fire alarm cables - tc life safety · circuit integrity fire alarm cables. for more detailed...
TRANSCRIPT
is one of the original and leadingmanufactures of Fire Alarm cables in the world.Security and Alarm cables are a vital part of thebuilding and construction industries.
Security and FireAlarm cables have been oneof the most trusted names in the Security industry.
offers the broadest line of firealarm cables in the industry! Our fire alarm cablesare designed to meet Conventional and Addressable system specifications. also offersCircuit Integrity fire alarm cables.
For more detailed information on our fire alarmcables, contact our Customer Service Department at
, or e-mail us at: . Information can also
be found on our website:
47
Mini Index
Power-Limited CablesFPLR/ Unshielded ………………………………………………………FPLR/ Shielded …………………………………………………………FPL- Low Cap/ Unshielded & Shielded……………………………FPL/ One and Two Conductor…………………………………………FPLP/ Unshielded ……………………………………………………FPLP/ Shielded ………………………………………………………FPLP/ Shielded Data Grade………………………………………
Non Power-Limited CablesNPLF/ Unshielded ……………………………………………………NPLF/ Shielded ………………………………………………………NPLFP Plenum/ Shielded & Unshielded ………………………
Circuit IntegrityCircuit Integrity in Conduit (CIC)/ Shielded…………………Circuit Integrity in Conduit (CIC)/ Unshielded………………Circuit Integrity (CI)/ Shielded…………………………………Circuit Integrity (CI)/ Unshielded………………………………
48495051525353
Over 95% of West Penn Wire cables are RoHSCompliant. For a detailed specification on individualproducts, contact our engineering department.
545556
57585960
Fire Alarm Cables
Applications:Indoor for:• Audio Circuits• Control Circuits• Initiating Circuits• Notification Circuits
Fire Alarm CablesPower-Limited Multiple Conductor/
Unshielded
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
980 1Pair
18 AWGSolid
6.5 Ω/Mft
PVC.010 None
PVC.015 .146 29 pf/ft*
RD, BK,WH, YE
982 4 18 AWGSolid
6.5 Ω/Mft
PVC.010 None
PVC.015 .178 29 pf/ft*
RD, BK,WH, YE
990 1Pair
16 AWGSolid
4.1 Ω/Mft
PVC.010
None PVC.015
.155 32 pf/ft* RD, BK,WH, YE
Standard spool size 1000ft.
Rating:• NEC Type FPLR• (UL) or (ETL)us Listed• Meets 300V requirements as specified in the NEC• Flame Rating: UL1666
Description:• ASTM bare copper • PVC insulation • Twisted pair or cabled
construction • Overall PVC jacket
992 416 AWG
Solid4.1 Ω/Mft
PVC.010
None PVC.015
.203 32 pf/ft* Red
994 1Pair
14 AWGSolid
2.6 Ω/Mft
PVC.012
None PVC.015
.195 35 pf/ft*RD, BK,BL, WH,
YE
700 414 AWG
Solid2.6 Ω/Mft
PVC.012
None PVC.015
.240 35 pf/ft* Red
998 1Pair
12 AWGSolid
1.8 Ω/Mft
PVC.012 None
PVC.015 .225 45 pf/ft* Red
Color Code- See page 49
48
Inches Inches Inches
Special Notes:• Selected Plenum Versions see pages 52• Selected Indoor/Outdoor Aquaseal Water
Resistant® Versions see pages 43.• Orange rip cord under jacket
990SNew
1Pair
16 AWGStrd.
4.1 Ω/Mft
PVC.010 None
PVC.015 .155 32 pf/ft* Red
994SNew
1Pair
14 AWGStrd.
2.6 Ω/Mft
PVC.012
None PVC.015
.195 35 pf/ft* Red
998SNew
1Pair
12 AWGStrd.
1.8 Ω/Mft
PVC.012
None PVC.015
.225 45 pf/ft* Red
Fire Alarm Cables
* Capacitance between conductors.
Applications:Indoor for:• Audio Circuits• Control Circuits• Initiating Circuits• Notification Circuits
Fire Alarm CablesPower-Limited Multiple Conductor/ Shielded
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
Thickness
Shielding& %
CoverageJacket Type& Thickness
Nom.O.D.
NECType
Nom.Capacitance
JacketColor
1083 422 AWG
Solid 17.5 Ω/Mft
PVC.010
Al. Foil100%
PVC.015 .146
54 pf/ft*97 pf/ft** Red
975 1Pair
18 AWGSolid
6.5 Ω/Mft
PVC.010
Al. Foil100%
PVC.015 .149
73 pf/ft*133 pf/ft** Red
991 1Pair
16 AWGSolid
4.1 Ω/Mft
PVC.010
Al. Foil100%
PVC.015 .160
82 pf/ft*148 pf/ft**
RD, BK,WH, YE
993 416 AWG
Solid4.1 Ω/Mft
PVC.010
Al. Foil100%
PVC.015 .207
82 pf/ft*148 pf/ft** Red
995 1Pair
14 AWGSolid
2.6 Ω/Mft
PVC.012
Al. Foil100%
PVC.015
.201 84 pf/ft*151 pf/ft**
Red
Description:• ASTM bare copper • PVC insulation • Twisted pair or cabled
construction • Overall shield 100% coverage of aluminum polyester foil binders as required with TC drain wire
• Overall PVC jacket
Rating:• NEC Type FPLR• (UL) or (ETL)us Listed• Meets 300V requirements as specified in the NEC• Flame Rating: UL1666Standard spool size 1000ft.
* Capacitance between conductors.** Capacitance between one conductor and
the other connected to the shield
999 1Pair
12 AWGSolid
1.8 Ω/Mft
PVC.012`
Al. Foil100%
PVC.015
.230 96 pf/ft*173 pf/ft**
Red
49
Special Notes:• Selected Plenum Versions see pages 53• Selected Indoor/Outdoor Aquaseal Water
Resistant® Versions see pages 44• Orange rip cord under jacket
Inches Inches Inches
Fire Alarm Cables
Color Code
AllCables
1.Black, 2. Red, 3. Brown, 4. Blue
JACKET: RD-Red, BK-Black,WH- White, YE-Yellow
977 418 AWG
Solid6.5 Ω/Mft
PVC.010
Al. Foil100%
PVC.015
.182 73 pf/ft*133 pf/ft**
Red
Applications:Indoor data cable for:• Data Circuits• Addressable Systems• Initiating Circuits• Notification Circuits
Power-Limited / Unshielded
Addressable Systems/ Data Cable
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
D980 1Pair
18 AWGSolid
6.5 Ω/Mft
Polyolefin.015 None
PVC.030 .182 16 pf/ft* Red
D982 418 AWG
Solid6.5 Ω/Mft
Polyolefin.015
NonePVC.030 .230 16 pf/ft* Red
D990 1Pair
16 AWGSolid
4.1 Ω/Mft
Polyolefin.015 None
PVC.030 .223 18 pf/ft* Red
Standard spool size 1000ft.
Rating:• NEC Type FPL• (UL) or (ETL)us Listed• Meets 300V requirements as specified in the NEC• Flame Rating: UL1685
Description:• ASTM bare copper • Polyolefin insulation • Short overall twist
lengths • Unshielded construction • Overall PVC jacket
Power-Limited / Shielded
Addressable Systems/ Data Cable
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
Thickness
Shielding&
% CoverageJacket Type& Thickness
Nom.O.D.
NECType
Nom.Capacitance
JacketColor
D975 1Pair
18 AWGSolid
6.5 Ω/MftPolyolefin
.015Al. Foil
100%
PVC.030
.210 25 pf/ft*45 pf/ft**
Red
D991 1Pair
16 AWGSolid
4.1 Ω/Mft
Polyolefin.015
Al. Foil100%
PVC.030
.226 30 pf/ft*54 pf/ft**
Red
D995 1Pair
14 AWGSolid
2.6 Ω/Mft
Polyolefin.020 Al. Foil
100% PVC.030
.262 30 pf/ft*54 pf/ft**
Red
Description:• ASTM bare copper • Polyolefin insulation • Short overall twist
length • Overall shield 100% coverage of aluminum polyesterfoil with TC drain wire • Overall PVC jacket
Standard spool size 1000ft.
* Capacitance between conductors.** Capacitance between one conductor and
the other connected to the shield
50
Inches Inches Inches
Special Notes:• Selected Plenum Versions see pages 53• Orange rip cord under jacket
Inches Inches Inches
Fire Alarm Cables
Color Code
AllCables
1.Black, 2. Red, 3. Brown, 4. Blue
JACKET: Red
* Capacitance between conductors.
Do not forget that West Penn Wire offers a com-plete and comprehensive line of:
• Connectors• Cable Assemblies• Installation Kits• Fiber Optic Accessories• A/V Wall Plates
800-245-4964 51
Applications:Indoor for:• Power-Limited Protective Circuits
Fire Alarm CablesPower-Limited One &Two Conductor/ Parallel
Description:• ASTM bare copper • PVC insulation • Two conductor parallel features- PERFECTSTRIPE®
Rating:• NEC Type FPL• (UL) or (ETL)us Listed• Flame Rating: UL1685
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
970 218 AWG
Solid6.5 Ω/Mft
PVC.032
None -- .104x.204 --RD, WH,
OR, BN, BL,BK
971 216 AWG
Solid4.1 Ω/Mft
PVC.032 None -- .115x.225 --
RD, WH,BK
972 214 AWG
Solid2.6 Ω/Mft
PVC.032 None -- .128x.250 --
RD, WH,BK
974 212 AWG
Solid1.8 Ω/Mft
PVC.032
None -- .146x.300 -- RD, BK
Inches Inches Inches
Colors
JacketColors
RD-Red, BK-BlackWH- White, YE-Yellow, OR-Orange,
BN-Brown
Fire Alarm Cables
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
962 114AWG
Solid2.6 Ω/Mft
PVC.020 None -- .104 --
BK, GN, BN,WH, RD,OR, YE
Inches Inches Inches
Single Conductor
Parallel Construction- Two Conductor
Applications:Indoor within ducts,plenums and other spacesused for environmental air:• Audio Circuits• Control Circuits• Initiating Circuits• Notification Circuits
Fire Alarm CablesPower-Limited/ Unshielded
Plenecon II ® Extra Flexible
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
60980B 1Pair
18 AWGSolid
6.5 Ω/Mft.010 None .015 .142 29 pf/ft* Red
60982B 418 AWG
Solid6.5 Ω/Mft
.010 None .015 .175 29 pf/ft* Red
60991B 1Pair
16 AWGSolid
4.1 Ω/Mft.010 None .015 .161 32 pf/ft* Red
60164B 416 AWG
Solid4.1 Ω/Mft
.010 None .015 .220 32 pf/ft* Red
60993B 1Pair
14 AWGSolid
2.6 Ω/Mft.012 None .015 .191 35 pf/ft* Red
60700B 414 AWG
Solid2.6 Ω/Mft
.012 None .015 .252 35 pf/ft* Red
60995B 1Pair
12 AWGSolid
1.8 Ω/Mft.012 None .015 .225 45 pf/ft* Red
Standard spool size 1000ft.
Rating:• NEC Type FPLP• (UL) or (ETL)us Listed• Meets 300V requirements as specified in the NEC• Flame Rating: NFPA-262 Smoke & Flame Test
Description:• ASTM bare copper • Polymer alloy insulation • Twisted pair or cabled construction • Flexible plenum jacket
52
Special Notes:• Plenum Installation Precautions see
Technical Reference Section Page 192
Inches Inches Inches
Fire Alarm Plenum Cables
Color Code
AllCables
1.Black, 2. Red, 3. Brown, 4. Blue
JACKET: Red
* Capacitance between conductors.
Applications:Indoor within ducts,plenums and other spaces used for environmental air:• Audio Circuits• Control Circuits• Initiating Circuits• Notification Circuits
Fire Alarm CablesPower-Limited / Shielded
Plenecon II ® Extra Flexible
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
Thickness
Shielding&
% CoverageJacket Type& Thickness
Nom.O.D.
NECType
Nom.Capacitance
JacketColor
60975B 1Pair
18 AWGSolid
6.5 Ω/Mft.010 Al. Foil
100% .015 .148 54 pf/ft*
97 pf/ft**Red
60977B 418 AWG
Solid6.5 Ω/Mft
.010Al. Foil
100% .015 .17854 pf/ft*97 pf/ft** Red
60990B 1Pair
16 AWGSolid
4.1 Ω/Mft.010
Al. Foil100% .015 .166
61 pf/ft*110 pf/ft** Red
603164B 416 AWG
Solid4.1 Ω/Mft
.010Al. Foil
100% .015 .21061 pf/ft*
110 pf/ft** Red
60992B 1Pair
14 AWGSolid
2.6 Ω/Mft.012
Al. Foil100% .015 .198
84 pf/ft*151 pf/ft** Red
Description:• ASTM bare copper • Polymer Alloy insulation • Twisted pair or
cabled construction • Overall shield 100% coverage of aluminumpolyester foil with TC drain wire • Flexible plenum jacket
Rating:• NEC Type FPLP• (UL) or (ETL)us Listed• Meets 300V requirements as specified in the NEC• Flame Rating: NFPA-262 Smoke & Flame TestStandard spool size 1000ft.
* Capacitance between conductors.** Capacitance between one conductor and
the other connected to the shield
60994B 1Pair
12 AWGSolid
1.8 Ω/Mft.012 Al. Foil
100% .015 .224 96 pf/ft*
173 pf/ft**Red
D60975^
1Pair
18 AWGSolid
6.5 Ω/Mft
.012 Al. Foil100%
.015 .165 25 pf/ft*45 pf/ft**
Red
D60990^
1Pair
16 AWGSolid
4.1 Ω/Mft
.015 Al. Foil100% .015 .184
30 pf/ft*54 pf/ft** Red
DATA GRADE PLENUM
^ - Data grade versions for addressable systems contain LowLoss Insulation and Overall FlexiblePlenum Jacket.
53
Special Notes:• Plenum Installation Precautions see
Technical Reference Section Page 192
Inches Inches Inches
Fire Alarm Plenum Cables
Color Code
AllCables
1.Black, 2. Red, 3. Brown, 4. Blue
JACKET: Red
Applications:Indoor for:• Audio Circuits• Control Circuits• Initiating Circuits• Notification Circuits
Fire Alarm CablesNonpower-Limited/ Unshielded
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
1990 1Pair
16 AWGSolid
4.1 Ω/Mft
PVC.016
Nylon.005
NonePVC.037 .252 -- Red
Standard spool size 1000ft.
Rating:• NEC Type NPLF• (UL) or (ETL)us Listed• Meets 150V requirements as specified in the NEC• Flame Rating: UL1685
Description:• ASTM bare copper • PVC insulation with Nylon • Twisted pair or
cabled construction • Overall PVC jacket
1994 1Pair
14 AWGSolid
2.6 Ω/Mft
PVC.016
Nylon.005
None PVC.037
.278 -- Red
54
Special Notes:• Selected Plenum Versions see pages 56• Orange rip cord under jacket
Inches Inches Inches
Fire Alarm Cables
Color Code
AllCables
1.Black, 2. Red
JACKET: Red
Applications:Indoor for:• Audio Circuits• Control Circuits• Initiating Circuits• Notification Circuits
Fire Alarm CablesNonPower-Limited/ Shielded
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
Thickness
Shielding&
% Coverage
Jacket Type&
ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
1975 1Pair
18 AWGSolid
6.5 Ω/Mft
PVC.016
Nylon.005
Al. Foil100%
PVC.037 .244
52 pf/ft*94 pf/ft** Red
1991 1Pair
16 AWGSolid
4.1 Ω/Mft
PVC.016
Nylon.005
Al. Foil100%
PVC.037 .264
57 pf/ft*103 pf/ft** Red
1995 1Pair
14 AWGSolid
2.6 Ω/Mft
PVC.016
Nylon.005
Al. Foil100%
PVC.037
.284 64 pf/ft*115 pf/ft**
Red
Description:• ASTM bare copper • PVC insulation with Nylon • Twisted pair or
cabled construction • Overall shield 100% coverage of aluminumpolyester foil with TC drain wire • Overall PVC jacket
Rating:• NEC Type NPLF• (UL) or (ETL)us Listed• Flame Rating: UL1685
Standard spool size 1000ft.
1997 414 AWG
Solid2.6 Ω/Mft
PVC.016
Nylon.005
Al. Foil100%
PVC.042 .388
64 pf/ft*115 pf/ft** Red
1999 1Pair
12 AWGSolid
1.8 Ω/Mft
PVC.016
Nylon.005
Al. Foil100%
PVC.042 .328
73 pf/ft*131 pf/ft** Red
55
* Capacitance between conductors.** Capacitance between one conductor and
the other connected to the shield
Inches Inches Inches
Special Notes:• Selected Plenum Versions see pages 56• Orange rip cord under jacket
Fire Alarm Cables
Color Code
AllCables
1.Black, 2. Red, 3. Brown, 4. Blue
JACKET: Red
Applications:Indoor for:• Audio Circuits• Control Circuits• Initiating Circuits• Notification Circuits
Fire Alarm CablesNonpower-Limited/ Shielded & Unshielded
Plenum
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
Thickness
Shielding&
% CoverageJacket Type& Thickness
Nom.O.D.
NECType
Nom.Capacitance
JacketColor
251980† 1Pair
18 AWGSolid
6.5 Ω/Mft
Fluoro-polymer
.020None .010 .185 -- Red
251975 1Pair
18 AWGSolid
6.5 Ω/Mft
Fluoro-polymer
.020
Al. Foil100%
.010 .195 -- Red
251991 1Pair
16 AWGSolid
4.1 Ω/Mft
Fluoro-polymer
.020
Al. Foil100% .010 .214 -- Red
Standard spool size 1000ft.
Rating:• NEC Type NPLFP• (UL) or (ETL)us Listed• Meets 150V requirements as specified in the NEC• Flame Rating: NFPA-262 Smoke & Flame Test
Description:• ASTM bare copper • Fluoroplymer insulation • Twisted pair or cabled
construction • Unshielded and Shielded Versions (Shielded versions)100% coverage of aluminum polyester foil with TC drain wire
• Overall fluoropolymer jacket
251994† 1Pair
14 AWGSolid
2.6 Ω/Mft
Fluoro-polymer
.020None .010 .210 -- Red
251995 1Pair
14 AWGSolid
2.6 Ω/Mft
Fluoro-polymer
.020
Al. Foil100%
.010 .220 -- Red
56
Special Notes:† Unshielded version• Plenum Installation Precautions see
Technical Reference Section Page 192
Inches Inches Inches
Fire Alarm Plenum Cables
Color Code
AllCables
1.Black, 2. Red
JACKET: Red
Applications:Indoor for:• Circuit Integrity• Fire Alarm Circuit Integrity• Survivability• Survivability from attack by fire
Circuit Integrity in Conduit/ Shielded
(CIC) - Riser Rated
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
Thickness
Shielding&
% CoverageJacket Type& Thickness
Nom.O.D.
NECType
Nom.Capacitance
JacketColor
5200FZ 216 AWG
7x244.0 Ω/Mft
CSR.035
Al. Foil100%
FRPE.056
.37 22pf/ft* Red
5100FZ 214 AWG
7x222.5 Ω/Mft
CSR.035 Al. Foil
100%
FRPE.056 .41 26pf/ft* Red
5000FZ 212 AWG
7x201.6 Ω/Mft
CSR.035
Al. Foil100%
FRPE.056 .44 27pf/ft* Red
Description:• ASTM bare copper • Ceramifiable Silicon Rubber (CSR)
Insulation • Twisted pair or cabled construction • Overall shield100% coverage of aluminum polyester foil with TCdrain wire • Overall FRPE Low-Smoke, Non-Halogen Jacket
Rating:• NEC Type FPLR• (UL) Listed• Meets 300V requirements as specified in the NEC - 105°C• Flame Rating: UL1666,
UL2196 - 2 Hour Flame Test ( in conduit only)Standard spool size 1000ft.
5220FZ 216 AWG
Solid4.0 Ω/Mft
CSR.035 Al. Foil
100%
FRPE.056 .36 20pf/ft* Red
5222FZ 416 AWG
Solid4.0 Ω/Mft
CSR.035 Al. Foil
100%
FRPE.056 .41 16pf/ft* Red
5120FZ 214 AWG
Solid2.5 Ω/Mft
CSR.035
Al. Foil100%
FRPE.056
.38 23pf/ft* Red
Color Code
AllCables
Black, Red- 4 or more are Blackand numbered
JACKET: Red
57
Inches Inches Inches
Fire Alarm Cables
* Capacitance between conductors.
Special Notes:• CSR- Ceramifiable Silicon Rubber • FRPE- Flame Retardant Polyethylene
Rating:• NEC Type FPLR• (UL) Listed• Meets 300V requirements as specified in the NEC - 105°C• Flame Rating: UL 1666,
UL2196 - Two Hour Flame Test ( in conduit only)
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
5200UZ 216 AWG
7x244.0 Ω/Mft
CSR.035 None
FRPE.056 .37 16pf/ft* Red
5100UZ 214 AWG
7x222.5 Ω/Mft
CSR.035
None FRPE.056
.40 18pf/ft* Red
Circuit Integrity in Conduit/ Unshielded
Riser Rated - (CIC)
Description:• ASTM bare copper • Ceramifiable Silicon Rubber (CSR)
Insulation • Twisted pair or cabled construction • Overall FRPE Low-Smoke, Non-Halogen Jacket
Standard spool size 1000ft.
Applications:Indoor for:• Circuit Integrity• Fire Alarm Circuit Integrity• Survivability• Survivability from attack by fire
5220UZ 216 AWG
Solid4.0 Ω/Mft
CSR.035 None
FRPE.056 .35 15pf/ft* Red
5120UZ 214 AWG
Solid2.5 Ω/Mft
CSR.035 None
FRPE.056 .38 17pf/ft* Red
58
Color Code
AllCables
Black, Red
JACKET: Red
Inches Inches Inches
Fire Alarm Cables
Special Notes:• CSR- Ceramifiable Silicon Rubber • FRPE- Flame Retardant Polyethylene
* Capacitance between conductors.
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
Thickness
Shielding&
% CoveragJacket Type& Thickness
Nom.O.D.
NECType
Nom.Capacitance
JacketColor
5320FM 218 AWG
Solid5.9 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .31 -CI 27pf/ft* Red
5322FM 418 AWG
Solid5.9 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .36 -CI 27pf/ft* Red
5300FM 218 AWG
7x265.9 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .32 -CI 27pf/ft* Red
Description:• ASTM bare copper • Ceramifiable Silicon Rubber (CSR)
Insulation • Twisted pair or cabled construction • Overall shield 100% coverage of aluminum polyester foil with
TC drain wire • Overall FRPE Low-Smoke, Non Halogen Jacket
5302FM 418 AWG
7x265.9 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .37 -CI 27pf/ft* Red
Applications:Indoor for:• Circuit Integrity• Fire Alarm Circuit Integrity• Survivability• Survivability from attack by fire
Circuit Integrity/ Shielded
(CI) - Riser Rated
Rating:• NEC Type FPLR-CI• (UL) Listed• Meets 300V requirements as specified in the NEC - 105°C• Flame Rating: UL1666, UL2196 - 2 Hour Flame TestStandard spool size 1000ft.
5220FM 216 AWG
Solid4.0 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .33 -CI 31pf/ft* Red
5222FM 416 AWG
Solid4.0 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .38 -CI 31pf/ft* Red
5200FM 216 AWG
7x244.0 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .35 -CI 31pf/ft* Red
5120FM 214 AWG
Solid2.5 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .36 -CI 33pf/ft* Red
5122FM 414 AWG
Solid2.5 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .41 -CI 33pf/ft* Red
5100FM 214 AWG
7x222.5 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .38 -CI 33pf/ft* Red
5020FM 212 AWG
Solid1.6 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .39 -CI
37pf/ft*Red
5022FM 412 AWG
Solid1.6 Ω/Mft
CSR.034
Al. Foil100%
FRPE.045 .46 -CI 37pf/ft* Red
Notes: Color Code Pg. 60
59
Inches Inches Inches
Fire Alarm Cables
* Capacitance between conductors.
CatalogNo.
No. of Cond.
ConductorType &
Nom. D.C.R
InsulationType &
ThicknessShielding Jacket Type
& ThicknessNom.O.D.
NECType
Nom.Capacitance
JacketColor
5320UM 218 AWG
Solid5.9 Ω/Mft
CSR.034 None
FRPE.045 .31 -CI 17pf/ft* Red
5220UM 216 AWG
Solid4.0 Ω/Mft
CSR.034 None
FRPE.045 .33 -CI 19pf/ft* Red
5120UM 214 AWG
Solid2.5 Ω/Mft
CSR.034
None FRPE.045
.36 -CI 21pf/ft* Red
5020UM 212 AWG
Solid1.6 Ω/Mft
CSR.034 None
FRPE.045 .39 -CI 23pf/ft* Red
Description:• ASTM bare copper • Ceramifiable Silicon Rubber (CSR)
Insulation • Twisted pair or cabled construction • Overall FRPE Low-Smoke, Non-Halogen Jacket
Circuit Integrity / Unshielded
Riser Rated - (CI)
Applications:Indoor for:• Circuit Integrity• Fire Alarm Circuit Integrity• Survivability• Survivability from attack by fireRating:
• NEC Type FPLR-CI• (UL) Listed• Meets 300V requirements as specified in the NEC - 105°C• Flame Rating: UL 1666, UL2196- Two Hour Flame Test
Standard spool size 1000ft.
5322UM 418 AWG
Solid5.9 Ω/Mft
CSR.034
None FRPE.045
.35 -CI 17pf/ft* Red
5222UM 416 AWG
Solid4.0 Ω/Mft
CSR.034
None FRPE.045
.38 -CI 19pf/ft* Red
5122UM 414 AWG
Solid2.5 Ω/Mft
CSR.034 None
FRPE.045 .41 -CI 21pf/ft* Red
5022UM 412 AWG
Solid1.6 Ω/Mft
CSR.034 None
FRPE.045 .45 -CI 23pf/ft* Red
60
Color Code
AllCables
Black, Red- 4 or more are Blackand numbered
JACKET: Red
Inches Inches Inches
Fire Alarm Cables
* Capacitance between conductors.
Special Notes:• CSR- Ceramifiable Silicon Rubber • FRPE- Flame Retardant Polyethylene