fault mva calc.ppt [compatibility m
TRANSCRIPT
Fault MVA Calculation
-by Tarun Goel-by Tarun Goel
Why Fault Analysis?
Fault Analysis to:� Calculate Power System Currents and Voltages
during Fault Conditions� Check that Breaking Capacity of Switchgear is not
exceeded� Determine the Quantities which can be used by � Determine the Quantities which can be used by
Relays to Distinguish between Healthy and Faulty Conditions
� Appreciate the effect of the method of earthing on the detection of Earth Faults
� Select the best relay Characteristics for Fault detection
� Conduct post fault analysis
Simple Generator Model
� Generator Model X will vary with time. Xd’’ – Xd’ – Xd
X
E
X
Parallel Generators
� If both generator EMFs are equal –they can be thought of as resulting from the same ideal source.
11 KV
20 MVA
20 MVA
X1=0.2pu
X1=0.2pu
j0.05
11 KV 11 KV
Parallel Generators (cont..)
j0.05 j0.05
1.0 1.0
j0.2j0.2
1.0
j0.2j0.2
Transformer Model
P S Zp = Primary Leakage Reactance
Zs = Secondary Leakage Reactance
Z = Magnetizing
P SZP ZS
ZM = Magnetizing Impedance = Large compared with Zp and Zs
ZM = Infinity = Open Circuit
ZT1 = Zp + Zs = positive sequence Impedance
ZM
N1
P SZT1 = Zp + Zs
N1
Motors
� Fault Current contribution decays with time
� Decay rate of the current depends on the system. (100-150ms)
� Typically modeled as a voltage behind as Impedance
M
Xd”
Induction Motors
� Small Motors
� Motor Load < 35kW – NEGLECT
� Motor Load > 35kW
� SCM = 4 X sum of FLCM
� Large Motors� Large Motors
� SCM = (motor FLC)/Xd”
� Approx. SCM = 5 X FLCM
Synchronous Motors
� Large Synchronous Motors
� SCM
: 6.7 X FLCM for 1200 rpm
: 5 X FLCM for 514 – 900 rpm
: 3.6 X FLCM for 450 rpm or less
Balanced 3-ph faults
� 3-ph faults may be represented by 1-ph circuit
� Valid because system is maintained in a balanced state during the faulta balanced state during the fault
� Volt equal and 120 apart
� Currents equal and 120 apart
� Power System plant symmetrical
� Phase Impedances equal
� Mutual Impedances equal
� Shunt Impedances equal
Balanced 3ph Faults
Generator TrafoLine X Line Y
LOADS
3 ph fault
EaEa
Ea
Ea
ZG ZT IaFZLX
IcF
IbF
ZLY
ZLOAD
Balanced 3ph faults(cont..)
Ea
Ea
Ea
ZG ZT IaFZLX
IcF
IbF
ZLY
ZLOAD
EaZG1 ZT1
Ia1 = IaF
ZLX ZLY
N1
F1
Positive Sequence (Single Phase) Circuit:-
ZLOAD
How to Analyze a different voltages
System?
� Per Unit System� Used to simplify calculations on systems with more than 2
voltages
pu value = (actual value)/(Base value in same units)
� Particularly useful when analyzing large systems with several voltage levels.
� All system parameters referred to common base quantities
� Base quantities fixed in one part of the system
� Base quantities at other parts at different voltage levels depend on ration of intervening transformers
Base quantities and Per Unit Values
� Base quantities normally used are:
� BASE MVA = MVAb = 3ph MVA
� Constant at all voltage levels
� Value – MVA rating of largest item of plant or 100MVA100MVA
� BASE VOLTAGE = KVb = ph-ph volt in KV
� Fixed in one part of the system
� This value is referred through transformers to obtain base voltages on other parts of system
� Base voltages on each part of transformer are in same ratio as voltage ratio.
� Other base quantities
� Base Imp = Zb = (kVb)X(kVb)/MVAb
� Base Current = I = MVA /kV (ph-e)� Base Current = Ib = MVAb/kVb(ph-e)
Example
Base voltage on each side of a transformer be in the same ratio as voltage ratio of transformer
11.8kV 11.8/141kV 132/11kV
Distribution System
Incorrect selection of kVb : 11.8kV / 132kV / 11kV
Correct selection of kVb : 11.05kV / 132kV / 11kV
: 11.8kV / 141kV / 11.75kV
Conversion of per unit values from one
Set of Quantities to Another
Zpu1 -> Zpu2
Actual Z = Za
Zpu1 = Za/Zb1
Zpu2 = Za/Zb2 = Zpu1 X Zb1/Zb2
= Z X (kV )X(kV )/MVA X MVA /(kV )(kV )= Zpu1 X (kVb1)X(kVb1)/MVAb1 X MVAb2/(kVb2)(kVb2)
Example
11kV20 MVA
11/132kV50 MVA
Line X Line Y
LOADS
3 ph Fault
132/33 kV50 MVA
0.3 pu
Line Y
LOADS
Fault
132/33 kV50 MVA
B
200/1
A
50/1
Relay settings depending on Fault MVA:
For Standard Inverse
Relay A: CTR = 50/1, Setting: 50A + TMS = 0.2
For fault current = 875A,
t(op) for A = 0.47sec
Grading required = 300 ms
Relay B: CTR = 200/1, Setting: 200A. TMS = ?
t(op) for B = 0.47 + 0.3 = 0.77sec
Hence TMS = 0.16
1
14.0
2−
×=
r
opI
TMSt
Fault
THANK YOU