fike sfpe webinar rev041614

52
Video Image Fire Detection Video Flame and Smoke Detection Benefits and Applications Presented by: Mac Mottley, General Manager Fike Video Image Detection

Upload: ashraf-adel-nashed-zaki

Post on 28-Dec-2015

78 views

Category:

Documents


13 download

TRANSCRIPT

Video Image Fire Detection

Video Flame and Smoke Detection Benefits and Applications

Presented by:

Mac Mottley, General Manager Fike Video Image Detection

Current State of Video Flame and Smoke Detection technology

Using existing Security Cameras

Benefit of Video Flame and Smoke Detection

Applications

Situational Awareness

“Flexible fire detection for challenging applications”

Video Image Fire Detection (VID)

Conventional detection devices are challenged by large volumes or high ceilings

Smoke Stratification Issues

Sprinkler systems designed for building protection, require heat to activate

First responders require early, “actionable intelligence” to avoid costly fire damage and firefighter injury.

Post fire event investigation

VID uses video analytics (software algorithms) to emulate human-eye fire recognition.

Analyze each frame (640 x 480) pixel by pixel using Digital Signal Processing (DSP) high and low pass filters (4.5 million data points per second)

Converts 15 frames of pixel data to one normalized pattern in one second.

Neural Network “Trained” with 1000’s of real and false fires.

Uses visible spectrum video images from stationary cameras

Looks at pixel luma value

Analytic process identifies characteristics of flames

Alarm and video output to user interface

Filter removes residual light, leaving only light that is originated from flames.

• Smoke Detection Algorithms

Smoke Signature Recognition

Smoke Aging (red-orange older, blue newer) for movement

Motion detection zones are setup in FOV

Detection zone may be attached to a schedule

Motion detection event categorized similar to a fire event

Environment Dictates Type of Housing ◦ Explosion Proof ◦ Dust or dirt ◦ NEMA 4x (water proof) ◦ Climate controlled (heat or cool) ◦ Wiper or air curtain

Handles up to 32 IP cameras

Available in 3TB (2U) and 6TB (3U) storage configurations

Wintel platform

Rack mountable

Ruggedized option available

View active alarm conditions Receive an audible voice warning Locate the event on building and site plans Coordinate response efforts

Video Management VID IP Network cameras CAT 5 Computer Cable IP Infrastructure (Switches) Network Video Recorder (NVR) Remote Monitoring Software Fire Alarm Dry contacts Monitor Module Fire Alarm Panel

Provide server based analytics to existing cameras

Enhance ROI of an installed security system

Inexpensive insurance to avoid catastrophic event

Open Network Video Interface Forum Standard ◦ Allows standard for connectivity ◦ Can now process IP cameras on a network ◦ Do not have to write multiple interface drivers

Not authorized as an NFPA / UL / FM system

Processes up to 16 ONVIF IP video feeds for smoke or fire

Recognizes ONVIF cameras on the network

Provides an ONVIF video stream for integration into third party VMS

Provides alarms and events in ONVIF format

Detection Algorithms Smoke Flame Reflected Fire Light Motion

All included on camera or VID Server Individually enabled and adjusted Detect or blocking zones (On/Off schedules) Sensitivities Time delay (Alarm verification) Relay output

Targeted Detection Reduce False Alarms

Facility Characteristic – Large Volume Space High Value Assets Desire for Security Outdoor flame detection Fire Characteristic - Visible Signature Occupant Characteristics – Trained On Site Security /

Monitoring

200 ft

100 ft

17.7.7.1 VID and all components thereof, including hardware and software, shall be listed for the purpose of smoke detection

17.7.2 VID shall comply with all of the applicable requirements of Chapters 1, 10, 14, 17, and 23 of the code ◦ Power supply criteria ◦ Communications integrity ◦ Listed for the purpose ◦ Alarm signal to FACP

17.7.7.2.1 System Shall be designed in accordance with the performance based design requirements of 17.3

17.7.7.3 Video signals generated by the cameras that are components of video image smoke detection systems shall be permitted to be transmitted to other systems for other uses only through output connections provided specifically for that purpose.

• Recognizes Use of Flame & Smoke VID Systems • Flame VID Classified as Radiant-Energy Sensing

Detector • UL – 268B Video smoke detection • FM – Uses FM 3260 (new FM 3232) and UL 268. • FM 5-48 (Jan. 2011) Recommends video smoke

detection • Property/Business Continuity vs. Life Safety

FM Global Update – January 2011

Oil and Gas Facilities Power Plants (coal and nuclear) Manufacturing facilities Aerospace & Defense Warehouses Hangars Cultural Properties Universities Transportation Engine Rooms

Large scale fire tests have been carried out by NIST in both 15m and 22m high aircraft hangars. These tests show that sprinklers can be expected to operate in these high ceiling areas as demonstrated by the following results; For the 15 m high facility “The 2.0 m diameter pan fires with heating rates ranging from approximately 5.6 MW to 6.8 MW, were the smallest size fires to activate any automatic sprinklers. The 2.5 m diameter pan fires (tests 6b and 8), which produced estimated heat release rates of 7.7 MW also activated a number of 79 °C to 93 °C automatic sprinklers.” The 79 °C sprinklers tested utilized a quick response thermal element.

100 ft Detection Range

1 ft2 Pan fires - Heptane, JP8, Alcohol, Gasoline

HRR – 150 to 200 KW

POE 4 channel

NVR

Monitor

Switch POE 4 channel

Control Room

Turbine Deck

The Risk of Fire is equal to

Probability of a Fire X

Loss associated with that Fire

High Sensitivity in High Hazard

• Stable environment

• Detect fire, smoke and possibly

fuel/oil vapor prior to fire

Who caused the fire? What caused the fire? Where is the fire? When did the fire start? How big is it?

Installed on standard PC Provides video surveillance, smoke,

flame and motion detection View and record the condition that

caused the alarm View and manage system via internet Send email alerts Audible voice warning Locate the event on building/site

plans Coordinate response efforts

Flexibility to reduce false alarms or provide targeted detection

Mask or section areas of camera view to: Disable smoke or flame detection

Enable motion detection

Scheduler allows programming to times of day and days of week

• System alarms when smoke or flame crosses plane, out of masked area

• Detection zones target specific equipment

Masking or Detect Zones

Flame Detect Zone

Smoke block RFL block

Potential false alarm

Timeline Screen

System records 24/7/365 History timeline of detected events View and download video from any time period Easily identify and download video of events Used in commissioning – eliminate false alarms

Audit Report Generation ◦ Commissioning report ◦ System tests Propane torch Smoke emitters Canned smoke Motion zones User initiated alarms

◦ Confirm original field of view

Fast Detection

IP

Coordinate response with live

video

Dry-contact

SpyderGuard Visual ID

Improved response time and situational awareness

Email message

Dial 911

Volume Detection Large coverage area Situational awareness Continuous video recording Standards and Listings

Faster detection Cost benefit Nuisance rejection Post event reconstruction NFPA 72, FM and UL

Provides a solution to fire and smoke detection in large volume facilities where

no detection has historically been deployed

Mac Mottley, General Manager

Fike Video Image Detection

E-mail: [email protected]

Webpage: www.signifire.com

Contact Information