fendolite mii
TRANSCRIPT
-
8/11/2019 Fendolite MII
1/4
Information given in this publication are given to the best of ourknowledge and in good faith. Trafalgar Building Products is notresponsible if recipients of test reports, assessments or literaturemisinterpret the contents and wrongly use products based on thoseinterpretations. Trafalgar Building Products reserves the right tochange specification without notice.
2005
FENDOLITE M
Fire Protection
Up To 4 Hours
Fire Protection
(to UL 1709 BS 476: Parts 20-21)
Protection from Hydrocarbon
fires
PAS 1 04
October 2005
-
8/11/2019 Fendolite MII
2/4
Fendolite
MII Fire Protection
2PAS 1.04October 2005
SALES OFFICE
NSW: Ph: (02) 9938 5499 Fax: (02) 9905 7019QLD: Ph: (07) 3267 8444 Fax: (07) 3267 5018VIC: Ph: (03) 9729 2141 Fax: (03) 9729 0715
What is Fendolite MII? Fendolite MII is a spray applied, single package factory controlledpremix, based on vermiculite and Portland cement
Fendolite MII produces a monolithic coating able to withstand thethermal shocks experienced in a high intensity hydrocarbon fire.Concrete structures in particular, will be protected from explosivespalling when coated with Fendolite MII.
Although low in density, thus reducing dead load, Fendolite MII ishighly durable and will not crack or spall under mechanical impact
Fendolite MII does not release toxic or hazardous fumes, andpresents no known health hazards either before, during or afterapplication.
The surface may either be spray textured, roller or float finished.
Fendolite MII is used for application on construction elements suchas individual steel or concrete sections particularly where off-site
application is required.
Structures protected with Fendolite MII can provide up to 240minutes fire resistance.
Fendolite MII is for use on structures and vessels in the oil, gas,petrochemical and power industries.
Properties and Performance
Colour and Finish Off-white, with a monolithic spray texture, floated or roller finished
Minimum Practical Thickness 8mm when unreinforced. 15mm when reinforced
Theoretical Coverage 32m2
per tonne at 40mm thickness
Cure By hydraulic set
Initial Set 2 to 6 hours at 20C and 50% RH
Density Minimum 680kg/m3 15% (when dry and in place)
Combustibility Non-Combustible to BS 476: part 4
Smoke Generation Does not contribute to smoke generation
Thermal Conductivity 0.19 W/mK at 20C
Corrosion Resistance Does not promote corrosion of steel. However, a primed substrateis recommended for long term corrosion resistance, particularlywhen the structure is to be fully exposed to the elements
pH Value 12.012.5
Sound Absorption Noise Reduction Coefficient (NRC) 0.35
Fire Resistance Steel and concrete structures protected with Fendolite MII haveundergone fire resistance tests in approved independentlaboratories to recognized standards throughout the world including:
Australia (to AS1530 part 4)UK (to BS 476: Parts 20-21:1987 Appendix D)
USA (to ATSM E119 UL263 and UL1709-design No. XR704)Germany (to DIN 4102)
Holland (to Fire Test Procedures for Tunnels GT-98036-1a)
-
8/11/2019 Fendolite MII
3/4
Fendolite
MII Fire Protection
3PAS 1.04October 2005
SALES OFFICE
NSW: Ph: (02) 9938 5499 Fax: (02) 9905 7019QLD: Ph: (07) 3267 8444 Fax: (07) 3267 5018VIC: Ph: (03) 9729 2141 Fax: (03) 9729 0715
Fire Protection Thickness
General Considerations Fire protection thickness requirements are often specified in owneroperators engineering codes of practice.
Alternatively, consult the Trafalgar Technical department.
Preparation
Typical Substrates Steel and concrete
Substrate Preparation The substrate shall be clean, dry and free from dust, loosemillscale, loose rust, oil and any other condition preventing goodadhesion.
Fendolite MII can be applied to unprimed and primed steelwork.
Prior to the application of Fendolite MII, primed steel should beprepared by the application of Fendolite MII Spatterkote.
Mesh Reinforcement Most fire tests conducted have been carried out without meshreinforcement, to demonstrate the ability of Fendolite MII to stay inplace under the most severe fire conditions. However, for maximumlong term in-service durability, the use of lightweight meshreinforcement is recommended for exterior work and for interiorwork where vibration or mechanical damage and the possibility ofsubsequent de-bonding exist.
Application
Initial Steps Application of Fendolite MII must be carried out by an applicatorrecognized by Trafalgar Building Products and applied inaccordance with the Installation Guide available from TrafalgarBuilding Products
Methods Mix Fendolite MII with potable water in a suitable mixer and apply
by a spraying machine approved by Trafalgar Building Products.
Fendolite MII may be float or roller finished or left with a spraytexture. A hand applied patching mix is available for minor repairs.
Limitations Fendolite MII may be applied when the substrate and airtemperatures are at least 2C and rising, but should not be appliedif the substrate or air temperatures are less than 4C and falling.Maximum air and substrate temperature is 50C.
Substrate temperature should be at least 2C above dewpointtemperature.
Topcoating
General Considerations An approved topcoat may be applied over Fendolite MII forprotection from frequent wash down, long term chemical spills, orfor improved resistance to fungal, algal and bacterial growth.
Packaging, Storage, Shelf Life
Packaging 20kg Bags
Storage Off the ground and kept dry until ready for use
Shelf Life 12 Months Maximum
-
8/11/2019 Fendolite MII
4/4
Fendolite
MII Fire Protection
4PAS 1.04October 2005
SALES OFFICE
NSW: Ph: (02) 9938 5499 Fax: (02) 9905 7019QLD: Ph: (07) 3267 8444 Fax: (07) 3267 5018VIC: Ph: (03) 9729 2141 Fax: (03) 9729 0715
Environmental
Not readily biodegradable.
Not expected to bioaccumulate.
Not expected to be toxic to aquatic life except at highconcentrations.
Do not discharge into drains and watercourses.
Health and Safety
Trafalgar Building Products activities are conducted with dueregard to all statutory requirements with appropriate safeguardsagainst exposing employees and the public to health and safetyrisks
A full copy of Trafalgar Building Products Health, Safety andEnvironmental Policy Document is available on request.
For further information, please see our Material Safety Data Sheet
Quality Assurance
Our Licensor, Cafco International operates a quality system inaccordance with BS EN ISO 9002: 1994, and has received fullaccreditation by BSI to these standards.
Operating to these standards means that all activities, which have abearing upon quality, are set out in written procedures. Systematicand thorough checks are made on all materials and their usage.Test equipment is subjected to regular checks and is referred backto national standards.