fire pump motor starting

98
Induction Motors: Parameters & Starting By: James S. Nasby -- Columbia Engineering

Upload: james-s-nasby

Post on 06-May-2015

10.690 views

Category:

Technology


15 download

DESCRIPTION

Motor Starting Techniques, Parameters and Applications.

TRANSCRIPT

Page 1: Fire Pump Motor Starting

Induction Motors: Parameters & Starting

By: James S. Nasby -- Columbia Engineering

Page 2: Fire Pump Motor Starting

2C.E.

Seminar Details & Background Background (History of Seminar) National Fire Protection Association

(NFPA)

“Pumps for Fire Protection Systems”

NEMA Standard MG-1Motors and Generators

See Also: Section VIII. References Cited

Page 3: Fire Pump Motor Starting

3C.E.

Topics to be CoveredI. Induction Motors –

General

II. Electrical Power Supply

III. Induction Motor Parameters

IV. 3Ø Motor Starting Types (8+1)

V. 3Ø Motor Running Types (3)

VI. Common Motor Wiring Types (14)

VII. Installation Considerations

Page 4: Fire Pump Motor Starting

4C.E.

I. Motors – GeneralMotor Types

Induction Motors Three Phase Non-Salient Pole Motors:

Usually Squirrel Cage Rotor Motors -but- can be Wound Rotor (Slip Ring) Induction Motors

Usually Squirrel Cage Design Type: Usually NEMA Design

“B”Normal Starting TorqueNormal Starting Current (KVA)

Synchronous Motors Not Covered

Page 5: Fire Pump Motor Starting

5C.E.

I. Induction Motors General Definitions

Motor Poles – Even Numbers (2, 4, 6, etc.)

Synchronous Speed (No Load Speed - Slip)

Starting Region – Fixed Impedance Running Region – Energy Converter Torques:

Stall = Locked = Zero Speed TorquePull-up TorqueBreakdown TorqueRated Torque

Starting Amps, KVA & Locked Rotor Code

Page 6: Fire Pump Motor Starting

6C.E.

Motor Starting Region – cont’dMotor Torque Curve

Motor Torque and Pump Torque Curves

Page 7: Fire Pump Motor Starting

7C.E.

II. Electrical Power Supplies

Power Sources - Mains

Types of Power Source– Three Phase A.C.

Power Source Characteristics

(Parameters)– Voltage (Utilization Voltage) -at- – Low voltage or Medium Voltage– Frequency – 50 Hz or 60 Hz– Starting Voltage Drop -vs- Starter

– Running Voltage Drop -vs- Motor

Page 8: Fire Pump Motor Starting

8C.E.

Power Supply Characteristics – cont’d

- Power Quality - Source Capacity - Weak or Stiff

Source– Starting Voltage Drop (15% of Controller

Rated)– Running Voltage Drop (5% of Motor Rated)– Method of Calculating - NEMA ICS-14– Gen-Sets - Frequency & Voltage

Voltage Balance (Amount of Imbalance) Small Voltage "Unbalance" = Large Current

Imbalance. (See NEMA MG-1, part 1-14.36)

Voltage Harmonics (Heats Windings)

Power Factors - Affected by Motor

Page 9: Fire Pump Motor Starting

9C.E.

III. Induction Motor ParametersGeneral Motor Characteristics Induction Motor Types

– Wound Rotor Motor (Slip Ring Motor)= Rotary Transformer

– Squirrel Cage Motor = Ditto– But with Slip Rings Shorted

Frequency – 50 Hz -vs- 60 Hz

NEMA Design Type “B” (MG-1)

Page 10: Fire Pump Motor Starting

10C.E.

NEMA Design Types

Standard Three Phase

Induction Motors are

NEMA Design “B”

( Rated Full Load Torque)

Rated | Speed (RPM)

Page 11: Fire Pump Motor Starting

11C.E.

Induction Motors - cont’d Motor Parameters - Electrical

Locked Rotor Code (KVA per Hp) Service Factors

– Usually 1.15 Maximum Allowed– Often Higher for Smaller Motors– Usually 1.0 Max. when used with VFD's

Service Factor (S.F.) -vs- Ideal Conditions– Max. Temperature (40 °C Max.) -and-– Max. Altitude (3,300 ft /1,000 m Max.) -and-

– Max. Voltage Imbalance (1% Max.)

Page 12: Fire Pump Motor Starting

12C.E.

Motor Parameters – cont’d Abbreviations & Acronyms Motor Currents

– FLA = Motor Full Load Amperes– FLC = Motor Full Load Current = FLA– LRC = LRA = Locked Rotor Current (Amps)– SFA = Service Factor Amps – Locked Rotor Code* – Codes F & G

Common

*May be Much Higher for Smaller Motors and for Energy Efficient Motors

Power Factor (PF) – Real -vs- ImaginaryStarting PF = 30% / 40% TypicallyRunning PF = 85% down to 8.0% from Full Load to No Load, Typically

Page 13: Fire Pump Motor Starting

13C.E.

Motor Parameters – cont’d Motor Current Curve

Motor Current -vs- RPM Curves

Rated Running Current = 100%

Page 14: Fire Pump Motor Starting

14C.E.

Induction MotorLocked Rotor Codes

Maximum Allowed Motor Locked Rotor Codes per NFPA-20:

Code "F" for 15 Hp & up -or-5.0 thru 5.59 KVA/Hp = approx. 540% FLA

Code "G" for for 15 Hp & up5.6 thru 6.3 KVA/Hp = approx. 600% FLA

Code "H" for 5 thru 10 Hp(up to 7.1 KVA/Hp = approx. 685% of FLA)

Code "J" for 5 Hp only(up to 8.0 KVA/Hp = approx. 772% of FLA)

Page 15: Fire Pump Motor Starting

15C.E.

Induction Motor Locked Rotor Codes

Table M-02 -- Motor Locked Rotor Code KVA Data and Allowed Horsepowers

"F" "G" "H" "J" Code Letter

Min. Max. Min. Max. Min. Max. Min. Max.

KVA per Hp 5.00 5.59 5.60 6.29 6.30 7.09 7.10 7.99 LRA/FLA 482% 540% 540% 608% 608% 685% 685% 772% Allowed Hp 15 Hp and up 15 Hp and up 5 thru 10 Hp 5 Hp only

Note: The LRA/FLA ratios shown are approximate for illustration only.

Note: Controllers (15 Hp and higher rated ) are NOT rated, tested, approved, or listed for starting codes above Code "G".

Page 16: Fire Pump Motor Starting

16C.E.

Table M-03 -- Maximum Motor Locked Rotor Currents

Motor Voltage - 60 Hz values Rated

Horsepower

Code

Letters 200 Vac 208 Vac 230 Vac 460 Vac 575 Vac

5 F - J 106 102 92 46 37 7.5 F - H 147 142 128 64 51 10 F - H 186 179 162 81 65 15 F - G 267 257 232 116 93 20 F - G 334 321 290 145 116 25 F - G 421 405 366 183 146 30 F - G 499 480 434 217 174 40 F - G 667 641 580 290 232 50 F - G 833 801 724 362 290 60 F - G 1,001 962 870 435 348 75 F - G 1,249 1,201 1,086 543 434 100 F - G 1,668 1,603 1,450 725 580 125 F - G 2,088 2,008 1,816 908 726 150 F - G 2,496 2,400 2,170 1,085 868 200 F - G 3,335 3,207 2,900 1,450 1,160 250 F - G 4,198 4,036 3,650 1,825 1,460 300 F - G 5,060 4,865 4,400 2,200 1,760 350 F - G 5,865 5,639 5,100 2,550 2,040 400 F - G 6,670 6,413 5,800 2,900 2,320 450 F - G 7,475 7,188 6,500 3,250 2,600 500 F - G 8,338 8,017 7,250 3,625 2,900

Note: The 460 Vac LRA values are from NFPA 20 Table 6-5.1.1. Others are calculated using voltage proportion.

Induction Motor Locked Rotor Currents

Page 17: Fire Pump Motor Starting

17C.E.

Motor Parameters – cont’d Motor Stalled (Locked Rotor) Power Factor = Approx 40%

Page 18: Fire Pump Motor Starting

18C.E.

Motor Parameters – cont’d Motor Theory and Formulae

Purpose – Electrical to Mechanical Energy Conversion

– Motor Starting Region (Rotary Solenoid)– Running Region (Energy Converter)

Motor Torque & Motor Current Draw -vs- Speed Curves A‑T‑L‑Starting

(Basic Motor Characteristics)– Power Factor & Phase Angles– Efficiencies

Page 19: Fire Pump Motor Starting

19C.E.

Motor Starting -vs- Motor Running Regions

Page 20: Fire Pump Motor Starting

20C.E.

Motor Starting -vs- Motor Running Regions

Motoring Region

Starting Region

Page 21: Fire Pump Motor Starting

21C.E.

Motor Parameters – cont’d Motor Torque Curve

Motor Torque and Pump Torque Curves

Page 22: Fire Pump Motor Starting

22C.E.

Motor Parameters – cont’d Motor Torque Curve

Motor Torque and Pump Torque Curves

Page 23: Fire Pump Motor Starting

23C.E.

Motor Parameters – cont’d Motor Current Curve

Motor Current -vs- RPM Curves

Rated Running Current = 100%

Page 24: Fire Pump Motor Starting

24C.E.

Motor Parameters – cont’d Motor Current Curve

Motor Current -vs- RPM Curves

Rated Running Current = 100%

Motoring RegionStarting Region

Page 25: Fire Pump Motor Starting

25C.E.

Motor Theory and Formulae

Motor Starting Region

For a Motor at Stall, Motor Impedance is Constant. So: I = E / Z (Ohm’s Law)

Current is Directly Proportional to Motor Voltage. I.E.:

Motor Current = Voltage / Impedance

Power Factor (P.F.) is Typically 30% to 40% at Stall (and for most of the starting region)

Page 26: Fire Pump Motor Starting

26C.E.

Motor Theory and Formulae

Motor Starting Region – cont’d

In the Starting (Accelerating) Region:

Torque is Proportional to the Square of the Applied Motor Voltage

T = K1 x V2 -or- Since Current is proportional to Voltage (see above):

T = K2 x I2

Thus: Torque is also Proportional to the Square of the Motor Current

Page 27: Fire Pump Motor Starting

27C.E.

Motor Theory and FormulaeMotor Starting Region – cont’d

Example of Starting Torque Proportional to the Square of Applied Motor Voltage.

E.G. 57% Volts = 33% Rated Stall Torque.

Page 28: Fire Pump Motor Starting

28C.E.

Motor Theory and Formulae Motor Running Region

Motor Running Region (Energy Converter):

Mechanical Power is Torque x Speed: Pm = K3 x Tq x RPM

Motor Torque is Whatever the Load Requires

Electrical Power Input is: Pe = Pm + Motor Losses = Pm / Efficiency

But, Electrical Power Input is also given as: Pe = K4 x V x Ireal (Volts x Real Current)

So: Ireal = K5 x Pe / VoltsThus Motor Current is Inversely

Proportional to Motor Voltage with a Running Motor

Page 29: Fire Pump Motor Starting

29C.E.

Motor Running -vs- Motor Starting Regions

Rated Torque (100%) times Rated Speed (E.g. 1750 RPM) yields Motor Rated Horsepower.

Page 30: Fire Pump Motor Starting

30C.E.

IV. Motor Starting General ‑ Overview – Types of

Reduction– Voltage Reduction: Wye–Delta, Soft Start,

and Autotransformer– Current Reduction: Primary Impedance

(Primary Resistor, Primary or Neutral Reactor)

– Motor Impedance (Wound Rotor) Two Specialty Types

– Medium Voltage – Four Common Types: A-T-L, Primary Reactor, Neutral Reactor -and- Autotransformer

– Low Voltage - Wound Rotor (Not U.L. Listed)

Page 31: Fire Pump Motor Starting

31C.E.

Motor Starting - cont’d

Eight (+1) Common Low Voltage Starting Types:

Across‑the‑Line (A‑T‑L or Direct‑On‑Line) Part Winding (Half Winding) Start Primary Resistor Start Primary (or Neutral) Reactor Start Wye‑Delta (Star‑Delta) ‑ Open Transition Wye‑Delta (Star‑Delta) ‑ Closed Transition Soft Start / Soft Stop (SCR Phase

Modulation) Autotransformer VFD Ramp-up (and Ramp-down on some)

Page 32: Fire Pump Motor Starting

32C.E.

Motor Starting – cont’dAcross-the-Line (Direct On Line)

Page 33: Fire Pump Motor Starting

33C.E.

FullVoltageStart ------------Across-the-Line

Page 34: Fire Pump Motor Starting

34C.E.

Motor Starting – cont’dAcross-the-Line (Direct On Line)

Page 35: Fire Pump Motor Starting

35C.E.

Motor Starting – cont’dPart Winding Start

Note: The Motor Must be Wound Specifically for Part Winding Starting.

Page 36: Fire Pump Motor Starting

36C.E.

Part Winding Start

Page 37: Fire Pump Motor Starting

37C.E.

Motor Starting – cont’d

Part Winding Start

Page 38: Fire Pump Motor Starting

38C.E.

Motor Starting – cont’dPrimary Resistor Start

Page 39: Fire Pump Motor Starting

39C.E.

Primary Reactor Start

Page 40: Fire Pump Motor Starting

40C.E.

Motor Starting – cont’dPrimary Resistor Start

Note: 65% Resistor Impedance is

1.24 - 0.40 = 0.84 pu

Page 41: Fire Pump Motor Starting

41C.E.

Motor Starting – cont’dPrimary Reactor Start

Page 42: Fire Pump Motor Starting

42C.E.

Motor Starting – cont’dPrimary (or Neutral) Reactor Start

Note: 65% Reactor Impedance is

1.54 – 1.00 = 0.54 pu

Page 43: Fire Pump Motor Starting

43C.E.

Motor Starting Torque Comparison

Curves B, C & D are at 65% Motor Starting Voltage(Reference Source Credit on Next Slide)

“0”“0”

Page 44: Fire Pump Motor Starting

44C.E.

Motor Torque Comparison – cont’dA=ATL, B=A.T., C=Pri. Res., D=Reactor

Gerhart W. Heumann (G.E.), “MagneticControls of Industrial Motors”, Wiley & Sons.

Page 45: Fire Pump Motor Starting

45C.E.

Motor Starting – cont’dPrimary (or Neutral) Reactor Start

Page 46: Fire Pump Motor Starting

46C.E.

Wye-Delta Open Transition

Page 47: Fire Pump Motor Starting

47C.E.

Motor Starting – cont’dWye-Delta Open Transition

LPM Module = Leading Phase Monitor®

Page 48: Fire Pump Motor Starting

48C.E.

First Half Cycle Offset Waveforms

2.83 x LRA = 6 x 2.83 x FLA = 17.0 x FLA Maximum Theortical This curve shows starting a motor

which still has BACK EMF (voltage) present.

Page 49: Fire Pump Motor Starting

49C.E.

Motor Starting – cont’dWye-Delta Open Transition

Page 50: Fire Pump Motor Starting

50C.E.

Motor Starting – cont’dWye-Delta Open Transition

Page 51: Fire Pump Motor Starting

51C.E.

Motor Starting – cont’dWye-Delta Open Transition

Page 52: Fire Pump Motor Starting

52C.E.

Motor Starting – cont’dWye-Delta Transition Hazard

ClosedLeading

Lagging

Page 53: Fire Pump Motor Starting

53C.E.

Motor Starting – cont’dWye-Delta Closed Transition

Page 54: Fire Pump Motor Starting

54C.E.

Wye-Delta Closed Transition

Page 55: Fire Pump Motor Starting

55C.E.

Motor Starting – cont’dWye-Delta (Open or Closed Xtn.)

Page 56: Fire Pump Motor Starting

56C.E.

Wye-Delta Starting; Truths and Myths

Page 1 of 4

Page 57: Fire Pump Motor Starting

57C.E.

Wye-Delta Starting; Truths and Myths

Page 2 of 4

Page 58: Fire Pump Motor Starting

58C.E.

Wye-Delta Starting; Truths and Myths

Page 3 of 4

Page 59: Fire Pump Motor Starting

59C.E.

Wye-Delta Starting; Truths and Myths

Page 4 of 4

Page 60: Fire Pump Motor Starting

60C.E.

Motor Starting - cont’dSoft (Solid State - SCR) Start

Page 61: Fire Pump Motor Starting

61C.E.

Soft Start (Solid State - SCR)

Page 62: Fire Pump Motor Starting

62C.E.

Motor Starting - cont’dSoft (Solid State - SCR) Start

Note: These curves are for Soft Starters

without Current Limiting set.

Page 63: Fire Pump Motor Starting

63C.E.

Motor Starting - cont’dAutotransformer Start

Page 64: Fire Pump Motor Starting

64C.E.

Autotransformer Start

Page 65: Fire Pump Motor Starting

65C.E.

Motor Starting - cont’dAutotransformer Start

Page 66: Fire Pump Motor Starting

Motor Starting Characteristics

Parameter Chart

Fire Pump Starting Type Characteristics - for - Electric Fire Pump Motors and Controllers

Starting Characteristics (at Stall) -- Typical Values -for- Fully Load Pump (1) Starting Starting Starting Accelerate Motor Motor Amps Amps Starting Power Starting Full Load Type Contactors Closed & KVA & KVA Power % F.L. Torque to Starting Type Note Note (3) Transition % LRA % FLA Factor Note (4) % ATL Full Speed Notes Across-the-Line Any 1 N/A 100% 600% 40% 240% 100% Yes (a)

Part Winding Special (2) 2 Yes 65 390 40 156 48 Usually (b) Primary Resistor Any 2 Yes 65 390 80 314 42 Yes (c)

Primary Reactor Any 2 Yes 65 390 28 111 42 Yes (c) Neutral Reactor 6/12 Lead 2 Yes 65 390 28 111 42 Yes (c)

Wye-Delta Open 6/12 Lead 3 No 33/100 200/600 40 80/240 33 No (d) Wye-Delta Closed 6/12 Lead 4 Yes 33/100 200/600 40 80/240 33 No (d)(e)

Soft Start/Stop Any 1/2 Yes 40/67 240/400 Varies Ramps 16/44 Yes (f) Autotransformer Any 3 Yes 46 276 40 110 42 Yes (c)(g)

Page 67: Fire Pump Motor Starting

67C.E.

Motor Starting Characteristics

Parameter Notes to Chart

Motor Starting Characteristics Chart Notes (1) Refer to Factory details. (2) Part Winding Motors must be wound specifically for this service. Some motors may not

accelerate to full speed in the starting mode. See Note (b). (3) Units with two or more contactors have two basic steps (Accelerate & Run) with steps three

and four being for transitions. (4) Starting KW Power as a percent of motor full load power requirement. (a) Also called "A-T-L" or Direct-On-Line. Motor Power Factor taken as 40%. Other values

shown are due to the effects of the controller. (b) Part Winding Parameters vary with the motor. Starting Amps & KVA vary from around

60% to 70%, Starting Torque from around 45% to 50%. The motor can start a fully loaded pump if it has no large torque dip or cusp. See the text discussion on Part Winding Starting for details.

(c) Figures are for tap set at 65% which yields a motor voltage of 65% of line (mains) voltage. (d) The Dual Figures are for Starting and Transition. The transition values are to finish

accelerating a fully loaded pump. Examples include deluge or open systems, re-starting a fully loaded pump after a power failure or interruption, and failure of another pump feeding the same system.

(e) Ignores the momentary transition resistor loads. (f) Varies with pump load and particular Soft Starter used. Values shown are initial and

maximum for a typical fully loaded pump. MCS uses the second (Start) contactor for isolation. Others use only the Bypass contactor.

(g) The 46% Starting Amps & KVA figures include the Autotransformer exciting current.

Page 68: Fire Pump Motor Starting

68C.E.

V. Motor Running TypesConstant Speed Running Full Voltage Running

- Synchronous Speeds (3,600 RPM & etc.)- Slip Frequencies - Running (Rated)

Speeds Motor Lead Wire Running Currents

- Three Lead = Full Motor Current- Six Lead Parallel Run (Part Winding

Start)= 50% of FLC per set

- Six Lead (Wye-Delta Start)= 58% (57.7%) of FLC per set

Page 69: Fire Pump Motor Starting

69C.E.

Motor Running - cont’d

Variable Speed Running Wound Rotor Control

- Changes Motor Secondary Impedance -and-

- Motor Torque Curve Variable Frequency - Variable Speed

Control (VFDs)- Changes Motor Torque and Current

Curves

- Changes Motor Synchronous Speed –and-

- Changes Motor Running (Loaded) Speed

Page 70: Fire Pump Motor Starting

70C.E.

Wound Rotor Speed-Torque Curves

(Reference Source Credit on Next Slide)

Page 71: Fire Pump Motor Starting

71C.E.

Wound Rotor Speed-Torque Curves

- Flipped and Rotated -

Gerhart W. Heumann (G.E.), “Magnetic

Controls of Industrial Motors”, Wiley & Sons.

Page 72: Fire Pump Motor Starting

72C.E.

VFD = Motor Running Only (No Motor Starting Region)

Starting Region

(Reference Only)

Page 73: Fire Pump Motor Starting

73C.E.

Variable Speed ControllersPower Circuit Schematic

. .* Was Optional

Page 74: Fire Pump Motor Starting

74C.E.

Variable Speed Control

Page 75: Fire Pump Motor Starting

75C.E.

VFD – Principles of Operation

3 Phase

Line Freq.

AC to DC

Smoothing(Ripple Reduction)

DC / AC

(at "X" KHz)

Page 76: Fire Pump Motor Starting

76C.E.

VI.Motor Wiring – Motor Lead Configurations (Fourteen)

Three Lead – Three Coil

(Single Voltage) (T1‑T3) Six Lead – Three Coil

– Wye Running (T1‑T3 & T4‑T6)– Delta Running (T1‑T3 & T4‑T6)

Parallel Run (Six Lead - Six Coil)– T1‑T3 and T7‑T8 - or -– Both Sets Labeled T1‑T3

Page 77: Fire Pump Motor Starting

77C.E.

Motor Lead Configurations3 Lead – 3 Coil - Wye Running

Page 78: Fire Pump Motor Starting

78C.E.

Motor Lead Configurations3 Lead – 3 Coil - Delta Running

Page 79: Fire Pump Motor Starting

79C.E.

Motor Lead Configurations6 Lead - 3 Coil - Wye Running

Page 80: Fire Pump Motor Starting

80C.E.

Motor Lead Configurations6 Lead – 3 Coil - Delta Running

Page 81: Fire Pump Motor Starting

81C.E.

6 Lead – 6 Coil - Wye RunningParallel Running

Page 82: Fire Pump Motor Starting

82C.E.

6 Lead – 6 Coil - Delta Running Parallel Running

Page 83: Fire Pump Motor Starting

83C.E.

Motor Wiring – cont’d

Nine Lead (Dual Voltage) (T1‑T9)– Wye Wound– Delta Wound– Suitable for Part Winding Start ?

Twelve Lead (T1‑T12)– Dual Voltage– Single Voltage (Parallel Run)

Page 84: Fire Pump Motor Starting

84C.E.

9 Lead - 6 Coil - Wye RunningSeries Running

Page 85: Fire Pump Motor Starting

85C.E.

9 Lead - 6 Coil - Wye RunningParallel Running

Page 86: Fire Pump Motor Starting

86C.E.

9 Lead - 6 Coil - Delta RunningSeries Running

Page 87: Fire Pump Motor Starting

87C.E.

9 Lead - 6 Coil - Delta RunningParallel Running

Page 88: Fire Pump Motor Starting

88C.E.

12 Lead - 6 Coil - Wye RunningSeries Running

Page 89: Fire Pump Motor Starting

89C.E.

12 Lead - 6 Coil - Wye RunningParallel Running

Page 90: Fire Pump Motor Starting

90C.E.

12 Lead - 6 Coil - Delta RunningSeries Running

Page 91: Fire Pump Motor Starting

91C.E.

12 Lead - 6 Coil - Delta RunningParallel Running

Page 92: Fire Pump Motor Starting

92C.E.

Typical 12 Lead Motor Wiring Diagram

Courtesy of Marathon Electric

Page 93: Fire Pump Motor Starting

93C.E.

Starting Methods -vs- Motor

Types

Table M-04 - Motor and Starting Types

Starting Type Motor Type Starting Type Motor Type

Full voltage Standard/Any Primary Reactor Standard/Any

Part Winding Part Winding Primary Resistor Standard/Any

Wye Delta - Closed Delta Run Autotransformer Standard/Any

Wye Delta - Open Delta Run Soft Start (SCR) Standard/Any

Neutral Reactor Wye Running Wound Rotor Wound rotor

Page 94: Fire Pump Motor Starting

94C.E.

Motor Types -vs- Starting Types

Motor Description (a) Starting Method(b)

Run Type Number of Leads Part Winding

Wye (Star) Delta(c)

Neutral Reactor

"Other 5" Figure

Wye Run Three Lead No No No Yes 7-4

Delta Run Three Lead No No No Yes 7-5

Wye Run Six Lead, Single Coil No No Yes Yes 7-6

Delta Run Six Lead, Single Coil No Yes No Yes 7-7

Wye Run Six Lead Parallel Some(d) No No Yes 7-8

Delta Run Six Lead Parallel Some(d) No No Yes 7-9

Wye Run Nine Lead Series No No Yes Yes 7-10

Wye Run Nine Lead Parallel Some(d) No No Yes 7-11

Delta Run Nine Lead Series No No No Yes 7-12

Delta Run Nine Lead Parallel No(e) No No Yes 7-13

Wye Run Twelve Lead Series No No Yes Yes 7-14

Wye Run Twelve Lead Parallel Some(d) No Yes Yes 7-15

Delta Run Twelve Lead Series No Yes No Yes 7-16

Delta Run Twelve Lead Parallel Some(d) Yes No Yes 7-17

Notes: (a) The Motor "Type" (Wye or Delta) is the Running configuration, regardless of how the motor is started. Wound Rotor Motors are not covered in this chart. (b) "Other 5" are: Full voltage (A-T-L), Primary Resistor, Primary Reactor, Soft Start and Autotransformer. (c) Either Open or Closed Transition Wye-Delta (Star-Delta). (d) "Some" = May be used only of the motor is labeled as suitable for Part Winding Starting. (e) The 9 lead "Double Delta" method has unequal currents and is not suitable for standard Part Winding controllers.

Table M-06 -- Motor SuitabilityMotor Types -vs- Starting Types

Page 95: Fire Pump Motor Starting

95C.E.

VII. Induction Motors --Installation Considerations

Physical– Location ‑ Ideally Within Site of Controller– Motor Protection: Fire, Security, Other

Hazards Access – All Sides & Conduit Access Electrical N.E.C. (NFPA 70) ‑ §430 (& §

695)– Conduit & Hubs– Environmental– Conductor Sizing – Incoming & Motor Circuit– Voltage Drops: Start & Run– Cable Impedances and Run Lengths

(See NEMA ICS-14)

Page 96: Fire Pump Motor Starting

96C.E.

Motor Installation – cont’d

Start-up (Commissioning)

Current Measurements Voltage Measurements Estimating Motor Load

- FLA -vs- Voltage

- SFA (115%) - Max. Allowed Under Any Conditions (Temperature, Altitude, Voltage Imbalance) on ANY Phase

Page 97: Fire Pump Motor Starting

97C.E.

Motor Installation – cont’d

Environmental Open Drip Proof (ODP) Totally Enclosed Fan Cooled (TEFC) Outdoor Hazardous Locations, Explosion

Proof:– Motor, Controller, Wiring

Other– Salt Air– Wind Blown Sand or Dust– Temperatures– Altitude

Page 98: Fire Pump Motor Starting

98C.E.

Questions ?