flame detectors
DESCRIPTION
Flame watcher is a state-of-the-art Flame Detectors series having different ranges of UV & IR Flame Detector. Flame detectors are the first line of defense in fire detection and extinguishing system. Which provides an excellent safety measure against flame, preventing it from turning into a catastrophic fire, saving lives and assets. Flame Detectors is a Microcontroller based fully digitally addressable device. It utilizes smart sensor technology for Accurate Flame detection.it utilizes a sophisticated algorithm that offers excellent false alarm immunity. Provided with high sensitivity, it is capable of detecting hydrocarbon-based flame within a few seconds and prevents human loss as well as industrial loss. Flame Detectors Provide Industrial standard output such as 4-20mA / 0-10V, relays, RS-485. It is HART addressable and connectivity is provided via Bluetooth and Wi-Fi/ LoRa /IoT for the mobile alert. It is also equipped with a built-in data logging facility, which provides a Date-time stamped report of important / alarm events for further analysis. It has a Minimum of 90 cones of vision on the Horizontal & vertical axis and can detect fire up to 65 meters within a few seconds. Its performance can be tested by using a test Lamp (FTU-3311-FLP).UV/ IR Flame detector can be integrated with PLC/SCADA system. It is designed in such a way that, It is Universally Compatible, which enables it to be connected to any Fire alarm panel or any other control panel of any make, So in case of fire, it alerts the nearby personnel, generates the factory-wide alarm, and initiate preventing action such as sprinkler/form-based extinguishing system, evacuation protocol, etc.TRANSCRIPT
![Page 1: Flame Detectors](https://reader035.vdocuments.net/reader035/viewer/2022070100/6012948dea0e7c4f5c0aedf5/html5/thumbnails/1.jpg)
FLD-0011-FLP
UV FLAME DETECTOR
• Approval & Compliance for Flameproof :
Certified to EX-d IIC, IP66
Standard Compliance :
• IS/IEC 60079-0 : 2004
• IS/IEC 60079-1 : 2007
• IS/IEC 60529 : 2001
• Detector detects fire by using UV sensor
• Line of Sight visual range ( upto specific distance )
• Long distance detection & Moderate false alarm immunity
• Sensitivity Selection – To ensure no zone cross over detection
• High sensitivity combined with fast response time to ensure rapid &
accurate flame detection
• The high dynamic range allows detection of small & large flames,
nearby or over large distance
• Multiple output options for maximum flexibility and compatibility.
- (3) Relays for FLAME DETECTION, AUXILIARY & FAULT
- 0-20mA (Stepped)
- Optional HART protocol for configuration setting
- RS-485, MODBUS compatible
• High Reliability
• User programmable via Bluetooth, HART or RS-485
• Suitable For Indoor Applications
• Cold Storage
• Fume Hoods
• Warehouses
• Heating Rooms For Chemicals
• Radio Amplifier Rooms / Isolators For Antennas
• Battery Storage Rooms / Data Communication
• Laboratories
• Indoor Chemical, Fuel & Solvent Storage
![Page 2: Flame Detectors](https://reader035.vdocuments.net/reader035/viewer/2022070100/6012948dea0e7c4f5c0aedf5/html5/thumbnails/2.jpg)
Protection Class IP-66Cabinet Material Cast Aluminium alloy, LM-6 or Stainless Steel SS-316 Cable Entry DOUBLE COMPRESSION CABLE GLAND (Ex-Proof)
M20 X 1.5PWiring 12-22AWG (2.5mm²- 0.3 mm²)Dimension i ) 155mm x (H) Stopper plug x 263mm (W) with i Hooter & cable gland x 125mm (D) ii) 155mm (H) with Stopper plug x 223mm (W) with Stopper plug & cable gland x 125 mm (D) Mounting Wall Mounting Stand Weight Approx 2.53kg (LM 6) / 7.00 kg (SS-316)
Response Time Typically Less than 3 seconds (Depending on Flame Size
& Sensitivity)
Adjustable Time Delay Upto 30 seconds
Field of View 100° Horizontal, 90° Vertical, 120° Diagonal cone vision
Supply Voltage 18 to 36 VDC, typically 24VDC Power Consumption Less than 3W
Parameter Setting Field configuration settings done by Bluetooth or
MODBUS RTU Protocol.
Spectral Response UV Band - ( 185nm to 260nm )
Detection Range • n-Heptane : 88ft (27m) : : • Kerosene 82ft (25m)( At highest sensitivity
Setting for 1ft² pan fire ) • : 82ft (25m) Diesel Fuel • M ethanol : 66ft (20m) • Gasoline : 82ft (25m)
ORDERING INFORMATION
TECHNICAL SPECIFICATIONS
100° HORIZONTAL 90° VERTICAL 120° DIAGONAL
FIELD OF VIEW
ENVIRONMENTAL
ACCESSORIES (OPTIONAL)
Specifications subject to change without any prior notice* Before placing order please Refer the above ordering information or Contact below address for assistance.* if Hooter Cum Flasher is Connected then only Auxiliary, Fail Safe relay output available.
Version FLD-0011-FLP-R2-20-02-2020
Follow us on
ELECTRICAL
OUTPUT SIGNAL
GENERAL
4-20mA Current Output 250 to 600 ohms load driving capacity.
Fault : 1mA Normal : 4mA Fire detect : 20mA
LED Indication Blinking POWER LED, FIRE DETECT LED & COMMUNICATION LED
Relay Three SPDT relays 2A @ 24 VDC or 120 VAC for Fail safe, Fire detection & Auxiliary output. If Hooter Cum Flasher is Connected, then only AUXILIARY & FAIL SAFE RELAY output available.
Communication RS-485 communication port with MODBUS RTU protocol. HART Protocol use for configuration changes by using AEPL communicator(Proprietary Optional )
PERFORMANCE
0 0Operating Temperature -15 C to +50 C0 0Storage Temperature -20 C to +85 C
Humidity Less than 95% Non-Condensing.
• RS-485 to USB or RS-232 convertor Hooter Cum Flasher. •
• Protection Cover
FLAMEPROOF HOUSING
UV Sensor’s SpectralSensitivity
Ultraviolet Region
Rela
tive
Ener
gy
185nm 260 nm
UV & IR Spectrum
Visible Region Infrared Region
3000 nm 5000 nm500 nm 1000 nm 1500 nm 2000 nm 2500 nm 4000 nm
IR Sensor’s SpectralSensitivity
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:::
:
:
::
FLD-0011-FLP-UV DCC) Hooter Cum Flasher 1) No 2) Yes
BB) Transmission Output1) 4-20mA2) 4-20mA with HART
AA) Enclosure (FLP)1) LM-6 2) SS-316
D) Protection Cover 1) No 2) Yes