Fixed-Mounted Circuit-Breaker Switchgear up to 36 kV, SF 6 -Insulated Medium-Voltage Switchgear Catalog HA 35.51 2000 Supersedes: Catalog HA 35.51 · 1998

Upload: voliem

Post on 21-Jun-2018

239 views

Category:

Documents


0 download

TRANSCRIPT

Fixed-Mounted Circuit-BreakerSwitchgear up to 36 kV, SF6-Insulated

Medium-VoltageSwitchgearCatalog HA 35.512000Supersedes: Catalog HA 35.51 · 1998

NX PLUSFixed-Mounted Circuit-Breaker

Switchgear up to 36 kV,SF6-Insulated

2 Siemens HA 35.51 · 2000

Contents

Application, features, requirementsPage

General Information

© Siemens AG 2000

Technical Data

Electrical data 3View of a switchgear

General Information

Application, features, 2requirements

Appendix

Catalog index 13Conditions of sale and delivery, 15export regulations, trademarks,dimensions

Product Range

Circuit-breaker panel 4 and 5Disconnector panel 6 and 7Sectionalizer panel 8

Design

Panel construction 8 and 9Dimensions 10Module couplingSolid-state HMI 11Mechanical control board

Standards

Standards, specifications, 12guidelines

NX PLUS fixed-mountedcircuit-breaker switchgear is ofthe three-pole, metal-enclosed,metal-clad, SF6-insulated typefor indoor installation, forsingle busbar.

Typical uses

Transformer stations and sub-stations operated by:

• Power supply utilities

• Power stations

• Cement industry

• Automobile industry

• Iron and steel works

• Rolling mills

• Mining industry

• Textile, paper andfood industries

• Chemical industry

• Petroleum industry

• Pipeline installations

• Offshore installations

• Electrochemical plants

• Petrochemical plants

• Traction power supplies

• Shipbuilding industry

• Diesel power plants

• Emergency power supplyinstallations

• Lignite open-cast mines

Technical characteristics

• Three-pole primary enclosure

• SF6-insulated

• Vacuum circuit-breakers

• Three-position switch as bus-bar disconnector and feederearthing switch

• Make-proof earthing withvacuum circuit-breaker

• Panel width 600 mm(with busbar sectionalizerpanel<– 2000 A: 900 mm> 2000 A: 1200 mm)for all voltages up to 36 kV

• Hermetically sealed, weldedstainless steel switchgearcontainer

• Single-pole, solid-insulated,screened, bolted-typemodule coupling

• Cable connection with insideor outside cone plug-insystems

NX PLUSFixed-Mounted Circuit-BreakerSwitchgear up to 36 kV,SF6-Insulated

Siemens HA 35.51 · 2000 3

Technical Data

Electrical data

R-HA

35-0

60a

eps

NX PLUS fixed-mountedcircuit-breakerswitchgear

Operator safety

• Safe-to-touch andhermetically sealed primaryenclosure

• All high-voltage parts,including the cable sealingends, busbars and voltagetransformers, are surroundedby earthed layers or metalenclosures

• Capacitive voltage detectionsystem for verification ofsafe isolation from supply

• Operating mechanisms andauxiliary switches safelyaccessible outside theprimary enclosure(switchgear container)

• Protective system interlockto prevent operation whenenclosure is open

• Type-tested enclosures andinterrogative interlocksprovide high degree ofinternal arcing protection

Operational reliability

• Hermetically sealed primaryenclosure for protectionagainst environmental effects(dirt, moisture and small ani-mals)

• Operating mechanismcomponents maintenance-free in indoor environment(DIN VDE 0670 Part 1000)

• Breaker operatingmechanisms accessibleoutside the switchgearcontainer (primary enclosure)

• Inductive voltagetransformers metal-enclosedfor plug-in, mounting outsidethe main circuit

• Ring-core currenttransformers located outsidethe primary enclosure

• Complete interrogativeinterlocking system

• Welded switchgearcontainer, sealed for life

• Minimum fire load

Rated voltage up to 24 kV 36 kV(40.5 kV *)

Rated frequency 50/60 Hz 50/60 Hz

Rated short-duration power-frequencywithstand voltage

50 kV 70 kV(85 kV *)

Rated lightning impulsewithstand voltage

125 kV 170 kV(185 kV *)

Rated short-circuit breaking currentand rated short-time withstand current, 3 s

max. 31.5 kA 31.5 kA

Rated short-circuit making current max. 80 kA 80 kA

Rated normal current of busbar max. 2500 A 2500 A

Rated normal current of feeder max. 2500 A 2500 A

* On request

4 Siemens HA 35.51 · 2000

NX PLUSFixed-Mounted Circuit-Breaker

Switchgear up to 36 kV,SF6-Insulated

Product Range

Overview

Circuit-breaker panel

with cable connectionas inside cone for:

– Rated voltageup to 36 kV

– Rated short-circuitbreaking currentup to 31.5 kA

– Rated normalcurrents of busbarsand feedersup to 2500 A

HA35

-236

8b e

ps

Currenttrans-former

Voltagetransformer,plug-in type

1 x plug-incable, sizes2 or 3

Capacitivevoltagedetectionsystem

1 x plug-incable, size 2

2 x plug-incable, sizes2 or 3

4 x plug-incable, size 2

3 x plug-incable, sizes2 or 3

Solid-insulated bar(e.g. Durescabar)

Busbarcurrenttransformer

Surgearrester,plug-in type

Voltagetransformer,plug-in type

Surgearrester,plug-in type

Panel connectionversions

Panel connectionfittings

Fittingsafter circuit-breaker module 4)

Fittingsbefore circuit-breaker module

1)

or2)

or2)

or2)

and3)

or

or

or

Busbar fittings

or

1) Capacitive voltage detectionsystem according to LRM orIVDS system.

2) Not possible with ratednormal current of feederof 2500 A.

3) Not possible with busbarvoltage transformer.

4) Requires cable connection withcontainer for separate inside cone.

NX PLUSFixed-Mounted Circuit-BreakerSwitchgear up to 36 kV,SF6-Insulated

Siemens HA 35.51 · 2000 5

Product Range

Overview

Circuit-breaker panel

with cable connectionas outside cone for:

– Rated voltageup to 24 kV

– Rated short-circuitbreaking currentup to 25 kA

– Rated normalcurrents of busbarsup to 2500 A andfeeders up to 1250 A

1) Capacitive voltage detectionsystem according to LRM orIVDS system.

2) Not possible with busbarvoltage transformer.

HA35

-236

9b e

ps

1)

Surgearrester orlimiter,plug-in type

or

oror

or

or

and2)

Busbar fittings

Panel connectionfittings

Fittingsafter circuit-breaker module

Fittingsbefore circuit-breaker module

Capacitivevoltagedetectionsystem

1 x plug-incable, size 2

Busbarcurrenttransformer

Surgearrester,plug-in type

Voltagetransformer,plug-in type

1 x plug-incable

2 x plug-incable

3 x plug-incable

Panel connectionversions

Currenttrans-former

Voltagetransformer,disconnect-able

NX PLUSFixed-Mounted Circuit-Breaker

Switchgear up to 36 kV,SF6-Insulated

6 Siemens HA 35.51 · 2000

Product Range

Overview

Disconnector panel

with cable connectionas inside cone for:

– Rated voltageup to 36 kV

– Rated short-circuitbreaking currentup to 31.5 kA

– Rated normalcurrents of busbarsand feedersup to 2500 A

1) Capacitive voltage detectionsystem according to LRM orIVDS system.

2) Not possible with ratednormal current of feederof 2500 A.

3) Not possible with busbarvoltage transformer.

HA35

-237

0c e

ps

1)

or

oror2)

or2)

or2)

and3)

or

or

Busbar fittings

Panel connectionfittings

Fittingsbefore cable connection module

Capacitivevoltagedetectionsystem

1 x plug-incable, size 2

Busbarcurrenttransformer

Surgearrester,plug-in type

Voltagetransformer,plug-in type

1 x plug-incable, sizes2 or 3

2 x plug-incable, sizes2 or 3

4 x plug-incable, size 2

3 x plug-incable, sizes2 or 3

Panel connectionversions

Solid-insulated bar(e.g. Durescabar)

Surgearrester,plug-in type

Currenttrans-former

Voltagetransformer,plug-in type

NX PLUSFixed-Mounted Circuit-BreakerSwitchgear up to 36 kV,SF6-Insulated

Siemens HA 35.51 · 2000 7

Product Range

Overview

Disconnector panel

with cable connectionas outside cone for:

– Rated voltageup to 24 kV

– Rated short-circuitbreaking currentup to 25 kA

– Rated normalcurrents of busbarsup to 2500 A andfeeders up to 1250 A

1) Capacitive voltage detectionsystem according to LRM orIVDS system.

2) Not possible with busbarvoltage transformer.

HA35

-237

1b e

ps

1)

or

oror

or

or

and2)

Busbar fittings

Panel connectionfittings

Fittingsafter cable connection module

Fittingsbefore cable connection module

Capacitivevoltagedetectionsystem

1 x plug-incable, size 2

Busbarcurrenttransformer

Surgearrester,plug-in type

Voltagetransformer,plug-in type

1 x plug-incable

2 x plug-incable

3 x plug-incable

Panel connectionversions

Surgearrester orlimiter,plug-in type

Currenttrans-former

Voltagetransformer,disconnect-able

NX PLUSFixed-Mounted Circuit-Breaker

Switchgear up to 36 kV,SF6-Insulated

8 Siemens HA 35.51 · 2000

Product Range

Overview Panel construction

Sectionalizer panel

for:

– Rated voltageup to 36 kV

– Rated short-circuitbreaking currentup to 31.5 kA

– Rated normalcurrent of busbarsup to 2500 A

1) Not possible with ratednormal current of busbarof 2500 A.

Panel with integratedinside cone

Features

• Rated voltage up to 36 kV

• Rated short-circuit breakingcurrent up to 31.5 kA

• Rated normal currents ofbusbars and feedersup to 2500 A

Panel with separateinside cone

Features

• Rated voltage up to 36 kV

• Rated short-circuit breakingcurrent up to 31.5 kA

• Rated normal currents ofbusbars and feedersup to 2500 A

Panel with outside cone

Features

• Rated voltage up to 24 kV

• Rated short-circuit breakingcurrent up to 25 kA

• Rated normal currents ofbusbars up to 2500 A andfeeders up to 1250 A

HA35

-237

2d e

ps

Fittingsbefore circuit-breakermodule

Busbarfittings

Capacitivevoltagedetectionsystem

Currenttransformer

1)

NX PLUSFixed-Mounted Circuit-BreakerSwitchgear up to 36 kV,SF6-Insulated

Siemens HA 35.51 · 2000 9

Design

Legend

1 Door of low-voltage compartment

2 SIPROTEC 4 bay controller, type7SJ63, for control and protection

3 Voltage detection system CAPDIS

4 EMERGENCY-OFF pushbutton,mechanical

5 Door to mechanical control board

6 Cover of cable connection compartment

7 Busbar cover

8 Busbar module, welded,SF6-insulated

9 Three-pole busbar system

10 Three-position switch,SF6-insulated, with the threepositions:ON – OFF – EARTHING PREPARED

11 Module coupling between busbarmodule and circuit-breaker module

12 Circuit-breaker module, welded,SF6-insulated, with integrated cableconnection

13 Vacuum interrupter of circuit-breaker

14 Pressure-relief duct

15 Integrated cable connection asinside cone

16 Optional low-voltage compartment935 mm high

17 Standard low-voltage compartment735 mm high

18 Ring-core current transformer

19 Manual and motor operatingmechanism of three-position switch

20 Mechanical control board

21 Manual and motor operatingmechanism of circuit-breaker

22 Voltage transformer connectionsocket as inside cone

23 Cable connection compartment

24 Module coupling between circuit-breaker and cable connectionmodule

25 Cable connection module, welded,SF6-insulated, with separate cableconnection

26 Separate cable connection asinside cone

27 Voltage transformer connectionsocket as outside cone

28 Cable connection as outside cone

29 Connection cables

30 Rupture diaphragm

HA35

-237

4d e

ps

PLUSNX

7

8

9

10

12

13

14

15

16

17

18

19

20

21

22

23

11

30

30

6

4

2

1

5

3

30

24

18

25

26 23

2230

30

12

18

27

29

2328

Panel with integrated inside cone

Panel with separate inside cone(lower part of panel shown)

Panel with outside cone(lower part of panel shown)

NX PLUSFixed-Mounted Circuit-Breaker

Switchgear up to 36 kV,SF6-Insulated

10 Siemens HA 35.51 · 2000

Panel construction

Design

1 Busbar conductor

2 Silicon sleeve

3 Conductive layer

4 High-quality joint

5 Cast-resin bushing

6 Container wall

7 Screening elements

8 Cast-resin insulation

9 Bolted busbar joint

10 Pressure ring

HA35

-237

6b e

ps

23

5

6

4

9 8 7

1

10

Busbar module(SF6-insulated)

Busbar module(SF6-insulated)

Module coupling(solid-insulated)

R-HA

35-0

61ep

s

Module coupling

• Connects panels with eachother, as well as containerswithin a panel

• Single-pole, bolted-type

• Consisting of round copperwith cast-resin insulation

• Bolted busbar joint withsilicon rubber insulation

• Stress control by means ofelectrically conductive layersof insulation (inside andoutside)

• Screened by earthing outerlayers with switchgearcontainer

• Switchgear installation,extension or panelreplacement without anywork on the SF6-gas system

Module coupling

1 Module coupling

2 Busbar module

3 Current transformer

350**

1600

2250

280 280

2450

7 8 9

HA35

-237

5f e

ps

600*80

1 6

2

3

4

3

5

Dimensions

* Width of the sectionalizerpanel<– 2000 A: 900 mm,> 2000 A: 1200 mm

**Useful depth of thelow-voltage compartment

4 Circuit-breaker module

5 End wall

6 Bushing in adjacentpanel

7 Busbars

8 Low-voltagecompartment,735 mm high

9 Option:low-voltagecompartment,935 mm high

Dimensions

NX PLUSFixed-Mounted Circuit-BreakerSwitchgear up to 36 kV,SF6-Insulated

Siemens HA 35.51 · 2000 11

Panel construction

Design

R-HA

35-0

62a

eps

Solid-state HMIwith panel door closedwith SIPROTEC 4 bay controller andCAPDIS voltage detection system

Mechanical control boardwith panel door open

*) The basic unit for this is in thelow-voltage compartment

1 LCD SIPROTEC 4

2 Keys for navigation

3 Control keys

4 Function keys

5 LEDs

6 Key-operated switches

7 LCD CAPDIS

8 Test sockets

9 Signalling relay(accessible from the rear)

SIPROTEC 4 bay controller, type 7SJ63 *)and voltage detection system CAPDIS

1 ON/OFF position indication for three-positionswitch

2 ON/OFF operating shaft for three-position switch

3 OFF/EARTHING PREPARED operating shaft forthree-position switch

4 OFF/EARTHING PREPARED position indicationfor three-position switch

5 Mimic diagram

6 Ready indication for busbar module(gas compartment monitoring)

7 Ready indication for circuit-breaker module(gas compartment monitoring)

8 Interlocking for preselection for 2 and 3

9 ON/OFF position indication for circuit-breaker

10 Manual spring charging for circuit-breaker

11 ON pushbutton for circuit-breaker withsealable cap, mechanical

12 Locking device for “feeder earthed”

13 OFF pushbutton for circuit-breaker, mechanical

14 “Spring charged” indication for circuit-breaker

15 Operating cycle counter for circuit-breaker

R-HA

35-0

64ep

s

1 2 3 4

5

8

12

13

14

15

9

11

10

7

6

Solid-state HMI (human-machine interface)

SIPROTEC 4 bay controller,type 7SJ63, Profibus capable,for control, protection, sig-nalling, communication andmeasurement for stand-aloneor master operation.

Features

• LCD for process and equip-ment data, graphically asfeeder mimic controldiagram and as text

• Four programmable functionkeys for frequentlyperformed actions

• Fourteen programmable LEDsfor indicating any desired data

• Two key-operated switchesfor changeover between“local and remote control”and “interlocked andnon-interlocked position”

Voltage detection systemCAPDIS

Features

• Voltage detection systemaccording to VDE 0682,Part 415

• Indication of– Voltage state– Dead state

(active zero indication)– Error

• Integrated signalling relay

• Self-testing, therefore repeatedtesting, demandedin the standards,is not required

• Additional testsockets for phasecomparison withan LRM phasecomparator

Mechanicalcontrol board

Features

• Arranged behindpanel door

• Opening of doorswitches off theSIPROTEC 4 baycontroller,type 7SJ63,automatically(protective func-tion is maintained)

• Three-position switch inter-locked with circuit-breaker

• Cancelling of feeder earthingcan be blocked mechanically

R-HA

35-0

71ep

s

1

2

3

4

7

8

5

6

9

12 Siemens HA 35.51 · 2000

NX PLUSFixed-Mounted Circuit-Breaker

Switchgear up to 36 kV,SF6-Insulated

Standards

The NX PLUS switchgearcomplies with the standardsand specifications listed below:

• VDE 0670, Part 1000

• VDE 0670, Part 6

• VDE 0670, Part 101 et seq.

• VDE 0670, Part 2

• IEC 60694

• IEC 60298

• IEC 60056

• IEC 60129

In accordance with theobligatory harmonization in theEuropean Community, thenational standards of themember countries conformto IEC 60 298.

Type of service location

NX PLUS switchgear can beused as an indoor installation inaccordance with VDE 0101:

• Outside closed electricaloperating areas in locationsnot accessible to the generalpublic. Tools are requiredto remove switchgearenclosures.

• In closed electrical operatingareas. A closed electricaloperating area is a room orarea which is used solely forthe operation of electricalinstallations. This type ofarea is locked at all timesand accessible only toauthorized trained personneland other skilled staff.Untrained or unskilled per-sons must be accompaniedby authorized personnel.

Internal arc test, resistanceto internal arcs

Internal arc test

Tests have been carried outwith NX PLUS switchgear, inorder to verify its behaviourunder conditions of internalarcing.

The resistance to internalarcing complies with therequirements of

• VDE 0670, Part 6,Appendix AA

• IEC 60298, Appendix AA

Resistance to internal arcs

The possibility of faults in theNX PLUS fixed-mountedcircuit-breaker switchgear ismuch less than in previoustypes, due to the single-poleenclosure of external compo-nents and the SF6 insulationof the switchgear:

• All external fault-causingfactors have beeneliminated, such as:

– Pollution deposits– Moisture– Small animals and foreign

bodies

• Maloperations are preventedby the clear, logical layout ofthe operating elements

• The three-position switchand the vacuum circuit-breaker provide short-circuit-proof earthing of the feeder

Should arcing occur in spite ofthis, the pressure is relievedtowards the rear into a duct.

In the improbable event of afault inside the module contai-ner, the SF6 insulation restrictsthe arc energy to only about 1/3of that for air. The pressure-relief facility in the rear panelof the module container isdesigned to operate in an over-pressure range of 2 to 3.5 bar.The gases are dischargedtowards the rear into a duct.

The pressure-relief duct divertsthe gases upwards.

Protection against electricshock, the ingress of waterand solid foreign bodies

The NX PLUS fixed-mountedcircuit-breaker switchgear isfully enclosed and entirelyunaffected by climaticinfluences.

• All medium-voltage switchingdevices are enclosed instainless steel containers,which are welded gas-tightand filled with SF6 gas.

• Live parts outside theswitchgear container aresingle-pole insulated andscreened.

• There are no points at whichleakage currents of high-voltage potential are able toflow off to earth.

• All essential components ofthe operating mechanismare made of non-corrodingmaterials.

Climate and ambientconditions

The NX PLUS fixed-mountedcircuit-breaker switchgearoffers the following degrees ofprotection:

• IP3XD for external enclosure

• IP65 for parts underhigh voltage

in accordance with:

– DIN VDE 0670, Part 6

– IEC 60298 with IEC 60529

Standards

Standards, specifications, guidelines

NX PLUSFixed-Mounted Circuit-BreakerSwitchgear up to 36 kV,SF6-Insulated

Siemens HA 35.51 · 2000 13

Appendix

Power Transmission and Distribution GroupCatalog Index of the Medium-Voltage Division (please contact your Siemens Representative)

Designation Title Order No.

High-Voltage Equipment (Above 52 kV)

HG 21.4 Surge Counting Devices for Surge Arresters E50001-K1521-A401-A1-7600

Medium-Voltage Equipment (High-Voltage Equipment up to 52 kV)

HG 11.11 3AH Vacuum Circuit-Breakers E50001-K1511-A111-A4-7600

HG 11.15 3AY2 Components up to 36 kV for 3AH Vacuum Circuit-Breakers E50001-K1511-A151-A1-7600HG 11.21 3TL Vacuum Contactors E50001-K1511-A211-A1-7600HG 11.31 Disconnectors and Earthing Switches E50001-K1511-A311-A1-7600HG 11.51 NXACT Vacuum Circuit-Breaker Modules E50001-K1511-A511-A1-7600

HG 12 Vacuum Switches, Switch-Disconnectors, HV HRC Fuse E50001-K1512-A101-A4-7600

HG 13 Switchgear Interlock Units, Control Valves, Compressed Air Systems E86010-K1513-A101-A1-7600

HG 21 Overvoltage Protection E50001-K1521-A101-A1-7600HG 21.2.5 3EH2 Surge Arresters E50001-K1521-A251-A3-7600HG 21.2.7 2EE2 Special-Purpose Surge Arresters for the Protection of Motors,

Generators and Furnace Transformers E50001-K1521-A271-A3-7600

HG 22 Insulators of Cast Resin (Excerpt) E50001-K1522-A111-A1-7600

HG 24 Current and Voltage Transformers E50001-K1524-A101-A2-7600

HG 25 Air-Cored Reactors, High-Voltage Capacitors E86010-K1525-A101-A4-7600

Medium-Voltage Switchgear

HA 25.21 Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers (Metal-Clad) E50001-K1425-A311-A6-7600HA 25.31 Type 8BK40 Switchgear up to 17.5 kV/63 kA with Withdrawable Circuit-Breakers E50001-K1425-A411-A3-7600HA 25.71 NXAIR Withdrawable Circuit-Breaker Module Switchgear up to 12 kV, Air-Insulated E50001-K1425-A811-A1-7600

NXAIR M Withdrawable Circuit-Breaker Module Switchgear up to 24 kV, Air-Insulated E50001-K1425-E811-A1-7600

HA 27.11 Type 8BK30 Switchgear up to 12 kV with Withdrawable Vacuum Contactors E50001-K1427-A111-A3-7600

HA 35.11 Panels up to 36 kV with Fixed-Mounted Circuit-Breakers, SF6-Insulated,Types 8DA10 and 8DB10, Single-Pole, Metal-Enclosed, Metal-Clad,Single-Busbar Switchgear, Duplicate-Busbar Switchgear E50001-K1535-A101-A6-7600

HA 35.41 Type 8DC11 Panels up to 24 kV, Fixed-Mounted VacuumCircuit-Breaker Switchgear, SF6-Insulated E50001-K1435-A401-A4-7600

HA 35.51 NXPLUS Fixed-Mounted Circuit-Breaker Switchgear up to 36 kV, SF6-Insulated E50001-K1435-A511-A2-7600

HA 40.1 Switchgear for Secondary Distribution Systems up to 24 kV,SF6-Insulated, Types 8DJ and 8DH: General Part E50001-K1440-A111-A2-7600

HA 41.11 Fixed-Mounted Ring-Main Units up to 24 kV, SF6-Insulated, Type 8DH10 E50001-K1441-A101-A2-7600

HA 45.11 Secondary Distribution Switchgear up to 24 kV, SF6-Insulated, Type 8DJ10 E50001-K1445-A111-A7-7600HA 45.31 Secondary Distribution Switchgear up to 24 kV, SF6-Insulated, Type 8DJ20 E50001-K1445-A311-A3-7600

HA 51.1 Type 8FB1 Compact Transformer Substations up to 24 kV E50001-K1451-A111-A2-7600

Medium-VoltageSwitchgear

High-Voltageand Medium-VoltageEquipment

NX PLUSFixed-Mounted Circuit-Breaker

Switchgear up to 36 kV,SF6-Insulated

14 Siemens HA 35.51 · 2000

Appendix

Notes

NX PLUSFixed-Mounted Circuit-BreakerSwitchgear up to 36 kV,SF6-Insulated

Siemens HA 35.51 · 2000 15

Appendix

Conditions of Sale and Delivery Export Regulations Trademarks

Printed in GermanyKGK 03.00 8.0 VO/- 16 En 101620 6101/D6048

Subject to theGeneral Conditions of Supplyand Deliveryfor Products and Servicesof the Electrical and ElectronicIndustry and to any otherconditions agreed upon withthe recipients of catalogs.

nThe technical data, dimensionsand weights are subject tochange unless otherwisestated on the individual pagesof this catalog.

The illustrations are forreference only.

We reserve the right to adjustthe prices and shall charge theprices applying on the date ofdelivery.

In accordance with the presentprovisions of the GermanExport List and the US Com-mercial Control List, exportlicences are not required forthe products listed in thiscatalog.

An export licence may howeverbe required due to country-specific application and finaldestination of the products.

Relevant are the export criteriastated in the delivery note andthe invoice regarding a possibleexport and reexport licence.

Subject to change withoutnotice.

All dimensions in this catalogare given in mm.

All product designations usedare trademarks or productnames of Siemens AG or ofother suppliers.

Responsible for:

Technical contents:Stephan Werner,Siemens AG, Dept. EV MS1 VMErlangen

General editing:Gabriele Pollok,Siemens AG, Dept. EV BK TErlangen

Dimensions

Published by

Siemens Aktiengesellschaft

Power Transmission and DistributionMedium-Voltage DivisionPostfach 32 20

91050 ErlangenDEUTSCHLAND

Order No.: E50001-K1435-A511-A2-7600www.ev.siemens.de/index_e.htm