fire alarm systems chapter-8 smoke detector

Upload: acmvorg

Post on 25-Feb-2018

270 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    1/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-1

    Chapter-8

    Initiating Devices: Smoke Detectors

    Smoke detector Smoke-sensing fire detector fire alarm system smoke detector

    Smoke d

    etector

    () (able to detect fire early)

    () (allows emergency personnel to respond)

    () ( life safety) () (highly reliable)

    smokedetector ionization spot-type smoke detector photoelectric spot-type smoke detector liner beam-type smoke detector air-sampling smoke detector duct-typesmoke detector

    - (smoke detector spacing with beams less than 0.1 H.)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    2/35

    Fire Alarm Systems

    8-2

    -() Smoke detector spacing with beamdepths greater than 0.1 H and spaced more than 0.4

    H.

    -() Smoke detector spacing with beamdepths greater than 0.1 H and spaced less

    than 0.4 H.

    - (smoke) (stratification)

    -Air sampling detector smoke detector heat detector

    -Smoke detector with protectivemechanical guard

    -Ceiling jet formed by fire plume

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    3/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-3

    ..

    smoke detector (ambient conditions exist)() () (temperature below 32F (0C))

    () () (temperature above 100F (38C))

    () (relative humidity above 93 percent)

    () 300 ft/min(300 ft/min or 1.5 m/sec)

    ..

    Smoke d

    etector

    Smoke detector (environmental conditions that influence smoke detector response)

    Air Velocity Altitude Temperature

    >300 ft/min >3000 ft Humidity 100F Color of

    Protection (>91.44m/min) (>914.4 m) >93% RH (37.8C) SmokeIon X X X X O

    Photo O O X X X

    Beam O O X X O

    Air sampling O O X X O

    X: Can affect detector response. O: Generally does not affect detector response.

    ..

    Smoke Detector

    Smoke detector ()

    () Photoelectric () Ionization

    . Ionization Detectors

    () Ionization detector ionization chamber ionizing radiation (source) Ionizing radiation Americium-241 Ionization chamber Alpha particles(helium nuclei) () (+ve plate) (-ve plate) () (+ve plate) (-ve plate)

    () (ionizationchamber) () current smoke detector activate

    Smoke detector heat detector alarm activate (very early in a fires development or incipient stage) Photoelectric smoke detector (smoldering fire)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    4/35

    Fire Alarm Systems

    8-4

    (flaming fire) (smoldering) reset

    -() Multi-criteriadetector

    () Projected beamtype smokedetector with reflector.

    () Typical projected beamtypesmoke detector.

    -Device programmingunit and smoke detector.

    Addressable smoke detector

    showing programming switches.

    Typical spot type smoke detector.

    -() Initiating device base showing

    duplicate terminals.

    -() Smoke detector with base showing incoming

    and outgoing terminals.

    Photoelectric smoke detector (1) optical chamber

    (2) cover

    (3) case moulding

    (4) Photodiode (detector)

    (5) infrared LED

    -Photoelectric smoke detector

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    5/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-5

    -Manufacturers calibrated test instruments

    -Photoelectric smoke detectorSensing chamber in a photoelectric smoke

    detector. Smoke particles deflect the light

    beam and trigger the alarm.

    -Circuit of an ion chamber detector.Combustion particles reduce electrical flow and

    trigger the alarm.

    -Typical single- station smoke alarm -Operation of an ionization smoke detector

    -Technician removing wire from device -Aerosol smoke product for functional

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    6/35

    Fire Alarm Systems

    8-6

    to check electrical supervision test of a smoke detector

    -Functional test of a smokedetector

    -Technician using aheat detector tester

    -Compressed-airsmoke detector cleaner

    Ionization smoke detector (sensing chamber/metal chamber) (ionization ) (radioactive material) (radioactive material) radiation

    (low, and steady electrical current) Electrode current

    (smoke particles) chamber (air molecules) (ionize) electrode conductivity Conductivity electronic circuit current fire alarm signal Conductivity (pre-set threshold) fire alarm signal

    -Ionisation type smoke detector : Normal operation -Fire operation

    Photoelectric optical smoke detector (smoulderingfire) (more sensitive to largeparticles) flaming fire (lesssensitive to small particles)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    7/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-7

    -Ionization smoke detector

    -Ionization smoke detector

    .

    .

    Ionization Smoke Detector

    Advantages)

    () (detects invisible products of combustion)

    () (aerosol) (detect other aerosol)

    () (quick acting)

    () Clean room computer room

    .

    .

    Ionization Smoke Detector

    Disadvantages)

    () (detects the

    Ionisation type smoke detector (fast flaming fires) reset (automatically resets when the atmosphere clears)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    8/35

    Fire Alarm Systems

    8-8

    presence of smoke only, not toxicity)

    () False alarm (high false alarm rate)

    () (radioactive material) (hazardsfor ionization detection)

    -Operation of a photoelectric light obscuration smoke detector

    -Photoelectric light-scattering smoke detector

    .Photoelectric Light-Scattering Smoke Detector

    .

    .

    Light-Scattering Smoke Detector

    Photoelectric light-scattering smoke detector (light source) (photosensitive sensor) Light Emitting Diode(LED)(light source) Dark chamber (beam of light) photo diode chamber

    photosensitive sensor Light source (rays)photosensitive sensor

    -Operation of a photoelectric light-scattering smoke detector

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    9/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-9

    (smoke particle) (chamber) photo cell (smoke particle) (light path) (reflection) (scattering) Photo cell photo cell current current

    firealarm signal

    -Circuit of photoelectric smoke detector

    -Ionization smoke detector -Projected-Beam smoke detector

    ionization smoke detector photoelectric smoke detector System smoke detector Ionization smoke detector Photoelectric smoke detector Photoelectric smoke detector smoldering fire sensitive

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    10/35

    Fire Alarm Systems

    8-10

    -Light-Scattering smoke detector -Reflected type beam smoke detector

    -Photoelectric smoke detector

    -Smoke detector Smoke alarm Intelligent smoke detector

    ..Photoelectric Smoke Detector

    Advantages)

    () (sensitive to visual particles of smoke)() (detects smothering low heat fires)() (provide early warning)

    ..Photoelectric Smoke Detector

    Disadvantages)

    () (early contamination by dust causing reduced sensitivity)

    () (detects presence of smoke, not toxicity)() (must be cleaned on a regular basis)() False alarm (high false alarm rate)

    .

    .

    Photoelectric Detectors

    Locations)

    (office) clean rooms raised floor spaces (computer rooms) (telecommunications rooms) (electrical equipment rooms)(sleeping rooms) smoke detector

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    11/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-11

    -Photoelectric type smoke detector : Normal operation

    -Photoelectric type smoke detector : Fire situation

    -Beam detector deflection characteristics (Vertical plane view)

    .Beam Smoke Detector

    Photoelectric device (light beam) Photocell activate

    -Photoelectric linear projected beam smoke detector(Light obscuration smoke detector)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    12/35

    Fire Alarm Systems

    8-12

    (diffusing the projected light beam by a specified percentage of obstruction)beam detector alarm Beam blockage trouble signal Optical Beam Detectors

    -Beam detector coverage characteristics (Horizontal Plane View)

    -Beam Detector Spacing

    -Sitting of supplementary optical beam detectors

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    13/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-13

    Optical Beam Detector Difficult access for detector installation, maintenance, testing and replacement

    Exposure to direct sunlight

    Multiple reflective surfaces causing false alarms

    Building movement

    Multi-level detection Aesthetics

    Smoke detector false alarm () Cooking smoke () Spray paint() Steam from a hot shower () Sanding dust() Dust stirred up while cleaning () Solder smoke

    .Ion Smoke Detector Photo Smoke Detector Sensitivity)

    ) Ion Detectors

    Ion smoke detector sensing chamber (ionizes) (smaller smoke particles) smoldering fire (large

    particles) smoldering fire sensitivity (smaller smoke particles) oversensitive

    (ionization )

    ) Photo Detectors

    Photo smoke detector chamber smoke particle (reflection) Photo smoke detector smoldering fire (larger smoke particle) (flaming fire) (small particles) smoldering fire sensitivity (large particles) oversensitive

    Flaming fire (small particles) Smoldering fire (large particles)

    Smoke detector

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    14/35

    Fire Alarm Systems

    8-14

    smoke detector Ion Photo combined smoke detector (enclosure) ion smoke detector photo smoke detector Combinedsmoke detector smoldering fire (largeparticles) flaming fire (small particles)

    Combination smoke detector less sensitive false alarm

    -Pendant-mounted air duct installation. Inlet tube orientation.

    .. Smoke Detector Location)

    Beam (affect air flow) () smoke detector beam (underside) (open areas) flat ceiling smokedetector (distance between smoke detectors)(.)

    .Air-sampling Smoke Detector

    Air-sampling smoke detector (tubing) (samplingport) (protected space) (smoke particles)

    detection chamber (particle)detector fire alarm signal

    -Aspirating detector ceiling mounted pipework

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    15/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-15

    .Air Sampling Smoke Detectors

    air-sampling system Air sampling aspirating type fire detection system ()(fiveprimary components)

    () Air-sampling system () Detector

    () Aspiration system () Control system () Filter assembly

    -Use of Sampling Tubes to Convey Smoke-Laden Air to the Central Detection Unit of an Air-Sampling Detector.

    -Air SamplingType SmokeDetectors

    -Air Sampling Smoke Detector with CoverRemoved

    -Internal View of a Duct-Type Smoke Detector.

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    16/35

    Fire Alarm Systems

    8-16

    .Air Duct-type Smoke Detector

    Air ductsmoke detector (detect) duct (air outlet) Heating, ventilation and AirConditioning (HVAC) system

    Air duct smoke detector () (area smoke detection)()(early warning)() (buildings regular fire detection system)

    -Duct detectors -Duct-type smoke detector

    ..Duct Detectors

    () Duct detector photoelectric detector Duct (outside the ductwork) Duct (sample the air

    inside the duct) ductprobe () Smoke control device duct

    (control the flow of air in ductwork)Air Handling Unit(AHU)

    Table 8-1 Environmental Conditions that Influence Smoke Detector Response

    Detection

    Protection

    Air Velocity

    >91.44 m/min

    (>300 ft/min)

    Altitude >

    9.4.4 m (>

    3000 ft)

    Humidity >

    93% RH

    Temperature

    37.8C

    (100F)

    Color of

    Smoke

    Ion X X X X OPhoto O O X X X

    Beam O O X X O

    Air sampling O O X X O

    X = Can affect detector response.

    O = Generally does not affect detector response.

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    17/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-17

    . Smoke Detector Placement)

    smoke detector nationaland local standard manufacturers specification Smoke detector NFPA 72 () feet(9m) apart Firedetection and fire alarm systems for buildings(BS 5839-1:2013) () ()

    -Smoke detector with listed heatdetection

    -Duct probe unit installed in return air duct

    -Partitions extending higher than 85 percent of the floor-to ceiling height (thickness of the ceiling jet)

    ()()(approximately one-tenth the floor-toceilingheight.) () (8 ft (2.4 m ceiling) ceiling jet thickness

    ()9.6 in. (244 mm) () joist heat detector ceiling jet

    (Locating a heat detector on the bottom of a 4

    Spot-type smoke detector (area of coverage) 21 feet(6.5m) Detector (L) (W)() (9.1m) (diagonal measurement) 42feet (13m) detector

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    18/35

    Fire Alarm Systems

    8-18

    in. (100 mm) joist would place the detector in the center of the ceiling jet, an ideal location for

    undelayed response.)

    detector () (space is not accessible

    for storage purposes)

    () (steam pipes) (electric wiring)(conveyors) equipment

    () (floor over the space is tight)

    () detector (No flammable liquids are processed,handled, or stored on the floor above)

    -Detector coverage and spacing under flat ceilings

    -Detector coverage for pitched

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    19/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-19

    -Ceiling Obstructions Treated as Walls

    -Proximity of Detectors to Ceiling Fittings

    -Horizontal ceiling comprising a series of small cells (Honeycomb Ceilings)

    .Detector Coverage)

    Detector (constructioncharacteristics) () Corridors () Pitched ceilings() Flat ceilings () Shafts/Flues

    () Honeycomb ceilings () Stairways

    Detector detect (range) Smokedetector heat detector detect smoke detector coverage heat detector detector

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    20/35

    Fire Alarm Systems

    8-20

    Spacing and Siting of Detectors for Honeycomb Ceilings(Horizontal ceiling comprising a series of

    small cells)

    .Detector

    Conventional addressable analog addressable fire alarm system detector (fullcoverage) detector (environment) (potential fire hazards)

    detector

    -Joists: 3 ft (0.9 m) or less on center, more than 4 in. (100 mm) deep Beams: More than 3 ft(0.9 m) on center, more than 4 in. (100 mm) deep Effect of Joists and Beams on the Ceiling Jet.

    .

    Environmental and Fire Type Considerations

    detector smoke detector

    heat detector flame detector smoke detector activate

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    21/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-21

    (areas with materials that overheat, smolder, or

    ignite) (electrical equipment) ( paper) (wood) (visible smoke is the first indicator a fire has started) optical(photoelectric) smoke detector (best protected)

    ionization smoke detector detector

    .

    Selection of Detectors for Different Area

    S.No Plant Area Type of Detector

    1

    Main control room, Computer

    room, Electronic cubicle

    room and control rooms in

    outlying areas.

    Combination of - Ionisation smoke detector and Optical

    type smoke detector

    2

    Switchgear rooms in main

    Plant and outlying areas,

    battery charger room, record

    and shift-in-charge engineers

    room

    Ionisation type smoke detector.

    3 Office rooms / storage rooms Ionisation type smoke detector

    4Battery rooms and

    chemically corrosive areas.

    Corrosion resistant, Rate of rise of temperature heat

    detector with fixed temperature setting.

    5 Cable gallery

    Combination of Optical type smoke detectors and Linear

    heat sensor running above all HV and LV power cable trays.

    Unless the vertical distance between cable tray is less than

    500 mm in which case alternate trays (in addition to the top

    and bottom trays). The optical smoke detector and LHS

    detectors along with necessary number of interface units in

    the cable gallery will be cross zoned to actuate the water

    spray system

    6 Station building / Plant area Infrared flame detectors (where oil tanks are located),spray tanks rate of rise of temp. detector with fixed element

    ( combustible materials) detector (combustible materials) detector

    flame detector

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    22/35

    Fire Alarm Systems

    8-22

    . Smoke Detector

    Smoke detector (power sources)() (can be batteries or household power)

    () smoke detector (battery operated are easy to install and are economical to purchase)

    () (independent of housepower so they will operate during power failures)

    ()British Standard fire code smoke detector (British Standard fire code will permit battery operated units (existing buildings))

    () hard wired smoke detector (British Standard building code requires hard wired smoke alarms for new construction)

    () (should install both on every level of homeplus in the sleeping rooms.)

    () smoke alarm (British Standardfire code (British Standard fire code requires hard wired smoke alarms fornew construction)

    () (lack of maintenance (ie. not replacing batteries) is greatestconcern)

    .

    Fire Detector

    Criteria to Determine Layout)

    () operation (design, construction and operational features of all types ofdetectors shall be in accordance with relevant standards.)

    ()fire detector

    () (total area to be protected)() (type of building construction)

    () (air movement & air velocity)() (ceiling obstructions)() equipment (concentration of equipment in the area covered)()sensitivity

    () (area is divided into zones to be protected)

    () detector detector (the zones of individual detectors should overlap and no blind zone shouldbe left. )

    () (Areas above false ceiling and below false flooring shall be considered as

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    23/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-23

    separate zones.)

    () detector (Under ideal conditions of smooth ceiling and average roomsize, one detector is recommended to protect the area.)

    () (largest combustible gas concentration) ionisation detector

    () (air conditioned areas) ionization optical typesmoke detectors

    ()Detector (highest point of the ceiling) (manufacture) minimum coverage

    ()Complete coverage detector (location)

    ()smoke detector () () () (35to 40 sq.m per detector for general application.)

    ()Main control room electronic cubicle room computer room ()()(20 to 25 sq.m per detector)

    () IS/NFPA (the exact requirementshall calculated based on relevant IS/NFPA standard)

    Table 8-5 Common sources of aerosols and particulate matter moisture

    Moisture Humid outside air

    Humidifiers

    Live steam

    Showers

    Slop sink

    Steam tables

    Water spray

    Atmospheric

    contaminants

    Corrosive atmospheres

    Dust or lint

    Excessive tobacco smoke

    Heat treating

    Linen and bedding handling

    Pneumatic transport

    Sawing, drilling, and grinding

    Textile and agricultural

    processing

    Combustion

    products

    and fumes

    Chemical fumes

    Cleaning fluids

    Cooking equipment

    Curing

    Cutting, welding, and

    Engine

    exhaust

    Diesel trucks and locomotives

    Engines not vented to the

    outside

    Gasoline forklift trucks

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    24/35

    Fire Alarm Systems

    8-24

    brazing

    Dryers

    Exhaust hoods

    Fireplaces

    Machining

    Ovens

    Paint spray

    Heating

    element with

    abnormal

    conditions

    Dust

    accumulations

    Improper

    exhaust

    Incomplete combustion

    Smoke detector (sources of electrical and mechanicalinfluences on smoke detectors)

    Electrical Noise and Transients Airflow

    Vibration or shock

    Radiation

    Radio frequency

    Intense light Lightning

    Electrostatic discharge

    Power supply

    o Gusts

    o Excessive velocity

    - Smoke detector with protective plasticcover.

    - Concealed Smoke Detector(SD) inLocked Room with Remote Indicator(RI).

    detector (predicting detector response)

    (anticipated fires) system(intended respond) ()(ceiling shape and surface)

    ()(ceiling height)

    () (configuration of contents in the protectedarea)

    () (combustion characteristicsand probable equivalence ratio of the anticipated fires involving the fuel loads within the

    protected area)

    ()(compartment ventilation)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    25/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-25

    () (ambient temperature, pressure,altitude, humidity, and atmosphere)

    Table 8-x Comparison of combination, multi-criteria, and multi-sensor detectors

    Detector Type Features

    Combination

    Multiple sensors

    Does not utilize a mathematical evaluation principle, just a simple or functionMultiple listings

    Multi-criteria

    Multiple sensors

    Mathematically evaluated

    Only one alarm signal

    Single listing

    Multi-sensor

    Multiple sensors

    Mathematically evaluated

    Capable of generating multiple alarm signals

    Multiple listings

    .Mounting

    -Mounting installations permitted (top) and not permitted (bottom).

    .Detector Spacing)

    beam detector (for sloping ceilings with beams running perpendicular across slope, the fol-lowing shall apply)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    26/35

    Fire Alarm Systems

    8-26

    () Spot-type detector beam (bottom of the beams)() (average height over slope)(ceiling height)

    () (spacingshall be measured along a horizontal projection of the ceiling)

    () Beam (smooth ceiling spacing shall be permitted within beam pockets)

    () % beam spot type detector (For beam depths less than or equal to 10 percent of theceiling height (0.1 H), spot-type detectors shall be located with smooth ceiling spacing.)

    () 0.4H % % beamspot-type detector (For beam depths greater than 10 percent of theceiling height (0.1 H), spot-type detectors shall not be required to be located closer than (0.4 H)

    and shall not exceed 50 percent of smooth ceiling spacing.)

    beam (for sloping ceilings with beams running parallel up slope, the following shall apply)() Spot-type detector(s) shall be located on the ceiling within beam pocket(s).

    () The ceiling height shall be taken as the average height over slope.

    () Spacing shall be measured along a horizontal projection of the ceiling.

    () Smooth ceiling spacing shall be permitted within beam pocket(s) parallel to the beams.

    () For beam depths less than or equal to 10 percent of the ceiling height (0.1 H), spot-type detectorsshall be located with smooth ceiling spacing perpendicular to the beams.

    () For beam depths greater than 10 percent of the ceiling height (0.1 H), the following shall applyfor spacing perpendicular to the beams.

    () For beam spacing greater than or equal to 40 percent of the ceiling height (0.4 H), spot-typedetectors shall be located in each beam pocket.

    () For beam spacing less than 40 percent of the ceiling height (0.4 H), spot-type detec-tors shall notbe required in every beam pocket but shall be spaced not greater than 50 percent of smooth

    ceiling spacing.

    beam (for sloped ceilings with beam pockets formed by intersectingbeams, the following shall apply)

    () Spot-type detector(s) shall be located at the bottom of the beams.

    (

    ) The ceiling height shall be taken as the average height over slope.

    () Spacing shall be measured along a horizontal projection of the ceiling.

    () For beam depths less than or equal to 10 percent of the ceiling height (0.1 H), spot-type

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    27/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-27

    detectors shall be spaced with not more than three beams between detectors and shall not

    exceed smooth ceiling spacing.

    () For beam depths greater than 10 percent of the ceiling height (0.1 H), spot-type detectors shallbe spaced with not more than two beams between detectors, but shall not be required to be

    spaced closer than (0.4 H), and shall not exceed 50 percent of smooth ceiling spacing.

    -High Air Movement Areas (Not to Be Used for Under-Floor or Above-Ceiling Spaces).

    Smoke Detector Spacing Based on Air Movement

    Smoke Detector Spacing Based on Air

    Movement

    Minutes per

    Air Change

    Air

    ChangesSpacing per Detector

    per Hour ft2 m2

    1 60 125 12

    2 30 250 23

    3 20 375 35

    4 15 500 46

    5 12 625 58

    6 10 750 70

    7 8.6 875 81

    8 7.5 900 84

    9 6.7 900 84

    10 6 900 84

    -Ceiling height limits (general)

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    28/35

    Fire Alarm Systems

    8-28

    -Remote Indicator Used for Concealed

    Detectors.

    -Beam Measurements for predicting

    effects on detection

    -Four-Wire Smoke Detectors Supervised for the Absence of Operating Power by an End-of-Line Power Supervision Relay.

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    29/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-29

    -Alarm verification timing diagram.

    ASmoke detector goes into alarm.ABRetard-reset period (control unit)

    Control unit senses detector in alarm and retards (delays) alarm signal, usually by de-

    energizing power to the detector. Length of time varies with design.

    BCRestart period (detector power-up time)Power to the detector is reapplied and time is allowed for detector to become operational for

    alarm. Time varies with detector design.

    ACRetard-reset-restart periodNo alarm obtained from control unit. Maximum permissible time is 60 seconds.

    CDConfirmation periodDetector is operational for alarm at point C. If detector is still in alarm at point C, control unit

    will alarm. If detector is not in alarm, system returns to standby. If the detector re-alarms at

    any time during the confirmation period, the control unit will alarm.

    DEOptional region

    Either an alarm can occur at control unit or restart of the alarm verification cycle can occur.

    ADAlarm verification period

    Consists of the retard-reset-restart and confirmation periods.

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    30/35

    Fire Alarm Systems

    8-30

    -Inclined Manometer for Velocity Pressure Readings in Low Velocity Ducts, 400 ft/min to 2000ft/min (2.0 m/sec to 14.2 m/sec).

    -Smoke Alarm with IntegralNotification Appliance for the Hearing

    Impaired.

    -Single-Station Smoke Alarm with RemoteNotification Appliance.

    If appropriate, the Plans and Specifications addressed in D.3.3 should be updated based on the resultsof the test.

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    31/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-31

    -Hard-Wired Multiple-Station(Interconnected) Smoke Alarms.

    -Multiple- Station Smoke Alarm AuxiliaryRelay Module for Remote Notification Appliance.

    -Wireless Interconnected Multiple- StationSmoke Alarm Device.

    -AC-Powered Ionization Smoke Alarm withBattery Backup.

    -Fixed- Temperature Combination SmokeAlarm and Heat Alarm.

    -Low-Profile Rate-of-Rise Heat Detector.

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    32/35

    Fire Alarm Systems

    8-32

    -Wireless Interconnected Multiple- Station Smoke Alarms.Table 8-5 Ceiling height limits (general).

    Table 8-6 Ceiling height limits (category P systems and 5 minute fire service attendance).

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    33/35

    Chapter-8 Initiating Devices: Smoke Detectors

    8-33

    Table 8-7 Ceiling height limits (category P systems and 5 minute fire service attendance).

    -End-

    Contents

    .. ...........................................................................................

    ..Smoke detector .........................................................

    ..Smoke Detector ...............................................................................................

    .Ionization Detectors ....................................................................................................... 3

    ..Ionization Smoke Detector (Advantages) .................................................

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    34/35

    Fire Alarm Systems

    8-34

    ..Ionization Smoke Detector (Disadvantages) .........................................................

    .Photoelectric Light-Scattering Smoke Detector .................................................................. 8

    ..Light-Scattering Smoke Detector .................................................................................

    ..Photoelectric Smoke Detector (Advantages) .....................................................

    ..Photoelectric Smoke Detector (Disadvantages) ..................................................

    ..Photoelectric Detectors (Locations) ...........................................

    .Beam Smoke Detector .................................................................................................. 11

    .Ion Smoke Detector Photo Smoke Detector(Sensitivity) .................... 13

    ..Smoke Detector(Location) ..............................................................................

    .Air-sampling Smoke Detector ......................................................................................... 14

    .Air Sampling Smoke Detectors ....................................................................................... 15

    .Air Duct-type Smoke Detector ........................................................................................ 16

    ..Duct Detectors .............................................................................................................................

    .Smoke Detector (Placement) .................................................................... 17

    .Detector (Coverage) ................................................. 19

    . Detector ................................................................................................... 20

    .Environmental and Fire Type Considerations ................................................................. 20

    .Selection of Detectors for Different Area ....................................................................... 21

    .Smoke Detector .............................................................. 22

    .Fire Detector (Criteria to Determine Layout) ......... 22

    .Mounting ................................................................................................................... 25

    .(Detector Spacing) ................................................................. 25

  • 7/25/2019 Fire Alarm Systems Chapter-8 Smoke Detector

    35/35

    Chapter-8 Initiating Devices: Smoke Detectors