ff-844 h1

27
 1 © 2009 Fieldbus Foundati on Dr. Alexander Weiss Business Unit Industrial Projects LEONI Kerpen Gmb H Foun dati on Fieldbus Cable Speci fi cation FF-844 Status & Outlo ok

Upload: jkauto09

Post on 16-Jul-2015

351 views

Category:

Documents


14 download

TRANSCRIPT

Page 1: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 1/27

1

© 2009 Fieldbus Foundation

Dr. Alexander Weiss

Business Unit Industrial Projects

LEONI Kerpen GmbH

Foundation FieldbusCable Specification FF-844

Status & Outlook

Page 2: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 2/27

2 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Introduction

Standards for Fieldbus Cables

Intrinsic Safety Concept

Requirements for Foundation Fieldbus

Cable Design and MaterialsFire Behaviour

Installation

Product Overview ICON®Bus for FoundationFieldbus

Conclusion & Outlook

Overview

Page 3: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 3/27

3 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Foundation Fieldbus

Cables based on one common standard

– defined cable design parameters

– defined electrical properties

to

cover different Fieldbus applicationsguarantee high quality level of product

enable users to easily select the right cable for their

application

Introduction

Page 4: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 4/27

4 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Standards for Foundation Fieldbus cables

Cable specification Foundation Fieldbus FF-844 H1

Cable design based on EN 50288-7 or UL 13 / UL 2250

– no listing for EN type products

– UL type products may be UL listed

Electrical properties: FF-844 H1 and IEC 61158-2, type A – IEC 61158-2, type A

has the most severe requirements,

restricted to singlepairs, whereas FF-844 H1 specifies multipairs, too

IEC 61158-2 types B to D should not be referred to for fieldbus cables – FF-844 H1

electrical properties of each pair in multipair cables shall be according

to IEC 61558-2, type A

Standards

Page 5: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 5/27

5 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Standards for Foundation Fieldbus cables

Demands on intrinsically safe cables and installations

– IEC 600079-14, Intrinsically Safe Cables

– IEC 600079-27, Field Intrinsically Safe COncept (FISCO)

Standards

Page 6: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 6/27

6 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

The Basic Principle of Ignition ProtectionIntrinsically Safe “i”

For the ignition of a potentially explosive atmosphere aspecific energy is necessary.

The ignition protection intrinsically safe makes sure that

the “existing” energy can not ignite the explosive

atmosphere.

An intrinsically safe electric circuit may not be the

reason for an ignition. This applies for normal operating

conditions and in case of faults (e.g. short circuits).

Intrinsic Safety

Page 7: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 7/27

7 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Classification of hazardous areas (“zones”)according to IEC 60079-14

Classification depending on risk of ignition – Zones 0, 1 & 2

classify explosive atmosphere of air / flammable gas, vapour or mist

– Zones 20, 21 & 22

classify explosive atmosphere of air / cloud of combustible dust

Zones 0 & 20: permanent risk

Zones 1 & 21: occasional risk

Zones 2 & 22: risk not likely; when occurring, will persistonly for short period

Intrinsic Safety

Page 8: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 8/27

8 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Device category ia and ib, according to standardIEC 60079-11

Category ia suitable for Zone O: – In case of 2 independent faults it is not allowed to have an ignition.

Category ib suitable for Zone 1 and 2:

– In case of 1 fault it is not allowed to have an ignition.

Intrinsic Safety

Page 9: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 9/27

9 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Demands on Intrinsically Safe Cablesaccording to IEC 60079-14

Flame retardant according to IEC 60332-1(unless the cables are laid in earth, in sand-filled

trenches/ducts or otherwise protected against flame

propagation)

Mutual capacitance: max. 200 pF/m

Inductance: max. 1 µH/m or L/R-Ratio: max. 30 µH/Ohm

(L: loop inductance / R: Loop resistance)

Radial thickness of insulation: min. 0.2 mm

Test Voltage Ueff: min. 500 V

Diameter of conductor: min. 0.1 mm, has to be applied for

single strands of e.g. multistranded conductor too

Intrinsic Safety

Page 10: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 10/27

10 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Standard IEC 60079-27, FISCO and FNICO

Field Non-Incendive COncept (FNICO)

Field Intrinsically Safe COncept (FISCO) – Demands on ignition protection intrinsically safe IS

– All participants in the bus (devices) must be “FISCO”-approved

– Every field device takes up a constant basic current of at least 10mA

– Only one supply source per fieldbus segment

– Ignition protection type ia (Zone O), maximum cable length 1000 m

and with ignition protection ib (Zone 1 and Zone 2) 1900 m

– Maximum length of each spur cable: 60 m for device groups IIC, IIB

– Maximum length of each trunk cable, including all spur cables 1 km

for device group IIC and 5 km for device group II

Intrinsic Safety

Page 11: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 11/27

11 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Standard IEC 60079-27, FISCO and FNICO

Parameter for the fieldbus-IS

– loop resistance R = 15...150 Ω/km – loop inductance L = 0.4...1 mH/km

– mutual capacitance C = 45...200 nF/km

Intrinsic Safety

Page 12: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 12/27

12 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

General requirements for Foundation Fieldbuscables, FF-844 H1, revision 1.2, January 26, 2009

property requirement

characteristic impedance 100 Ω ± 20%

attenuation < 3 dB/kmcapacitive unbalance to shield ≤ 4 nF/km

ICON® Bus ≤ 2 nF/km

(The higher the value the higher is the interference

susceptibility)

temperature range -30°C to +90°C

conductor tinned, annealed copper

FF-844 H1

Page 13: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 13/27

13 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Conductor materials for fieldbus cables

Plain, annealed copper

– suitable for most applications, most common conductor material – excluding high temperatures >130°C

Tinned copper (FF-844 H1 cable specification)

– temperatures up to 180°C

Silver plated copper

– temperatures up to 200°C

Nickel plated copper

– temperatures up to 260°C

Restriction to tinned conductors means

abandonment of the most common conductor material

exclusion of all high temperatures applications

Cable Design

Page 14: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 14/27

14 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Conductor dimensions

FF-844 H1 refers to different standards

– FF-844 H1 specifies min. AWG 18 (approx. 0.9 mm²)Common conductor makeups are

solid, 7-stranded, flexible stranded (i.e. 19 stranded)

standard specified unit dimension

FF-844 H1 AWG 18 (min.)

EN 50288-7 mm² 0.5 / 0.75 / 1.0 / 1.5 / 2.5

UL 13 / UL 2250 AWG 22 (min.)

solid 7-stranded 19-stranded

Cable Design

Page 15: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 15/27

15 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Commonly used insulation materials

foam skin polyethylene (02YS)

solid polyethylene (2Y)crosslinked polyethylene (2X)

perfluoro alkoxyalkane (PFA) for temperatures >150°C

Comparison of some properties of insulationmaterialsproperty foam skin PE solid PE XPE FEP PFA

signal velocity [% of co] 77 66 66 69 71

max. temperature 70°C 70°C 90°C 200°C 260°C

Restriction to min. 90°C in FF-844 H1 means

exclusion of the best material in terms of signal velocity

Cable Design

Page 16: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 16/27

16 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Screens for Foundation Fieldbus cables – overall screen for singlepair cables

– individual and overall screen for multipair cablesscreen types

– plastic coated aluminium tape in contact with drain wire (ST)

– plastic coated aluminium tape in contact with copper wire braid

(ST+C) – plastic coated aluminium tape in contact with drain wire and copper

wire braid (ST+Ce)

(ST) (ST+C) (ST+Ce)

Cable Design

Page 17: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 17/27

17 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Armour types

copolymer coated, corrugated, overlapped steel tape

(SR)round steel wire armour (SWA)

steel wire braid (Q)

(SR) SWA Q

Cable Design

Page 18: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 18/27

18 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Extended chemical protection

special oil resistant PVC, Yö

multi layer sheath, (L)2Y4Y, “ALNYC*)” sheath – a multilayer sheath can replace a lead sheath.

This function is achieved as combination of several layers.

– inner layer of plastic coated aluminium tape (L)

– inner sheath of polyethylene (2Y)

– outer sheath of polyamide (4Y)

*) ALNYC:

AL Aluminium tape, polyethylene laminated

NYC Sheath of polyamide, Nylon Coating

lead sheath (M)

– layer of lead

– cover (sheath) of plastic

Cable Design

Page 19: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 19/27

19 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Sheath materials

polyvinyl chloride (PVC)

– is the most common material – flame retardent, but

– emits corrosive and poisonous gases in case of fire

low smoke, zero halogen, flame retardent compound (LSZH)

– for extended safety in case of fire

– low smoke emission, no corrosive or poisonous gases in case of fire

– for protection of human life and material assets

high temperature applications

– perfluoroethylene propylene copolymer (FEP)

– perfluoro alkoxyalkane (PFA)

other materials

– to be selected based on application

Cable Design

Page 20: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 20/27

20 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Flame retardence behaviour

Generally cables pass several fire tests

– single cable tests IEC 60332-1, UL 1581 – bunched cable tests IEC 60332-3-24, UL 1685

To increase safety low smoke, zero halogen cable designs

are available

– smoke emission IEC 61034,light transmittance min. 60% (PVC max. 40%)

– halogen content IEC 60754-1

– corrosivity of smoke gases IEC 60754-2

These LSZH designs are especially suited for

– low smoke, no corrosive and/or poisonous gases in case of fire

– for protection of human life and high value material assets

Fire Behaviour

Page 21: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 21/27

21 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Fast Assembly (FA)

For quick and easy installation

Using special stripping toolCable design with extruded inner sheath

and without drain wire

stripping tool resultcable stripping

Fast Assembly

Page 22: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 22/27

22 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

FOUNDATION Fieldbus FF (H1) spurand trunk cables, single pair (excerpt)

fixed installation indoor and outdoor, on racks,in conduits

suitable for fast assembly

flexible installation indoor and outdoor, on

racks, in conduits

fixed installation indoor and outdoor, on racks,

in conduits. For direct burial

Cables

Page 23: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 23/27

23 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

FOUNDATION Fieldbus FF (H1) spur and trunkcables, multi pair (excerpt)

in addition to single pair designs multi pair versions areavailable

electrical properties of each pair are like in single pair

cable

installation area like single pair designs

Fast Assembly armouredfor direct burial

flexibleinstallation

fixedinstallation

Cables

Page 24: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 24/27

24 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Foundation Fieldbus by LEONI Kerpen GmbH

FF-844 H1

IEC 61158-2, type AEN 50288-7 or UL13/UL2250

ISA S50.02-1992 (physical layer standard) for FF

Fieldbus

Multipair cables with “Type A” properties

Foundation Fieldbus cables with UL-approval

Different armour typesCables with chemical protection

High temperature versions

Tailor made solutions

Conclusion

Page 25: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 25/27

25 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Conclusion

Foundation Fieldbus cable specification

provides a very good frame for design and properties of

fieldbus cables

is focussed on high quality products

refers to designs based on common standards

Further improvementsconductor to be selected based on application (copper;

plain, tinned, silver- or nickel plated)

temperature range (min. requirements) -30°C to +70°C

– include foamskin PE as best insulation material in terms of

electrical properties

generally refer to IEC 61158-2, type A for electrical

properties

Page 26: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 26/27

26 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

What is the dedication of the FoundationFieldbus cable specification

set a common standard for high quality fieldbus cables – referring to state-of-the-art standards

cover today´s established fieldbus technologies

– ensure use of the best suited materials

be open for higher level applications like

– at high temperatures

– more stringent electrical requirements than type “A”

ensure a standard in accordance with related equipmentstandards, like for connectors, field devices

Other topics to ensure

– customer related requirements

– possible local requirements

Outlook

Page 27: FF-844 H1

5/14/2018 FF-844 H1 - slidepdf.com

http://slidepdf.com/reader/full/ff-844-h1 27/27

27 © 2009 Fieldbus FoundationDr. Weiss, LEONI Kerpen GmbH

Thank You for Your Attention