakingpilot container, master container or solenoid.Secondly, it provides a means by which pressuretrapped in the actuation circuits may be manuallyrelieved.The manual vent valve relieves automatically upto a pressure of approximately 2 bar and seals atpressures above this.Pressure is relieved manually by pulling theknurled reset plunger.

    Connection to the local manual/pneumaticactuator requires the use of one 3/16 x 1/4 BSPadaptor (P/C 309.017.004), one of 3/16 nipple(P/C 309.005.009) and one 3/16 x 1/8 BSPadaptor (P/C 309.017.005).Technical SpecificationNet Weight: 0.12Kg

    Product Code302.200.021Manual vent valve

    Manual Vent Valve

    The Pilot Non Return Valve is designed to allowCO2 pressure into various parts of the pneumaticactuation system, but prevent that pressure frombeing lost when the source pressure diminishes.It is essential that it is fitted the correct wayround, otherwise the system may not operate.

    Technical SpecificationNet Weight: 0.02KgThread Size: 3/16 Enots (male)

    Product Code302.200.015Pilot line non return valve

    Pilot Line Non Return Valve

    The type D manifold check valve has a dualfunction and is generally used with the mastercontainer to permit operation of slave containers.Its first function is that of the standard manifoldcheck valve and its second is to provide aconnection from which CO2 pressure may betapped to pneumatically operate slave containers.Product Code302.200.020Type D manifold check valve

    Manifold Check Valve (Type D)

    The 1/2" flexible discharge hose connects thecontainer valve outlet to the check valve on themanifold and is sufficiently flexible toaccommodate the small variations found incontainer heights. Swivel female couplings allowease of installation in any orientation.Technical SpecificationNet weight 0.85 kgs.

    Product Code306.200.00515mm Discharge hose

    Discharge Hose

    309.017.004 309.017.005

    309.005.009

    ext2.qxd 13/02/01 17:08 Page 26

  • Page 27

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The CO2 manifold is designed to enable all thecontainers in a row to be connected to the supplypipe.The standard manifolds are for 2, 3, 4 or 5containers and are available in two sizes, 25mm(1) and 32mm (1 1/4). The manifolds may bejoined using sockets or tees to produce any

    configuration to suit any number of containers ona system.Non-standard sizes may be produced to order.All manifolds are galvanised inside and out andpressure tested to 190 bar.

    CO2 ManifoldsProduct Code Description Weight307.200.009 25mm (1) x 2 Point Manifold 2.5Kg307.200.010 25mm (1) x 3 Point Manifold 3.5Kg307.200.011 25mm (1) x 4 Point Manifold 4.5Kg307.200.012 25mm (1) x 5 Point Manifold 5.5Kg307.200.013 32mm (1 1/4) x 2 Point Manifold 3.0Kg307.200.014 32mm (1 1/4) x 3 Point Manifold 4.0Kg307.200.015 32mm (1 1/4) x 4 Point Manifold 6.0Kg307.200.016 32mm (1 1/4) x 5 Point Manifold 7.4Kg

    The Odouriser 2000 is designed to give adistinctive small to the CO2 and is particularlyuseful in basements or low lying areas in thevicinity of the system or any place where CO2could drift to following a discharge.Liquid citrus odour is contained in the body of theodouriser and is sealed in by a lead disc.Pressure of the discharging CO2 causes the discto rupture and allows the liquid to escape and mixwith the CO2. One type odouriser is used for

    each 2000Kg of CO2. The odouriser must bereplaced after each operation of the system.Connection to the pipework is 1/2 A.P.I. (male).Technical SpecificationNet Weight: 0.275Kg

    Product Code305.200.003Odouriser

    Odouriser 2000

    The Pressure Operated Distribution Valve isdesigned to be used as a safety stop valve or asa distribution / selector valve.The valve may be operated either via pilotpressure or manually through handwheeloperation.A pressure of approximately 11 bar is required toopen the valve and keep it open. Removal of thepilot pressure from the valve will allow it to closeand depending on the requirements it may be

    necessary to lock the pressure in. The valve isprovided with switches as standard to provide asignal to confirm operation of the valve. Sizes20mm to 50mm are provided with NPT screwedconnections. Sizes 80mm to 150mm are availableto order and are provided with flangedconnections. The actuation port is 1/8 A.P.I.

    Pressure Operated Distribution Valve

    Valve Sizes Product Code20mm (3/4) 302.200.02825mm (1) 302.200.02932mm (1 1/4) 302.200.03040mm (1 1/2) 302.200.03150mm (2) 302.200.03280mm (3) 302.200.033100mm (4) 302.200.034150mm (6) 302.200.035

    The S Type Nozzle is used in most total floodingapplications. It is normally recommended that thenozzles are uniformly positioned on the ceiling ofan enclosure to ensure a satisfactory distributionof CO2. Where it is not practical to position thenozzles on the ceiling, it may be acceptabledepending on the room dimensions to positionthem around the perimeter at high level.For CO2 total flooding systems there are no strict

    rules governing the number of nozzles thatshould be applied to any type of hazard, however,nozzle spacing is dependent on the room height,flow rate, potential obstructions etc., but as a ruleof thumb, the nozzle may be used to cover anarea of approximately 30 square metres in a room3 metres high, the nozzle coverage table providesadditional guidance. In order to reduce the possibility of the nozzleorifice becoming blocked during discharge,terminal nozzles should be installed in a tee and ashort length of pipe (100mm) capped/pluggedshould be fitted to act as a dirt trap.

    Technical SpecificationNet Weight: 0.135KgFinish: Satin ChromeConnection to the pipework is 15mm (1/2) NPT(female).

    Product Code310.200.001Type S nozzle 15mm (1/2) (Code 3-18)Orifice codes must be stated at the time of order.

    S Type NozzleEnclosure Height Nozzle Coverage

    3.6m 15m2

    3.3m 20m2

    3.0m 30m2

    2.7m 40m2

    2.4m 50m2

    2.1m 60m2

    1.8m 70m2

    1.5m 80m2

    1.2m 90m2

    1.0m 100m2

    ext2.qxd 13/02/01 17:08 Page 27

  • Page 28

    tyco Fire &Security

    Tyco ElectronicProduct Group

    The racking is designed to securely fix a singlecontainer to a wall or supporting structure. Itcomprises of two sections of steel channel andtwo pairs of universal clamps.The steel channel sections are fixed securely tothe wall or supporting structure. The universalclamps have a special slotted section whichallows each half to be fitted into the steel channel.The two halves are clamped together in positionaround the container using a nut and bolt.

    Technical SpecificationNet Weight: 3.0Kg

    Product Code311.006.015Container bracket assy (single container)

    Container Racking - Single Container

    The racking is designed to securely fix a singlerow of containers to a wall or supportingstructure. It comprises of two sections of steelchannel and two pairs of universal clamps foreach container used.Additional containers may be racked using anynumber or configuration of the two and threecontainer racking assemblies.Technical SpecificationNet Weight: 5.5Kg ( Two containers)

    8.5Kg (Three containers)

    Product Codes311.006.011Container bracket assy (single row 2 cont.)311.006.012Container bracket assy (single row 3 cont.)

    Container Racking - Two/Three Containers - Single Row

    The fog nozzle is a discharge horn designed toproject CO2 in the direction of the fire hazard.CO2 is discharged in the form of a mist or fogand the discharge velocity is relatively low, thusmaking it suitable for use in local applicationsystems particularly where flammable liquids areinvolved and there could be a danger ofsplashing from the impingement of CO2.Nozzle positioning is dependent on the type ofhazard, the method employed in calculating theCO2 quantity, the nozzle height and flow required.Connection to the pipework is 20mm (3/4) NPT(male).

    Product Code 310.200.007 describes a two holeversion of the nozzle (Orifice Code 3 only) andProduct Code 310.200.008 describes a four holeversion (Orifice Codes 3.5 to 18).Technical SpecificationNet Weight: 0.46Kg

    Product Codes310.200.007Fog nozzle (code 3 only)310.200.008Fog nozzle (code 3.5-18)

    Fog Type Nozzle

    The Duct Nozzle is a variation on the fog typenozzle. It is provided with facilities to incorporatea flanged mounting plate and one of two types ofburst disc - an internal (P/C 310.200.011) orexternal (P/C 310.200.012) type.The flanged mounting plate permits the nozzle tobe mounted on the outside of trunking or steelenclosures.The burst discs are designed to prevent theingress of dirt, insects or other particulate matterwhich could at some stage block the nozzle.Connection to the pipework is 20mm (3/4) NPT(male).

    Product Code 310.200.009 describes a two holeversion (Orifice Code 3 Only) and Product Code310.200.010 describes a four hole version (OrificeCodes 3.5 to 18).Technical SpecificationNet Weight: 1.1Kg

    Product Codes310.200.009Duct nozzle (code 3 only)310.200.010Duct nozzle (code 3.5-18)

    Duct Type Nozzle

    The Manual By-Pass Valve is used to allow CO2to be safely vented to atmosphere if it becomestrapped within a closed pipework section. Thevalve is available as standard in 15mm (1/2) NPT.The valve is used in the normally closed positionand is provided with a locking bracket into whicha standard padlock may be fitted.Technical SpecificationNet Weight: 0.25Kg

    Product Code302.001.00815mm (1/2) Manual ball valve

    Manual By-Pass Valve

    Manual Stop Valves are used to isolate the supplyof CO2, (usually at the container manifoldlocation), from the discharge pipework.The valves and are each fitted with a switchbox toenable an indication of valve open or valve

    closed to be given. The valves are also providedwith a locking bracket into which a standardpadlock may be fitted. Other sizes are available toorder.

    Manual Stop Valves - Lockable/ContactedProduct Code Description Weight302.200.016 15mm (1/2) Manual locking valve and switches 1.2Kg302.200.017 20mm (3/4)Manual locking ball valve and switches 1.42Kg302.200.018 25mm (1) Manual locking ball valve and switches 1.6Kg302.200.019 32mm (1 1/4) Manual locking ball valve and switches 1.75Kg

    ext2.qxd 13/02/01 17:09 Page 28

    Front CoverIntroductionTable of ContentsInergen 200 Bar Equipment & ComponentsInergen ContainersRelease Head IIPneumatic ActuatorSolenoid Actuator - StandardSolenoid Actuator - Explosion ProofSolenoid Resetting ToolManual Release Actuator (Local)Twin Release ArrangementPressure Switch (Manual Reset)Pressure Switch (Automatic Reset)Container Pressure Indicator - Standard (DKE-4)Container Pressure Indicator - Supervised (KM-2)ManifoldsManifold Outlet CapHigh Pressure FittingsDischarge HoseActuation Line Check ValveActuation Line Vent ValveTotal Flooding NozzlesInergen Bowl Type NozzlesPressure Reducing Unit - Single Container SystemsPressure Reducing Units - Multiple Container SystemsDistribution ValvesPressure Relief ValveManual By-Pass ValveInergen Pilot ContainerPilot Container Release SolenoidPilot Container Manual/Pneumatic ActuatorOdouriser 2000Inergen Container Racking - Multiple Containers (Retention Ring)Actuation Hoses, Fittings, Manifolds & FixingsInergen Actuation AncillariesInergen Racking - Single ContainersInergen Container Racking - Multiple Containers (Wall Racks)Manual Release Caution PlateDoor Caution Plate (Lock Off)Door Caution Plate (No Lock Off)Inergen AncillariesInergen Nozzle Trim RingKITS - Solenoid Operated

    FM200 Equipment & Components - StandardAgentFM200 Containers - LPCB ApprovedSolenoid Actuator - StandardFM200 Solenoid LeadSolenoid Actuator - FlameproofLocal Manual ActuatorPneumatic ActuatorUnion AdaptorRemote Manual Actuator (Mechanical)T528 Manual Release UnitPressure Switch - StandardPressure Switch - FlameproofSupervisory Pressure SwitchSupervisory Pressure Switch - BASEEFA/CENELECFM200 Nozzles - Engineered: AluminiumFM200 Container Brackets (Welded Containers) - 6.5/13/25.5 LitreFM200 Container Brackets (Welded Containers) - 8/16/32 LitreFM200 Container Brackets (Seamless Containers)FM200 Container Brackets (Welded Containers) - 52/106/147/180 LitreManifoldsFM200 Manifold Support BracketsDischarge HosesManual Release Caution PlateDoor Caution Plate - Lock OffDoor Caution Plate - No Lock-OffFM200 Actuation AncillariesKITS - Master Containers (Solenoid Operated)KITS - Master Containers (Solenoid Operated)

    FM200 Equipment & Components - UL ListedAgentFM200 Containers - Dot (UL)Solenoid Actuator - Stackable (UL)Solenoid Actuator - Side Mounted (UL)Local Manual ActuatorSolenoid Actuator - Pneumatic Actuator (UL)FM200 Container Brackets (UL)FM200 Actuation Ancillary (UL)Supervisory Pressure Switch (UL)Gas Released Pressure Switch (UL)FM200 Manifolds (UL)FM200 Manifold Support BracketsDischarge HosesFM200 Nozzles: Engineered: Brass (UL)FM200 Manual Release Caution Plate (UL)FM200 Door Caution Plate - Lock Off (UL)FM200 Door Caution Plate - No Lock-Off (UL)

    Carbon Dioxide Equipment & ComponentsContainers ECLocal Manual/Pneumatic Actuator (Type D)Pneumatic Actuator (Type D)Pilot Hoses (527mm & 374mm)Manual Vent ValvePilot Line Non Return ValvePneumatic Actuation FittingsManifold Check ValveManifold Check Valve (Type D)Discharge HoseCO2 ManifoldsOdouriser 2000Pressure Operated Distribution ValveS Type NozzleFog Type NozzleDuct Type NozzleManual By-Pass ValveManual Stop Valves - Lockable/ContactedContainer Racking - Single ContainerContainer Racking - Two/Three Containers - Single RowContainer Racking - Four/Six Containers Double RowManual Release Caution PlateDoor Caution PlateNitrogen Pilot Container SolenoidN2 Pilot Container Complete with Gauge and S.P.S.Pressure TripT528 Manual Release UnitCO2 Manifold System PartsCO2 AncillariesCO2 Manual Ball ValvesCO2 Pressure Relief ValveMetron ActuatorKITS - Solenoid Operated

    Wet Chemical System ComponentsAgentWet Chemical ContainersWet Chemical Container BracketsMechanical Control HeadMicroswitch Kit (SPDT) for Control HeadElectrical Control HeadPneumatic Actuation Container (PAC-10)Wet Chemical NozzlesWet Chemical Cable Release PartsCorner PulleyFusible Link Line Test and Anchor PointFusible Links

    Pipework, Fittings & General ComponentsPipeworkFittingsSocketsUnionsElbowsTeesNipplesPlugsReducing Bushes

    FixingsFinishing PartsCorner PulleyT528 Mechanical Manual Release Units

    DocumentationTechnical Manuals & User Manuals

    Index