File Note
\\GLOBAL.ARUP.COM\LONDON\BEL\JOBS\200000\271000\271309 - MS AMS1314\4 INTERNAL DATA\05 REPORTS\10 PERMITTING\UPDATED REPORTS APPLICATION 27FEB2020\15-
6_STOOKINSTALLATIES-V3-NL.DOCX
Page 1 of 5Arup | F0.15
Postal address:
PO Box 57145
1040 BA Amsterdam
Visitor address:
Naritaweg 118
1043 CA Amsterdam
The Netherlands
www.arup.com
t +31 20 3058 500
Project title Microsoft AMS13-14 Job number
271309-00
cc - File reference
-
Prepared by Sander van Rosmalen
Date
10 maart 2020
Subject i
Diesel aangedreven noodstroomaggregaten
1 Inleiding
Microsoft is voornemens om twee 36 MW datacenters te bouwen in het Agriport gebied van de
gemeente Hollands Kroon. Voor deze activiteiten dient conform de indieningsvereisten nadere
technische informatie te worden verstrekt over de diesel aangedreven noodstroomaggregaten.
2 Technische informatie
In het ontwerp zijn 2 stuks 500kW dieselgeneratoren en 40 stuks 3,3MW dieselgeneratoren
geprojecteerd. De gevraagde technische informatie van deze generatoren is in de onderstaande
tabellen weergegeven. Deze informatie is conform de technische gegevens zoals ontvangen van de
fabrikant (zie bijlagen).
3.3MW diesel aangedreven noodstroomaggregaten:
Merk: MTU type 20V4000 DS4000
Datum ingebruikname: Nog onbekend.
Soort brandstof: Diesel
Maximaal brandstofverbruik per jaar: 2862 liter/jaar
Thermisch vermogen: 8450 kW
Motorisch vermogen: 3308 kW
Nominaal vermogen: Niet opgegeven door fabrikant
Rendement Niet opgegeven door fabrikant
File Note
271309-00 10 maart 2020
\\GLOBAL.ARUP.COM\LONDON\BEL\JOBS\200000\271000\271309 - MS AMS1314\4 INTERNAL DATA\05 REPORTS\10 PERMITTING\UPDATED REPORTS APPLICATION 27FEB2020\15-
6_STOOKINSTALLATIES-V3-NL.DOCX
Page 2 of 5Arup | F0.15
500kW diesel aangedreven noodstroomaggregaten:
Merk: MTU type 10V1600 DS500
Datum ingebruikname: Nog onbekend.
Soort brandstof: Diesel
Maximaal brandstofverbruik per jaar: 375 liter/jaar
Thermisch vermogen: 1051kW
Motorisch vermogen: 407 kW
Nominaal vermogen: Niet opgegeven door fabrikant
Rendement Niet opgegeven door fabrikant
File Note
271309-00 10 maart 2020
\\GLOBAL.ARUP.COM\LONDON\BEL\JOBS\200000\271000\271309 - MS AMS1314\4 INTERNAL DATA\05 REPORTS\10 PERMITTING\UPDATED REPORTS APPLICATION 27FEB2020\15-
6_STOOKINSTALLATIES-V3-NL.DOCX
Page 3 of 5Arup | F0.15
A1 Datasheet generator MTU 20V4000 DS4000
DIESEL ENGINEMTU 20V4000 DS4000for 400V/50Hz/Standby Power/NEA (ORDE) + T ier 2 OptimizedEngine Type MTU 20V4000G9 4LF / Water Charge Air Cooling
PRODUcT HIGHLIGHTS
Optional equipment and finishing shown. Standard may vary.
// Benefits - Low fuel consumption - Optimized system integration ability
- High reliability - High availability of power - Long maintenance intervals
// MTU Onsite Energy is a single-source supplier
// Support - Global product support offered
// Standards - Engine-generator set is designed and manufactured in facilities certified to standards ISO 2008:9001 and ISO 2004:14001 - Generator set complies to ISO 8528 - Generator meets NEMA MG1, BS5000, ISO, DIN EN and IEC standards
Power Rating - System ratings: 3000 kWel - Accepts rated load in one step per NFPA 110 (US Standard for 60Hz Systems of National Fire Protection Agency) - Generator set complies to G3 according to ISO 8528-5
- Generator set exceeds load steps according to ISO 8528-5
// Performance Assurance Certification (PAC) - Engine-generator set tested to ISO 8528-5 for transient response
- 85% load factor - Verified product design, quality and performance integrity - All engine systems are prototype and factory tested
// Complete range of accessories available - Control panel - Power panel - Fuel system - Fuel connections with shut-off valve mounted to base frame - Starting/charging system - Exhaust system - Electrical driven radiator - Medium and oversized voltage alternators
// Emissions - Tier 2 optimized engine - NEA (ORDE) optimized
// Certifications - CE certification option
2 / // / MTU 20V4000 DS4000 / 50 Hz / 400V
APPLIcATION DATA➀
// Engine
Manufacturer MTUModel 20V4000G94LFType 4-cycleArrangement 20VDisplacement: l 95.4Bore: mm 170Stroke: mm 210Compression ratio 16.4Rated speed: rpm 1500Engine governor ADEC (ECU 9)Max power: kWm 3308Air cleaner Dry
// Fuel System
Maximum fuel lift: m 5Total fuel flow: l/min 27 // Fuel Consumption➁
l/hr g/kwhAt 100% of power rating: 818 205At 75% of power rating: 598 200At 50% of power rating: 429 215
// Liquid Capacity
Total oil system capacity: l 390Engine jacket water capacity: l 260Intercooler coolant capacity: l 50
// Combustion Air Requirements Combustion air volume: m3/s 4.7Max. air intake restriction: mbar 30
// Cooling/Radiator System Coolant flow rate (HT circuit): m3/h 80Coolant flow rate (LT circuit): m3/h 44Heat rejection to coolant: kW 1270Heat radiated to charge air cooling: kW 930Heat radiated to ambient: kW 105Fan power for electr. radiator (40°C): kW 105
// Exhaust System Exhaust gas temp. (after turbocharger): °C 482Exhaust gas temp. (before turbocharger): °C 693Exhaust gas volume: m3/s 11.9Maximum allowable back pressure: mbar 50 Minimum allowable back pressure: mbar –
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level). ➁ Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml. All fuel consumption values refer to rated engine power and are approximate values.
3 / // / MTU 20V4000 DS4000 / 50 Hz / 400V
■ Represents standard features Represents optional features
// Engine
■ 4-Cycle■ Standard single stage air filter■ Oil drain extension & shut-off valve
■ Closed crankcase ventilation■ Governor-electronic isochronous■ Common rail fuel injection
■ Tier 2 optimized engine■ NEA (ORDE) optimized engine
// Generator LSA 54.2 UL18 /4p (see DATA Sheet of Alternator)
■ 4 pole three-phase synchronous generator
■ Brushless, self-excited, self-regulating, self-ventilated
■ Digital voltage regulator ■ Anti condensation heater
■Protection IP23
■ Excitation by AREP + PMI■ Voltage setpoint adjustment ± 5% ■ Meets NEMA MG 132, IEC 600341■Leroy Somer low voltage generator
STANDARD AND OPTIONAL FEATURES
// System Ratings (kW/kVA)
Generator model Voltage NEA (ORDE) optimized 40°C/300m without radiator kWel kVA* AMPSLeroy Somer LSA54.2 UL18 / 4p
400V 3000 3750 5412.66 (Low volt. Leroy Somer)
cos phi = 0,8
// Cooling System
■ Jacket water pump■ Thermostat(s)■ Water charge air cooling
Electrical driven front-end cooler Jacket water heater Pulley for fan drive
4 / // / MTU 20V4000 DS4000 / 50 Hz / 400V
■ Represents standard features Represents optional features
STANDARD AND OPTIONAL FEATURES, CONTINUATION
// Control Panel
■ Pre-wired control cabinet for easy application of customized controller (V1+)
Island operation (V2) Automatic mains failure operation
with ATS (V3a) Automatic mains failure operation
incl. control of generator and mains breaker (V3b)
Island parallel operation of multiple gensets (V4)
Automatic mains failure operation with short (< 10s) mains parallel overlap synchronization (V5)
Mains parallel operation of a single genset (V6)
Mains parallel operation of multiple gensets (V7)
■Basler controller Deif controller ■ Complete system metering■ Digital metering■ Engine parameters■ Generator Protection Functions■ Engine protection■ SAE J1939 engine ECU
communications■ Parametrization software■ Multilingual capability■ Multiple programmable contact inputs■ Multiple contact outputs■ Event recording■ IP 54 front panel rating with
integrated gasket
Remote annunciator Daytank control Generator winding temperature
and temperature monitoring■ Modbus TCP-IP for complete Genset (see Basler controller)
Power Panel
Available in 600x600 mm Phase monitoring relay 230V/400V Supply for battery charger Supply for jacket water heater
Supply for anti condensation heating Plug socket cabinet for 230V
compatible Euro/USA
// Fuel System
■ Flexible fuel connectors mounted to base frame
Fuel filter with water separator Fuel filter with water separator
heavy-duty
Switchable fuel filter with water separator
Switchable fuel filter with water separator heavy-duty
Separate fuel cooler
Fuel cooler integrated into cooling equipment
// Starting/Charging System
■ 24V starter ■ Starter batteries, cables, rack, disconnect switch
■ Battery charger■ Redundant starter 2x 15kW
5 / / / / MTU 20V4000 DS4000 / 50 Hz / 400V
■ Represents standard features Represents optional features
STANDARD AND OPTIONAL FEATURES, CONTINUATION
// Exhaust System
■ Exhaust bellows with connection flange
■ Exhaust silencer with sound attenuation
//
Mounting System
■ Welded base frame ■ Resilient engine and generator mounting
■ Modular base frame design
File Note
271309-00 10 maart 2020
\\GLOBAL.ARUP.COM\LONDON\BEL\JOBS\200000\271000\271309 - MS AMS1314\4 INTERNAL DATA\05 REPORTS\10 PERMITTING\UPDATED REPORTS APPLICATION 27FEB2020\15-
6_STOOKINSTALLATIES-V3-NL.DOCX
Page 4 of 5Arup | F0.15
A2 Datasheet generator MTU 10V1600 DS500
Project AMS 13-14
Base Spec Rev. 02 Page 1
Basic Specification of
MTU Container 10V1600DS500
Project AMS 13-14
Base Spec Rev. 02 Page 2
Content
2 Product Overview ...................................................................................................................... 3
2.1 Application Data ................................................................................................................. 4
2.2 System Rating ..................................................................................................................... 5
2.3 Weights and Dimensions .................................................................................................... 6
2.4 Sound Data .......................................................................................................................... 6
2.5 Rating Definitions and Conditions ...................................................................................... 6
3 Enclosure, Frame ....................................................................................................................... 9
3.1 Base frame and engine/genset mounting ............................................................................ 9
3.2 Enclosure ............................................................................................................................. 9
4 Engine ...................................................................................................................................... 10
4.1 Electric Starting System .................................................................................................... 11
4.2 Jacket Water Heater .......................................................................................................... 12
4.3 Oil Handpump ................................................................................................................... 12
4.4 Three-way valve for fuel filling ........................................................................................ 13
4.5 Fuel pre-filter with water separator ................................................................................... 13
4.6 Fuel Tank .......................................................................................................................... 14
5 Generator ................................................................................................................................. 15
5.1 Voltage Regulator: DER1 ................................................................................................. 15
6 Controller ................................................................................................................................. 16
6.1 Modbus connectivity ......................................................................................................... 16
6.2 Telesignal MM07 .............................................................................................................. 16
6.3 Earth leakage relais ........................................................................................................... 17
6.4 Emergency Button............................................................................................................. 17
6.5 Entrance box IP67 ............................................................................................................. 18
6.6 Circuit Breaker .................................................................................................................. 18
6.7 Pack of heaters for humidity conditions ........................................................................... 19
6.8 Grounding and other protections ....................................................................................... 19
7 Certifications & Documents .................................................................................................... 20
Project AMS 13-14
Base Spec Rev. 02 Page 3
2 Product Overview
Diesel Generator Set
MTU 10V1600 DS500
Benefits
- Industry-leading average load factor
- Low fuel consumption
- Emissions optimizations available
- High availability and reliability
- Outstanding load acceptance
- Long maintenance intervals
Standards
- Engine-generator set is designed and manufactured in facilities certified to standards ISO 2008:9001
- Generator set complies to ISO 8528 and fulfills performance level G3
- Generator meets BS5000; NEMA MG 1; ISO; DIN EN and IEC standards
Optimization
- Fuel optimized
Wide Standard Scope of Supply
- 4P circuit breaker
- Island operation control panel
- Integrated fuel tank
- Industrial silencer
- Batteries & battery charger
Complete range of accessories available
- Sound attenuated enclosure
- Fuel system accessories
- Control panel & ATS
- Range of additional electronical options
Project AMS 13-14
Base Spec Rev. 02 Page 4
2.1 Application Data
Project AMS 13-14
Base Spec Rev. 02 Page 5
2.2 System Rating
Project AMS 13-14
Base Spec Rev. 02 Page 6
2.3 Weights and Dimensions
2.4 Sound Data
2.5 Rating Definitions and Conditions
Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load,
the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour
in twelve. Ratings are in accordance with ISO 8528-1, ISO 3046-1, BS 5514, AS 2789 and DIN 6271.
Average load factor: < 75%.
Derating factor:
- Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derating.
- Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature
derating.
Rated power for reference conditions at 25°C and 100m above sea level.
Project AMS 13-14
Base Spec Rev. 02 Page 7
Project AMS 13-14
Base Spec Rev. 02 Page 8
Note: Dimensions above including extended fuel tank option
Project AMS 13-14
Base Spec Rev. 02 Page 9
3 Enclosure, Frame
3.1 Base frame and engine/genset mounting
- Base frame and engine-/genset mounting
- Resilient mounting of engine and generator (Integral vibration isolated mounts)
- Formed steel base frame
- Forklift pockets integrated
- Intergrated fuel tank drain cap and level sensors
3.2 Enclosure
Standard Features:
- Sound attenuated canopy made out of high quality steel metal with powder coating
- Isolation material is Rockwool with glass fiber mat/tissue
- Reinforced lifting eye for crane lifting
- Oil sump extraction kit and bunded chassis (work as liquids retention tray)
- Integrated fuel tank with level sensor included and chassis cap
- Chassis integrated cat flap for easy access with all cables
- Direct accessible emergency stop button
Illumination:
- 2x LED light inside the canopy
Project AMS 13-14
Base Spec Rev. 02 Page 10
4 Engine
Engine Dimensions (LxWxH) mm Mass, dry kg
10V 1550 x 1258 x 1188 1827
Engine Model
Bore/stroke mm 122/150
Cylinder configuration 10 Cyl. - 90°V
Displacement/cylinder l 1.75
Displacement, total l 17.5
Fuel specification EN 590, Grade No.1-
D/2-D (ASTM D975-00)
Engine Power Definition Mass, dry kg
Prime
Power
(3B)
Continuous service,
variable load,
Load factor:
75%, Operating
hours:
unrestricted,
Notes: All dimensions are approximate, for complete information refer to the installation drawing. Power definition according to ISO 3046 (ratings also
correspond to SAE J 1995 and SAE J 1349 standard conditions). Consult your MTU distributor/dealer for the rating that will apply to your specific application.
Rated power is without fan drive. The power consumption of any fan drive has to be deducted during designing of a generator set.
Liquid-cooled, four-stroke diesel engine, counter-clockwise direction of rotation (viewed on driving end)
with the following basic equipment:
Grey cast-iron crankcase, flywheel housing SAE 01, flywheel 14”, oil pan, forged crankshaft, forged
connecting rods, four-valve cylinder head, light-metal solid skirt pistons, piston cooling via oil spray nozzle,
dry exhaust manifolds, vibration damper; all necessary on-engine air, exhaust, coolant, fuel and oil pipework.
“Common-Rail” fuel injection system, with low- and high-pressure fuel pumps, fuel pressure accumulator,
high pressure fuel lines and electronically controlled injection, fuel main filter (duplex filter), fuel priming
pump for initial system filling and venting (low-pressure system),
closed fuel system.
Forced-feed lubrication system with piston cooling, lube oil circulation pump with safety valve, lube oil
multi-stage filter, lube oil heat exchanger, oil filler neck and oil dipstick for measurement on non-running
engine, closed crankcase venting system
Exhaust turbochargers, Intercooler integrated in radiator
Mechanical driven coolant circulation pump and coolant thermostat for jacket water cooling circuit.
Project AMS 13-14
Base Spec Rev. 02 Page 11
Front type radiator for jacket water and charge air cooling circuit with integrated expansion tank.
Set of engine mounting brackets at engine free and driving end
Integrated electronic engine control and monitoring system ADEC for
- Engine speed control
- Engine monitoring and display of engine operating parameters and alarms
- Engine protection against exceeding critical operating parameters
- Automatic start sequence control
- Acquisition and display of plant-related measured data
- Communication with an external system
- fuel consumption-optimized engine version
4.1 Electric Starting System
- Electric starter (24 VDC / 2-pole)
- Battery charge alternator with ground
connection
- Starting batteries (sealed lead acid)
installed and connected to the engine
(supports/ rack included)
- Battery isolator for quick disconnection of
starting batteries
Project AMS 13-14
Base Spec Rev. 02 Page 12
4.2 Jacket Water Heater
- For pre-heating the engine prior to
operation
- Standard for all S1600 1,5 kW
4.3 Oil Handpump
- Hand pump for lube oil extraction
- Approx. 24 l/min at 88 doublestrokes per
minute
- Standard for all enclosed power units
- As option available on OPU
Project AMS 13-14
Base Spec Rev. 02 Page 13
4.4 Three-way valve for fuel filling
To use with an external tank as an option.
- The valve body is double. One valve is for
fuel suction and the other for the fuel
return of the engine.
- The installation of the valve can be
internally (with quick-connects inside the
engine compartment) or externally (with
quick-connects on the outside of the
engine compartment).
4.5 Fuel pre-filter with water separator
- Heavy duty fuel prefilter with water
separator
Project AMS 13-14
Base Spec Rev. 02 Page 14
4.6 Fuel Tank
Increased Fuel Tank Capacity of 2090 Liter:
- Metal fuel tank as sub-based tank
(delivered as separate item for optimal
container fitting)
- Only available for enclosed power units
- Increases the standard integrated fuel tank
to guarantee long operation hours up to
24h and longer
- Made of high resistance steel plates, with
interior reinforcements
- Fuel filling opening of 120mm of diameter
- Bund Retention level Alarm
Tank Capacity:
Standard Fuel tank: 740 L (Net 617 litre incl. 20% overfill)
Increased Fuel tank: 2090 L (Net 1742 litre incl. 20% overfill)
Fuel Consumption Genset:
Electrical Load: 75% 344 kVA
Running hours 1h 24h 48h
Consumption 80 L 1920 L 3840 L
*Consumption values are typical avareage value as information – only suitable or design purposes to a limited extent
Increased fuel tank (2090 L) suitable for 22 h running hours including 20% overfill margin.
Project AMS 13-14
Base Spec Rev. 02 Page 15
5 Generator
The alternators are made in compliance with the 2006/42, 2006/95, 2004/108 CEE
directives and their amendments, and the CEI 2-3, EN 60034-1, IEC 34-1, VDE 0530,
BS4999-5000, CAN/CSA-C22.2 N°14 -N°100 regulations.
Model Alternator
Name
Meccalte
Alternator
DG10V1600A1E HM355A3 ECO-40 3S/4
Brand: MECC- ALTE
- Insulation class: H- class
- Enclosure protection: IP21
- IP23 protection cover
o Cover for alternator protection
- Exciting system: A.V.R. (Electronic)
- Voltage sensing: +/- 1% for 6R or +/-
0,5% for others
- Single bearing alternator
- Poles: 4
- Winding connections: star-series
- PT100 Winding and bearing temperature
sensors
- Anti-condensation heater
- PMG- permanent Magnet Generator
5.1 Voltage Regulator: DER1
- Built in models: 10V1600
- Single and three phases sensing automatic detection
- Precision of voltage regulation: ± 0,5% in stabilized conditions (load, temperature).
Project AMS 13-14
Base Spec Rev. 02 Page 16
6 Controller
MM7 - Standard Genset Controller:
- Standard controller suitable for island
operation
o Not Included - Automatic Transfer
Switch for main control
- The control unit is a device able to control:
the operation, the monitoring and the
protection of a genset
- Features:
o Alarm History
o Pre-Heating engine control
o Fuel transfer control
o Engine temperature control
o Programmable Alarms
o Programmable Outputs
o Multilingual
6.1 Modbus connectivity
Kit CAN / MODBUS TCP/IP to communicate with an overlaid EPMS system
6.2 Telesignal MM07
Expansion module for CAN communication incl. 12 relays
- Relays: 4 switched contact and 8 single contact.
- It allows the activation of remote signalling elements.
- It allows the programing of the relays according.
Project AMS 13-14
Base Spec Rev. 02 Page 17
6.3 Earth leakage relais
The X52DS series earth leakage relays are designed to measure the leakage or unbalance currents caused by
conductors or appliances insulation losses and to react, in case the set limits are exceeded, switching off the
power supply to the defective system.
Main features and functions:
- Wide range of trip currents and delays to guarantee the necessary selectivity in order to keep in
operation the parts of the system not involved in the fault.
- Three ranges of tripping current and two of delay to increase the setting accuracy.
- Continuous check of the good connection with the toroidal transformer, performed an the measuring
winding, with trip action in case of negative result.
- Selectable manual or automatic reset.
- Selectable normal or positive safety operating mode of the trip contacts.
- Inputs for remote reset.
6.4 Emergency Button
- Direct access for user on EPU outside next
to the control panel window.
- Wired to the control panel to disrupt power
supply and operation of genset in case of
emergency.
Project AMS 13-14
Base Spec Rev. 02 Page 18
6.5 Entrance box IP67
- External armoured cable termination panel
for canopied genset 800-1000A.
- Included: power cables to connect
alternator and entrance box
- aluminum grand plate
- terminal strip to remote start and auxiliary
power line.
6.6 Circuit Breaker
Brand: Schneider Electric
- Protect the genset and the electrical
equipment.
- On standard only manual CB.
- CB model depending on the genset
Amperes
Project AMS 13-14
Base Spec Rev. 02 Page 19
6.7 Pack of heaters for humidity conditions
- Alternator anti-condensation heater
- Controller anti-condensation heater
- Enclosure preheating resistance
6.8 Grounding and other protections
Genset is completely grounded to the Baseframe
- Proof of resistance of the copper plates is
available
- Enclosure as well completely grounded
incl. doors
- For ATS grounding available as well.
Furthermore plastic protection cover is
installed to avoid direct contact
Project AMS 13-14
Base Spec Rev. 02 Page 20
7 Certifications & Documents
End of Line Test-Report
- CE- declaration of Mecc-Alte Generator
Wiring diagrams
MTU Documentation
- Genset Manual overall
- MTU Spec Sheets
- Engine Manual
- Alternator Manual
- Controller Manual
- Service plan
- Installation Drawing
- Spare Parts Catalog (on request)
- FAT-Report of Genset