FOUNDATION Specification 31.25 kbit/s Physical Layer Profile Document FF-816 Revision 2.0; Sept 2001

IEC61158-2: 2000 Fieldbus Standard for Use in Industrial Control Systems Part 2 : Physical Layer Specification and Service Definition

ISA-S50.02-1992 Fieldbus Standard for Use in Industrial Control Systems Part 2 : Physical Layer Specification and Service Definition

SpecificationsSpecifications

Page 3: Fieldbus 1 Physical Layer Fieldbus Physical Layer

4

Fie

ldb

us

Additional devices may be connected toa Fieldbus networkat any point

Fieldbus Digital OperationFieldbus Digital Operation

T T

Host system doesnot have to be at thenetwork terminator

100R1 µF

Page 4: Fieldbus 1 Physical Layer Fieldbus Physical Layer

5

Fie

ldb

us Tree, Spur, & Daisy-chain topologyTree, Spur, & Daisy-chain topology

T T

Tree

Spur

Daisy-chain

X

Page 5: Fieldbus 1 Physical Layer Fieldbus Physical Layer

6

Fie

ldb

us Fieldbus Digital OperationFieldbus Digital Operation

T T

Up to 32 devices per segment(more with repeaters)

Total network length achievable depends on cable quality

A maximum of four repeaters recommended

Page 6: Fieldbus 1 Physical Layer Fieldbus Physical Layer

7

Fie

ldb

us

T T

10m10m

50m60m

80m

60m

30m

80m

Adding up all trunk + spurs= 680 metres

300m

Fieldbus max cable lengthsFieldbus max cable lengths

Page 7: Fieldbus 1 Physical Layer Fieldbus Physical Layer

8

Fie

ldb

us

CableType

CableDescription

Size MaxLength

Type ‘A’ Single twisted pairwith shield

0.8 mm2

18 AWG1900 metres

Type ‘B’ Multi-twisted-pairwith individual shields

0.32 mm2

22 AWG1200 metres

Type ‘C’ Multi-twisted-pairwithout shield

0.13 mm2

26 AWG400 metres

Type ‘D’ Multi-core, without twisted pairsand having an overall shield

1.25 mm2

16 AWG200 metres

Cable specificationCable specification

Recommendedmaximum length

680 m

680 m

Page 8: Fieldbus 1 Physical Layer Fieldbus Physical Layer

9

Fie

ldb

us

Type ‘A’ cable typically offers the following at 25OC :

characteristic impedance at 31.25 kHz : 100 ± 20% max attenuation at 39kHz (1.25 x 31.25) : 3.0 dB/km max capacitive unbalance to shield : 4nF/km,

tested using a 30m or longer sample max d.c. resistance (per conductor) : 24 /km max propagation delay change 8kHz to 39kHz : 1.7 us/km conductor cross sectional area : 0.8 mm2

: (18 AWG) min shield coverage shall be 90%

Fieldbus CablesFieldbus Cables

Where the field link is intrinsically safe : The use of a screened cable

removes the necessity for segregation of IS from non-IScables for safety reasons

removes the need to assess fault interaction segregation is desirable to ensure interference is minimised IS cables should be clearly identified where colour is used to identify the cables it should be light

blue

Page 9: Fieldbus 1 Physical Layer Fieldbus Physical Layer

10

Fie

ldb

us

R L C R L C R L C

Characteristic ImpedanceCharacteristic Impedance

Type ‘A’ cable typically offers the following at 25OC :

characteristic impedance at 31.25 kHz : 100 ± 20% max attenuation at 39kHz (11/4 x 31.25) : 3.0 dB/km

decibels = 20 log (V in / V out)

max capacitive unbalance to shield : 4nF/km max d.c. resistance (per conductor) : 24 /km

characteristic impedance at 31.25 kHz

Page 10: Fieldbus 1 Physical Layer Fieldbus Physical Layer

11

Fie

ldb

us Fieldbus Cables :

to IEC61158-2 & IEC60332-3 Cat C flame test

Fieldbus Cables :to IEC61158-2 & IEC60332-3 Cat C flame test

Manufact. Cat.No.

Type Conductors Gauge Resistance

Belden 3076F ‘A’ single pair 18 AWG 22 /km

Belden 3077F ‘B’ single pair 22 AWG 56 /km

All Belden cables are : Low Smoke Non Halogen (LSNH): optional in steel wire armour (SWA): outer covering in orange PVC

Belden UK Ltd. 10 Watergate RowWatergate StreetChester, Cheshire, UKCH1 2LDTel +44 (0)1244 350 535

Lapp

Kerpen

BICC Cables

Page 11: Fieldbus 1 Physical Layer Fieldbus Physical Layer

12

Fie

ldb

us

metres

TotalDevices

1 Deviceper Spur

2 Devicesper Spur

3 Devicesper Spur

4 Devicesper Spur

1-12 120 90 60 30

13-14 90 60 30 0

15-18 60 30 0 0

19-24 30 0 0 0

25-32 0 0 0 0

Maximum spur lengths are the sameirrespective of cable type

Recommended spur lengthsRecommended spur lengthsFigures

not

absolute

Page 12: Fieldbus 1 Physical Layer Fieldbus Physical Layer

13

Fie

ldb

us

T

Max length Type ‘A’ : 1900 m

Max length Type ‘C’ : 400 m

1200 / 1900 + 200 / 400 = 1.13

result > unity : not recommended

Type ‘A’1200m(1900)

Mixing cable typesMixing cable types

Type ‘C’200m(400)

T

The ability to power the field devices over the networkis considered in detail later

Communication limitations