Page 1: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

FIRE DAMPERS

WE SAVE

LIVES

PRODUCTS CATALOGUE

PRODUCTS BULLETIN

Page 2: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

Dubai Head Office:

Tel: +971 4 706 97777Fax: +971 4 706 9787

Abu Dhabi Branch:

Tel: +971 2 645 0107Fax: +971 2 645 0167

Email: [email protected]

P.O. Box 50708, DubaiUnited Arab Emirates

w w w . b e t a g . c o m

Page 3: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

FDF FIRE DAMPER FOR STATIC SYSTEMS

FDC FIRE DAMPER FOR STATIC SYSTEMS

FDC FIRE DAMPER FOR DYNAMIC SYSTEMS

ACCESS DOOR

1- 4

5-9

10-14

15-16

index

Page 4: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

FEATURES:– U.L. Classified for static system in accordance with UL 555 & NFPA 90A.– Civil Defense approved– Fire rated for 1½ hour.

CONSTRUCTION– Casings: 1.2 mm thick manufactured from corrosion resistant galvanized mild steel– Blades: Rollformed single skin interlocking galvanized curtain shutter of 0.8 mm thk– Blade guide / Locking ramps: Galvanized steel locking ramps ensures positive blade closure within integral blade guide.

o– Fusible Link: Typical “two-pleces” fusible links rated at 165 F.– Springs: Stainless steel coil tension spring.– Mounting; Horizontal / Vertical– (Installation as per instruction on page no 4)– Sizes: Maximum Width 31” & Maximum Height 33” (Out to Out)– Sleeves: are optional. details are as per pages 3 & 4

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

CasingsManufactured from corrosionResistant galvanized steel asStandard

Blade guide /Locking rampsGalvanized steel locking ramps ensurespositive blade closure within integralblade guides.

SpringsStainless steel coil tensionspring ensuring powerful bladeclosure when appropriate

Fubible links /release mechanism

Typical “two-pieces” fusible linksOrated at 165 F

Alternative temperature rated fusiblelinks mechanisms available

Blades

(Rollformed single skin interlockinggalvanized high integrity curtain shutterof 0.8 mm thickness)

FIRE DAMPER FOR STATIC SYSTEM - FDF MODEL - SINGLE SECTION

FIRE DAMPER MODEL FDF

Page 5: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

25MM

80MM

H -

5 M

M

30

” M

AX

H +

20

+ X

MM

30” MAX

W - 5 MM

W + 40 MM

100% Free Area fire damper FDFFigure - 2

X-DIMENSIONAL

FDF

Height(mm)

X(mm)

100-400

401-750

40

60

FIRE DAMPER MODEL FDF

Page 6: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

Surrounding Masonry Floor or Wall

EXPANSION GAP

Mounting Channel

D U C Tby others

D U C Tby others

FIRE DAMPER MODEL FDF

TYPE MOUNTING SIZE OPTIONS

FDS - SLEEVE

Size: Width x Height

H: HORIZONTAL

V: VERTICAL

FDF: 100% Free area fire damper

Figure - 3

ORDERING SYSTEM

COVER ANGLE

M6 Bolt & Nut

SLEEVE

BLADE

FUSIBLE LINK

M6 Bolt & Nut

FDP Firedamper

BLADE RAMP

SPRING

Surrounding Masonry Floor or Wall

38x38x3mm thk

2

3

4

5

1

7

Duct Sleeve Connection

90mmas a minimum

152mm maximum

CROSS – SECTION DETAIL

FIRE DAMPER MODEL FDF

7

6

Page 7: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

1 >> The damper should be installed centrally within surrounding masonry floor or wall

2>> The damper should be installed in a rectangular galvanized steel sleeve with a min. thickness of 1.2 mm This sleeve

should be attached to the damper not to the builder’s work using the mounting channels by 6mm dia bolts spaced at not

more than 255mm centres. Bolts for mounting channels located maximum 45 and 145 mm from corners of sleeve and frame,

perspectively.

3>> The damper is suitable only for rectangular space and can not be used for annular space.

4>> Allowance for expansion between sleeve and builder’s work in both horizontal and vertical planes to be 3mm per 305mm

of length.

5>> The sleeve should be of suitable length to extend through the wall to enable the fitting of the cover angles and

ductwork. Minimum of 90mm and maximum of 152mm beyond the floor or wall.

6>> The cover angles should be attached to the sleeve by 6mm dia bolts at a minimum of 225mm centres, and should

form a complete frame around the sleeve and cover over the expansion gap required between sleeve and wall opening. The

four corner of the cover angles are not to be welded.

The bolts connecting the cover angles to the sleeve to be 102mm maximum from the corners.

7>> The expansion gap should be filled with compressible, non-combustible material (mineral wool).

8>> The cover angle should be of such a size as always to from a cover over the wall opening by 25mm minimum and should

be manufactured from a minimum size of 38*38*3mm steel angle

9>> A fusible link UL tested Elsie brand which is rated at 165 degree F is used.

10>> The duct-sleeve connection to be of double “S” slip type.

Breakaway joints shown shall have no more than two No. 10 (4.8 mm dia.) sheet metal screws on each side and on the

bottom located in the center of the slip pocket and shall penetrate both sides of the slip pocket.

Breakaway joints for horizontal ducts (vertical fire damper) shall be provided on the top, bottom and on the sides with double

“S” slip type as illustrated.

Breakaway joints for vertical ducts (horizontal fire damper) shall be provided on both other opposite sides with double “S”

slip type.

Connecting ducts shall not be continued and shall terminate at the sleeve. Installation shall comply with NFPA 9OA.

11>> All fixing of frames must be positioned clear of damper blade path so as not to impede proper closure.

7

2

5

4

6

6

3

1

1

2

FIRE DAMPER MODEL FDF

INSTALLATION & OPERATING INSTRUCTIONS

3

Page 8: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

FIRE DAMPER FOR STATIC SYSTEM - FDC MODEL - SINGLE & MULTIPLE SECTIONS

SINGLE SECTION

MULTIPLE SECTION

FDC (NOT 100% FREE AREA)

FDC (NOT 100% FREE AREA)

FDC (100% FREE AREA)

FIRE DAMPER MODEL FDC

Page 9: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

– UL classified for static systems in accordance with UL 555 & NFPA 90A

– Civil Defence ApprovedO– Fusible link set at 165 F

– Fire rated for 1½ hour

– Mounting type: vertical

FEATURES:

CONSTRUCTION

FIRE DAMPER FOR STATIC SYSTEMS - FDC MODEL - SINGLE & MULTIPLE SECTIONS

FIRE DAMPER MODEL FDC

MAXIMUM UL CLASSIFIED SIZES (OUT TO OUT)

section

SINGLE

MULTIPLE

MAXIMUM WIDTH (”)

36

72

MAXIMUM HEIGHT (”)

36

72

Steel Rivet

Riser Angle (Optional)galvanized steel0.9mm min thick

Casingroll formed 0.9 mm thick manufactured

from galvanized steel coil

Blade guide / locking rampgalvanized steel locking ramp ensures

positive blade closure within integral blade guide

Springsstainless steel coil tension springensuring powerful blade closure

when appropriate Bottom Anglegalvanized steel0.9mm min thick

Sleeve(Optionally by Fire Damper Manufacturer)more details in installation and operating instructions

Fusible linkOset at 165 F

Bladesroll formed single skininterlocking galvanized steel (.8mm thick)of high integrity curtain shutter

Sleeve(optionally byfire damper manufacturer)

Blade

Fusible link

Locking ramp

Bottom angle

Blade

Fusible link

Bottom angle

Cross sectional viewmultiple section

Lockingramp

Blade

Riser angle (optional)

Fusible link

Steel rivet

Locking ramp

Spring

Bottom angle

Cross sectional viewsingle section

Figure – 1

Figure – 2

Page 10: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

Sleeve Thickness (mm)

0.9

1.2

1.5

2

TABLE 1

Surrounding MasonryGypsum Floor or wall/partition

expansion gap

DUCTby others

without riser angle(not 100% free area)

DUCTby others

without riser angle(100% free area)

Steel rivetdia.4.8x12

(mm)

Bottom angle(35 mm)

Duct Sleeve(Connection) 90mm

as minimum152mm maximum

(CROSS SECTION DETAILS)SINGLE SECTION FDC FIX TO WALL

FDCFire damper

Riser angle(optional)

(optionally byfire damper mfg.)

SLEEVE

Mounting angle35x35x2.5Mounting angle35x35x2.5

7

6

5

1

2

4

3

Figure 3

Figure 4 (FRONT VIEW)MULTIPLE SECTION FDC WITH SLEEVE

11. In Multiple Section FD, center cross section point which obtain from attaching four individual section are welded from two sides. In multiple section FD, individual section FD attached with each other by steel rivet 4.8mm dia, space between rivet not more than12. 225 mm centers, and (½”) 13 mm from the corners.

13. Multiple section FD is enclosed with a single rectangular galvanized steel sleeve (optionally by Fire Damper Manufacturer). The fixing of the sleeve to the FD frame using steel rivet 4.8mm dia. Space not more than 225mm center to center and (½”) 13mm from corners. Sleeve (optionally by Fire Damper Manufacturer) thickness as per what mentioned on Table no.1

14. The maximum size of the multiple fire damper assembly that is assembled is 72”x72”.15. In multiple section FD, The maximum size of the individual section that are attached together is 36”x36”.

Bottom angle Bottom angle

Bottom angleBottom angle

Center cross sectionwelded point fromboth sides

35mm

35mm

INSTALLATION AND OPERATING INSTRUCTIONS

FIRE DAMPER MODEL FDC

1. The damper should be installed centrally within the surrounding masonry / gypsum floor or wall

2. The damper should be installed in rectangular galvanized steel sleeve (optionally by Fire Damper Manufacturer) with a minimum thickness of 0.9mm. this sleeve should be attached to the damper not to the builder’s work using

steel rivets 4.8mm dia. and spaced at not more than 225mm centers and 13 mm from corners (½”)

3. The damper is suitable only for rectangular space and can not be use for annular space.

4. Allowance for expansion between sleeve and builders’ work in both horizontal and vertical planes to be 3mm per 305 mm of length and width.

5. The sleeve (optionally by Fire Damper Manufacturer) should be of suitable length to extend through the wall to enable the fitting of the cover angles and ductwork. Minimum of 90 mm and maximum 152 mm beyond the floor or wall / include thicknesses of sleeve in table 1.

71

1 2

5

2

7. The mounting angles should be of such a size as always to form an overlap with the wall / floor by 25 mm minimum and should be manufactured from a minimum size of 35x35x2.5mm Gl angle.

O8. A fusible link is UL tested, Elsie brand, set at 156 F

9. The duct--sleeve connection to be of as per what shown in (figure5) page 8 Connecting ducts shall not be continuous and shall terminate at the sleeve. Installation shall comply with NFPA 90A

10. All fixing of frames must be positioned clear of the damper blade path so as not to impede proper closure.

3

3

6

6. The mounting angles should be attached to the sleeve (optionally by Fire Damper Manufacturer) by 8mm dia bolts at a maximum of 225mm centers, and should form a complete frame around the sleeve and cover over the expansion gap required between sleeve and wall / floor opening. The four corners of the mounting angles are not to be welded. The bolts connecting the mounting angles to the sleeve to be 102 mm maximum from the corners. Mounting angles will be send in loose parts.

Page 11: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

EXPLODED ASSEMBLY FOR FDC TYPE WITH SLEEVE

ASSEMBLY PROCEDURES:

1. Fix the damper into the sleeve matching their center axis and hole provision using steel rivet

2. If the riser angle (optional) is use then, fix the riser angle (optional) into the fire damper sleeve

matching their hole provision using steel rivet. If not go to step no. 3.

3. Fix the fire damper with sleeve into the concrete / gypsum wall opening by a front mounting angle

35x35 matching their hole provision using M8 Hex bolt and nut. Opening size should have clearance of 3 mm

per 305 mm of length and width.

4. Finally when the Fire Damper with sleeve is already fitted to the wall, fix the back mounting angle 35 x 35 matching

their hole provision using M8 Hex bolt and nut.

HEMMED “S” SLIP INSIDE SLIP JOINT DOUBLE “S” SLIP PLAIN “S” SLIP

STANDING “S” SLIP STANDING “S” SLIP(ALTERNATE BAR)

STANDING “S” SLIP(ANGLE REINFORCED)

STANDING “S” SLIP(BAR REINFORCED)

Figure - 5

Figure - 6

A B

F

E

C

DUCT - SLEEVE CONNECTIONS

FIRE DAMPER MODEL FDC

D

Page 12: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

( mm )

above 915 – 1830

above 915 – 1830

( inches )

above 36’ – 72”

above 36” – 72”

Multiple section

SIZES RANGE

* MULTIPLE SECTION

Size Options

FDC-sleeve(optionally by FD Manufacturer)

size: Width x Height

Vertical

FDC not 100% Free area

Type Mounting

FDC NOT 100% FREE AREA

FDC NOT 100% FREE AREA

FDC 100% FREE AREA* SINGLE SECTION

ORDERING SYSTEM

FIRE DAMPER MODEL FDC

Size Options

FDC-sleeve(optionally by FD Manufacturer)

size: Width x Height

Vertical

FDC (100%) Free area

Type Mounting

X ( mm )

25

50

75

90

H ( mm )

80 -- 150

151 -- 450

451 -- 650

651 -- 825

SIZES RANGE

( mm )

80 - 825

100 - 915

( inches )

3.2” - 32.5”

4” - 36”

H

W

( mm )

100 – 915

100 - 915

( inches )

4” - 36”

4” - 36”

H

W

Size Options

FDC-sleeve(optionally by FD Manufacturer)

size: Width x Height

Vertical

FDC not 100% Free area

Type Mounting

Figure - 7

W-5mm

116

mm

H-5

mm

riser

ang

le

H-5

+X

mm

Figure - 8

H-5

mm

116

mm

- mW

5m

H-5

mm

W-5mm

116 mm

Figure - 9

SIZES RANGE

H

W

Page 13: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

FDC (100% FREE AREA)

FDC (NOT 100% FREE AREA)

FIRE DAMPER MODEL FDC

FIRE DAMPER FOR DYNAMIC SYSTMES - FDC MODEL - SINGLE SECTION

Page 14: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

FEATURES:

CONSTRUCTION

– UL classified for dynamic systems in accordance with UL 555 & NFPA 90A

– Civil Defense approvedO

– Flusible link set at 165 F

– Fire rated for 1½ hour

– Mounting type: vertical2

– Flow rating is 2000 cfm / ft

– Static pressure is4 in.wc

MAXIMUM UL CLASSIFIED SIZE (OUT TO OUT)

Blade

Riser Angle (optional)

Fusible link

Steel rivet

Locking ramp

Srings

Bottom angle

Cross sectional viewsingle section

Figure – 1

Figure – 2

SECTION

SINGLE

MAXIMUM WIDTH (”)

36 36

MAXIMUM HEIGHT (”)

Sleeve(Optionally by Fire Damper Manufacturer)more details in installation and operating instructions

Fusible linkO

set at 165 F

Bladesroll formed single skininterlocking galvanized steel (.8mm thick)of high integrity curtain shutter

Steel Rivet

Riser Angle (Optional)galvanized steel0.9mm min thick

Casingroll formed 0.9mm thick manufactured

from galvanized steel coil

Blade guide / locking rampgalvanized steel locking ramp ensures

positive blade closure within integral blade guide

Springsstainless steel coil tension springensuring powerful blade closure

when appropriate Bottom Anglegalvanized steel0.9mm min thick

FIRE DAMPER FOR DYNAMIC SYSTEMS - FDC MODEL - SINGLE SECTION

FIRE DAMPER MODEL FDC

Page 15: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

Surrounding MasonryGypsum Floor or wall/partition

expansion gap

DUCTby others

without riser angle(not 100% free area)

DUCTby others

without riser angle(100% free area)

Steel rivetdia.4.8x12

(mm)

Bottom angle(35 mm)

Duct Sleeve(Connection) 90mm

as minimum152mm maximum

(CROSS SECTION DETAILS)SINGLE SECTION FDC FIX TO WALL

FDCFire damper

Riser angle(optional)

(optionally byfire damper mfg.)

SLEEVE

Mounting angle35x35x2.5Mounting angle35x35x2.5

7

6

5

1

2

4

3

INSTALLATION AND OPERATING INSTRUCTIONS

FIRE DAMPER MODEL FDC

1. The damper should be installed centrally within the surrounding masonry / gypsum floor or wall

2. The damper should be installed in rectangular galvanized steel sleeve (optionally by Fire Damper Manufacturer) with a minimum thickness of 0.9mm. this sleeve should be attached to the damper not to the builder’s work using

steel rivets 4.8mm dia. and spaced at not more than 225mm centers and 13 mm from corners (½”)

3. The damper is suitable only for rectangular space and can not be use for annular space.

4. Allowance for expansion between sleeve and builders’ work in both horizontal and vertical planes to be 3mm per 305 mm of length and width.

5. The sleeve (optionally by Fire Damper Manufacturer) should be of suitable length to extend through the wall to enable the fitting of the cover angles and ductwork. Minimum of 90 mm and maximum 152 mm beyond the floor or wall / include thicknesses of sleeve in table 1.

71

1 2

5

2

7. The mounting angles should be of such a size as always to form an overlap with the wall / floor by 25 mm minimum and should be manufactured from a minimum size of 35x35x2.5mm Gl angle.

O8. A fusible link is UL tested, Elsie brand, set at 156 F

9. The duct--sleeve connection to be of as per what shown in (figure4) page 13 Connecting ducts shall not be continuous and shall terminate at the sleeve. Installation shall comply with NFPA 90A

10. All fixing of frames must be positioned dear of the damper blade path so as not to impede proper closure.

3

Figure 3

43

6

6. The mounting angles should be attached to the sleeve (optionally by Fire Damper Manufacturer) by 8mm dia bolts at a maximum of 225mm centers, and should form a complete frame around the sleeve and cover over the expansion gap required between sleeve and wall / floor opening. The four corners of the mounting angles are not to be welded. The bolts connecting the mounting angles to the sleeve to be 102 mm maximum from the corners. Mounting angles will be send in loose parts.

Sleeve Thickness (mm)

0.9

1.2

1.5

2

TABLE 1

Page 16: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

EXPLODED ASSEMBLY FOR FDC TYPE WITH SLEEVE

ASSEMBLY PROCEDURES:

1. Fix the damper into the sleeve matching their center axis and hole provision using steel rivet

2. If the riser angle (optional) is use then, fix the riser angle (optional) into the fire damper sleeve

matching their hole provision using steel rivet. If not go to step no. 3.

3. Fix the fire damper with sleeve into the concrete / gypsum wall opening by a front mounting angle

35x35 matching their hole provision using M8 Hex bolt and nut. Opening size should have clearance of 3 mm

per 305 mm of length and width.

4. Finally when the Fire Damper with sleeve is already fitted to the wall, fix the back mounting angle 35 x 35 matching

their hole provision using M8 Hex bolt and nut.

FIRE DAMPER MODEL FDC

DUCT - SLEEVE CONNECTIONS

HEMMED “S” SLIP INSIDE SLIP JOINT DOUBLE “S” SLIP PLAIN “S” SLIP

STANDING “S” SLIP STANDING “S” SLIP(ALTERNATE BAR)

STANDING “S” SLIP(ANGLE REINFORCED)

STANDING “S” SLIP(BAR REINFORCED)

Figure - 4

Figure - 5

A B

F

E

C

D

Page 17: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

Type Mounting Size Options

FDC-sleeve(optionally by FD Manufacturer)

size: Width x Height

Vertical

FDC (100%) Free area

X ( mm )

25

50

75

90

H ( mm )

80 -- 150

151 -- 450

451 -- 650

651 -- 825

SIZES RANGE

( mm )

80 - 825

100 - 915

( inches )

3.2” - 32.5”

4” - 36”

Figure - 6

FDC 100% FREE AREA

FDC not 100% FREE AREA

Type Mounting Size Options

FDC-sleeve(optionally by FD Manufacturer)

size: Width x Height

Vertical

FDC not 100% Free area

H

W

( mm )

100 - 915

100 - 915

( inches )

4” - 36”

4” - 36”

H

W

Figure - 7

H-5

mm

116

mm

W-5mm

5W

- mm

116

mm

H-5

mm

riser

ang

le

H-5

+X

mm

FIRE DAMPER MODEL FDC

ORDERING SYSTEM

SIZES RANGE

Page 18: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

Beta Access Doors are made of Galvanized mild steel sheets of 1.20mm thickness

The Insulation is Manson thickness is 1”3 3Higher Insulation thickness can also be provided, upon request. The Density is 24kg/ m (1.5 lb/ft )

Opening and Closing is achieved through a Cam Lock

TYPE SIZE

SIZE: WIDTH X HEIGHT

ACD. ACCESS DOOR WITHOUT HINGES

ACDH; ACCESS DOOR WITH HINGES

WIDTH + 2 X 25

WIDTH - 5

CAM LOCK

CONTINOUSHINGE

WIDTH - 5 HEIGHT - 525

20

25

ACCESS DOOR ASSEMBLYWITH 1 CAM LOCK & HINGE

Figure – 1

HE

IGH

T -

5

HE

IGH

T +

2 x

25

ORDERING SYSTEM

ACCESS DOOR

Page 19: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour

WIDTH + 2X25

WIDTH - 5

HE

IGH

T -

5

HE

IGH

T +

2 X

25

CAM LOCK

FRAME WIDTH - 5

DOOR PANEL - ADOOR PANEL - B

HEIGHT - 5

25

20

25

Figure - 2

ACCESS DOOR ASSEMBLYWITH 2 CAM LOCK

ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

ACCESS DOOR