Installation of Fieldbus

Page 2: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 2

Agenda

Foundation Physical Layer

Choosing Components and Layout

System Design

Field Checkout and Commissioning

Trouble Shooting a Fieldbus System

Page 3: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 3

Fieldbus Technology

HSE

Bridge

16

16

H1

H1

H1

H1

H2

H1

H1

Devices

Devices

Devices

Automation

and

Display Systems

General Fieldbus Topology

Page 4: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 4

Foundation Fieldbus was designed by

the Process Industry for the Process

Industry

Page 5: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 5

Agressive environment

Page 6: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 6

Typical installation

Page 7: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 7

Instruments are spread over large areas

Page 8: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 8

Hazardous Areas

Page 9: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 9

Electromagnetic Interference

Transients

Radio Frequency

Interference

Electromagnetic

Interference

DCS I/O

HA

RT

FF

4-2

0 m

A

T/C

Thermocouple

Wired Direct

Single-Input

Transmitter

(4-20mA)

Single-Input

Transmitter

(HART)

Multi-Input

Transmitter

(Fieldbus)

4-20 mA

mV

Capacitive

Coupled

Noise per

IEC Standards

(Light Industry)

All Cables with Shielded, Twisted

Pairs, Grounded at the DCS

Page 10: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 10

Electromagnetic Interference

°C

Noise per IEC Stds (Light Industry)

Time

Fieldbus

Transmitter

HART

Transmitter

4-20 mA

Transmitter

Thermocouple

Wired Direct

Page 11: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 11

Terminator

Fieldbus Foundation Fieldbus

Terminator

Power

Supply

Power

Filter

Power

Filter

Junction

Boxes

Operator

Interface

ConfiguratorLocal

Operator

Interface

9~32 V

IEC 1158-2 Standard

Page 12: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 12

Number of devices per segment

Based on present device power consumption, Power conditioner current limitation and resistance of wires, experience demonstrates that up to

16 Devices per segment

can be used.

Page 13: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 13

Fieldbus Cable Types

Cable Type and Description Size Length

–Type A (New)Shielded, twisted-pair

– H1: 31.25 Kbps #18 AWG 1900* m

–Type B (Existing) Multi-twisted-pair, w/shield

– H1: 31.25 Kbps #22 AWG 1200* m

–Type C Multi-twisted-pair, w/o shield

– H1: 31.25 Kbps #26 AWG 400* m

–Type D Multi-core, w/o shield

– H1: 31.25 Kbps #16 AWG 200* m

* Spurs count in overall length

Page 14: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 14

Cable Length

Total cable length should be less than 1900 m (shielded, 18 AWG, Type B)

Connecting up to 12 devices in a powered bus, the Spur length limit should be:

* 120 m with one device * 90 m with two devices * 60 m with three devices * 30 m with four devices

Length reduces with more devices in the network

Standard is Conservative!

Page 15: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 15

Installation Procedures

Fieldbus requires standard wiring practices

Page 16: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 16

Fieldbus Segment Power

FloatingPower Supply

For Multiple

Segments PowerConditioner

100 Ohms 10 mH

PowerConditioner

Fieldbus

Ground

Fieldbus

Active filter, equivalent to:

Ground

Page 17: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 17

Polarity Insensitive Devices

Some suppliers provide Polarity Insensitive Fieldbus Devices

Host TerminationPanel

Home Run CableJunction Boxes

FieldJunction Boxes

+

-

-Wiring crossover is

NO PROBLEM!

+

This enables fast and safe commissioning of the Fieldbus Network

Page 18: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 18

I (mA)

Iq1 16 ~ 20 mA

Current Consumption And Signal Shape

Page 19: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 19

Power Supply

For Multiple

Segments

PowerConditioner

T T

Iq1 Iq2 Iq3 Iqn

V1 V3V2VPS Vn

VPC

Maximum Voltage : 32 V

Minimum Voltage : 9 V

Total Current = Iq1 + Iq2 + Iq3 + ……... Iqn

Maximum current limited by the power conditioner.

Example: 400 mA

Voltage and Current

Page 20: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 20

Short Circuit Protection

Short

Circuit

Pre wired Junction Box

Page 21: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 21

Power Supply

Terminator Terminator

100 Ohms 1uF

Termination and Twisted Pair Shielding

May Be PolaritySensitive

Trunk

Spur

Page 22: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 22

H1 Card

Pwr Cond

w/ Term

Lambda pwr sup

LRS 55-24

Spur Block

note 1Spur Block

GP1

Block

Spur Block

Spur Block

GP2

Block

Spur Block

Spur Block

Spur BlockSpur Block

Spur BlockSpur Block

FIT

PIT PIT

PIT

PIT ROVROV

PITPIT

FIT

ROVROVPIT PIT

370m 3m 9m

9m

9m

9m3m

9m9m

GP1

GP2

Terminator Located at Far Ends of Main Segment Trunk

Page 23: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 23

Communications under abnormal conditions

T TT1

S1 S2 S3 Sn

PFPS

Normal

TT1

S1 S2 S3 Sn

PFPS ?

One terminator missing

T TT1

S1 S2 S3 Sn

PFPS

Too many terminators

T T

Page 24: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 24

V=9-32 Volts,Floating

Power Supply

For Multiple

Segments

PowerConditioner

Ground

50 Ohms 5 mH

+V/2

-V/2

Balanced Conductor

Power Conditioning For Fieldbus Segments

Page 25: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 25

Important rules

Shield should be grounded at a single point!

Do not ground signal wires

Observe terminator location

Page 26: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 26

Shield should be grounded at a single point

I

Page 27: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 29

Example Power Supply – One per Segment

Page 28: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 31

Fieldbus Supports Multiple Topologies

T TT1

S1 S3 Sn

PCPC

S23

S22

S2

S21

T1 +S1 +S2 + S21 +S22 +S23 ….+ Sn<1900 m

Page 29: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 32

Daisy-Chain Topology

GoodPractice

Disconnecting a Single Device May Result in Loss of Downstream Devices

Trunk

Page 30: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 33

Branch Topology

A Device May BeDisconnected WithoutImpacting Downstream Devices

Trunk

Spur

Page 31: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 34

Tree TopologyA Device May BeDisconnected WithoutImpacting Other Devices

Trunk

Spur

Page 32: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 35

Example - Field Junction Box

Page 33: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 36

Example - Field Junction Box

Page 34: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 37

Standard is conservative

Total length of cable should be less than 1900 m (shielded, 18 AWG, Type B)

When connecting up to 12 devices in a powered bus, the Spur length limit should be:

* 120 m with one device * 90 m with two devices * 60 m with three devices * 30 m with four devices.

More devices in the network reduce the lengths given above

Page 35: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 38

Communications under abnormal conditions

T TT1

S1 S2 S3 Sn

PFPS

Long spurs (240 m)

T TT1

S1 S2 S3 Sn

PFPS

Long Trunk (4000 m)

Page 36: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 39

Intrinsic Safety Installations

k - depends on the power consumption of the devices, Entity parameters

and barrier

PS SB

1

Hazardous

Area

Safe area

1

2

k

Control System

T

T

Maximum cable length

is determined by the

Capacitance and

Inductance allowed by

the installation

Page 37: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 40

Intrinsic Safety Installations

k - depends on the power consumption of the devices, Entity parameters

and barrier

k+n < 16

Total cable length < 1900 m

T

T

PCPS

SB

1

Hazardous

Area

Safe area

1

2

k

Control System

1 n

Maximum cable length

is determined by the

Capacitance and

Inductance allowed by

the installation

Page 38: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 41

Intrinsic Safety Installations

T

T

PCPS

SB

1

SB

2

SB

n

Hazardous

Area

Safe area

1.1

1.2

1.k

k - depends on the power consumption of the devices and cable length

n - depends on the barrier type and cable length

TT

Control System

Page 39: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 42

Traditional Intrinsic Safety Installation(4-20 mA Analog / HART)

I.S. Transmitter

Vmax

Imax

Pmax

Ci/Ceq

Li/Leq

CONTROL ROOM

EQUIPMENT

Voc

Isc

Ca

La

Po = .25 x Voc x Isc

Cable

C/ft

L/ft

Hazardous Area Safe Area

I.S.

Barrier

1 Measurement per I.S. Barrier

Safety Assessment:Vmax >= Voc

Imax >= Isc

Pmax >= Po

Ci + Ccable <= Ca

Li + Lcable <= La

Page 40: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 43

Intrinsic Safety - Conventional Approach (Entity Model)

What does it Mean ?

– Using an MTL Barrier as an Example

– More current = Less Volts

85mA

9V

Available bus current

excluding voltage drop

due to cable resistance

0 Voltage (V) 18

170

Cu

rre

nt (m

A)

MTL5053 Load Line

(105 )

Page 41: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 44

So How Much Current do the devices need ?

– 3051

• 17mA

– 3244

• 17mA

– Communication Current Required

• 10mA

Intrinsic Safety - Conventional Approach (Entity Model)

X 2

X 2

78mA

= 34mA

= 34mA

= 10mA

Page 42: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 45

Intrinsic Safety - Conventional Approach (Entity Model)

What does it Mean ?

– Using an MTL I.S. Fieldbus Power Supply as an Example

– More current = Less Volts

0 Voltage (V) 18

170

Cu

rre

nt (m

A)

MTL5053 Load Line

(105 )

85

9V

Bus Load Line

Including 1900m of Cable

(105 + 84 )

47

Current available

for field devices

Page 43: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 46

(Source Resistance of the Barrier) + (Fieldbus Cable Loop Resistance)

(Open Circuit Output Voltage of the Power Supply) - 9Volts

The Entity Model - Cable Length and Quality

The Calculation.

– Current available =

MTL5053 = 105 Ohms

MTL5053 = 18V

Tx Minimum Lift

off voltage

The Main Issue

1900m = 84

Page 44: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 47

Type Description SizeMax

Length

A Shielded, Twisted Pair#18 AWG

(.8 mm2)

1900 m

(6232 ft.)

BMultiple-Twisted-Pair with

Shield

#22 AWG

(.32 mm2)

1200 m

(3963 ft.)

CMulti-Twisted-Pair Without

Shield

#26 AWG

(.13 mm2)

400 m

(1312 ft.)

DMulti-core, w/o Twisted Pairs

and Having Overall Shield

#16 AWG

(1.25 mm2)

200 m

(656 ft.)

“Typical” Length Restrictions With Existing Wire

What types of Wire

Page 45: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 48

Junction Box

H1 Fieldbus

Entity Model Point Failure

Break In The Cable

Break In The Cable

Break In The Cable

Assumes that ALL the Electrical Characteristics Manifest

themselves at the Cable Break

Page 46: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 49

Intrinsic Safety - FISCO Approach

Current

15V

110mA

More Current Available

Page 47: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 50

So How Much Current do the devices need ?– 3051

• 17mA

– 3244• 17mA

– 8742C• 12mA

– Communication Current Required

• 10mA

Intrinsic Safety - FISCO Approach

X 3

X 2

X 1

107mA

= 51mA

= 34mA

= 12mA

= 10mA

Page 48: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 51

FISCO - What types of Wire

Cable parameters

– Loop resistance 15 to 150 ohms / km

– Inductance per unit length 0.4 to 1mH / km

– Capacitance per unit length 80 to 200nF

Length of cable

– Trunk up to 1000 m

– Spur up to 30m

– Splice up to 1m

Page 49: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 52

Junction Box

H1 FieldbusT1 T2

S1S2

S3 S4 S6S7

S 5

FISCO - Rules and Capacities

S1+S2+S3+S4+S5+S6+S7 < 30m

T1+T2 < 1000 M

Page 50: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 53

Junction Box

H1 Fieldbus

FISCO - Point Failure

Break In The Cable

Break In The Cable

Break In The Cable

Assumes that the Electrical Characteristics are Distributed

around the Segment

Page 51: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 54

Summary -What do they have in Common ?

Only one source of power applied to the fieldbus segment

Field devices designed to contribute no energy to the bus (whether transmitting or receiving)

Each device has small permitted effective internal inductance and capacitance (similar maximum values defined in both approaches)

Bus segment terminated at both ends (terminator is resistor-capacitor series combination)

Page 52: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 55

Entity Model

– Linear (resistively limited) power supply characteristic

– Power supply approval defines max. system C and L values, and therefore bus cable limitations

– Bus power defined as 1.2W max. at 60ºC, to simplify device approval

– Current available for devices: 60mA on 1900m bus, 90mA on short bus (using Type 'A' cable) on IIC or IIB systems

– Typically 4 (20mA) devices on IS bus segment - in any gas group

FISCO

– Square or trapezoidal power supply characteristic

– Power supply approved without max. C and L values, allowing bus length up to 1km with a variety of cable types

– Higher power supplied to bus: up to 1.9W in IIC (Groups A & B) and 4.9W in IIB (Group C) systems. Each device must be approved compatible with this power.

– Current available for devices: 110mA for IIC, greater for IIB systems

– Typically 6 (20mA) devices on IS bus in IIC, 10 devices in IIB gas group

Summary -What are the Differences ?

Page 53: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 56

Intrinsic Safety - Conventional Approach (Entity Model)

I.S. Transmitter

Vmax

Imax

Pmax

Ci/Ceq

Li/Leq

CONTROL ROOM

EQUIPMENT

Voc

Isc

Ca

La

Po = .25 x Voc x Isc

Cable

C/ft

L/ft

Hazardous Area Safe Area

I.S.

Barrier

24 Measurements per I.S. Barrier

Safety Assessment:Vmax >= Voc

Imax >= Isc

Pmax >= Po

Ci + Ccable <= Ca

Li + Lcable <= La

Page 54: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 57

Intrinsic Safety - FISCO Approach

I.S. Transmitter

Vmax, Imax, Pmax

FISCO

CONTROL ROOM

EQUIPMENT

Vo, Io, Po

FISCO

Cable

C/ft, L/ft

FISCO

Safety Assessment:Vmax >= Voc

Imax >= Isc

Pmax >= Po

Hazardous Area Safe Area

FISCO

Barrier

32 Measurements per FISCO Barrier

Page 55: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 58

SAFE AREA

ZONE 0

Protection Method

EExia IIb T4

ZONE 0

Protection Method

EExia IIc

120 Metres

Maximum

1900 Metres

Maximum

Hawke Intrinsically Safe Installation

Page 56: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 59

Choose Components For Reliability

Physical Installation – Wiring, connectors, grounding, shielding– Short Circuit Protection

Power for Fieldbus– Redundant Power Conditioners

– Isolated Power

Control System Interface– Redundant H1 Cards

– Diagnostics, communication statistics

Devices Design and Functionality– Watchdog timer, Anti-jabber

– Diagnostics and Mode Shedding

– Failsafe mode

– Backup Link Active Scheduling Capability

Page 57: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 60

Installation

24 V DC

Power

Supply

Power

Conditioner

Power

Conditioner

Terminators

Page 58: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 61

Safer Installation

24 V DC

Power

Supply

24 V DC

Power

Supply

Power

Conditioner

Power

Conditioner

Page 59: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 62

High Availability System Design

Page 60: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 63

Installation Cost Reduced By Brick and T’s

Power

Conditioner

Terminator

Page 61: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 64

Quick connection Junction Boxes

Page 62: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 65

Gland Cap Terminator

The Components

Page 63: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 66

Terminator “T” Connector

Page 64: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 67

Typical Installation

Page 65: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 68

Typical Installation

Page 66: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 69

IDENTIFY

NUMBER &

TYPE OF

INSTRUMENTSFROM P&ID

DETERMINE

FUNCTION

BLOCK COUNT

LISTED FOR

EACH TYPE OF

INSTRUMENT

DEVELOP

INSTRUMENT

GROUPINGS

BASED ON

BLOCK COUNT

& SERVICE

CONFIGURE

INSTRUMENT

GROUPINGS

ON PLANS& SECTIONS

ESTABLISH

SPURS AND

TERMINATORS

& WIRING

LAYOUT

FOR SEGMENT

PRODUCE

SEGMENT

DRAWING

BASED ON

COMMON

COMPONENTS

PUT THE ACTUAL DRAWING TOGETHER USING COMMON CLONED

CAD BLOCKS RELATING TO PRE-ENGINEERED COMPONENTRY.

SIX STEPS TO A SUCCESSFUL DESIGN

Page 67: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 70

A SEGMENT DRAWING CAN DOCUMENT AN ENTIRE SECTION OF PLANT

Cloned CAD Blocks

Cobbled Together

Allow Segment

Drawings To Be

Assembled Quickly and Easily

(BOTH LOOPS AND

CONNECTION DRAWINGS

REPLACED BY ONE

SEGMENT DRAWING)

Backbone ID

Wire Ferrule

Relates to

Box Tag

Backbone ID

Box Tag

Relates To

Wire Ferrule

Color Coding

Eliminates Need

For Individual

Wire Tags

Spur Block When

Instruments Are Teed

Off Backbone. Always

Install Block Where Two

Or More Instruments

Are Located Together

Systematic Tagging Links the Whole

Instrumentation Complex Together

Page 68: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 71

INSTRUMENT PANEL “FRONT END”

POWER CONDITIONER

TERMINATOR BLOCK

SIGNAL TO

PROCESS CONTROLLER

FLOATING 24VDC

UNGROUNDED

POWER SUPPLY

TO

FIELD

INSTRUMENT GROUND

Page 69: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 72

“FRONT END” POWER CONDITIONERS

Page 70: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 73

“FRONT END” FLOATING SEGMENT POWER SUPPLY

Page 71: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 74

A FEW PRE-ENGINEERED ELEMENTS THAT RELATE TO THE PHYSICAL INSTALLATION SUPPORT THE SEGMENT DRAWING

TYPICAL SPUR ITB

SUPPORTING DRAWINGS

Page 72: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 75

FIELD INSTALLATION MADE UP OF PRE-ASSSEMBLED ELEMENTS

Prefabricated

Components

Allow For

Minimal

Documentation

WE USED “MC-HL”

FIELDBUS CABLE

Page 73: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 76

FASTER ENGINEERING, FASTER DESIGN AND -- MUCH FASTER INSTALLATION

Page 74: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 77

Automatic Address Assignment

Devices may be connected to the bus with the same permanent default address.

A configuration utility in the host assigns an unused valid address to each device.

This feature allows fast and safe commissioning of the Fieldbus Network!

No dip switches, no pre-configuration.

Page 75: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 78

Checkout of Fieldbus Wiring

Page 76: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 79

Required Equipment

– Battery Powered Digital Volt-Ohm Meter

– Battery Powered Scope

– Signal Generator

Page 77: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 80

Systematic Approach

– Don’t Rush

– Follow Procedures

• Grounding Checks

• Proper Voltages

• Terminators Functioning

Page 78: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 81

Verify Results

– Don’t Rush!

– Be Consistent

• Terminology

• Procedures

• Troubleshooting

• Initial Checkout

• Training

Page 79: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 82

Terminator Terminator

100 Ohms 1uF

FIELDBUS WIRING CHECKOUT BEFORE CONNECTING POWER TO THE SEGMENT

Trunk

0.01

• Check isolation between shield

and Fieldbus wires

• Check isolation between

Fieldbus wires

• Lift shield from Ground and

Check isolation between shield

and Ground

Volt/Ohm Meter

Page 80: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 83

Cable Example

Go

No-Go

Page 81: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 84

Terminator Terminator

100 Ohms 1uF

FIELDBUS WIRING CHECKOUT BEFORE CONNECTING POWER TO THE SEGMENT

Trunk

Spur

•Check termination

•Check capacitive

coupling to ground

Fieldbus checking tool

20 mA

Page 82: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 85

Terminator Terminator

100 Ohms 1uF

FIELDBUS WIRING CHECKOUT BEFORE CONNECTING POWER TO THE SEGMENT

May Be PolaritySensitive

Trunk

Spur

1. Verify connections

HMI

Page 83: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 86

Fieldbus Segment Power

Power Supply

For Multiple

SegmentsV=9-32 Volts

PowerConditioner

/Power Supply

Ground

Fieldbus

Ground

0.01

Volt/Ohm Meter

Fieldbus power, grounding installation and checkout may vary

with the components selected.

Page 84: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 87

Device Parameter Values, Links and Order of Execution Must be Loaded

Page 85: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 88

Foundation Fieldbus Devices Support Deterministic Scheduling of Control and Communications

TIC100.OUT

FIC101.OUT /BCKCAL_OUT

FCV101.

BCKCAL_OUT

TIC100.OUT

Cyclic Com.Acyclic Com.

TT

FCV

FT

macro-cycle macro-cycle

/BCKCAL_OUTFIC101.OUT

FCV101.

BCKCAL_OUT

BUS

Block Execution

Page 86: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 89

MACROCYCLE MAY BE SET BASED ON CONTROL EXECUTION REQUIRMENT

Page 87: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 90

Commissioning Fieldbus Devices -Automatic Address Assignment

Devices may be connected to the bus with the same default address.

A configuration utility in the host assigns an unused valid address to each device.

This feature allows fast and safe commissioning of the Fieldbus Network!

No dip switches, no pre-configuration.

Page 88: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 91

As New Devices Are Attached, They may be Identified and Moved to Permanent Addresses

Page 89: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 92

What Happens When Things Don’t Go Right?

Page 90: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 93

COMMON REASON FOUND FOR COMMUNICATION ERRORS ON A NEW FIELDBUS INSTALLATION

1. Missing or defective terminator at far end ofthe main segment

2. Shield or conductor has ground reference inthe field - causing ground loop.

3. Faulty or overloaded power conditioner and/or power supply

4. Loose wiring connections 5. Defective cable from manufacturer 6. Use of uncertified component or devices.

Page 91: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 94

Troubleshooting made easy

24 V DC

Power

Supply

Power

Conditioner

Terminators

19.7 V /

* Number of instruments

* Weakest signal

* LAS signal

* Voltage

* Noise level

* Peak Noise

Page 92: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 95

Fieldbus Diagnostic can easily indicatea faulty installation!

Page 93: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 96

DIAGNOSTIC SUPPORT AVAILABLE FOR FOUNDATION FIELDBUS BLOCKS

Engineering Unit Value + STATUS attributes of input and output parameters

Target and Actual attributes of Mode parameter

BLOCK_ERR Parameter

Page 94: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 97

Example

BLOCK_ERR - PROVIDES INSIGHT INTO DEVICE HEALTH AND STATE of DEVICE CONFIGURATION

BLOCK_ERR ATTRIBUTESOtherBlock Configuration ErrorLink Configuration ErrorSimulation ActiveLocal OverrideDevice Fault State SetDevice Needs Maintenance SoonInput Failure/PV Bad StatusOutput FailureMemory FailureLost Static DataLost NV DataReadback Check FailedDevice Needs Maintenance NowPower-upOut-of-Service

Page 95: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 98

STATUS ATTRIBUTE OF INPUT AND OUTPUT PARAMETERS - INDICATES QUALITY OF VALUE

ExampleSTATUS ATTRIBUTE GOODUNCERTAINNon-specificSubstitute/Manual

entryInitial ValueSensor Conversion

not AccurateEngineering Units

Range ViolationSub-normal

BADNon-specificConfiguration ErrorNot connectedDevice FailureSensor FailureNo CommunicationOut of Service

LIMIT

Not LimitedLow LimitedHigh LimitedConstant

+

Page 96: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 99

“ACTUAL” ATTRIBUTE OF MODE - REFLECTS DOWNSTREAM CONDITION AND INPUT STATUS

TARGET/ACTUAL CONDITION

(Target/Actual NORMAL

Match)

( ) / OS Device is OS

Auto, Cas / Man PV BAD

Rcas / Cas, Auto Host is NotRout / Cas, Auto Communicating

( ) / Iman No Path to Process(Downstream)

( ) / LO Fault State Active(Output Block)Input Track Active

(Control Block)

Example

Page 97: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 100

TRANSDUCER BLOCKS PROVIDE DEVICE SPECIFIC INFORMATION WHICH MAY BE HELPFUL

Page 98: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 101

COMMUNICATION STATISTICS PROVIDE INSIGHT INTO THE INTEGRITY OF THE FIELDBUS SEGMENT

Page 99: Fieldbus Tutorial Part 4 - Installation of Fieldbus

[File Name or Event]Emerson Confidential27-Jun-01, Slide 102

Summary

Observe trunk and spur lengths.

Locate the two terminators in the opposite far ends of the trunk.

Check installation according to standard wiring practices.

Limit the number of the devices on the segment according to power consumption and wire length.

Set Network Parameters based on the “slowest” device in both Primary and Backup Link Masters.

Calibrate in the Transducer Block and compensate off sets in the Analog Input Block.

For Macro cycles shorter than 250 ms, restrict the number of devices based on desired Operator Interface update.