feeder protection system - plc
TRANSCRIPT
239g Multilin
Dis
trib
utio
n Fe
eder
Pro
tect
ion
• Themostflexibleprotectionandcontroldevicefordistributionfeederapplications
• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts
• Uniqueandsecuredownedconductordetection,backedupbymanyyearsoffieldexperience
• Flexibleloadencroachmentallowssecureoperationduringheavyloadconditions
• Voltageandfrequencyelementstoprovideloadsheddingandtransferschemesforincreasedsystemuptimeandimprovesystemstability
• Advancedautomationcapabilitiesforprovidingcustomizedprotectionandcontrolsolutions
• ApplicationflexibilitywithmultipleI/Ooptionsandprogrammablelogic(FlexLogic™)
• RobustnetworksecurityenablingCriticalInfrastructureProtectionthroughusercommandlogging,anddualpermissionaccesscontrol
• Advancedfaultanddisturbancerecording,includinginternalrelayoperatingsignalsprovidedthuseliminatingtheneedforredundantrecordingdevices
• Ambienttemperaturemonitoringwithalarmingwhenoutsidetemperatureexceedsupperthresholds
• Reducedrelaytorelaywiringandassociatedinstallationcoststhroughhigh-speedinter-relaycommunications
• EmbeddedIEC61850Protocol
• Primaryprotectionandcontrolforfeedersonsolidly,impedanceorresonant(PetersonCoil)groundedsystems
• Busblocking/Interlockingschemes• Distributionloadsheddingschemesbasedonvoltageand
frequencyelements
• High-speedfaultdetectionforarcflashmitigation• Throwoverschemes(bustransferschemeapplications)• Back-upprotectionfortransmissionlines,feedersand
transformers• DistributedGeneration(DG)interconnectprotection,including
activeandpassiveanti-islanding
• Metering-current,voltage,power,energy,frequencyandharmonics
• Oscillography–analoganddigitalparametersat64samples/cycle
• EventRecorder-1024timetaggedeventswith0.5msscanofdigitalinputs
• DataLogger-16channelswithsamplingrateupto1sample/cycle
• SettingSecurityAuditTrailfortrackingchangestoF60configuration
Monitoring and Metering
Protection and Control• Highimpedancefaultdetection(DownedConductorDetection)• Directionaltime,instantaneousphase&groundovercurrent
protection• Loadencroachmentsupervision• Wattmetricgroundfaultdetection• Incipientcablefaultdetection• Four-shotautorecloserwithsynchronismcheck• Breakercontrolandbreakerfailure• Abnormalfrequencyprotection(Rateofchange,underand
overfrequency)Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,
RS232,RS422,G.703,IEEEC37.94• MultipleProtocols-IEC61850,DNP3.0Level2,Modbus
TCP/IP,IEC60870-5-104• DirectI/O–secure,high-speeddataexchangebetweenURs,
forDG,distributionautomationapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber
opticportsand2copperports
F60FEEDER PRotECtion SyStEM
AdvancedProtection,ControlandAutomationSolutionsforDistributionFeeders
FEatuRES
aPPliCationS
KEy BEnEFitS
EnerVista™ Software• GraphicalLogicDesignerandLogicMonitortosimplify
designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensure
referencematerialanddeviceutilitiesareup-to-date• EnerVista™Integratorprovidingeasyintegrationofdatain
theF60intoneworexistingmonitoringandcontrolsystems
• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingF60functions• Redundantarchitecturefordependabilityandsecurity
iEC 61850 Process Bus interface
www.GEMultilin.com
F60Feeder Protection System
240
Dis
trib
utio
n Fe
eder
Pro
tect
ion
Protection and ControlTheF60FeederProtectionSystemprovidesfeederprotection,control,monitoringandmeteringinanintegrated,economical,andcompactpackage.AspartoftheUniversalRelay (UR) Family, the F60 features highperformance protection, expandableI/O options, integrated monitoring andmetering, high-speed communications,and extensive programming andconfigurationcapabilities.
TheF60incorporatesauniqueandmaturedalgorithmtodetecthighimpedancefaultssuchasdownedconductordetection.Italsoprovidesfastanddeterministicexecutionof programmable logic necessary forsubstation automation applications.Graphical programming tools (ViewPointEngineer),supportedbya libraryof logiccomponents,maketheF60simpletouseandconfigure.
The F60 has awide range of protectionelementsthathavemanyyearsofprovenfield experience. Protection and controlfeaturesincludes:
Downed Conductor (Hi-Z) Detection
Fires, injuries, and even fatalities maybe caused by a live downed conductor.Unfortunately, thesehighrisk incidencesoften go undetected by conventionalprotectiverelays.
The Hi-Z element in the F60, unique toGE Multilin, provides reliable detectionof faults causedbydownedconductors.
832727AC.CDR
52
50P22 2 2 2 22 22 2
2
2 2
6
4
2
1
1
1
2
2
50G
50_2
51G
51_2
79CLOSE TRIP
50BF 51P/V 67P 67_2 32 50N 51N 67N/G 50NBF
81U
81O
27P
59P
59N
59X 59_227X
25
Monitoring
F60 Feeder Protection System
TransducerInputsMETERING
DEVICENUMBER25 (2)27P27X3250BF/50BNF(2)50DD50G (2)50N (2)50P (2)50_2 (2)51G (2)51N (2)51N (2)51P (2)
SynchrocheckPhase UndervoltageAuxiliary UndervoltageSensitive Directional PowerBreaker FailureDisturbance DetectorGround Instantaneous OvercurrentNeutral Instantaneous OvercurrentPhase Instantaneous OvercurrentNegative Sequence InstantaneousOvercurrentGround Time OvercurrentNeutral Time OvercurrentPhase Time Overcurrent
FUNCTION
51_2 (2)5259N59P59X59_267N (2)67P (2)67_2 (2)
7981O (4)81U (6)
Negative Sequence Time OvercurrentAC Circuit BreakerNeutral OvervoltagePhase OvervoltageAuxiliary OvervoltageNegative Sequence OvervoltageNeutral Directional OvercurrentPhase DirectionalNegative Sequence DirectionalOvercurrentAutomatic RecloserOverfrequencyUnderfrequency
FlexElement™
Functional Block Diagram
Sophisticated algorithms developedover the past 20 years, detect downedconductors, tree branch contacts, andinsulation fault in underground cables.This unique, field proven algorithmincorporates artificial intelligence tomaximizedependability.KeybenefitsofHi-ZdetectionintheF60:
•Reliabledetectionoffaultscausedbydownedconductors
•Fasterresponsetohazardoussituations
•Dependableandsecureoperationusingartificialintelligence
•EasyintegrationbyaddingamoduletotheF60
Thisprotection featurecanalsobeusedtodetectarcing faults.Basedon testingand in-service field data, the F60 hasshown a high degree of security anddependability.
Directional overcurrent Protection
The F60 also has Built-in standard IEEE,IEC, IAC and FlexCurves™ overcurrentcharacteristics (TOC), most commonlyusedforprimaryandback-upprotectioninvariousprotectivezones. IthasphaseIOC elementswith separate outputs foreachphase. EachTOCelementhas thefollowingprogrammablecharacteristics:
The F60 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
ANSIDeviceNumbers&Functions
F60 - Protection, Metering, Monitoring and Control
DeviceNumber Function25(2) SynchronismCheck27P PhaseUndervoltage27X AuxiliaryUndervoltage32 SensitiveDirectionalPower50BF/50BNF BreakerFailure50DD DisturbanceDetector50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50_251G
NegativeSequenceInstantaneousOvercurrent
51N GroundTimeOvercurrent51N(2) NeutralTimeOvercurrent51P(2) PhaseTimeOvercurrent51_2(2) NegativeSequenceTimeOvercurrent52 ACCircuitBreaker59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage59_2 NegativeSequenceOvervoltage67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent67_2 NegativeSequenceDirectionalOvercurrent79 AutomaticRecloser81O Overfrequency81U Underfrequency
www.GEMultilin.com 241
F60Feeder Protection System
Dis
trib
utio
n Fe
eder
Pro
tect
ion
Forneutraldirectionalsensing,theresidualcurrent of the phase CTs is used as theoperatingcurrent.Forcurrentpolarization,a residual CT is used to measure zero-sequencecurrent.Forvoltagepolarization,thecalculatedormeasuredzerosequencevoltagecanbeused.Themaximumtorqueangleisprogrammable.
load Encroachment
The Load Encroachment function in theF60providesthecapabilitytomanageloadgrowthinfeeders.Theloadencroachmentelementcanbesetforthefeeder’sexpectedmaximum load, reducing the likelihoodoffalsetrippingfor loadconditionswhilemaintaining dependability to trip forlegitimatefaults.
TheloadencroachmentsupervisionintheF60 based on positive-sequence voltageand current andapplies a characteristicasshown.Itallowsthephaseovercurrentelements to be set to see end-of-linephase faults in heavily loaded feederapplications.
•Pickupcurrentlevelfortrip,alarm,orcontrol
•Choiceof17curveshapes(includingFlexCurves)andcurvemultipliers
•Instantaneousorlinearresettimecharacteristictocoordinatewithupstreamtransformerdamagecurvesanddownstreamreclosersandfuses.
•Voltagerestrainttoincreasesensitivity
The majority of distribution systemsare either solidly grounded or groundedthrough a low impedance. Fast faultclearance is required due to the groundfault impact . Following functions areincorporatedintheF60toprovidesecuregroundprotection:
•NeutralIOCandTOC
•GroundIOCandTOC
TheF60allowsdirectionalelementstobeusedtosupervisethegroundovercurrentprotection elements to provide sensitivetrippingforfaultsinonedirection.Typicalapplication for directional overcurrentincludes:
•Isolatefaultedfeedersinringbusorparallelfeederarrangements
•Detectionofbackfeedoffaultcurrentfromfeederswithmotorsorgenerators
•Sensitivehigh-speedgroundprotectionoftransformers
over/under Voltage Protection
The F60 includes the following voltageelements:
•Upto2phaseundervoltageand1overvoltageelements
•1auxiliaryundervoltage/overvoltageelement
•1neutralovervoltageelement
The following are some of the keyapplicationswherevoltageelementscanbeused:
•Sourcetransferschemes.
•Loadsheddingschemes
•Backupcapacitorbankprotectionandcontrol
•Backupmotorprotectiontopreventautomaticrestart.
abnormal Frequency Protection
The F60 offers overfrequency andunderfrequency elements to improvenetwork (grid) stability using voltageor frequency based load sheddingtechniques.TheF60canbeintegratedintoa communications network containingN60NetworkStabilityrelaystoimplementwide area intelligent load sheddingschemes. It also provides back upprotection when protecting feedersand other frequency sensitive powerequipment.
Frequency Rate of Change Protection
Frequencyrateofchange(df/dt)elementsincludedintheF60toprovideprotectionagainstsystemdisturbancesthroughloadshedding and to provide anti-islandingprotection for distributed generatorinterconnections.
LOAD ENCROACHMENTOPERATE
LOAD ENCROACHMENTOPERATE
REACH
X
R- REACH
Flexible Load Encroachment characteristic in F60 can be set by adjusting the load angle and the reach.
F60-1
FIBER/COPPER
CB1 CB2
TCB1
CB3 CB4 CB5 CB6
F60-2
Auto transfer schemes can be implemented using programmable Flexlogic. Wirings between relays can be easily eliminated by using F60 peer-to-peer communication.
Comprehensive Protection & Control
www.GEMultilin.com
F60Feeder Protection System
242
Dis
trib
utio
n Fe
eder
Pro
tect
ion
Cold load Pickup
Acoldloadconditioncanbecausedbyaprolongedoutageoftheload,byopeningofthecircuitbreaker,orbyalossofsupplyevenifthebreakerremainsclosed(cyclicloads like HVAC, refrigeration systems).F60 canautomatically detect conditionsthatwould lead tocold loadpickupandselectivelyblockprotectionelements forsecurityduringfeederenergization.
Wattmetric Ground Fault Protection
A sensitive wattmetric zero-sequencedirectionalfunctioncanbeusedonisolatedorresonant(Petersencoil)grounded,low-resistancegroundedandsolidlygroundedsystemstodetectgroundfaults.Thisfunctiondeterminesthepresenceanddirection of ground faults bymeasuringthevalueanddirectionofzero-sequencepower. This flexible element responds topowerderivedfromzero-sequencevoltageand current in a direction specified bytheelementcharacteristicangle. Powercan be selected as active, reactive, orapparent.Therefore,theelementmaybeused to sense either forward or reversegroundfaults
autorecloser
Two built-in autoreclosers are providedforusewithdistributionlinesinthree-poletrippingschemeswithuptotwobreakers.Uptofourselectablerecloser“shots”arepossiblepriortolockingout.
Breaker Failure and Control
TheF60providestherequiredelementstoperformtwo independentbreakerfailurefunctions. Use the F60 to carry out fullindependent breaker failure protectionover the breakers associated to thefeeder when connected to a substationwith a breaker-and-a-half or ring busarrangement.
Therelayalsoprovidesforcontrolofoneortwobreakersfromfaceplatepushbuttons,remotecommunicationsorcontactinputs.A breaker position can be indicated byLEDsonthefaceplate.
iEC 61850 Process BusThe IEC 61850 Process Bus module isdesignedtointerfacewiththeGEMultilinHardFiberSystem,allowingbi-directionalIEC 61850 fiber optic communications.The HardFiber System is designed tointegrate seamlessly with the existing
Universal Relay applications, includingprotection functions,FlexLogic,meteringandcommunications.
The GEMultilin HardFiber System offersthefollowingbenefits:
• CommunicatesusingopenstandardIEC61850messaging
• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations
• IntegrateswithexistingF60’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule
• DoesnotintroducenewCyberSecurityconcerns
VisittheHardFiberSystemproductpageontheGEMultilinwebsiteformoredetails.
advanced automationTheF60incorporatesadvancedautomationfeatures including powerful FlexLogic™programmablelogic,communication,andSCADAcapabilitiesthatfarsurpasswhatisfoundintheaveragefeederrelay.TheF60integratesseamlesslywithotherURrelaysforcompletesystemprotection,includingthe unit and auxiliary transformers, andBalanceofPlantprotection.
Flexlogic™
FlexLogic™ is the powerful UR-platformprogramming logic engine thatprovidesthe ability of creating customizedprotection and control schemes therebyminimizingtheneed,andtheassociatedcosts,ofauxiliarycomponentsandwiring.Using FlexLogic™, the F60 can beprogrammedtoproviderequiredtrippinglogicalongwithcustomschemelogicforauto transfer schemes (Main-Tie-Main),loadsheddingbasedonfrequency,voltageand communication, loop restorationschemes,otherremedialactionschemesanddynamicsettinggroupchanges.
Scalable HardwareTheF60isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemandingapplicationneeds.Theexpandablemodulardesignallowsforeasyconfigurationandfutureupgrades.
FlexLogicTM Designer
Flexlogic™ allows for customizing the F60 to operate and control the breakers and other auxiliary devices needed to fit most feeder protection schemes and applications.
www.GEMultilin.com 243
F60Feeder Protection System
Dis
trib
utio
n Fe
eder
Pro
tect
ion
• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes
• Typesofdigitaloutputsincludetrip-ratedForm-AandSolidStateRelay(SSR)mechanicallylatching,andForm-Coutputs
• RTDsandDCmAinputsareavailabletomonitorequipmentparameterssuchastemperature&pressure
Monitoring and MeteringTheF60includeshighaccuracymeteringandrecording forallACsignals.Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. Currentand voltageparameters are availableas total RMS magnitude, and asfundamental frequency magnitude andangle.Also,harmonicmeasurements forvoltageandcurrentupto25thforpowerqualityapplications.
Fault and Disturbance Recording
The advanced disturbance and eventrecording features within the F60 cansignificantly reduce the timeneeded forpostmortem analysis of power systemeventsandcreationofregulatoryreports.Recordingfunctionsinclude:
• SequenceofEvent(SOE)-1024timestampedevents
• Oscillography,
-64digital&upto40Analogchannels
• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel
• FaultReports-Powerfulsummaryreportofpre-faultandfaultvalues
• Extensivebreakerinfo(continuouscoilmonitor,arcingcurrent,operatingtime,operationcounterforassetmanagement)
The very high sampling rates and largeamount of storage space available fordata recording in the F60 can eliminatetheneed for installingcostly standalonerecordingequipment.
advanced Device Health Diagnostics
TheF60performscomprehensivedevicehealth diagnostic tests during startupand continuously at runtime to testits own major functions and criticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impactsecurityandavailabilityofprotection,andpresentdevicestatusviaSCADAcommunicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issues helps improve systemuptime.
• Comprehensivedevicehealthdiagnosticperformedduringstartup
• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals
CommunicationsThe F60 provides advanced commun-icationstechnologiesforremotedataandengineering access,making it easy andflexibletouseandintegrateintonewand
existing infrastructures. Direct supportfor fiber optic Ethernet provides high-bandwidth communications allowing forlow-latency controls andhigh-speed filetransfersof relay faultandevent recordinformation. The available redundantEthernet option and the embeddedmanaged Ethernet switch providethe means of creating fault tolerantcommunicationarchitectures inaneasy,cost-effectivemannerwithouttheneedforintermediarycommunicationhardware.
TheF60supportsthemostpopularindustrystandardprotocols enablingeasy, directintegrationintoDCSandSCADAsystems.
• IEC61850
• DNP3.0
• EthernetGlobalData(EGD)
• IEC60870-5-104
• ModbusRTU,ModbusTCP/IP
interoperability with Embedded iEC61850
Use the F60 with integrated IEC61850to lower costs associated with feedersprotection, control and automation. GEMultilin’s leadership in IEC61850 comesfrom thousandsof installeddevicesandfollows on seven years of developmentexperiencewithUCA2.0.
• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessagingfortransfertripping,interlockingschemes,looprestoration,andloadsheddingschemes.
• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVista™ViewpointEngineer
• IntegrateGEMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVista™ViewpointMonitoring
Direct i/o Messaging
DirectI/Oallowsforsharingofhigh-speeddigital information betweenmultiple URrelaysviadirectback-to-backconnectionsor multiplexed through a standard DS0multiplexerchannelbank. Regardlessoftheconnectionmethod,DirectI/Oprovidescontinuousreal-timechannelmonitoring
Fiber LAN, single or redundant, for added security
Fault 1
Source
Fault 2
CB1
CB2
CB3Reverse zone interlocking protection - By using the IEC61850/GOOSE or hi-speed Direct I/O capability blocking signals can be transferred upstream, allowing minimal coordination delays. Fast clearance can be provided for Fault 1 and still maintain coordination for Fault 2.
www.GEMultilin.com
F60Feeder Protection System
244
Dis
trib
utio
n Fe
eder
Pro
tect
ion
that suppliesdiagnostics informationonchannelhealth.DirectI/Oprovidessuperiorrelay-to-relaycommunications that can be used inadvancedinterlocking,generationrejectionandotherspecialprotectionschemes.
• Communicationwithupto16URrelaysinsingleorredundantringsratherthanstrictlylimitedtosimplisticpoint-to-pointconfigurationsbetweentwodevices
• ConnecttostandardDS0channelbanksthroughstandardRS422,G.703orIEEEC37.94interfacesorviadirectfiberopticconnections
• Noexternalorhandheldtesterrequiredtoprovidechanneldiagnosticinformation
Multi-language
TheF60supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista™ setup software, and productmanual. Easily switch between Englishandanadditional languageon the localdisplayswithoutuploadingnewfirmware.
EnerVistatM SoftwareTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifieseveryaspectofusing theF60 relay. TheEnerVista™suiteprovidesall thetoolstomonitor thestatusofyour theprotectedasset ,maintain the relay, and integrateinformation measured by the F60 intoDCS or SCADA monitoring systems.Convenient COMTRADE and Sequenceof Events viewers are an integral partof the UR Setup software included witheveryUR relay, tocarryoutpostmortemeventanalysistoensureproperprotectionsystemoperation.
EnerVista™ launchpad
EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededforconfiguringandmaintainingGEMultilinproducts. The setup software withinLaunchpad allows configuring devicesin real-time by communicating usingserial,Ethernet,ormodemconnections,orofflinebycreatingsettingfilestobesenttodevicesatalatertime.Included in Launchpad is a documentarchiving and management system
that ensures critical documentation isup-to-date and availablewhen needed.Documentsmadeavailableinclude:
• Manuals
• ApplicationNotes
• GuideformSpecifications
• Brochures
• WiringDiagrams
• FAQ’s
• ServiceBulletins
Viewpoint Monitoring
ViewpointMonitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:
• Plug-&-PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
Analyze feeder faults and disturbances using both analog and digital power system quantities that are measured and recorded up to a rate of 64 samples per cycle.
Record the operation of the internal F60 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during faults and disturbances.
Power System troubleshootingTheF60containsmanytoolsandreportsthatsimplifyandreducetheamountoftimerequiredfortroubleshootingpowersystemevents.increaseuptimeandreducelossofproduction.
www.GEMultilin.com 245
F60Feeder Protection System
Dis
trib
utio
n Fe
eder
Pro
tect
ion
Viewpoint Engineer
Viewpoint Engineer is a set of powerfultools that will allow the configurationandtestingofURrelaysatasystemlevelin an easy-to-use graphical drag-and-drop environment . Viewpoint Engineerprovides the followingconfigurationandcommissioningutilities:
• GraphicalLogicDesigner
• GraphicalSystemDesigner
• GraphicalLogicMonitor
• GraphicalSystemMonitor
Viewpoint Maintenance
ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:
• SettingsSecurityAuditReport
• DeviceHealthReport
• SingleClickFaultDataRetrieval
EnerVista™ integrator
EnerVista™ Integrator is a toolkit thatallowsseamlessintegrationofGEMultilindevices intonewor existingautomationsystems.IncludedinEnerVista™Integratoris:
• OPC/DDEServer
• GEMultilinDrivers
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
typical Wiring
LEDIndicators
Multi-LanguageDisplay• English• Russian• French• Chinese
UserProgrammablePushbuttons
user interfaceThe F60 front panel provides extensivelocal HMI capabilities. The local displayisusedformonitoring,statusmessaging,faultdiagnosis,anddeviceconfiguration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.
FFFFFFFF
8c8a5a 5c 7c6a 7a6c
VX
VA VB
VC VX
VA VB
VC
1c 4a
FFFFFFFFFFFF
3c2c 4c1a 4b1b 2a 3a2b 3b
IA IB IC IGIA5
IA1
IB5
IC5
IG5
IB1
IC1
IG1
FFFFFF5a 5c 7c6a 7a6c
VA VB
VCVA VB
VC
CONNECTION
1
PowerSupply
9
CPU
8
CT/VT
6
Inputs/outputs
6Inputs/outputs
*
6Inputs/outputs
*
6Inputs/outputs
*
6Inputs/outputs
*
JU MX LW KV BHT DN G FPS R
A B C
52
I
V
I
V
6BH1b
H2b
H3b
H4b
H5b
H6b
H1a
H2a
H3a
H4a
H5a
H6a
H1c
H2c
H3c
H4c
H5c
H6c
H1
H5
H2
H6
H3
H4
H8a
H7b
H7a
H8c
H7c
SURGEH8b
CRITICALFAILURE
OUTPUT
CONTROLPOWER
HILO
1
FILTERSURGE
B3a
B1b
B8a
B6b
B8b
B6a
B3b
B1aB2b
B5b
RS-232
DB-9
(front)
UR COMPUTER
1
TXD RXD
RXD TXD
SGND SGND
1 832
207645
22
CONNECTORCONNECTOR
2 23 34 45 56 67 78 89 9
F60
DC
M7a
M1a
M2b
M7c
M1c
M7b
M1b
M8cM8b
M2c
M8a
M2a
M4a
M5b
M4c
M6b
M3bM3a
M6a
M4b
M5c
M5a
M3c
M6c
6K M1
M5
M2
M6
M3
M7
M4
M8
6C
P1
P5
P2
P6
P3
P7
P4
P8
P7a
P1a
P2b
P7c
P1c
P7b
P1b
P8cP8b
P2c
P8a
P2a
P4a
P5b
P4c
P6b
P3bP3a
P6a
P4b
P5c
P5a
P3c
P6c
U6a
U8a
U5b
U7b
U5a
U7a
U6c
U8c
U5c
U7c
SURGE
U1a
U8b
U4c
U2c
U3aU3c
U1c
U3b
U1b
U4a
U2a
6D
SURGE
W6a
W8a
W5b
W7b
W8b
W5a
W7a
W6c
W8c
W5c
W7c
6AW1
W2
W3
W4
W1a
W2b
W1cW1b
W2c
W2a
W4a
W4c
W3bW3a
W4b
W3c
I
V
I
V
Minimum
PROVIDED
TC 1
TC 2
832769A5.CDR
Multilin
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
www.GEMultilin.com
F60Feeder Protection System
246
Dis
trib
utio
n Fe
eder
Pro
tect
ion
ordering note: ToviewthelatestoptionsavailablefortheF60,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.
080626-v1
F60 - * ** - H * * - F ** - H ** - M ** - P ** - u ** - W ** For Full Sized Horizontal MountBaseUnit F60 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable) G RS485+Multi-modeST10BaseF H RS485+Mutli-modeSTRedundant10BaseF J RS485+Multi-modeST100BaseFX K RS485+Multi-modeSTRedundant100BaseFX N RS485+10/100BaseT S RS485+6port,100Mbps,ManagedEthernetSwitchSoftwareOptions 00 NoSoftwareOptions 03 IEC61850Mount/Coating H Horizontal(19"rack)-Standard A Horizontal(19"rack)-HarshChemicalEnvironmentOption V Vertical(3/4size)-Standard B Vertical(3/4size)-HarshChemicalEnvironmentOptionUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons F VerticalFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DCpowersupply L 24-48V(DConly)CT/VTDSP 8F Standard4CT/4VT 8G SensitiveGround4CT/4VT 8H Standard8CT 8J SensitiveGround8CT 8L Standard4CT/4VTw/enhanceddiagnostics 8M SensitiveGround4CT/4VTw/enhanceddiagnostics 8N Standard8CTw/enhanceddiagnostics 8R SensitiveGround8CTw/enhanceddiagnostics 8Z HI-Z4CT(highimpedancefaultdetection)IEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX Nomodule 4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 67 67 8Form-A(NoMonitoring)Outputs 6C 6C 6C 6C 6C 8Form-COutputs 6D 6D 6D 6D 6D 16DigitalInputs 6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 6F 6F 8FastForm-COutputs 6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs 6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5C 5C 5C 5C 5C 8RTDInputs 5E 5E 5E 5E 5E 4dcmAInputs,4RTDInputs 5F 5F 5F 5F 5F 8dcmAInputsInter-RelayCommunications 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7S G.703,2Channels 7W RS422,2Channels 76 IEEEC37.94,820nm,multimode,LED,1Channel 77 IEEEC37.94,820nm,multimode,LED,2Channel 2S 6port,100Mbps,ManagedEthernetSwitch,HI(125/250VAC/DC) 2T 6port,100Mbps,ManagedEthernetSwitch,LO(24-48Vdc)
ordering
• URApplicationsILearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
accessories for the F60 • ViewGuideformspecifications
• Downloadtheinstructionmanual
• Reviewapplicationsnotesandsupportdocuments