false sense of security??? - pbworks

40
1 IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire protection systems are passive in nature. They are designed for an occupancy They are designed for an occupancy They do not operate on a daily basis How do you know they will work if needed? You are ultimately responsible Regular inspection • Regular testing Regular maintenance

Upload: others

Post on 10-Dec-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

1

IS YOUR SPRINKLER SYSTEM GIVING YOU

A FALSE SENSE OF SECURITY?

Best Practices in Fire Safety An ASSE Virtual Symposium

March 1 & 2, 2011Walter S. Beattie CSP, CFPS, CSHM

False Sense of Security???

• Fire protection systems are passive in nature.

• They are designed for an occupancy• They are designed for an occupancy

• They do not operate on a daily basis

• How do you know they will work if needed?

You are ultimately responsible

• Regular inspection

• Regular testingg g

• Regular maintenance

2

Are You …

• Checking sprinkler control valves?

• Performing waterflow

• Flowing your hydrants?• Flushing the

underground mains?alarm tests?

• Running your diesel fire pump weekly or electric monthly?

• Performing annual fire pump tests?

• Inspecting your fire water tanks?

• Testing the antifreeze?• Handling your

impairments properly?

Where do I find requirements?

NFPA® 25Standard for the Inspection, Testing, and

Maintenance of Water-Based Fire Protection Systems

Insurance carrierFire department

Corporate standards

NFPA 25• establishes the MINIMUM requirements

– Inspection• A visual examination of a system to verify that it appears to be

i i di i d i f f h i l din operating condition and is free of physical damage.– Testing

• a physical trying or operation of a system, or part of a system to ensure or prove that it is functioning properly, as intended, or to an acceptable standard of operation.

– Maintenance• The work performed to repair and/or maintain equipment in

operable condition.

3

NFPA 25 Covers:

• Sprinkler Systems• Standpipe and Hose

SystemsP i Fi S i

• Foam-Water Sprinkler Systems

• Water Mist SystemsV l V l• Private Fire Service

Mains• Fire Pumps• Water Storage Tanks• Water Spray Fixed

Systems

• Valves, Valve Components, and Trim

• Obstruction Investigation

• Impairments

Setting up an inspection program

• Documented (In writing!!!!)

• In-house

• Contracted

• In-house Inspections & Contracted testing & Maintenance

4

Records, plans, and calculations

• Original as-built installation drawings• Hydraulic calculations• Original acceptance test records• Original acceptance test records• Component data sheets• Letters regarding the review and acceptance

of the system

Before you test

• Notify the alarm supervisory service

• Notify department heads• Notify operators of

critical equipment• Make a general plant

announcement• Others as needed

Wet Pipe Sprinkler Systems

Weekly Checks

5

Are the Valves Open?Unsupervised - Weekly

Are the Valves Open?

Are the Valves Open?

6

Are the Valves Open?

Are the Valves Open?

7

Check the Gauges

Is equipment accessible?

8

Has the hazard increased?

Wet Pipe Sprinkler Systems

Monthly Checks

Monthly

• Weekly Checks• Supervised Valves• Gauges• Gauges• Obvious Damage

9

10

11

12

Wet Pipe Sprinkler Systems

Quarterly Checks

Quarterly Inspections & TestsWet Pipe Sprinklers

• Valve Supervisory Devices• Supervisory Signal Devices• Hydraulic Nameplate• Hydraulic Nameplate• Fire Department Connections• Test Waterflow Devices

– Mechanical such as Water Motor Gong• Weekly & Monthly Checks

13

Fire Department Connection

14

Valve Tamper Switch

Semi Annual Wet Pipe Sprinklers

• Weekly Checks• Monthly Checks• Quarterly Checks• Quarterly Checks• Test Valve Supervisory

Devices

Annual Wet Pipe Sprinklers

• Hangers• Sprinklers• Pipe & Fittings• Pipe & Fittings• Spare Sprinklers• Main Drain Test• Antifreeze test

15

SoniTech NDT - www.sonitechndt.comUsed with Permission

16

5 Year +Wet Pipe Sprinklers

• Obstructions

5 Year +Wet Pipe Sprinklers

• Gauges

17

Testing of Sprinklers

• Submit to Recognized Testing Laboratory• Fast Response elements – 20 years & 10

year interval• Sprinklers 50 Years – 10 year intervalp y• Sprinklers 75 Years – 5 year interval• Extra high temp - 325°F+ every five years• Dry sprinklers – test 10 year intervals• Harsh Environment 5 Years + 5 Years• Heads prior to 1920 - REPLACE

Dry Pipe Sprinkler Systems

18

Dry Pipe Valve Checks

• Wet Pipe checks• Air pressure – Weekly• Compare riser air gauge to compressor gauge• Compare riser air gauge to compressor gauge• Water Column Test• Ice buildup

19

Dry Pipe System Rust & Corrosion

SoniTech NDT - www.sonitechndt.comUsed with Permission

Dry Pipe System Ice Plugs

SoniTech NDT - www.sonitechndt.comUsed with Permission

20

Dry Pipe System Ice Plugs

SoniTech NDT - www.sonitechndt.comUsed with Permission

Standpipes & Hoses

• Inspect– Control Valves – Weekly/Monthly– Pressure Regulating Devices – QuarterlyPressure Regulating Devices Quarterly– Piping, Connections, Cabinet, Hose – Annually

• Tests– Hose Storage Device – Annually– Hose, Pressure Control/Reducing Valves,

Hydrostatic Test, Flow Test – 5 Years

21

These valves are designed to reduce hose pressure from high

pressure pumps.

One Meridian PlazaPhiladelphia, PA

February 23, 1991Where pressure reducing valves

were not properly set…3 Firefighters Died

Private Fire Service Mains

• Check Valves Weekly/Monthly• Hydrants – Annually and after each operation• Hose Houses Quarterly• Hose Houses – Quarterly• Monitor Nozzles – Semiannually• Piping – Annually• Testing – 5 Years

22

23

Monitor Nozzle

Interior Corrosion

SoniTech NDT - www.sonitechndt.comUsed with Permission

24

Interior Corrosion

SoniTech NDT - www.sonitechndt.comUsed with Permission

Microbiological Induced Corrosion (MIC)

Microbiological Induced Corrosion (MIC)

25

Fire Pumps

26

Fire Pumps

• Pump House Checks– Temperature– LouversLouvers

• Weekly Running– Valves open– Start on Pressure Drop– Start with both batteries– Check batteries– Check for leaks

Fire Pumps - Electric• Electrical Systems

– Power lights on– Transfer/Isolating switches– Phase reversal lights

Oil l l i i l i h l– Oil level in vertical motor sight glass– Electrical components

• Run Monthly at least 10 minutes (change 2011)– Constantly attended– I advise to run weekly for reliability

• Packings dripping – Bearing not too hot

27

Fire Pumps - Diesel

• Fluid levels• Batteries – Full – Corrosion???• Controller switches & Setting• Controller switches & Setting• Fuel Tank level not less than 2/3 full• Run Weekly at least 30 minutes

– Constantly attended• Packings dripping – Bearing not too hot

28

29

Fire Pump Annual Test

30

31

Water Storage Tanks

32

33

Water Storage Tanks• Inspect Water Level (alarm)• Inspect Heating System• Inspect Water Temperature (alarm)• Exterior Inspection

– Corrosion– Ice Build-up– Erosion for fabric tanks

• Tank Fill Valves• 5 Year Inspection & Maintenance

Tank Level Indicators

Tank Collapse• Covering the vent

valve during tank painting is fairly standard practice; unfortunately leaving it covered when drawing out of the tank is very non-standard practice.

34

Water Spray Fixed Systems

Water Spray Fixed Systems

• Check Valves & Water Supply• Detection Systems (NFPA 72)• Inspect Hangers Supports Fittings Heads &• Inspect Hangers, Supports, Fittings, Heads, &

Components• Quarterly Alarms• Annual Operational Tests

35

Backflow Preventer

Backflow Preventer

36

Impairments

37

Impairments

• Have a Good Impairment Program• Follow Your Impairment Program• Inform Management Fire Department• Inform Management, Fire Department,

Alarm Company, Insurance Carrier• Discontinue Hazardous Operations• No Hot Work or Smoking• Work Continuously

Impairment of Water Supply to a Fire Pump

Photo courtesy of Robert Woodard. Used with permission.

Excess Pressure Pumps

38

Types of Sprinkler Heads

Standard Pendant Standard Upright

39

Types of Sprinkler Heads

In-Rack sprinklerInstalled

In-RackGrinnell 165F K=5.6 Duraspeedwith watershield

Types of Sprinkler Heads

Large DropViking LD 286F

K17-231 Special HeadCentral (Tyco)

Types of Sprinkler Heads

ESFR - UprightViking VK-520K-14 165F

ESFR – PendantASCOA K-1K-14 155F

40

Types of Sprinkler Heads

• Dry Sprinkler– Fusible Link Releases– Sleeve Moves up– Water Goes Around Mechanism– Water Discharge

Types of Sprinkler Heads

Releasing head for deluge systems