FIRE DAMPERS
WE SAVE
LIVES
PRODUCTS CATALOGUE
PRODUCTS BULLETIN
![Page 2: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/2.jpg)
Dubai Head Office:
Tel: +971 4 706 97777Fax: +971 4 706 9787
Abu Dhabi Branch:
Tel: +971 2 645 0107Fax: +971 2 645 0167
Email: [email protected]
P.O. Box 50708, DubaiUnited Arab Emirates
w w w . b e t a g . c o m
![Page 3: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/3.jpg)
FDF FIRE DAMPER FOR STATIC SYSTEMS
FDC FIRE DAMPER FOR STATIC SYSTEMS
FDC FIRE DAMPER FOR DYNAMIC SYSTEMS
ACCESS DOOR
1- 4
5-9
10-14
15-16
index
![Page 4: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/4.jpg)
FEATURES:– U.L. Classified for static system in accordance with UL 555 & NFPA 90A.– Civil Defense approved– Fire rated for 1½ hour.
CONSTRUCTION– Casings: 1.2 mm thick manufactured from corrosion resistant galvanized mild steel– Blades: Rollformed single skin interlocking galvanized curtain shutter of 0.8 mm thk– Blade guide / Locking ramps: Galvanized steel locking ramps ensures positive blade closure within integral blade guide.
o– Fusible Link: Typical “two-pleces” fusible links rated at 165 F.– Springs: Stainless steel coil tension spring.– Mounting; Horizontal / Vertical– (Installation as per instruction on page no 4)– Sizes: Maximum Width 31” & Maximum Height 33” (Out to Out)– Sleeves: are optional. details are as per pages 3 & 4
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
CasingsManufactured from corrosionResistant galvanized steel asStandard
Blade guide /Locking rampsGalvanized steel locking ramps ensurespositive blade closure within integralblade guides.
SpringsStainless steel coil tensionspring ensuring powerful bladeclosure when appropriate
Fubible links /release mechanism
Typical “two-pieces” fusible linksOrated at 165 F
Alternative temperature rated fusiblelinks mechanisms available
Blades
(Rollformed single skin interlockinggalvanized high integrity curtain shutterof 0.8 mm thickness)
FIRE DAMPER FOR STATIC SYSTEM - FDF MODEL - SINGLE SECTION
FIRE DAMPER MODEL FDF
![Page 5: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/5.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
25MM
80MM
H -
5 M
M
30
” M
AX
H +
20
+ X
MM
30” MAX
W - 5 MM
W + 40 MM
100% Free Area fire damper FDFFigure - 2
X-DIMENSIONAL
FDF
Height(mm)
X(mm)
100-400
401-750
40
60
FIRE DAMPER MODEL FDF
![Page 6: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/6.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
Surrounding Masonry Floor or Wall
EXPANSION GAP
Mounting Channel
D U C Tby others
D U C Tby others
FIRE DAMPER MODEL FDF
TYPE MOUNTING SIZE OPTIONS
FDS - SLEEVE
Size: Width x Height
H: HORIZONTAL
V: VERTICAL
FDF: 100% Free area fire damper
Figure - 3
ORDERING SYSTEM
COVER ANGLE
M6 Bolt & Nut
SLEEVE
BLADE
FUSIBLE LINK
M6 Bolt & Nut
FDP Firedamper
BLADE RAMP
SPRING
Surrounding Masonry Floor or Wall
38x38x3mm thk
2
3
4
5
1
7
Duct Sleeve Connection
90mmas a minimum
152mm maximum
CROSS – SECTION DETAIL
FIRE DAMPER MODEL FDF
7
6
![Page 7: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/7.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
1 >> The damper should be installed centrally within surrounding masonry floor or wall
2>> The damper should be installed in a rectangular galvanized steel sleeve with a min. thickness of 1.2 mm This sleeve
should be attached to the damper not to the builder’s work using the mounting channels by 6mm dia bolts spaced at not
more than 255mm centres. Bolts for mounting channels located maximum 45 and 145 mm from corners of sleeve and frame,
perspectively.
3>> The damper is suitable only for rectangular space and can not be used for annular space.
4>> Allowance for expansion between sleeve and builder’s work in both horizontal and vertical planes to be 3mm per 305mm
of length.
5>> The sleeve should be of suitable length to extend through the wall to enable the fitting of the cover angles and
ductwork. Minimum of 90mm and maximum of 152mm beyond the floor or wall.
6>> The cover angles should be attached to the sleeve by 6mm dia bolts at a minimum of 225mm centres, and should
form a complete frame around the sleeve and cover over the expansion gap required between sleeve and wall opening. The
four corner of the cover angles are not to be welded.
The bolts connecting the cover angles to the sleeve to be 102mm maximum from the corners.
7>> The expansion gap should be filled with compressible, non-combustible material (mineral wool).
8>> The cover angle should be of such a size as always to from a cover over the wall opening by 25mm minimum and should
be manufactured from a minimum size of 38*38*3mm steel angle
9>> A fusible link UL tested Elsie brand which is rated at 165 degree F is used.
10>> The duct-sleeve connection to be of double “S” slip type.
Breakaway joints shown shall have no more than two No. 10 (4.8 mm dia.) sheet metal screws on each side and on the
bottom located in the center of the slip pocket and shall penetrate both sides of the slip pocket.
Breakaway joints for horizontal ducts (vertical fire damper) shall be provided on the top, bottom and on the sides with double
“S” slip type as illustrated.
Breakaway joints for vertical ducts (horizontal fire damper) shall be provided on both other opposite sides with double “S”
slip type.
Connecting ducts shall not be continued and shall terminate at the sleeve. Installation shall comply with NFPA 9OA.
11>> All fixing of frames must be positioned clear of damper blade path so as not to impede proper closure.
7
2
5
4
6
6
3
1
1
2
FIRE DAMPER MODEL FDF
INSTALLATION & OPERATING INSTRUCTIONS
3
![Page 8: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/8.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
FIRE DAMPER FOR STATIC SYSTEM - FDC MODEL - SINGLE & MULTIPLE SECTIONS
SINGLE SECTION
MULTIPLE SECTION
FDC (NOT 100% FREE AREA)
FDC (NOT 100% FREE AREA)
FDC (100% FREE AREA)
FIRE DAMPER MODEL FDC
![Page 9: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/9.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
– UL classified for static systems in accordance with UL 555 & NFPA 90A
– Civil Defence ApprovedO– Fusible link set at 165 F
– Fire rated for 1½ hour
– Mounting type: vertical
FEATURES:
CONSTRUCTION
FIRE DAMPER FOR STATIC SYSTEMS - FDC MODEL - SINGLE & MULTIPLE SECTIONS
FIRE DAMPER MODEL FDC
MAXIMUM UL CLASSIFIED SIZES (OUT TO OUT)
section
SINGLE
MULTIPLE
MAXIMUM WIDTH (”)
36
72
MAXIMUM HEIGHT (”)
36
72
Steel Rivet
Riser Angle (Optional)galvanized steel0.9mm min thick
Casingroll formed 0.9 mm thick manufactured
from galvanized steel coil
Blade guide / locking rampgalvanized steel locking ramp ensures
positive blade closure within integral blade guide
Springsstainless steel coil tension springensuring powerful blade closure
when appropriate Bottom Anglegalvanized steel0.9mm min thick
Sleeve(Optionally by Fire Damper Manufacturer)more details in installation and operating instructions
Fusible linkOset at 165 F
Bladesroll formed single skininterlocking galvanized steel (.8mm thick)of high integrity curtain shutter
Sleeve(optionally byfire damper manufacturer)
Blade
Fusible link
Locking ramp
Bottom angle
Blade
Fusible link
Bottom angle
Cross sectional viewmultiple section
Lockingramp
Blade
Riser angle (optional)
Fusible link
Steel rivet
Locking ramp
Spring
Bottom angle
Cross sectional viewsingle section
Figure – 1
Figure – 2
![Page 10: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/10.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
Sleeve Thickness (mm)
0.9
1.2
1.5
2
TABLE 1
Surrounding MasonryGypsum Floor or wall/partition
expansion gap
DUCTby others
without riser angle(not 100% free area)
DUCTby others
without riser angle(100% free area)
Steel rivetdia.4.8x12
(mm)
Bottom angle(35 mm)
Duct Sleeve(Connection) 90mm
as minimum152mm maximum
(CROSS SECTION DETAILS)SINGLE SECTION FDC FIX TO WALL
FDCFire damper
Riser angle(optional)
(optionally byfire damper mfg.)
SLEEVE
Mounting angle35x35x2.5Mounting angle35x35x2.5
7
6
5
1
2
4
3
Figure 3
Figure 4 (FRONT VIEW)MULTIPLE SECTION FDC WITH SLEEVE
11. In Multiple Section FD, center cross section point which obtain from attaching four individual section are welded from two sides. In multiple section FD, individual section FD attached with each other by steel rivet 4.8mm dia, space between rivet not more than12. 225 mm centers, and (½”) 13 mm from the corners.
13. Multiple section FD is enclosed with a single rectangular galvanized steel sleeve (optionally by Fire Damper Manufacturer). The fixing of the sleeve to the FD frame using steel rivet 4.8mm dia. Space not more than 225mm center to center and (½”) 13mm from corners. Sleeve (optionally by Fire Damper Manufacturer) thickness as per what mentioned on Table no.1
14. The maximum size of the multiple fire damper assembly that is assembled is 72”x72”.15. In multiple section FD, The maximum size of the individual section that are attached together is 36”x36”.
Bottom angle Bottom angle
Bottom angleBottom angle
Center cross sectionwelded point fromboth sides
35mm
35mm
INSTALLATION AND OPERATING INSTRUCTIONS
FIRE DAMPER MODEL FDC
1. The damper should be installed centrally within the surrounding masonry / gypsum floor or wall
2. The damper should be installed in rectangular galvanized steel sleeve (optionally by Fire Damper Manufacturer) with a minimum thickness of 0.9mm. this sleeve should be attached to the damper not to the builder’s work using
steel rivets 4.8mm dia. and spaced at not more than 225mm centers and 13 mm from corners (½”)
3. The damper is suitable only for rectangular space and can not be use for annular space.
4. Allowance for expansion between sleeve and builders’ work in both horizontal and vertical planes to be 3mm per 305 mm of length and width.
5. The sleeve (optionally by Fire Damper Manufacturer) should be of suitable length to extend through the wall to enable the fitting of the cover angles and ductwork. Minimum of 90 mm and maximum 152 mm beyond the floor or wall / include thicknesses of sleeve in table 1.
71
1 2
5
2
7. The mounting angles should be of such a size as always to form an overlap with the wall / floor by 25 mm minimum and should be manufactured from a minimum size of 35x35x2.5mm Gl angle.
O8. A fusible link is UL tested, Elsie brand, set at 156 F
9. The duct--sleeve connection to be of as per what shown in (figure5) page 8 Connecting ducts shall not be continuous and shall terminate at the sleeve. Installation shall comply with NFPA 90A
10. All fixing of frames must be positioned clear of the damper blade path so as not to impede proper closure.
3
3
6
6. The mounting angles should be attached to the sleeve (optionally by Fire Damper Manufacturer) by 8mm dia bolts at a maximum of 225mm centers, and should form a complete frame around the sleeve and cover over the expansion gap required between sleeve and wall / floor opening. The four corners of the mounting angles are not to be welded. The bolts connecting the mounting angles to the sleeve to be 102 mm maximum from the corners. Mounting angles will be send in loose parts.
![Page 11: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/11.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
EXPLODED ASSEMBLY FOR FDC TYPE WITH SLEEVE
ASSEMBLY PROCEDURES:
1. Fix the damper into the sleeve matching their center axis and hole provision using steel rivet
2. If the riser angle (optional) is use then, fix the riser angle (optional) into the fire damper sleeve
matching their hole provision using steel rivet. If not go to step no. 3.
3. Fix the fire damper with sleeve into the concrete / gypsum wall opening by a front mounting angle
35x35 matching their hole provision using M8 Hex bolt and nut. Opening size should have clearance of 3 mm
per 305 mm of length and width.
4. Finally when the Fire Damper with sleeve is already fitted to the wall, fix the back mounting angle 35 x 35 matching
their hole provision using M8 Hex bolt and nut.
HEMMED “S” SLIP INSIDE SLIP JOINT DOUBLE “S” SLIP PLAIN “S” SLIP
STANDING “S” SLIP STANDING “S” SLIP(ALTERNATE BAR)
STANDING “S” SLIP(ANGLE REINFORCED)
STANDING “S” SLIP(BAR REINFORCED)
Figure - 5
Figure - 6
A B
F
E
C
DUCT - SLEEVE CONNECTIONS
FIRE DAMPER MODEL FDC
D
![Page 12: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/12.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
( mm )
above 915 – 1830
above 915 – 1830
( inches )
above 36’ – 72”
above 36” – 72”
Multiple section
SIZES RANGE
* MULTIPLE SECTION
Size Options
FDC-sleeve(optionally by FD Manufacturer)
size: Width x Height
Vertical
FDC not 100% Free area
Type Mounting
FDC NOT 100% FREE AREA
FDC NOT 100% FREE AREA
FDC 100% FREE AREA* SINGLE SECTION
ORDERING SYSTEM
FIRE DAMPER MODEL FDC
Size Options
FDC-sleeve(optionally by FD Manufacturer)
size: Width x Height
Vertical
FDC (100%) Free area
Type Mounting
X ( mm )
25
50
75
90
H ( mm )
80 -- 150
151 -- 450
451 -- 650
651 -- 825
SIZES RANGE
( mm )
80 - 825
100 - 915
( inches )
3.2” - 32.5”
4” - 36”
H
W
( mm )
100 – 915
100 - 915
( inches )
4” - 36”
4” - 36”
H
W
Size Options
FDC-sleeve(optionally by FD Manufacturer)
size: Width x Height
Vertical
FDC not 100% Free area
Type Mounting
Figure - 7
W-5mm
116
mm
H-5
mm
riser
ang
le
H-5
+X
mm
Figure - 8
H-5
mm
116
mm
- mW
5m
H-5
mm
W-5mm
116 mm
Figure - 9
SIZES RANGE
H
W
![Page 13: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/13.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
FDC (100% FREE AREA)
FDC (NOT 100% FREE AREA)
FIRE DAMPER MODEL FDC
FIRE DAMPER FOR DYNAMIC SYSTMES - FDC MODEL - SINGLE SECTION
![Page 14: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/14.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
FEATURES:
CONSTRUCTION
– UL classified for dynamic systems in accordance with UL 555 & NFPA 90A
– Civil Defense approvedO
– Flusible link set at 165 F
– Fire rated for 1½ hour
– Mounting type: vertical2
– Flow rating is 2000 cfm / ft
– Static pressure is4 in.wc
MAXIMUM UL CLASSIFIED SIZE (OUT TO OUT)
Blade
Riser Angle (optional)
Fusible link
Steel rivet
Locking ramp
Srings
Bottom angle
Cross sectional viewsingle section
Figure – 1
Figure – 2
SECTION
SINGLE
MAXIMUM WIDTH (”)
36 36
MAXIMUM HEIGHT (”)
Sleeve(Optionally by Fire Damper Manufacturer)more details in installation and operating instructions
Fusible linkO
set at 165 F
Bladesroll formed single skininterlocking galvanized steel (.8mm thick)of high integrity curtain shutter
Steel Rivet
Riser Angle (Optional)galvanized steel0.9mm min thick
Casingroll formed 0.9mm thick manufactured
from galvanized steel coil
Blade guide / locking rampgalvanized steel locking ramp ensures
positive blade closure within integral blade guide
Springsstainless steel coil tension springensuring powerful blade closure
when appropriate Bottom Anglegalvanized steel0.9mm min thick
FIRE DAMPER FOR DYNAMIC SYSTEMS - FDC MODEL - SINGLE SECTION
FIRE DAMPER MODEL FDC
![Page 15: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/15.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
Surrounding MasonryGypsum Floor or wall/partition
expansion gap
DUCTby others
without riser angle(not 100% free area)
DUCTby others
without riser angle(100% free area)
Steel rivetdia.4.8x12
(mm)
Bottom angle(35 mm)
Duct Sleeve(Connection) 90mm
as minimum152mm maximum
(CROSS SECTION DETAILS)SINGLE SECTION FDC FIX TO WALL
FDCFire damper
Riser angle(optional)
(optionally byfire damper mfg.)
SLEEVE
Mounting angle35x35x2.5Mounting angle35x35x2.5
7
6
5
1
2
4
3
INSTALLATION AND OPERATING INSTRUCTIONS
FIRE DAMPER MODEL FDC
1. The damper should be installed centrally within the surrounding masonry / gypsum floor or wall
2. The damper should be installed in rectangular galvanized steel sleeve (optionally by Fire Damper Manufacturer) with a minimum thickness of 0.9mm. this sleeve should be attached to the damper not to the builder’s work using
steel rivets 4.8mm dia. and spaced at not more than 225mm centers and 13 mm from corners (½”)
3. The damper is suitable only for rectangular space and can not be use for annular space.
4. Allowance for expansion between sleeve and builders’ work in both horizontal and vertical planes to be 3mm per 305 mm of length and width.
5. The sleeve (optionally by Fire Damper Manufacturer) should be of suitable length to extend through the wall to enable the fitting of the cover angles and ductwork. Minimum of 90 mm and maximum 152 mm beyond the floor or wall / include thicknesses of sleeve in table 1.
71
1 2
5
2
7. The mounting angles should be of such a size as always to form an overlap with the wall / floor by 25 mm minimum and should be manufactured from a minimum size of 35x35x2.5mm Gl angle.
O8. A fusible link is UL tested, Elsie brand, set at 156 F
9. The duct--sleeve connection to be of as per what shown in (figure4) page 13 Connecting ducts shall not be continuous and shall terminate at the sleeve. Installation shall comply with NFPA 90A
10. All fixing of frames must be positioned dear of the damper blade path so as not to impede proper closure.
3
Figure 3
43
6
6. The mounting angles should be attached to the sleeve (optionally by Fire Damper Manufacturer) by 8mm dia bolts at a maximum of 225mm centers, and should form a complete frame around the sleeve and cover over the expansion gap required between sleeve and wall / floor opening. The four corners of the mounting angles are not to be welded. The bolts connecting the mounting angles to the sleeve to be 102 mm maximum from the corners. Mounting angles will be send in loose parts.
Sleeve Thickness (mm)
0.9
1.2
1.5
2
TABLE 1
![Page 16: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/16.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
EXPLODED ASSEMBLY FOR FDC TYPE WITH SLEEVE
ASSEMBLY PROCEDURES:
1. Fix the damper into the sleeve matching their center axis and hole provision using steel rivet
2. If the riser angle (optional) is use then, fix the riser angle (optional) into the fire damper sleeve
matching their hole provision using steel rivet. If not go to step no. 3.
3. Fix the fire damper with sleeve into the concrete / gypsum wall opening by a front mounting angle
35x35 matching their hole provision using M8 Hex bolt and nut. Opening size should have clearance of 3 mm
per 305 mm of length and width.
4. Finally when the Fire Damper with sleeve is already fitted to the wall, fix the back mounting angle 35 x 35 matching
their hole provision using M8 Hex bolt and nut.
FIRE DAMPER MODEL FDC
DUCT - SLEEVE CONNECTIONS
HEMMED “S” SLIP INSIDE SLIP JOINT DOUBLE “S” SLIP PLAIN “S” SLIP
STANDING “S” SLIP STANDING “S” SLIP(ALTERNATE BAR)
STANDING “S” SLIP(ANGLE REINFORCED)
STANDING “S” SLIP(BAR REINFORCED)
Figure - 4
Figure - 5
A B
F
E
C
D
![Page 17: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/17.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
Type Mounting Size Options
FDC-sleeve(optionally by FD Manufacturer)
size: Width x Height
Vertical
FDC (100%) Free area
X ( mm )
25
50
75
90
H ( mm )
80 -- 150
151 -- 450
451 -- 650
651 -- 825
SIZES RANGE
( mm )
80 - 825
100 - 915
( inches )
3.2” - 32.5”
4” - 36”
Figure - 6
FDC 100% FREE AREA
FDC not 100% FREE AREA
Type Mounting Size Options
FDC-sleeve(optionally by FD Manufacturer)
size: Width x Height
Vertical
FDC not 100% Free area
H
W
( mm )
100 - 915
100 - 915
( inches )
4” - 36”
4” - 36”
H
W
Figure - 7
H-5
mm
116
mm
W-5mm
5W
- mm
116
mm
H-5
mm
riser
ang
le
H-5
+X
mm
FIRE DAMPER MODEL FDC
ORDERING SYSTEM
SIZES RANGE
![Page 18: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/18.jpg)
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
Beta Access Doors are made of Galvanized mild steel sheets of 1.20mm thickness
The Insulation is Manson thickness is 1”3 3Higher Insulation thickness can also be provided, upon request. The Density is 24kg/ m (1.5 lb/ft )
Opening and Closing is achieved through a Cam Lock
TYPE SIZE
SIZE: WIDTH X HEIGHT
ACD. ACCESS DOOR WITHOUT HINGES
ACDH; ACCESS DOOR WITH HINGES
WIDTH + 2 X 25
WIDTH - 5
CAM LOCK
CONTINOUSHINGE
WIDTH - 5 HEIGHT - 525
20
25
ACCESS DOOR ASSEMBLYWITH 1 CAM LOCK & HINGE
Figure – 1
HE
IGH
T -
5
HE
IGH
T +
2 x
25
ORDERING SYSTEM
ACCESS DOOR
![Page 19: FIRE DAMPER 19 pages– UL classified for static systems in accordance with UL 555 & NFPA 90A – Civil Defence Approved – Fusible link set at 165O F – Fire rated for 1½ hour](https://reader033.vdocuments.net/reader033/viewer/2022042113/5e8ecd5564fc3f31760a0294/html5/thumbnails/19.jpg)
WIDTH + 2X25
WIDTH - 5
HE
IGH
T -
5
HE
IGH
T +
2 X
25
CAM LOCK
FRAME WIDTH - 5
DOOR PANEL - ADOOR PANEL - B
HEIGHT - 5
25
20
25
Figure - 2
ACCESS DOOR ASSEMBLYWITH 2 CAM LOCK
ALL DETAILS SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
ACCESS DOOR