fg wilson control systems · • printed circuit board assemblies • multi-pin plug and socket...

24
FG Wilson Control Systems www.FGWilson.com

Upload: others

Post on 29-Jan-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

  • FG Wilson Control Systems

    www.FGWilson.com

  • Contents

    1002T Analogue Control Panel

    FG Wilson DCP-10 and DCP-20 Digital Control Panels

    PowerWizard 1.1, 1.1+ and 2.1 Digital Control Panels

    PowerWizard Remote Monitoring Options

    PowerWizard Remote Monitoring and Control Options

    easYgen–2500SynchronisingControlPanel

    easYgen–3200SynchronisingControlPanel

    easYgenControlPanelOptions–NetBiterFGW200

    easYgenControlpanelOptions–I/OExpansionModule

    Load Transfer Panels

    CTIPanelFeatures

    ATIPanelFeatures

    Features and Options

  • Putting You in Control

    Whateveryourpowerrequirements,FGWilsoncanprovideacontrolsystemtosuityourneeds.Ourgeneratorsetexperts

    designandvalidateFGWilsoncontrolsystemstooptimiseyourgeneratorsetperformanceandputyouincontrol.

    AllFGWilsoncontrolpanelsarecompact,versatileandeasytouse.Ourcomprehensiverangeincludeskey-start

    analoguecontrolpanelsforstraightforwardfunctionalityandreliability;digitalcontrolpanelssuitableforuseinmains

    failureapplications,providingadvancedmetering,protectionanddiagnostics;andthenextgenerationofadvanced

    synchronisingpanelswithintegratedloadmanagementcapability,suitableforsynchronisingupto32generatorsets.

    Ourrangeofloadtransferpanelsaredesignedtoenhancetheoperationofyourstandbygeneratorsetinconjunctionwith

    ourelectroniccontrolpanels,toprovideautomaticcontrolofyourstandbygeneratorsetintheeventofapoweroutage,

    24hoursaday,365daysayear.

    Formorechallengingpowerrequirements,ourPowerSolutionsTeamisdedicatedtothedesignandproductionof

    bespokecontrolsystemstomeetyourindividualneeds,regardlessofcomplexity.

    FG Wilson Control Systems

  • 1002T

    The1002TControlPanelisequippedwithallthenecessarygeneratorsetinstrumentationandprotectiondevices,whilstprovidingthestraightforwardfunctionalityandreliabilityofakey-startpanel.

    1002TAnalogue Control Panel

    • Simplifiedmonitoringofgeneratorsetconditionsata glance• Heavyduty,reliableindustrialpushbuttonsandswitches

    • Visualindividualwarningandshutdownsthrough LED’s• Universalpictorialfaultlampindicators

    Features• Analoguemetering:voltmeter,ammeter,hours-run counter,combinedfrequencyandtachometer• 7positionvoltmeterphaseselectorswitch• 4positionammeterphaseselectorswitch• Preheat(startaidactiveLEDindicator)• DCsupplyfromstartingbatteryprotectedbyMCB’s• Printedcircuitboardassemblies• Multi-pinplugandsocketconnectionsforeaseof servicing• Engineprotectionthroughcriticalshutdowns• ACinstrumentsare90°deflection,flushmounted• ACinstrumentsinaccordancewithIEC60051and 60529,DIN43700and43718,BSEN60051and 61010,UL94

    Benefits

  • FG Wilson DCP-10 and DCP-20

    TheFGWilsonDCPrangeallowsyoutomonitorandcontrolyourgeneratorsetwithease,providingimportantdiagnosticinformationwhilstensuringyourunitoperateswithinsafeparameters.

    FGWilsonDCPdigitalcontrolpanels,providesimple, intuitivemenunavigationandcontrolofyourgenerator setoperations.KeyinformationisdisplayedviatheLCDscreenandLED’susinguniversallyrecognisedsymbols,eliminatingtheneedforcomplexinstructionsorlanguagesettings.

    • Automaticstartcontrolmodule

    • Integratedmetering&controls

    • Monitoring,protection,operationalstatus,fault conditionsandmeteringdisplayedviaLCD&LED’s

    • Configurationofparametersvialicencefreesoftware

    • Robustelectronicspackage

    • Symbolsforsimple,intuitivecontrol

    Features• Configurationofparametersbyfrontpanelpush buttonsorbyPCviaminiUSBinterface(DCP-10)or communicationsoftware(DCP-20)• TrueRMSVoltageSensing• Engine&ACmonitoring• Run/AutokeyswithLEDindicators• Under/Overvoltageprotection• Larger128×64graphicLCD(DCP-20only)• RS485,RS232orUSBportforremotecommunication (DCP-20only)• Powermetering(DCP-20only)

    Benefits

    FG Wilson DCPDigital Control Panels

    FG Wilson DCP-10 is standard on 5.5 – 220 kVA range

  • PowerWizardPowerWizard – Providing safe control of your generator setTheFGWilsonPowerWizardrangeofdigitalcontrolpanels,combinestraightforwardmenunavigationwith advanced metering and protection technology. They are used in automatic mains failureapplicationsinconjunctionwithtransferpanels.

    OurPowerWizardrangeallowsyoutomonitorandcontrolyourgeneratorsetwithease,whilstensuringyourunitoperateswithinsafeparametersandprovidesimportantdiagnosticinformationwhenneeded.

    Digital Control Panels

    PowerWizard 1.1, 1.1+ and 2.1

    • Robustelectronicspackageforindustryleadingreliability• Singlemenulayoutforeaseofnavigationandmonitoringwithshortcutkeysforimmediateaccesstoengine or AC metering

    • 10.5-32VDCprovidingasinglemoduletocoverthe wholeFGWilsongeneratorsetrange• Comprehensiverangeofstandardfeaturesandoptions toensurethemostappropriateconfigurationforyour needs• ServicedusingstandardEST

    Features• TrueRMSVoltageSensing• CAN1DataLinkforcommunicationtoelectronic engines,CAN2(2.1only)AccessoryDataLinkfor additional modules• 40uniqueeventslogconfigurationincludingfirst,last andnumberofoccurancesandrealtimeclock• EngineandACMonitoring• Twodisplaylanguages(CustomerLanguage& TechnicianLanguage)• Upto5sparefaultchannels• Configurablesenderinput• Dedicatedkeytoresetallfaultsandmainmenushort cutkey• Run/Auto/StopkeyswithLEDindicators• Integratedmeteringandcontrolsreducingcomponents andwiring,aidingreliabilityandeaseofservice• Generatorsetvoltageandover/underfrequency protection(1.1+and2.1only)• MODBUSconnectiontobuildingmanagementsystem viaRS485(2.1only)• Powermetering(2.1only)

    Benefits

    PowerWizard 1.1+ is standard on 275 – 2500 kVA range

  • PowerWizardRemote Monitoring Options

    Remote MonitoringThePowerWizardAnnunciatorisa16-channneldisplayunitforremotelymonitoringthestatusofFGWilsongeneratorsetsatadistanceofupto240metres.TheAnnunciatorcommunicatesviatheCAN2datalinkwhichcomesasstandardongeneratorsetsfittedwiththePowerWizard 2.1 Control Panel. Eachofthe16channelsontheAnnunciatorhastwoLEDstodisplaystatusandalarmsignalsdirectlyfromthePowerWizard2.1ControlPanelonthegeneratorset.Thepre-setchannelslinkedtoeachLEDdisplaycanbeindividuallyconfiguredusingtheElectronicServiceTool(EST).ThisallowsOperatorstomonitordifferentgeneratorsetstatusandalarmsignalstosuitsite-specificrequirements.InadditiontotheLEDdisplay,theAnnunciatorincludesanaudiblealarm,analarmacknowledgepushbuttonandalamptestpushbutton.

    PW Panel Option Codes Annunciator Dimensions

    A mm (in) B mm (in) C mm (in)

    PW 2.1 ANN16 158(6.22) 130(5.12) 288(11.34)

    AB

    C

    AB

    C

  • The FG Wilson Communications Interface Module andSoftwarePackageallowsoperatorstomonitorandcontrolallgeneratorsetfunctionsfromavirtualcontrolpanelontheirPC.

    Dependingontheoperator’sdistancefromthegeneratorset and the type of connection available to link to thegenerator set, two options are offered:

    • Fordistancesupto1,000metres,whereitisconvenienttohaveahard-wiredconnection,ageneratorsetcanbe monitored using the Communications InterfaceModuleandSoftwarePackageontheoperator’sPCor laptop.

    • Alternatively, when laying a hard-wired connectionis not convenient, the samemonitoring and controlfunctionalityisavailable,butcommunicationbetweentheoperator’sPCorlaptopandtheControlPanelismadethroughamodemandthetelephonenetwork.Dependingontheoperator’sdistancefromthegeneratorsetandthetypeofconnectionavailabletolinktothe generator set, two options are offered:

    Remote Monitoring and Control

    Additional remote monitoring and control options,via the internet, GSM and GPRS are available withPowerWizard2.1ControlPanels.Pleasecontactyourlocal FGWilsonDealerforfurtherinformation.

    Operator laptopor PC

    Using Telephone Network

    TelephoneNetwork

    Modem

    Using Hard-wired Connection

    Generator set withPowerWizard 2.1

    Control Panel

    CommunicationsInterfaceModule

    CommunicationsInterfaceModule

    Generator set withPowerWizard 2.1

    Control Panel

    Connection Via Panel Option Codes

    PW2.1

    Hand-wiredConnection(Upto1,000m) REM1

    TelephoneNetwork REM2*

    *Modemtolinktheoperator’sPCorlaptopwiththetelephonenetworkisnotincluded.Note:PCorlaptopisnotincludedinanyoftheaboveoptions.

    PowerWizardRemote Monitoring and Control Options

  • easYgen–2500Synchronising Control Panel

    easYgen–2500

    • Capableofset-to-setsynchronisingforupto16generator sets

    • Userfriendlyinterface• Easysystemnavigationviaprogrammablesoftkeys• MultiplecommunicationprotocolsforcommunicationwithEngineControlUnits(ECUs),externalI/Oboards,PLCs and modems

    • Multilingualcapability:English,Chinese,French,German,Italian,Japanese,Polish,Portuguese,Russian,SpanishandTurkish

    • Capableofworkingwithallcommonindustrialinterfaces

    Features

    • Powerandreactivepowerloadsharingupto16unitsincludingload-dependentstart/stop

    • Enginestart/stopandgeneratorsetmeasuringandprotection

    • Runninghoursbalancing• Breakercontrol:synchronization,open-closecontrol, only-opencontrol,breakermonitoring• Deadbusclosurenegotiation• PLC-likeprogrammingwithLogicsManager• 300-entry,timeanddatestamplog• Operatinghours/start/maintenancecounters• Configurabletriplevels/delays/alarmclasses• Fieldconfigurableapplicationsettings• Multi-levelpasswordprotection

    Benefits

    The easYgen-2500 offers industry leading power management and control

    TheeasYgen-2500isageneratorset-to-setcontrollerforparallelingandloadsharingapplicationsofupto16generatorsets.AspecialfeatureoftheeasYgen-2500istheenhancedloadsharingsystem.Thisprovidesadvancedgeneratorloaddependentstart/stopfunctionalitywithautomaticgeneratorsetselectiontoensureoptimalsystemefficiency.

  • Generator Set• Over/undervoltage• Over/underfrequency• Deadbusdetection• Overload• Reverse/reducedpower• Timeovercurrent• Instantaneousovercurrent• Inversetimeovercurrent• Phaserotation• Unbalancedload• Powerfactor

    Engine• Over/underspeed• Batteryover/undervoltage• Speed/frequencymismatch

    Inputs / Outputs (I/O)

    • 3phasetruer.m.s.generatorsetcurrent/power• 1speedinput(magnetic/switching)• 10configurablediscretealarminputs• Fiveconfigurableanalogueinputs• Fourconfigurableanalogueoutputs (+/–10V,+/–20mA,PWM;configurable)

    • TwoCANbusinterface(loadshare,Toolkit)• 11RelayOutputsIsolated• RS485Modbusinterface• ServicePort (RS232–WoodwardDPCcablerequired)

    ProtectionService / Configuration

    Loadshare Line57/58

    CAN 1

    CAN BusEngine Level

    MPU

    Measuring

    FrequencyBiasing

    VoltageBiasing

    10 Digital Inputs

    11 Digital Outputs

    5 Analogue Inputs

    ECU

    2 x I / OExpansion

    board

    USB toCAN

    DPCCable

    SCADA

    87/90

    CAN 22 Analogue Outputs

    Service Port RJ45

    55/56

    USB

    • J 1939

    • 16 Digital Inputs• 16 Digital Outputs

    easYgen–2500

  • easYgen–3200†Synchronising Control Panel

    easYgen–3200

    • Capableofgeneratorset-to-set,set-to-mainsandmultiple set-to-mainssynchronisationforupto32generatorsets• Enhancedsystemflexibilitymeetsdemandingcustomer specifications• Userfriendlyinterfacevia320x240pixelgraphical interactive5.7”LCD• Easysystemnavigationviaprogrammablesoftkeys• Multilingualcapability:English,Chinese,French, German,Italian,Japanese,Polish,Portuguese, Russian,Spanish,TurkishandFinnish• Multiplecommunicationprotocolsforcommunication withEngineControlUnits(ECUs),externalI/Oboards, PLCs and modems

    Features

    • Powerandreactivepowerloadsharingupto32unitsincludingload-dependentstart/stop

    • Enginestart/stopandgeneratorsetmeasuringandprotection

    • Automaticbaseloading• Runninghoursbalancing• Import/exportcontrol• Deadbusclosurenegotiation• ECUmonitoringandalarmmanagementaswellas remotestart/stopandcontrolcommands• PLC-likeprogrammingwithLogicsManager• 300-entry,timeanddatestamplog• Operatinghours/start/maintenancecounters• Configurabletriplevels/delays/alarmclasses• Fieldconfigurableapplicationsettings• Multi-levelpasswordprotection• RP3000remotedisplaypanelavailablefor managementandcontrolfromadjacentplantroom

    Benefits

    The easYgen-3200 offers industry leading power management and control

    The easYgen-3200 is a versatile control unit, incorporating all the features of the easYgen-2500includingenhancedloadsharing,andisadaptabletoeveryapplication.Typicalapplicationsinclude co-generation, standby,AMF,peak shaving, import / exportordistributedgeneration. This controlpanelissuitableforsynchronisingupto32generatorsetsrunninginislandmode,mainsparallelandmultiple unit mains parallel operations.

    † Available through Power Solutions

  • Generator Set• Over/undervoltageandfrequency• Deadbusdetection• Overload• Unbalancedload• Reverse/reducedpower• Timeovercurrent• Instantaneousovercurrent• Measured ground fault• Phaserotation• Powerfactor

    Engine• Over/underspeed• Batteryover/undervoltage• Auxiliaryexcitation• Speed/frequencymismatch

    Mains• Over/undervoltageandfrequency• Phaseshift• Rotation field

    Inputs / Outputs (I/O)

    • Twoseparatesetsof3-phasetruer.m.s.voltage measuringinputsforthegeneratorsetand mains,and2-phasebusbarvoltage• 3-phasetruer.m.s.generatorsetcurrent/power• 1-phasetruer.m.s.currentinputfreelyconfigurable• 1speedinput(magnetic/switching)• 10configurablediscretealarminputs

    Protection Service / Configuration

    Guidance / LoadShare Level

    RS232

    CAN 1

    RS485 1

    CAN Bus Engine Level

    CA

    N 2

    MPU

    FrequencyBiasing

    VoltageBiasing

    10 Digital Inputs

    12 Digital Outputs

    3 Analogue Inputs

    AC Measurement:• 4 x U Gen, 3 x l Gen• 2 x U Bus• 4 x U Mains, 1 x l Mains

    MCB GCB

    • J 1939 including 100 SPN text events

    • 16 Digital Inputs• 16 Digital Outputs

    ECU

    2 x I/OExpansion

    board

    PLC /SCADA

    • Upto12programmablediscreteoutputs• Threeconfigurableanalogueinputs• Twoconfigurableanalogueoutputs• TwoCANbuscommunicationnetworks(upto 32participants,isolated)• TwoserialportssupportingModbusRTU Protocol,RS-485andRS-232(isolated)

    easYgen–3200

  • easYgen Control Panel OptionsNetBiter® FGW200Remote management for new and existing generator set installations

    With softwaredesignedexclusively forFGWilson, theFGW200offersnewopportunities for remote accessovertheinternetandmobilephone.TheNetBiterunitissuitableforuseinnewandexistinginstallationsduetocontrolpanelAutoDetectsoftwarewhichoffersplugandplaycapability.

    Remote management that takes customer service to a new level by:

    Features

    • NewAutoDetectsoftwareallowsretrofittoPowerWizard2.1,easYgen-2500, easYgen-3200controlpanelsandATItransferpanels

    • Builtinwebinterfacefordatamonitoring• BuiltinalarmmanagerforSMS,emailandSNMP• Builtindataloggerofhistoricaltrends• GSM/GPRSmodemincluded• Allsoftwareincluded,easilyupgradedremotelyandprovidedwithnolicensingcost

    • Reducingtheneedtotraveltoremotesitesfor maintenancepurposes• Minimisingdowntimewithinstantinformationabout equipmenthealth• Theftpreventionthroughgeneratorsettracking• Fuellevelmonitoringtooptimisefuelinventory• Startuploggingtohelppreventgeneratorsetmisuse• AllowingmultipleprojectanddevicemanagementthroughNetBiter.net

  • I/O Expansion Module†

    Connection to and from external system devices enabling more flexibility to meet your specfic power requirements.

    Features

    easYgen Control Panel Options

    • 8configurablediscretealarminputs• 8configurablerelayoutputs• ConnectiontoeasYgencontrolpanelviaCANbus• InputandoutputconfigurationviaonboardeasYgenrelaymanager

    • RemotecontrolofoutputrelaysviaCANbus• TheI/OExpansionModulecanbeusedwithothermanufacturer’scontrols.ConsultWoodwardproductmanual37135forinformationregardingtheaddressassignmentsoftheCANbusinterface

    † Available through Power Solutions

  • Load Transfer Panels24 Hour Power Protection 365 days a year...

    Load Transfer Panel Range

    • Fullyautomaticmainsfailuresensingandgeneratorsetstart signal

    • Pre-programmedenablingthepaneltorunoninstallationwiththeabilitytocustomiseifnecessary

    • Fastactingswitchesreducetransfertimesbetweensetandutilitypower

    • Availablefrom63–3200A• SeamlessintegrationwithFGWilsondigitalcontrol

    panels

    Benefits

    FG Wilson’s range of intelligent Load Transfer Panels offer you peace of mind.

    TheFGWilsonLoadTransferPanelrangeoffersanelectronicallycontrolledresponsetopoweroutages. Withflexible,upgradeableoptionsandahighleveloffunctionalityFGWilsontransferpanelsprovide24-hourautomaticcontrolofstandbygeneratorsets,365daysayear.

    • Automaticandmanualoperation• Automaticallyprovidesgeneratorsetstartsignalupon detectionofmainsfailure,overvoltageorlossofphase• Automaticmainsre-transferfunction• Flexible,upgradeableoptions• Testoperationsandsequencesaccessiblefrompanelorremotely

    • Manualswitchoperationpossibleviaexternalhandle• LEDfunctionsdisplayshowinggeneratorset/mains availabilityandswitchposition• LCDdisplayforvoltageandtimers• LoadtransferpanelrangemeetsATSIEC60947-6-1 standard

    Features

  • Model Rating ATI Transfer Dimensions Weight

    A mm (in) B mm (in) C mm (in) kg (Ib)

    ATI250 250A 900(35.4) 600(23.6) 323(12.7) 39(86.0)

    ATI400 400A 900(35.4) 600(23.6) 323(12.7) 44(97.0)

    ATI630* 630A 1100(43.3)† 600(23.6) 398(15.7) 66(145.5)

    ATI800* 800A 1375(54.1) 775(30.5) 600(23.6) 125(275.6)

    ATI1000* 1000A 1375(54.1) 775(30.5) 600(23.6) 130(286.6)

    ATI1250* 1250A 1800(70.8) 1005(39.6) 775(30.5) 230(507.1)

    ATI1600* 1600A 1800(70.8) 1005(39.6) 775(30.5) 330(727.7)

    ATI2000* 2000A 2200(86.6) 1000(39.4) 1000(39.4) 400(881.8)

    ATI2500* 2500A 2200(86.6) 1000(39.4) 1000(39.4) 400(881.8)

    ATI3200* 3200A 2200(86.6) 1000(39.4) 1000(39.4) 400(881.8)

    Model Rating ATI Transfer Dimensions Weight

    A mm (in) B mm (in) C mm (in) kg (Ib)

    CTI63 63A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

    CTI100 100A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

    CTI125 125A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

    CTI160 160A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

    *Floorstanding.†DimensionAforthetopcableentrymodelwillchangeto1350mm(53.1in)

    ATI wall mountedCTI wall mounted Floor standing (ATI only)

    Load Transfer Panels

  • CTI Panel Features

    CTI Load Transfer Panel – Ratings 63 – 160 AmpsKey: – Standard Feature – Optional Feature

    Programmable Countdown Timers

    Setroutinetimesfordelayonstarts,delayontransfer,delay

    on re-transfer and run on timer.

    Manual HandleFullyintegratedhandleformanual operation.

    PadlockableSwitchcanbepadlockedinallthreepositionsforaddedsecurityandsafety.Onlypossibleinmanualoperationmode.

    Wall Mounting KitPanelcanbewallmounted

    forgreaterflexibilityinpositioning.

    Auto/Manual/Test Mode Status IndicationAllowson/offloadtestsatroutineservicechecks.

    LCD DisplayShowsdetailedstatusofsystematalltimesfor

    greater awareness and control.

    Control TerminalsGenerator set remote start signal and terminals for remotelymonitoringthesystem.

    System Status Indicators

    Showsstatusofutilitypower,generatorsetandswitchat

    all times.

    Voltage Sensing Tap

    Allows for pole voltagesensing.

    KeypadForstraightforwardprogramming and testing. Passwordprotectionisincluded.

    Terminal shroudForaddedprotection.

    Auxiliary ContactsAuxiliary/voltfreecontactsforremotelymonitoringtheswitchposition.

    Solid Neutral KitAllowstheconnectionofneutralcablesfromutilitypower, generator set and loadwithouthavingthe

    neutralbrokenbytheswitchduring transfer operations.

    Auxiliary ControlsAuxiliaryinputsforautomaticcontrol,remotetestonloadandmanual re-transfer.

    Top and Bottom Cable Entry Aids ease of installation

    Lightning Protection Ensuringsystemsafety

    Load Terminal Extensions Improvingeaseofinstallation

    Ingress Protection IP54 Protectionforthecontrolpanel

    Load Transfer Panels

  • ATI series

    ATI Load Transfer Panel – Ratings 250 – 1600 Amps

    RS485 Communications ModuleEnablesaccesstothesystemremotelythrough

    telephoneorPCviamodem.

    LCD DisplayShowsdetailedstatusofsystematalltimesforgreater awareness and control.

    Programmable Countdown TimersSetroutinetimesfordelayonstarts,delayontransfer,delayonre-transferandrunon timer.

    Wall Mounting KitPanelcanbewallmounted

    forgreaterflexibilityinpositioning(ATI250and

    400).

    Power MeteringTomeasureloadcurrent,kW,kVAr,kVA,powerfactor.

    Manual HandleFullyintegratedhandlefor

    manual operation.

    PadlockableSwitchcanbepadlockedinallthreepositionsforadded

    securityandsafety.

    Solid NeutralAllowstheconnectionofneutralcablesfromutilitypower, generator set and loadwithouthavingthe

    neutralbrokenbytheswitchduring transfer operations.

    Auto/Manual/Test Mode Status IndicationAllowson/offloadtestsatroutineservicechecks.

    Auxiliary ContactsAuxiliary/voltfreecontactsforremotelymonitoringsystem;switchposition,padlockandautomaticormanualoperation.

    Volt Free ContactsForpoweravailableandgeneratoravailable.

    Lightning ProtectionEnsuresthesafetyofsystemduringlightningstorms(includesvoltfreecontactsforutilitypowerandgeneratorset).

    System Status Indication

    Showsstatusofutilitypower,generatorsetandswitchat

    all times.

    KeypadForstraightforwardprogramming and testing. Passwordprotectionisincluded.

    Two Wire Start Signal

    Simpletwowireconnectionforautomaticcontrol.

    Bottom Gland PlateRemovableglandplateproviding

    increasedaccessibilitywithasizeableareaforutilitypowerandgeneratorsetcablestobe

    connected.

    Installation Typicalinstallationsetup

    Ingress Protection IP54Protectionforthecontrolpanel

    Wall Mounting PanelsWallmountwithease–includesfittings

    Top Cable Entry Aids eased installation

    Key: – Standard Feature – Optional Feature

    ATI Panel Features

  • ATI series

    ATI Load Transfer Panel – Ratings 2000 – 3200 Amps

    RS485 Communications ModuleEnablesaccesstothesystemremotelythrough

    telephoneorPCviamodem.

    LCD DisplayShowsdetailedstatusofsystematalltimesforgreater awareness and control.

    Programmable Countdown TimersSetroutinetimesfordelayonstarts,delayontransfer,delayonre-transferandrunon timer.

    Manual HandleFullyintegratedhandlefor

    manual operation.

    PadlockableSwitchcanbepadlockedinallthreepositionsforadded

    securityandsafety.

    Auto/Manual/Test Mode Status IndicationAllowson/offloadtestsatroutineservicechecks.

    Auxiliary ContactsAuxiliary/voltfreecontactsforremotelymonitoringsystem;switchposition,padlockandautomaticormanualoperation.

    Volt Free ContactsForpoweravailableandgeneratoravailable.

    Lightning ProtectionEnsuresthesafetyofsystemduringlightningstorms(includesvoltfreecontactsforutilitypowerandgeneratorset).

    System Status Indication

    Showsstatusofutilitypower,generatorsetandswitchat

    all times.

    KeypadForstraightforwardprogramming and testing. Passwordprotectionisincluded.

    Two Wire Start Signal

    Simpletwowireconnectionforautomaticcontrol.

    Bottom Gland PlateRemovableglandplateproviding

    increasedaccessibilitywithasizeableareaforutilitypowerandgeneratorsetcablestobe

    connected.

    Installation Typicalinstallationsetup

    Ingress Protection IP54Protectionforthecontrolpanel

    Key: – Standard Feature – Optional Feature

    ATI Panel Features

  • Features and Options1002T DCP-10 DCP-20 PW 1.1 PW 1.1+ PW 2.1 easYgen 2500

    easYgen3200+

    Instrumentation

    LCDDisplaywithAutoPowerff – – –

    BatteryTrickleChargeAmmeter – – –

    AudibleAlarm –

    RemoteAnnunciator – – – – –

    AC

    Met

    erin

    g

    Voltmeter3-phase(L-L&L-N)

    Amps(perphaseandaverage)

    Frequency

    kW(total&perphase) – – – –

    kVA(total&perphase) – – – –

    kVAr(total&perphase) – – – –

    PowerFactor(overallandperphase) – – – –

    kWHours – – – –

    kVArHours – – – –

    DC

    Met

    erin

    g

    BatteryVoltmeter –

    EngineHoursRun

    EngineJacketWaterTemperature(in°Cor°F) –

    LubeOilPressure(inPsi,kPAorbar) –

    EngineSpeed(rpm) – –

    CrankAttemptCounter – – – –

    StartCounter – – – –

    Protection

    FailtoStart –

    Low Oil Pressure

    HighEngineTemperature

    Underspeed,Overspeed –

    LossofEngineSpeedDetection – – –

    Low/HighBatteryVoltage –

    BatteryChargerFailure(ifBatteryChargerfitted) – – –

    UnderVolts,OverVolts – –

    UnderFrequency,OverFrequency – – – –

    Overcurrent – – – – –

    ConfigurableSenderInput (for'OilTemperature'or'FuelLevel'optionsonly) – – – –

    EarthLeakageProtection – – –

    EarthFault Protection – – –

    Low Fuel LevelAlarm –

    Low Fuel LevelShutdown – – –

    HighFuel LevelAlarm – – –

    FuelTransferSystemControl – –

    Low CoolantLevelShutdown – – –

    Low Coolant Temperature Alarm –

    HighLubeOilTemperatureShutdown – – –

    OverloadviaAlarmSwitchonBreaker – – – –

    OverloadviaOverCurrentRelay – – – – –

    Low Gas Pressure – – – – – – –

    HighGasPressure – – – – – – –

    HighExhaustTemperatureAlarm – – –

  • 1002T DCP-10 DCP-20 PW 1.1 PW 1.1+ PW 2.1 easYgen 2500easYgen3200+

    Protection Monitoring

    NameofEachEvent – – –

    EngineHoursatFirstOccurrenceofEvent – – –

    TimeandDateofFirstOccurrenceofEvent – – – – –

    EngineHoursatLastOccurrenceofEvent – – –

    NumberofOccurrencesofEvent – – –

    Instrumentation

    SpareFaultChannels

    NumberofChannelsAvailable 0 0 4 3 5 5 5 6

    Exceptions:

    OnmodelsP730P1–P1100E1 – – – – 3 3 4 5

    OnmodelsP1250–P2500-1 – – – – 2 2 3 4

    Controls

    2LEDStatusIndicators(1redshutdown,1amberwarning) – –

    Runkey,AutoKeyandStopKeywithLEDindicators –

    Lamp Test

    AlarmAcknowledgeKey –

    MenuNavigationKeys –

    DedicatedKeytoresetallevents – – – – –

    EngineandACMeteringShortCutKeys – – – – –

    MainMenuandEventLogShortCutKeys – – –

    ControlModuleKeyswithTactileFeedback – – –

    CAN1DataLink-J1939forcommunicatingwith electronicenginecontrolmodules – – –

    CAN2AccessoryDataLink-foradditionalmodulesremoteannuncia-tor,digitalinput/outputmodule – – – – –

    RemoteMonitoringandControlDataLink(ModBus) – – – – –

    RealTimeClock – – – – –

    ServiceMaintenanceIntervalWarning – – – – –

    Remote Monitoring and Control – – – – –

    StaticBatteryCharger – – –

    StaticBatteryChargerwithAutoBoost –

    VoltFreecontactsfor:CommonAlarm&GeneratorSetRunning –

    EngineCoolantHeaterControls – – –

    Control Panel Heater – – – – –

    VoltsAdjustPotentiometer – – –

    SpeedAdjustPotentiometer – – –

    SpeedAdjustSwitch – – –

    OilTemperatureDisplay – – – –

    Oil Temperature Gauge – – – – –

    LubeOilTemeperaturedisplayedonLCDscreen – – –

    FuelLevelSwitch – – – –

    FuelLevelSender&Display – – –

    PanelLockdownStopPushButtonwithsecuritykey – – – – –

    NetbiterInternetMonitoringandControlUnit – – – – – –

    MainsLoadSensingUnit – – – – – – –

    Additional8inputsand8outputs – – – – – – –

    Key: –Standard;–Optional

    Panel Display languagesArabic*,Bulgarian*,Chinese,Czech*,Danish*,Dutch*,English,Estonian*,Finnish*,French,German,Greek*,Hungarian*,Icelandic*,Italian,Janpanese,Latvian*, Lithuanian*,Norwegian*,Polish,Portuguese,Romanian*,Russian,Slovak*,Slovene*,Spanish,Swedish*,Turkish.

    *NotavailableforeasYgencontrolpanels.+AvailablethroughPowerSolutions.

  • Features and Options

    CTI ATI < 1600A ATI > 2000AMotorised Mechanically Held Switch

    Facilityformanualchangeover

    Protection

    Utlitypoweravailable

    Utilitypoweronload

    Generatoravailable/Generatoronload

    Utilitypowerandgeneratoroffload

    Manualmode/Automaticmode

    Testonload/Testoffload

    Manualre-transferforenabled/required

    Power/Errorindication(LED)

    Facia

    Universalsymbolstoallowformultiplelanguages

    Liquid Crystal Display

    UtilityPowerL1-2,L1-3,L2-3voltage

    UtilityPowerL1-N,L2-N,L3-Nvoltage

    GeneratorSetL1-N,L2-N,L3-Nvoltage

    GeneratorSetL1-2,L1-3,L2-3voltage

    UtilityPowerFrequency/GeneratorSetFrequency

    Numberoftimesswitchtransfersfrommainstogeneratorset

    Timer settings

    Standards

    CompleteenclosuremeetsstandardIEC60947-6-1

    SwithmeetsstandardAC31B

    Controls

    Under/Overfrequencyfailure

    Under/Overfrequencyrestoration

    Manual/Autore-transfer

    Modeselectpushbutton

    Under/OverVoltsFailure

    Under/OverVoltsRestoration

    DelayonStartTimer

    DelayonTransfer

    DelayonRe-Transfer

    DeadBandTimer

    Run On Timer

    Auto/ManualControlKeyswitch

    LampTestPushbutton

    Padlockfacility

    SelectionbetweenContactororSwitchMode – –

    Cable entry

    Top –

    Bottom

    Load Terminal Extensions

    Improvingeaseofinstallation – –

  • Features and Options

    CTI ATI < 1600A ATI > 2000AAuxiliary Contacts

    Formonitoringofswitchposition(Includingpadlocking&auto/manual) –

    Lightning Protection

    Ensuringthesafetyofsystemduringlightningstorms

    Ingress Protection IP54

    Protectionforcontrolmodule

    Power Metering

    Tomeasureloadcurrent,kW,kVAr,kVA,Powerfactor –

    Volt Free Cotacts

    Forutilitypoweravailability&generatoravailable

    Communication Module

    PluginmodulethatusesJbus/modbusprotocoltoallowremotecommunicationofthechangeoversystem –

    Voltage Sensing Tap

    Allowingforpolevoltagesensing – –

    Solid Neutral Kit

    Toconnectneutralcablesfromthemains,generatorsetandload –

    Terminal Shroud

    Foraddedprotection – –

    Key: –Standard;–Optional

    Note:Optionsavailabledependsontheexactconfigurationofthegeneratorsetpackage.Notalloptionsareavailableonallpackages.PleasecontactyourlocalFGWilsonDealerformoreinformation

  • FG Wilson manufactures product in the following locations:Northern Ireland • Brazil • China • India • USAWith headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com.

    FG Wilson is a trading name of Caterpillar (NI) Limited.In line with our policy of continuous product development, we reserve the right to change specification without notice. ControlPanelRange/0513/GB