floor-standing-type-fvqcveb-pdf - daikin home | daikin ... · use only those parts and accessories...

20
All rights reserved 02/14 SS c PCSPH1411 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. Cautions on product corrosion Warning Ask a installer or contractor to install this product. Do not try to install the product by yourself. Improper installation can result in water or refrigerant leakage, electrical shock, or explosion. Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. out notice. !"#$"%& '() +$,,%- .#(/0,( 123#%"- 45 1#( 6783"$ 9:"(3"- ;%078#/ <"(0"%- =#/78 <70>- 4?@A B"$C D,C& E@'F GH'I?J@@KGH'I?5G' +#L D,C& E@'F GH'I?5GM

Upload: vukhue

Post on 18-Mar-2019

234 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

All rights reserved 02/14 SSc

PCSPH1411

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Ask a installer or contractor to install this product. Do not try to install the product by yourself. Improper installation can result in water or refrigerant leakage, electrical shock, or explosion.

Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, or explosion.

Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

out notice.

!"#$"%&'()*+$,,%-*.#(/0,(*123#%"-*45*1#(*6783"$*9:"(3"-*;%078#/*<"(0"%-*=#/78*<70>-*4?@AB"$C*D,C&**E@'F*GH'I?J@@KGH'I?5G'+#L*D,C&*E@'F*GH'I?5GM

Page 2: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Daikin meets your needs with this full lineup of inverters for various types of indoor units and power supplies.

1 2

FCQ50KVEA

71 100 125 14050 603HP 4HP 5HP 6HP2HP 2.5HP

FCQ60KVEA

FBQ50DAVET FBQ60DAVET

FVQ50CVE FVQ60CVE

RZR50LVVM RZR60LVVM

FCQ71KVEA FCQ100KVEA

FHQ71CAVEB FHQ100CAVEB

FAQ71CVEA

FBQ71DAVET

FAQ100CVEA

FBQ100DAVET

FCQ125KVEA FCQ140KVEA

FCQ100KVLT FCQ125KAVLT FCQ140KAVLT

FBQ100DAVET FBQ125DAVET FBQ140DAVET

FCQ60KVEAX2 FCQ71KVEAX2

FHQ125CAVEB

FBQ125DAVET

FHQ140CAVEB

FBQ140DAVET

FVQ71CVEB FVQ100CVEB FVQ125CVEB FVQ140CVEB

RZR125LVVM RZR140LVVM

FBQ60DAVETX2 FBQ71DAVETX2

FVQ60CVEX2 FVQ71CVEBX2

Indoor unit

Indoor unit

CEILING MOUNTED CASSETTE TYPE

Round Flow

Indoor unit

CEILING SUSPENDED TYPE

Indoor unit

WALL MOUNTED TYPE

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

FLOOR STANDING TYPE

Indoor unit

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

Indoor unit

Indoor unit

FLOOR STANDING TYPE

Indoor unit

Outdoor unit

Series

RZR71LVVM RZR100LVVM

OUTDOOR UNIT

CEILING MOUNTED CASSETTE TYPE

Round Flow

3 Phase, 220 V3 Phase, 380 V

1 Phase, 220–230 V

1 Pha

se, 2

20–2

30 V

Pair

Sim

ulta

neou

s Twi

n Mu

lti

RZQ125KCTLT RZQ140KCTLT

Indoor unit

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

Indoor unit

Outdoor unitOutdoor unit

RZQ100KCTLTRZQ125LUYLT RZQ140LUYLTRZQ100LUYLT

OUTDOOR UNIT

CEILING MOUNTED CASSETTE TYPE

Round Flow

Pair

3 Pha

se, 2

20V/

380 V

NEW NEW

NEW

NEW

NEW

NEW

NEW

NEW

NEW

NEW

NEW

NEW

NEW NEW

NEW NEW

NEW NEW

NEW

NEW NEW

NEW NEW

NEWNEW NEW

NEW NEW

Page 3: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Non-inverter

Inverter Time

Running current

Starting current

Time

Running current

Curre

ntCu

rrent

At startup, full power is used to achieve the set temperature quickly. Then, the capacity is adjusted according to the outdoor temperature changes and subtle indoor load changes to achieve fine capacity control resulting in a more stable room temperature.

Inverter performs variable control of frequency, which determines air conditioner’s power performance.

Enhanced comfort with Inverter

34 new combinations added!

Small temp. differenceCools a room

in less time

Cooling operation

Inverter power controlNon-inverter type air conditioner

Time

Temp

Set temp

Non-inverter type air conditioners must be switched on and off repeatedly, causing large fluctuations of the room temperature.

Achieved higher COP

Comfortable

Energy saving

Comfortable

Comfortable currents of air are sent to every corner of the room.

Simultaneous Twin Multi OperationSimultaneous Twin Multi Operation

Energy saving

3 4

At startup, inverter raises frequency smoothly, eliminating the starting current spike.

COP is equal to capacity (kW) divided by power consumption (kW), and the larger the COP value, the higher the energy efficiency, enabling cooling and heating with less electricity and increasing the energy saving performance.

Note : *Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24.0°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

What is COP (Coefficient of Performance)

COP

1

2

3

4

FCQ50KVEARZR50LVVM

4.83

Cooli

ng*

FCQ140KVEARZR140LVVM

2.85

Cooli

ng*

FCQ125KVEARZR125LVVM

3.40

Cooli

ng*

FCQ100KVEARZR100LVVM

3.60

Cooli

ng*

FCQ71KVEARZR71LVVM

3.57

Cooli

ng*

FCQ60KVEARZR60LVVM

4.30

Cooli

ng*

CEILING MOUNTED CASSETTE TYPE

(1 Phase, 220–230 V)Round Flow

Full Lineup of Inverter SeriesFull Lineup of Inverter SeriesDaikin meets your needs with this full lineup of inverters for various types of indoor units and power supplies.

CEILING MOUNTED CASSETTE TYPERound Flow

CEILING MOUNTED CASSETTE TYPERound Flow

CEILING MOUNTED CASSETTE TYPERound Flow

CEILING SUSPENDED TYPE

WALL MOUNTED TYPE

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPEFLOOR STANDING TYPE

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

FLOOR STANDING TYPE

Pair

Pair

Pair

Twin

1 Pha

se, 2

20–2

30 V

3 Pha

se,

220 V

3 Pha

se,

380 V

CEILING MOUNTED CASSETTE TYPERound Flow

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

50 60 71 100 125 140

: New Lineup : Continuous

Refrigerant branch piping kit for Twin Multi operation

2 sets of Twin Multi

For example, four indoor units are judiciously spaced in this wide

single-floor restaurant to deliver comfortable currents of air to every corner of the room.

Page 4: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Airflow distribution

Creates uniform comfort throughout

the space

Comfort enhanced by Round Flow!

With uniform temperature distribution

Enhanced Comfort

Greater comfortImproved energy saving

• Condition after exposure to the smoke of 600 cigarettes in 1 m3 enclosed space.

Treated surface

Untreated surface

Grimy surface

Resists soiling

External panels are treated with a coating that repels dirt.

Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.

Avoids uneven temperature and discomfort caused by drafts.

To prevent dirt sticking to the external panels, they have been coated with a surface treatment.

Because air flows out from corner outlets, comfort spreads more widely.

360° airflow Air movement is gentle with Round Flow

Condensation does not easily form on and dirt does not cling to non-flocking flaps. It is easy to clean.

Non-flocking flapsSilver ion anti-bacterial drain pan

Prevents mould and microorganisms growing out of the dust and moisture that adheres to the filters.

Filter has anti-mould and bactericidal treatment

Grime prevention and bactericidal coating: Make cleaning easier.

Adapts easily to the installation space.

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet.

3-way flow L-shaped 2-way flow

Opposite 2-way flow

(E.g., installed in a corner)

(E.g., installed in a long room)

(E.g., installed near a wall)

(E.g., installed in middle of ceiling)

4-way flow also possible.

All-round flow

360° airflow can maintain comfort even if air discharge speed is lower.

Typical flow patterns There are a total of 23 flow patterns.

If you raise the set temperature by 1 to 1.5°C,and velocity is decreased by 25%, you still obtain the same feeling temperature and comfort.

Operation sound increases when using 2-way or 3-way flow.

• • • • • *1 *2 • *2 • • • *2 • • • • • • • • • • *2

CleanlinessComfort Work & Servicing Control features OthersOptionsFeatures

Accessory required for indoor unitOption

*1Applicable when wired remote controller is used*2For the outdoor units

*3Applicable when BRC1E62 is used*4Applicable when BRC1C61 is used

CEILING MOUNTED CASSETTE TYPE

FCQ50/60/71/100/125/140K

Swin

g pa

ttern

sel

ectio

n

Switc

habl

e fa

n sp

eed

(2 s

tep)

Aut

o sw

ing

Prog

ram

me

"Dry

"

Hig

h ce

iling

app

licat

ion

Nig

ht q

uiet

ope

ratio

n

Dra

in p

ump

mec

hani

sm

Silv

er io

n an

ti-ba

cter

ial

drai

n pa

n

Ant

i-bac

teria

l air

filte

r

Pre

char

ged

for

up to

30

m

Long

-life

filte

r

Filte

r sig

n

Cei

ling

soili

ng p

reve

ntio

n

Low

gas

pre

ssur

e de

tect

ion

Emer

genc

y op

erat

ion

Self-

diag

nosi

s fu

nctio

n

Ultr

a lo

ng-li

fe fi

lter

Hig

h-ef

ficie

ncy

filte

r

Fres

h ai

r int

ake

kit

Con

trol b

y 2

rem

ote

cont

rolle

rs

Aut

o-re

star

t

Gro

up c

ontro

l by

1 re

mot

e co

ntro

ller

Exte

rnal

com

man

d co

ntro

l

Cen

tral r

emot

e co

ntro

l

Inte

rlock

con

trol

DIII

-NET

com

mun

icat

ion

stan

dard

Ant

i cor

rosi

on tr

eate

dhe

at e

xcha

nger

s

Two

sele

ctab

le

tem

pera

ture

-sen

sors

Round Flow

Cassette air conditioner with 360° uniform airflow sets the standardCassette air conditioner with 360° uniform airflow sets the standard

Note: Remote controller cable not included. Cables must be procured locally.

BRC1E62

(Wired Remote Controller)Navigation Remote Controller

A signal receiver must be added to the indoor unit.

Wireless LCD remote controller

Wireless remote controller and signal receiver unit are sold as a set.

Signal receiver unit

(Installed type)

5 6

Remote controller

*3 *3 *3 *3 *4

Setp

oint

rang

e se

t

Wee

kly

sche

dule

tim

er

Setp

oint

aut

o re

set

Off

timer

(pro

gram

med

)

On/

Off

timer

BRC7F633F

Page 5: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Options required for specific operating environments

High-efficiency filterAvailable in two types: 65% and 90% colorimetry.

Using this kit, a duct can be fitted to increase the intake of outdoor air.

*Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

**Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking.

***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and may also influence temperature sending.

Fresh air intake kit

Even in smoky environments where the air conditioning is on most of the time, the ultra long-life filter only has to be changed once a year.

Ultra long-life filter Panel spacerUse when only minimal space is available between drop ceilings and ceiling slabs.

Sealing material of air discharge outletSealing material block air discharge openings not used in 2-way or 3-way blow.

Branch duct (direct-connection round duct)Outside

Note: Use of options will increase operating sound.

The units can be installed in the following different ways.

Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing your unit.

Direct installation type

Flexible duct

T-joint pipe

Intake duct(procured locally)(duct length: 4 m max.)

Intake duct(procured locally)(duct length: 4 m max.)

Connectionchamber

Suctionchamber

Duct flange (with insulation material) Intake duct(procured locally)

Chamber type (with T-joint pipe and without fan)

Flexible duct(procured locally)T-joint pipe(procured locally)

Chamber type (without T-joint pipe and fan)

KDDP55X160KDDP55B160K KDDP55B160

Easier to maintain

With Ultra long-life filters (option), maintenance is not required in normal shops or offices for up to four years.

The condition of the drain pan anddrain water can be checked byremoving the drain plug andintake grille. Drain plug

Just open the

intake grille!

40mm

Panel spacer

A round duct can be attached without the need for a chamber.A flanged port for direct connection of a round duct is provided. An existing branch duct chamber can also be fitted (square slit hole).

Connectionchamber

Suctionchamber

Smoky atmosphere: annual filter change

Ordinary store or office: filter change every 4 years

*For dust concentration of 0.3 mg/m3 (Requires separately sold Air Cleaner.) 1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year

*For dust concentration of 0.15 mg/m3

4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years

Note:

Quick and easy to installJust 256 mm high. Installable in tight ceiling spaces (50K-71K)

Fine square panels Compact body and quiet operation

*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor.

Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

Note: Air direction is set to the standard position when the unit is shipped from the factory. The position can be changed from the remote controller.

Panel size is same for all models, FCQ50-140K.It is easy to maintain a neat appearance when multiple units are installed.

Optimal comfort and convenience assured by air discharge modes

Both indoor unit and wired remote controller (option (BRC1D61,BRC1E62) ) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature must be set during commissioning by the technicians.

Two selectable temperature-sensors

Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level.

Suitable for high ceilings

Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

On/Off timer

Indoor unit High Low

125K 44 34140K 44 36

100K 43 3271K 35 2860K 35 2850K 35 28

dB(A)

Same for all models

Air direction

Auto air direction control

Settable to 5 different levels between 15° and 60°

Settable to 5 different levels between 25° and 60°

Auto-swing between15° and 60°

Auto-swing between25° and 60°

Recommended for shops with light coloured ceilings that

must be kept spotless.Standard position to

prevent draft.

Standard setting Setting to prevent soiling of ceiling*

The air direction is set automatically to the memorised position of the previous air direction.

Desired situation

Auto-swing

5-levelsair directionsetting

*Closing of the corner discharge outlets is recommended.

Number of air discharge outlets used

4-wayflow

3-wayflow

2-wayflow

4-wayflow

3-wayflow

2-wayflow

3.1 m3.4 m4.0 m

All round flow

2.7 m3.0 m3.5 m

3.0 m3.3 m3.5 m

3.5 m3.8 m-

3.4 m3.9 m4.5 m

All round flow

3.2 m3.6 m4.2 m

3.6 m4.0 m4.2 m

4.2 m4.2 m-

StandardCeiling height High ceiling

High ceiling

Criteria for ceiling height and number of air discharge outlets

950 mm 950 mm

Note: Factory settings are for standard ceiling height and all-round flow. High ceiling settings (1) and (2) are set with the remote controller by field setting.

256 mm *1 266 mm *2

*1 298 mm high with 100K–140K*2 308 mm high with 100K–140K

All models can be installed without using lifter because of the light weight.

Connection to a centralised control system is available without option

Low gas pressure detection

Drain pump is equipped as standard accessory with 850 mm lift.

Transparent drain socket

Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height.

Since the orientation of the intake grill can be adjusted after installing,the direction of the intake grill lines can be unified when multiple unitsare installed.

Note: If the wireless remote control option is installed, a light receptor unit is housed in one of the adjuster pockets.

Easy height adjustment

Installable in any direction

Because the drain socket is transparent, after the drain piping has been installed, it is easy to check if the drain come out through the socket.High setting provides maximum reach while low

setting minimises drafts.

Switchable fan speed: High/Low

175 mm

850 mm

100K–140K50K–71K

7 8

CEILING MOUNTED CASSETTE TYPE Round Flow

(Ceiling height is reference value)

Page 6: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

10

* For dust concentration of 0.15 mg/m3

Non-flocking flap

Indoor unit High Low71CA 38 34

100CA 42 34125CA 44 37

Middle363841

140CA 46 3842

Drain pump kit (built inside main unit)

600 mm

Easy maintenance

*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor.

Oil resistant grille

Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments.

Oil-resistant plastic is used for the air suction grille. This satisfies durability in restaurants and other similar environments.

Two time settings (2500 hrs and 1250 hrs) are available to match the installation environment. Maintenance time warning is displayed on the remote controller (filter sign).

Easy-clean, flat surfaces

Long-life filter lasts up to 6 months*

Comfortable

Both indoor unit and wired remote controller (option (BRC1E62) ) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature requires initial setting by the installer.

Dehumidification is a microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Two selectable temperature-sensors

Programme "Dry"

Installable on ceilings 4.3 m high

Flexible installation

*Water used in the test-run can now be drained from the air discharge opening rather than from the side as was formerly the case.

The unit fits more snugly into tight spaces. Flap neatly closes

when not in use.

Fresh white colour.

Drain pump kit (option) can be easily incorporatedDrain pipe connection can be done inside the unit. refrigerant and drain pipe outlets are at the same opening.

All wiring and internal servicing can be done from under the unit

Quiet operation

Installation flexibility for freedom of design

The latest stylish model

Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

dB(A)

Pipes more easily rigged

Low gas pressure detection

Condensation does not easily form on and dirt does not cling to non-flocking flap. It is easy to clean.

Non-flocking flap

The technology of the DC fan motor, wide sirocco fan, and large heat exchanger combine for greater airflow and quiet operation.

Sophisticated design

Connection to a centralised control system is available, without option.

Drain pump kit (option) includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.

Auto swing (up and down) and louvers (left and right by hand) bring comfort to the room

Switchable fan speed: High/Middle/Low and Auto

30 mm or more

30 mm or more

High/Middle/Low : 46/42/38 db(A)

("Auto" is applicable when BRC1E62 is used.)

Louver manually adjusts for straight or wide angle airflow

Accessory required for indoor unitOption

Note: Remote controller cable not included. Cables must be procured locally.

BRC1E62

(Wired Remote Controller)Navigation Remote Controller

A signal receiver must be added to the indoor unit.

Wireless LCD remote controller

Wireless remote controller and signal receiver unit are sold as a set.

BRC7GA56

9

CEILING SUSPENDED TYPE

FHQ71/100/125/140CA

Comfortable airflow travels throughout the roomComfortable airflow travels throughout the room

NEW

Signal receiver unit (Installed type)

CleanlinessComfort Work & Servicing Control features OthersOptionsFeatures

• • • *1 • • • • • • • • • *3*3*2 *5

*1Installable on max. 4.3 m high ceiling *2Applicable when wired remote controller is used*3For the outdoor units*4Applicable when BRC1E62 is used*5Option

Pre

char

ged

for

up to

30

m

Ant

i-bac

teria

l air

filte

r

Filte

r sig

n

*3

Low

gas

pre

ssur

e de

tect

ion

Emer

genc

y op

erat

ion

Self-

diag

nosi

s fu

nctio

n

Con

trol b

y 2

rem

ote

cont

rolle

rs

Aut

o-re

star

t

Gro

up c

ontro

l by

1 re

mot

e co

ntro

ller

Exte

rnal

com

man

d co

ntro

l

Cen

tral r

emot

e co

ntro

l

Ant

i cor

rosi

on tr

eate

dhe

at e

xcha

nger

s

DIII

-NET

com

mun

icat

ion

stan

dard

Fres

h ai

r int

ake

kit

Inte

rlock

con

trol

Dra

in p

ump

mec

hani

sm

Switc

habl

e fa

n sp

eed

(3 s

tep)

Aut

o sw

ing

Prog

ram

me

"Dry

"

Hig

h ce

iling

app

licat

ion

Two

sele

ctab

le

tem

pera

ture

-sen

sors

Remote controller

*4 *4 *4 *4

Setp

oint

rang

e se

t

Wee

kly

sche

dule

tim

er

Setp

oint

aut

o re

set

*3

Nig

ht q

uiet

ope

ratio

n

Off

timer

(pro

gram

med

)

Page 7: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

12

Comfortable

Maintenance possible from the front of the unitAll maintenance tasks can be carried out via front access. During service work, attachment and detachment of parts is easier.

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Programme "Dry"

Two selectable temperature-sensors

Comfort even on the far side of the roomTo carry air to the far side of long rooms, extra-high airflow adds 10% more fan speed the "high" setting. Air discharge strength is selected from the remote controller by field setting.

Easy cleaning

6-direction piping offers greater installation flexibility.

Compact & Sophisticated design

FAQ100

Flaps neatly close when not in use

Easy installing and servicing

Drain pump kit is available as option.

Removable and washable grille

Connection to a centralised control system is available without option

Drain pump kit can be installed on either left and right side of the air conditioner.

Height of drain up

Drain pump kit Indoor unit

Installs onto side of unit.

1,000 mm

Refrigerant piping

1,200mm

340mm

370mm shorter

9kg lighterHeight

FAQ100BV360mm

Width 1,570mm

Weight 26kg

FAQ100C340mm

1,200mm

17kg

Depth 200mm 240mm

Auto airflow rate (When BRC1E62 is used)

Switchable fan speed: High/Middle/LowCondensation does not easily form on and dirt does not cling to non-flocking flaps. It is easy to clean.

Non-flocking flaps

Flat panel, easy to wipe dust off

An air discharge modes ensure comfortable air distribution across the entire room

Auto swing (up and down) and wide-angle louvers (left and right by hand) facilitate even room temperature

Auto-swing 5-level air direction setting

Gettable to 5 different levels

Soft material louver bends airflow over a wider area

Wide-angle louvers (by hand)

11

WALL MOUNTED TYPE

FAQ71C

FAQ100C

FAQ71/100C

Compact design and easy installationCompact design and easy installation

• • •• *4 • *3 • • • • • • • • • *3

CleanlinessComfort Remote controller Work & Servicing Control features Others

Features

*2

*1Applicable when BRC1E62 is used *2Applicable when wired remote controller is used*3For the outdoor units

*4Applicable when BRC1C61 is used*5Option

Switc

habl

e fa

n sp

eed

(3 s

tep)

*1

Aut

o ai

rflow

rate

Aut

o sw

ing

Prog

ram

me

"Dry

"

Hig

h fa

n sp

eed

mod

e

On/

Off

timer

*1

Off

timer

(pro

gram

med

)

*1

Wee

kly

sche

dule

tim

er

*1

Setp

oint

rang

e se

t

*1*3

Setp

oint

aut

o re

set

Pre

char

ged

for

up to

30

m

Mou

ld-p

roof

air

filte

r

Filte

r sig

n

Emer

genc

y op

erat

ion

Self-

diag

nosi

s fu

nctio

n

Con

trol b

y 2

rem

ote

cont

rolle

rs

Aut

o-re

star

t

Ant

i cor

rosi

on tr

eate

dhe

at e

xcha

nger

s

DIII

-NET

com

mun

icat

ion

stan

dard

*5

Dra

in p

ump

mec

hani

sm

*3

Low

gas

pre

ssur

e de

tect

ion

Gro

up c

ontro

l by

1 re

mot

e co

ntro

ller

Exte

rnal

com

man

d co

ntro

l

Cen

tral r

emot

e co

ntro

l

Inte

rlock

con

trol

Two

sele

ctab

le

tem

pera

ture

-sen

sors

Nig

ht q

uiet

ope

ratio

nNEW

Right pipe

Left pipe

Back-left pipe

Back-right pipe

Bottom-left pipe

Bottom-right pipe

Accessory required for indoor unitOption

Note: Remote controller cable not included. Cables must be procured locally.

BRC1E62

(Wired Remote Controller)Navigation Remote Controller

A signal receiver must be added to the indoor unit.

Wireless LCD remote controller

Wireless remote controller and signal receiver unit are sold as a set.

BRC7EB519

Signal receiver unit (Installed type)

Page 8: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Increased freedom of design thanks to variable control over external static pressure

Comfort airflow achieved in accordance with conditions such as duct length.Using a DC fan motor, the external static pressure can be controlled within a range of 50 Pa to 200 Pa.

Thin, lightweight indoor unit makes delivery and installation easy.

With a height of only 300 mm, installation is possible even in buildings with narrow ceiling spaces.

3001,000

36

1,400700

HeightIndoor unit

WidthDepth

46Machine weight

50/60/71DA 100DA 125/140DA

Freely control external static pressure

50 Pa 200 PaSet to high static pressure for

advanced needs such as when using dampers and long ducts.

Set to low static pressure when ducts

are short.

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)

Ventilation grille

Door-installedventilation grille

Ventilation grille

Wall-installedventilation grille

Under-door cutout

Under-door cutoutWhen air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

Ventilates air through the partitioning wall. (See right)

Partitioning wall

Note: The under-door cutout method should be used only when there is a small volume of airflow.

(mm)

(mm)

(mm)

(kg)

Quiet operation

When testing standard integrated ceiling units that employ duct work, much time used to be required to adjust airflow to the right level. Thanks to the ability provided by Daikin to automatically perform this troublesome adjustment using a remote controller, this step is now quick and easy. (Adjust by H tap .)1. Adjust to approximately ±10% of the rated H tap airflow. 2. Once actual operation has begun, adjustment of the rated airflow is not possible.

Reduced installation timeUse remote controller to adjust airflow

Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.

Silver ion anti-bacterial drain pan

Maintenance is easy because the drain pan can be removed.

Easy maintenance

Clean

Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.This feature requires initial setting by the installer. *Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.

**Wireless remote controller does not have a temperature-sensor.

Two selectable temperature-sensorsComfortable

dB(A)100DA 125/140DA

HighLow

38 4033 36

50/60/71DA3732

300mm

Easier connection with the centralised control system

Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

Accessory required for indoor unitOption

Note: Remote controller cable not included. Cables must be procured locally.

BRC1E62

(Wired Remote Controller)Navigation Remote Controller

A signal receiver must be added to the indoor unit.

Wireless LCD remote controller

Wireless remote controller and signal receiver unit are sold as a set.

BRC4C64

Control featuresWork & ServicingComfort Cleanliness OthersOption

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

Features

*1Applicable when wired remote controller is used*2For the outdoor units*3Applicable when BRC1E62 is used*4Applicable when BRC1C61 is used*5Option

• *2• *1 *2 *2• • • • • • • *2• •

Switc

habl

e fa

n sp

eed

(2 s

tep)

Prog

ram

me

"Dry

"

Nig

ht q

uiet

ope

ratio

n

*5

Ant

i-bac

teria

l air

filte

r

Silv

er io

n an

ti-ba

cter

ial

drai

n pa

n

Pre

char

ged

for

up to

30

m

Filte

r sig

n

Self-

diag

nosi

s fu

nctio

n

Emer

genc

y op

erat

ion

Low

gas

pre

ssur

e de

tect

ion

Ant

i cor

rosi

on tr

eate

dhe

at e

xcha

nger

s

Hig

h ef

ficie

ncy

filte

r

Con

trol b

y 2

rem

ote

cont

rolle

rs

Aut

o-re

star

t

Gro

up c

ontro

l by

1 re

mot

e co

ntro

ller

Exte

rnal

com

man

d co

ntro

l

Cen

tral r

emot

e co

ntro

l

Inte

rlock

con

trol

DIII

-NET

com

mun

icat

ion

stan

dard

Two

sele

ctab

le

tem

pera

ture

-sen

sors

FBQ50/60/71/100/125/140DA

Signal receiver unit

(Separate type)

Enhance comfort using cleverly placed ductsEnhance comfort using cleverly placed ducts

*5

Long

-life

filte

r

13 14

Remote controller

*3 *3 *3 *3 *4

Setp

oint

rang

e se

t

Wee

kly

sche

dule

tim

er

Setp

oint

aut

o re

set

Off

timer

(pro

gram

med

)

On/

Off

timer

Page 9: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Floor Standing Type

New airflow control for more comfortNew airflow control for more comfort

15 16

Quiet operation

Quick and easy installation and maintenance

Lightweight indoor unit

Easier connection with the centralised control system.

Enables smooth transport and installation of the indoor unit.

The grill will not open even upon impact.

Long-life filter lasts about 1year * maintenance not requiredEnergy saving

A DC fan motor improves efficiency.* For dust concentration of 0.15 mg/ m3

Employs a safety lock function of suction grill.

Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

Long

-life

filte

r

100C 125C 140CHigh

Indoor unit 50/60/71C50 51 5343

Middle 47 48 5141Low 44 46 4838

dB(A)

39 47100C 125C 140C

WeightIndoor unit 50/60/71C

(kg)

FVQ50/60/71/100/125/140CNEW

• • •*2 *4 • *3 •• • • • • • • • • *3

CleanlinessComfort Remote controller Work & Servicing Control features Others

Features

•*1Applicable when BRC1E62 is used*2Applicable for FVQ50-100 *3For the outdoor units

*4Applicable when BRC1C61 is used

Switc

habl

e fa

n sp

eed

(3 s

tep)

Inde

pend

ent u

p-an

d-do

wn

airfl

ow

*1

Aut

o ai

rflow

rate

Aut

o sw

ing

Prog

ram

me

"Dry

"

Hig

h fa

n sp

eed

mod

e

On/

Off

timer

*1

Off

timer

(pro

gram

med

)

*1

Wee

kly

sche

dule

tim

er

*1

Setp

oint

rang

e se

t

*1*3

Setp

oint

aut

o re

set

Pre

char

ged

for

up to

30

m

Ant

i-bac

teria

l air

filte

r

Filte

r sig

n

Emer

genc

y op

erat

ion

Self-

diag

nosi

s fu

nctio

n

Con

trol b

y 2

rem

ote

cont

rolle

rs

Aut

o-re

star

t

Ant

i cor

rosi

on tr

eate

dhe

at e

xcha

nger

s

DIII

-NET

com

mun

icat

ion

stan

dard

*3

Low

gas

pre

ssur

e de

tect

ion

Gro

up c

ontro

l by

1 re

mot

e co

ntro

ller

Exte

rnal

com

man

d co

ntro

l

Cen

tral r

emot

e co

ntro

l

Inte

rlock

con

trol

Two

sele

ctab

le

tem

pera

ture

-sen

sors

Nig

ht q

uiet

ope

ratio

n

Comfortable fan speed control

To carry airflow to the far side of the room, airflow rate can be increased 5% or 10% depending on the installation condition or customer's request. (Field setting by remote controller.)

High fan speed mode

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Programme "Dry"

(applicable for FVQ50-100)

Airflow rate is automatically controlled in accordance with the difference between room temperature and set temperature.

Auto airflow rate is selectable.

Example applications

When coolingTurning louvers and upward and leaving and horizontal will reduce uneven room temperature.

New comfortable airflow control1) Left and right directions

2) Up and down directions Independent up-and-down airflow directions facilitate even room temperature and help save energy.

New unit

(by remote controller)

(by hand)

Freely select both up and down airflow direction with 8-louver (horizontal blade) operation.

Upper louver (1)Upper interlocking louvers (4)Lower interlocking louvers (2)Lower louver (1)

Each set of louvers to can be independently adjusted. (Manual adjustment)

Auto swing direction is selectable from 3 patterns to suit the layout of the room.Pattern 1 Wide swing toward the front

When installed in the center of a wall. When installed in the corner of a room.

Pattern 2 Swing on the left side Pattern 3 Swing on the right side

Switchable fan speed: High/Middle/Low and Auto("Auto" is applicable when BRC1E62 is used.)

Accessory required for indoor unit

Option

BRC1E62 can be

incorporated into the

main unit.

Note: Remote controller cable not included. Cables must be procured locally.

BRC1E62

(Wired Remote Controller)

Navigation Remote Controller

Page 10: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

These two features work to reduce noise. Guides are added to the bell mouth intake to reduce turbulence in the airflow generated by fan suction. The Aero Spiral Fan features fan blades with the bent blade edges, further reducing turbulence.

Smooth Air Inlet Bell Mouth and Aero Spiral Fan

Escaping eddies are sucked in by the bent blade edges, reducing overall turbulence.

The high efficiency compressor to achieve a high COP

2

1

DC fan motorEfficiency improved in all areas compared to AC motors, especially at low speeds.

Sine wave DC inverter >> Smooth sine wave DC inverter Use of an optimised sine wave smoothes motor rotation, further improving operating efficiency.

Sucked gas is compressed in the scrolling part before the heated motor, so that the machine compress the non­ expanded gas, resulting in high efficiency compression.

>> The structural scrollEnergy savings is realised, eliminating the friction and the leakage of refrigerant gas.

>> Swing compressor

Compressor equiped with Reluctance DC motor

3DC fan motor structure

With the bent blade edge

Without the bent blade edge

ReluctanceDC motor

Scroll section

Suction

Discharge Motor section

RZR50/60/71/100LV

Technology for energy efficiency

Swing bushing Refrigerant gas

Piston by incorporated blade and roller.

500 30 60 90 120

60

70

80

90

Small load Large loadLow capacity High capacity

Reluctance DC Motor

Conventional DC motor

More than 20%

AC motor

Rotational speed (rps)

Moto

r effi

cienc

y (%

)

Daikin DC Inverter models are equipped with the Reluctance DC motor for compressor. The Reluctance DC motor uses 2 different types of torque, neodymium magnet*1 and reluctance torque*2. This motor can save energy because it generates more power with a smaller electric power than an AC or conventional DC motor.

*1. A neodymium magnet is approximately 10 times stronger than a standard ferrite magnet.

*2. The torque created by the change in power between the iron and magnet parts.

Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory.

RZR125/140LV, RZQ100/125/140KC, RZQ100/125/140LU

(RZR/RZQ100-140 only)

3

1

2

OUTDOOR UNIT

New Compact Outdoor unit

Easy installation and maintenancePre charged for up to 30 metres

Long piping length

4­di rection piping offers greaterlayout freedom

Separation available

If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.

A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.

Facilitates pump down (Refrigerant recovery function)

Effective gas monitoring reduces the labor required for operation, maintenance, and repairs.

Low gas pressure detection function

The maximum capacity is maintained within a set level of power consumption, which makes it possible to keep comfort and effective demand control.

As the bottom frame is subject to corrosion, corrosion-proof galvarium steel plate is adopted to enhance the durability.Heat exchange fins provided with anti-corrosion treatment

Durability

Through use of a V­cut propeller fan that imitates the efficiency of the swan, a migratory bird, airflow becomes smooth and loss is reduced.

Energy saving

ConstructionNon-treated fin

Anti corrosion treated heat exchangers

Aluminium

AluminiumCorrosion resistantacrylic resin

Hydrophilic film

Allowed refrigerant piping length and level difference

Note : 1Additional refrigerant charging is required if the refrigerant pipe is longer than the length.

Demand Control Function

8:00 12:00 16:00 20:00

Pow

er

cons

umpt

ion

Time

Limitation

* Required for KRP58M51 (Option)

Max. length

Max. leveldifference

Pre charged1

RZR50­140LV RZQ100­ 140KC/LU

30 m

50 m(Equivalent length 70m)

70 m(Equivalent length 90m)

30 m

The outer panel for the piping connection part of the front, right side and backside can be removed and is easier for post-installation piping work.

*Pump­ down function is available for pre­ charged refrigerant amount.

(RZR/RZQ100-140 only)

Night time quiet operation functionThe Automatic night quiet mode will initiate 8 hours after the peak temperature is reached in the daytime, and normal operation will resume 10 hours after that.

49

50

RZR100LVRZQ100/125/140KC

RZQ100LU

48RZR50/60/71LV

Sound level1 (dB(A))

RZR125LVRZQ125/140LU

50

45

45

44

46RZR140LV

Rated2 Night Quiet Mode

Note : 1Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 2Value when cooling. Value will differ when heating.

Note : 3In case of RZQ series, period selectable from 22­ 8:00, 22­ 6:00, and 20­ 8:00. 4In case of RZR100

Reducing noise will reduce capacity slightly.

Comparison of outdoor unitsConventional

(RZQ71KC)NEW

(RZR71LV)

Height 770 mm 595 mmWeight 68 kg

Height 1,170 mmWeight 98 kg

43 kg

Conventional(RZQ100KC)

NEW(RZR100LV)

990 mm78 kg

595mm

990mm

Reduced installation work thanks to light, compact outdoor unit.

Compact and lightweight

RZR71LVVMRZQ71KCVLT

RZR100LVVMRZQ100KCVLT

RZR50LVVMRZR60LVVMRZR71LVVM RZR100LVVM

RZQ100LUYLTRZQ125LUYLTRZQ140LUYLT

RZQ100KCTLTRZQ125KCTLTRZQ140KCTLT

RZR125LVVMRZR140LVVM

Φ550V­ cut propeller fan

Imitating the performance of the swan

(RZR/RZQ100-140 only)

17 18

100

50

0

8:00

Peak in outdoor temperature

8 hours

Rated

10 hours

Quiet modeQuiet mode

12:00 16:00 20:00

22:003 8:003

0:00 4:00 8:00

45

49

Capa

city (

%)

Load

(%)

Oper

ation

So

und4 (d

B(A)

)

Reduced by175 mm

Reduced by25 kg

Reduced by180 mm

Reduced by20 kg

Page 11: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Signal receiver unit (For ceiling mounted cassette type)

LCD REMOTE CONTROLLER Optional accessory

Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.)

Facilitates maintenance and repairAll initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be remotely set without having to use stepladder access for manual setting.Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).

Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction.

SkyAir shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning units, thus simplifying interlocking operations.

Easily adaptable to large-scale, high-function, centralised remote control systems.Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.

LCD panel shows operating status in letters, numbers, and motion.Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.

Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).

Programming time display Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.

Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

Indoor units applicable for the remote controllerSignal receiver unit is contained inside decoration panel or indoor unit

CEILING MOUNTED CASSETTE TYPE

CEILING SUSPENDED TYPE

BRC7F633F

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE BRC4C64

BRC7GA56WALL MOUNTED TYPE BRC7EB519

LCD wireless remote controller

Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the ceiling mounted cassette type.

Wireless remote controller

Light receptor mounted type

BRC7F633F

The wireless remote controller is supplied in a set with a signal receiver.Shape of signal receiver unit differs according to the indoor unit.

The rubber switch and the oil-resistant plastic casing are adopted for durability.Only 17 mm thick. Can be installed either recessed or exposed.

Easy to read because of large LCD screen.Wired LCD remote controller

BRC1C61

Wired remote controller has built-in temperature-sensor (Applies to wired remote controllers (BRC1C61/1E62))

(Applies to wired remote controller (BRC1E62))

19 20

Clear Display

Navigation Remote Controller(Wired Remote Controller BRC1E62)

- 5 actions per day can be scheduled for each day of the week.- The holiday function will disable schedule timer for the days that have been set as holiday.- 3 independent schedules can be set. (e.g. summer, winter, mid-season)

Display is available in 11 languages.

Dot matrix display Backlight display

ConvenienceWeekly schedule Multilingual display

Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units. Remote controller options are shown on the page introducing each indoor unit model.

NEW

(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish, and Polish).NEW

A combination of fine dots enables various icons.Large text display is easy to see.

This simple, modern designed remote controller with fresh white colour matches your interior design. Operation is much easier and smoother, just follow the indications on the navigation remote controller.

Energy savingNEW

- Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts.- Period can be preset from 30 to 180 minutes in10-minute increments.

Off timer (programmed)

Setpoint range setNEW Setpoint auto reset

Restaurant sampleRestaurant opened

Temperature is set to 27ºC

27°C

- Saves energy by limiting the min. and max. set temperature.

- Avoids excessive heating or cooling.

- This function is convenient when the remote controller is installed at a place where any number of people may operate it.

- Even if the set temperature is changed, it returns to the preset temperature after apreset period of time.

- Period selectable from 30min/60min/90min/120min.

Full tables at lunchtimeThen is lowered to 24ºC for crowded room

24°C

After 30 minutes*Automatically returns to preset temperature (27ºC)

*Setting possible for after 30, 60, 90, and 120 minutes.

Returns to27°C

automatically

Page 12: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

LCD REMOTE CONTROLLER

Central remote controller

Easily adaptable to large-scale, high-function, centralised remote control system.

Centralised control, with setting as simple as it is with a standardremote controller, of up to 64 groups (1,024 indoor units) is possible.

DCS302CA61 (Option)

With its high functionality, the full colour “all-in-one” graphic controller facilitates management of SkyAir System in a variety of ways.

DCS601C51 (Option)Unified on/off controller

Centralised control of on/off by group or all at once for up to 256 indoor units.

DCS301BA61 (Option)

Schedule timer

Unified control of weekly schedule for up to 1,024 indoor units.

DST301BA61 (Option)

Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.

Simple system provides a diverse assortment of control modes.

Control by 1remote controller

Control pattern Wired remote controller Wireless remote controller

Control by 2remote controllers

Group control

Control by external command

Centralised remotecontrol

Interlock controlwith Heat Reclaim

Ventilator

(Basic system)

Link by remote controller group control.

Zone link control by centralised control.

For control from 2 locations such as in room and control room, exits, etc.

For simultaneous control of up to 16 indoor units.

Centralised control of up to 64 indoor groups from remote locationup to 1 kilometer away.

Control by 1 wireless remote controller and 1 wired remotecontroller (See note 2, 3)Signal receiver unit installed on indoor unit

Signal receiver unit installed on indoor unit

Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking Can also be operated independently by remote controller.

Central remote controller (option)

Heat ReclaimVentilator

Can be operated simultaneously or independently by remote controller (set by ventilation mode)

Heat ReclaimVentilator

Non-polar, double-core (max. wiring length 500 m)

Connects 2 wired remote controllers (See note 1)

Automatic address setting function Automatic address setting functionSignal receiver unit installed on 1 indoor unit

Optional wiring adaptor for electrical appendices is necessary

Can be operated simultaneously by remote controller (set by ventilation mode)

Heat ReclaimVentilator

Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking

Central remote controller (option)

Heat ReclaimVentilator

Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.

Optional wiring adaptor for electrical appendices is necessary

Note: 1BRC1E62 can connect to BRC1E62 only. 2It is not possible to use two wireless remote controllers. 3BRC1E62 cannot connect to wireless remote controller.

Central remote controller (option) Central remote controller (option)

Abundance of functions that provide comfortable air-conditioning in stores and offices. Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.

21 22

Cleanliness

Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.

Silver ion anti-bacterial drain panThe Air filter has a anti-bacterial treatment to help prevent the growth of bacteria and mould on it.

Anti-bacterial air filter

Sanitary filter has mould-resistant treatment.Mould-proof air filter

Note: Wireless remote controllers have no temperature-sensor.

Use the temperature-sensor in the indoor unit when controlling air conditioning from another room.

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling of the room.

Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.

High setting provides maximum reach while low setting minimises drafts.

Auto-swing Programme "Dry"

Switchable fan speed

(1) Air direction in standard setting

(2) Air direction in ceilingsoiling prevention setting

(standard, ceiling soiling prevention)

Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.

You can freely set 2 air discharge setting by remote controller.

Swing pattern selectionDelivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.

High-ceiling application

Airflow rate is automatically controlled in accordance with the difference between room temperature and set temperature.

Auto airflow rate

Two selectable temperature-sensors

Comfort

The air flow direction can be fixed at your desited angle by the remote controller.

Temperature-sensors are included in the indoor unit and optional wired remote controller. Temperature sensing closer to target area is possible to further increase the comfort level.

Remote Controller

Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts.

Off timer (programmed)

Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

On/Off timer

Up to five operation ON/OFF settings can be programmed per day for each day of the week. Not only can the time be set for the operation ON setting, but also the temperature.

Weekly schedule timer

Even if the set temperature is changed, it returns to the preset temperature after a preset period of time.

Saves energy by limiting the minimum and maximum set temperatures. Avoids excessive heating and cooling.

Setpoint auto reset

Setpoint range set

Applicable for wall mounted type

You can increase fan speed approximately 10% higher than the "high" setting.

High fan speed modeThe Automatic night quiet mode will initiate 8 hours after the peak temperature is reached in the daytime, and normal operation will resume 10 hours after that.

Night quiet operation

Independently adjust (manually) the eight horizontal blade louvers in both up and down directions to achieve an airflow that reduces uneven room temperature.

Independent up-and-down airflow

Page 13: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

If there is a malfunction elsewhere in the system, the fan or compressor can still be operated.

Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure. Reliability is assured and maintenance and inspection can be carried out more quickly.

You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.)

Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.

Emergency operation

Low gas pressure detection

Group control by 1 remote controller

Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.

External command control

Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 kilometer away.

Central remote control

Enables interlocking control with external equipment such as Heat Reclaim Ventilator.

Interlock control

The operating parameters of indoor and outdoor units, and sensor data at critical locations throughout the system, are constantly monitored using a microcomputer. To facilitate quick response in the event of a malfunction, a message appears on the LCD of the remote controller and an LED on the unit illuminates.

Self diagnosis function

Two types are available: 65% and 90% colorimetry. High-efficiency filter unit

You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed.

Fresh-air intake kit

Work and Servicing

Control features

Options

Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.

Maintenance is not required for one year (two years when a ceiling mounted cassette type is used).

If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.

The filter sign warns you when it is time to clean the filter. *When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.

Drain pump mechanism

Long-life filter

Pre charged for up to 30 metres

Filter sign

Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required.

Ceiling soiling prevention function

If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored.

Ultra long-life filter

Auto-restart

Using 2 remote controllers you can operate the equipment locally or from a remote location.Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.

Control by 2 remote controllers

Requires no maintenance for about 4 years* (10,000h) in stores and offices.*For dust concentration of 0.15 mg/m3

*Required for KRP58M51 (Option)

*Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

**Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking.

***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.

Note:

Others

To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated Anti corrosion treated heat exchangers (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.In high corrosive areas, regular maintenance needs to be carried out.

Anti corrosion treated heat exchangers

Standardly equipped interface enables connection to centralised control system without need of an adaptor.

DIII-NET communication standard

SPECIFICATIONS

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

dB(A)

CEILING MOUNTED CASSETTE TYPE

Cooling capacity1,2

Rated (Min. - Max.) kW

°CDBCoolingCertified Operation range

Sound level3

°CWBCoolingCertified Operation range

Motor outputCompressor

ModelName

Indoor unitOutdoor unitOutdoor unit

Dimensions(HXWXD)

Colour

mmmm

dB(A)

kWRefrigerant charge (R-410A) kg

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Unit

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Decoration panel

UnitDecoration panel

Machine weight kg

kgUnitDecoration panel

Airflow rate (H/L) m3/mincfm

Outdoorunit

Colour

mm

Heat insulation

Max. interunit piping length mmMax. installation level difference

Power supply

Type

Cooling

Sound level (H/L)3

Indoorunit

71FCQ71KVEARZR71LVVM

Hermetically sealed swing type1.76

7.1 (3.2-8.0)

100FCQ100KVEARZR100LVVM

43/32

49

990X940X32078

2.032.7

(Charged for 30 m)

32/20

10.0 (5.0-11.2)

125FCQ125KVEARZR125LVVM

44/34

o/ 9.5o/ 15.9

50

1,170X900X32097

24

298X840X840 256X840X84050X950X950

5.5

----------

1 Phase, 220–230 V, 60 Hz

30

Ivory white

Fresh white

Both liquid and gas piping

50 (Equivalent length 70)

Hermetically sealed scroll type

o/ 26.0 (Hole)

2.43.15

(Charged for 30 m)

VP25 (I.Do/ 25XO.Do/ 32)

33/22.51,130/706 1,165/794

12.5 (5.7-14.0)

140FCQ140KVEARZR140LVVM

44/36

21 to 46

14 to 25

3.1

14.0 (6.2-15.4)

kWPower consumption Cooling

125FCQ60KVEAx2RZR125LVVM

35/28

2.4

21/13.5741/477

12.5 (5.7-14.0)

140FCQ71KVEAx2RZR140LVVM

3.1

14.0 (6.2-15.4)

1.99 2.78 3.68 4.91 3.68 4.91

Night quiet mode

dB(A)Night quiet mode

50FCQ50KVEARZR50LVVM

1.12

5.0 (2.3-5.6)

60FCQ60KVEARZR60LVVM

35/28

48

595X845X30043

21 21

256X840X840

1.351.6

(Charged for 30 m)

21/13.5741/477

6.0 (2.6-6.3)

1.03 1.40W/WCOP 3.57 3.60 3.40 2.85 3.40 2.854.87 4.30

45 46464544

Cooling capacity1,2

Rated (Min. - Max.) kW

°CDBCoolingCertified Operation range

Sound level3

°CWBCoolingCertified Operation range

Motor outputCompressor

ModelName

Indoor unitOutdoor unitOutdoor unit

Dimensions(HXWXD)

Colour

mmmm

dB(A)

kWRefrigerant charge (R-410A) kg

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Unit

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Decoration panel

UnitDecoration panel

Machine weight kg

kgUnitDecoration panel

Airflow rate (H/L) m3/mincfm

Outdoorunit

Colour

mm

Heat insulation

Max. interunit piping length mmMax. installation level difference

Power supply

Type

Cooling

Sound level (H/L)3

Indoorunit

140FCQ140KAVLTRZQ140KCTLT

Hermetically sealed scroll type

13.3 (6.2–15.8)

100FCQ100KVLT

RZQ100LUYLT

43/32

101

32/20

10.0 (5.0–11.4)

125FCQ125KAVLTRZQ125LUYLT

44/34

o/ 9.5o/ 15.9

50

50X950X950

5.5

----------

3 Phase, 220V, 60Hz 3 Phase, 380V, 60Hz

30

Ivory white

Fresh white

Both liquid and gas piping

70 (Equivalent length 90 m)o/ 26.0 (Hole)

VP25 (I.Do/ 25XO.Do/ 32)

33/22.51,130/706 1,165/794

12.5 (6.0–14.3)

140FCQ140KAVLTRZQ140LUYLT

44/36

-5 to 50

14 to 25

13.1 (6.2–15.8)

kWPower consumption Cooling

100FCQ100KVLT

RZQ100KCTLT

10.0 (5.0–11.4)

125FCQ125KAVLTRZQ125KCTLT

43/32 44/34 44/36

4945

1,170X900X32099

24

298X840X840

3.7 (Charged for 30 m)

32/201,130/706

33/22.51,165/794

12.5 (6.0–14.3)

W/WCOP

23 24

2.41.9 2.9 2.41.8

3.47 3.912.77 3.51 3.852.773.603.61 3.40 3.563.61 3.40

2.9

Page 14: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

CEILING SUSPENDED TYPE

Refrigerant charge (R-410A)

SPECIFICATIONS

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

VP20 (I.Do/ 20XO.Do/ 26)

Hermetically sealed swing type

30

100FHQ100CAVEBRZR100LVVM

42/38/34

o/ 9.5o/ 15.9

990X940X32078

49

28/24/20988/847/706

10.0 (5.0-11.2)

o/ 26.0 (Hole)

2.032.7

(Charged for 30 m)

3.03

38/36/34235X1,270X690

595X845X30043

32

48

20.5/17/14724/600/494

1.6 (Charged for 30 m)

1 Phase, 220–240 V, 50 Hz/220–230 V, 60 Hz

Ivory white °CWB

kW

kWPower consumption

°CDBCertified operation range

Certified operation range

Motor output

CoolingNight quiet mode

Compressor

ModelName

Indoor unitOutdoor unit

Outdoor unit

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R-410A) kg

dB(A)dB(A)

Sound level3

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Machine weight kg

Airflow rate (SH/H/L) m3/min

Outdoorunit

Colour

mm

Heat insulation

Max. interunit piping length mmMax. installation level difference

Power supply

Type

Sound level (H/M/L)3

Indoorunit

Both liquid and gas piping

Cooling capacity1,2

Rated (Min. - Max.)

cfm

140FHQ140CAVEBRZR140LVVM

46/42/38

Hermetically sealed scroll type

34/29/241,200/1,024/847

13.3 (6.2-15.4)

3.1

4544 46

Fresh white

4.68

21 to 46

14 to 25

125FHQ125CAVEBRZR125LVVM

44/41/37235X1,590X690

1,170X900X32097

38

50

31/27/231,094/953/812

12.5 (5.7-14.0)

2.43.15

(Charged for 30 m)

4.01

1 Phase, 220–230 V, 60 Hz

50 (Equivalent length 70)

71FHQ71CAVEBRZR71LVVM

1.76

2.373.30W/WCOP 2.843.123.00

7.1 (3.2-8.0)

Cooling

25 26

°CWB

Cooling capacity1,2

Rated (Min. - Max.) kWkW

W/WPower consumption

°CDBCertified Operation range

Certified Operation range

Sound level3

Motor outputCompressor

ModelName

Indoor unitOutdoor unitOutdoor unit

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R-410A) kg

dB(A)dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Machine weight kg

Airflow rate (H/M/L)

Outdoorunit

Colour

mm

Heat insulation

Max. interunit piping length mmMax. installation level difference

Power supply

Type

Cooling1

CoolingNight quiet mode

Sound level (H/M/L)3

Indoorunit

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

WALL MOUNTED TYPE

m3/min

100FAQ100CVEARZR100LVVM

49/45/41

17340X1,200X240

o/ 9.5

49

Ivory white

30Both liquid and gas piping

Fresh white

o/ 15.9

Hermetically sealed swing type

o/ 26.0 (Hole)

1.6 (Charged for 30 m) 2.7 (Charged for 30 m)

10.0(5.0-11.2)

26/23/19

21 to 46

50 (Equivalent length 70m)

14 to 25

71FAQ71CVEARZR71LVVM

7.1(3.2-8.0)

45/42/40

484544

900X940X320595X845X3007843

2.031.76

290X1,050X23813

VP13 (O.Do/ 18 X I.Do/ 13)

18/16/14cfm 918/812/671635/565/494

2.19 3.37COP 3.24 2.97

1 Phase, 220–240 V, 50 Hz/220–230 V, 60 Hz

Power supply 1 Phase, 220 V, 60 Hz1 Phase, 220–230 V, 60 Hz

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

ModelName

Indoor unitOutdoor unitIndoor unitOutdoor unit

kW

°CDBCooling

°CWBCooling

Cooling

Cooling

Certified Operation range

Certified Operation range

Motor outputCompressor

Indoorunit

Dimensions (HXWXD)Air filter

Colour

mm

dB(A)

kWRefrigerant charge (R-410A)Sound level4

Cooling (H/L)Sound level4

dB(A)Cooling (H/L)Sound level4Air filter

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Machine weight kg

kg

Airflow rate(H/L)

Fan

CoolingAirflow rate(H/L)

Fan

Outdoorunit

Colour

Heat insulation

Max. interunit piping length mmMax. installation level difference

Type

----------

Both liquid and gas piping

mmOutdoor unit

Ivory white

kWCoolingPower consumption

Pa

cfm

Night quiet mode dB(A)

External static pressure(Middle-High)

Cooling capacity1,2

Rated (Min. - Max.)

30

21 to 46

14 to 25

m3/min

50FBQ50DAVETRZR50LVVM

5.0 (2.3-5.6)

50 (Equivalent length 70)

VP25 (I.Do/ 25XO.Do/ 32)

o/ 9.5o/ 15.9

o/ 26.0 (Hole)

1.12

1.39

60FBQ60DAVETRZR60LVVM

6.0(2.6-6.3)

300X1,000X700---------- 5

36

595X845X30043

Hermetically sealed swing type1.351.6

(Charged for 30 m)

635/53018/15

1.69

37/32

48

71FBQ71DAVETRZR71LVVM

7.1 (3.2-8.0)

1.76

2.22

2.9

140FBQ140DAVETRZR140LVVM

14.0(6.2-15.4)

4.71

45 4644

50-200 3

PaExternal static pressure(Middle-High) 50-200 3

100FBQ100DAVETRZR100LVVM

990X940X320

10.0 (5.0-11.2)

78

2.032.7

(Charged for 30 m)

1,130/81232/23

2.82

38/33

49

125FBQ125DAVETRZR125LVVM

12.5 (5.7-14.0)

300X1,400X70046

1,377/988

2.43.15

(Charged for 30 m)

39/28

3.73

40/36

1,170X900X32097

5045

125FBQ60DAVETx2RZR125LVVM

12.5 (5.7-14.0)

2.4

635/53018/15

3.73

37/32

300X1,000X70036

140FBQ71DAVETx2RZR140LVVM

14.0(6.2-15.4)

4.71W/WCOP 3.60 3.56 3.20 2.973.55 3.35 3.35 2.97

2.9

46

Hermetically sealed scroll type

3.16 3.153.19 3.16 3.153.193.96 4.223.13 3.96 4.163.13

Note : 1Rated cooling capacities are based on the following conditions: Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Initial setting is standard.4Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency(gravity method) 50% or more.

Cooling capacity1,2

Rated (Min. - Max.) kW

°CDBCoolingCertified Operation range

Sound level4

°CWBCoolingCertified Operation range

Motor outputCompressor

ModelName

Indoor unitOutdoor unit

Outdoor unit

Dimensions (HXWXD)

Colour

mm

kWRefrigerant charge (R-410A) kg

dB(A)dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Machine weight kg

m3/mincfm

Outdoorunit

Colour

mm

Heat insulation

Max. interunit piping length mmMax. installation level difference

Power supply

Type

CoolingNight quiet mode

Indoorunit

140FBQ140DAVETRZQ140KCTLT

Hermetically sealed scroll type

13.3 (6.2–15.8)

100FBQ100DAVETRZQ100LUYLT

38 / 33

101

32 / 23

10.0 (5.0–11.4)

125FBQ125DAVETRZQ125LUYLT

40 /36

o/ 9.5o/ 15.9

50

----------

3 Phase, 220V, 60HzIndoor unit 1 Phase, 220V, 60Hz

3 Phase, 380V, 60Hz

30

Ivory white

Both liquid and gas piping

70 (Equivalent length 90 m)o/ 26.0 (Hole)

VP25 (I.Do/ 25XO.Do/ 32)

39 / 281,130 / 812 1,377 / 988

12.5 (6.0–14.3)

140FBQ140DAVETRZQ140LUYLT

-5 to 50

14 to 25

13.1 (6.2–15.8)

kWPower consumption Cooling

100FBQ100DAVETRZQ100KCTLT

10.0 (5.0–11.4)

125FBQ125DAVETRZQ125KCTLT

38 / 33---------- 5

40 /36

4945

1,170X900X32099

46300X1,400X700

3.7 (Charged for 30 m)

32 / 231,130 / 812

39 / 281,377 / 988

12.5 (6.0–14.3)

W/WCOP

2.41.9 2.9 2.41.8 2.9

Page 15: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Indoor unit

For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option (shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.

Round flow type: List of optional parts required to achieve different flow patterns

1In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.

2Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position.3It is not possible to use panel spacers in a 2-way flow installation. 4It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.

Panel/grille relatedIndependently installable optional parts

Operation control relatedAuxillary function related

Filter related

Optional accessory parts

Independently installable optional partsOptional accessory parts

Independently installable optional partsOptional accessory parts

Panel spacer1

Panel spacer1 o o ox oWireless remote controller o o oo o

Fresh air intake kit (direct mount) o o oo ox o o

xx

High-efficiency filter2

Filter related Ultra-long-life filter2

o o ox

xUltra-long-life filter2 o o o xx

High-humidity operation kit

Panel/grille relatedOperation control relatedAuxillary function related

Panel spacer1

Wireless remote controller

Fresh air intake kit (direct mount)High-humidity operation kit

All round flow 4-way flow

o3 o3 xx o3

o3 o

x

xxo o

o3 o xx

o ox o o x

o3 o o xx

3-way flow 2-way flow

1-way branch / unit 3-way flowBranch duct1(Chamber type)(Round duct type)

o o o4 xx o2-way branch / unit 2-way flow1-way branch / unit 2-way flow

x o o4 xx ox o o4 xx o

Branch duct connection

Wireless remote controller

Fresh air intake kit (direct mount)

High-efficiency filter2

High-humidity operation kit

Ultra-long-life filter2

Panel spacer1 Wireless remote controller

Fresh air intake kit (direct mount)

High-efficiency filter2

High-humidity operation kit

Ultra-long-life filter2

Panel spacer1 Wireless remote controller

Fresh air intake kit (direct mount)

Fresh air intake kit (Chamber type)1,2 o o ox o

Fresh air intake kit (Chamber type)1,2 o3 o xx o

oo

xoo

o3

o

x

x

x

o

o o o

Fresh air intake kit (Chamber type)1,2

Fresh air intake kit (Chamber type)1,2

Fresh air intake kit (Chamber type)1,2

High-efficiency filter2

High-humidity operation kit

Ultra-long-life filter2

OPTIONS

Touch Controller4 DCS601C51

Note: 1Refer to page 8 for the details. 2Required for installing high-efficiency filter or ultra long-life filter. 3Wiring for wired remote controller to be procured locally.4The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 5Installation box for adaptor PCB (KRP1H98) is necessary.

Kit name

DCS302CA61BRC1E62

DCS301BA61DST301BA61

KRP1C63

KDDFP55B160

KDBH55K160FKDBP55H160FA

KKSJ55KA160

KDDP55B160KDDP55B160KKDDP55X160

KRP4AA53

KAFP551K160

KAFP556B80KAFP557B80KAFP552B80

KDTP55K80

KDJP55B160KDJP55B80BRC7F633FBRC1C61

KAFP553B80

KDTP55K160KAFP556B160KAFP557B160KAFP552B160KAFP553B160

BYCP125K-W1

KRP1H98

KAFP55B160KAFP55H160H

FCQ71KVEA FCQ100KVEA FCQ125KVEAFCQ50KVEA FCQ60KVEA FCQ140KVEA FCQ100KVLT FCQ125KAVLT FCQ140KAVLTName of option Remark

Chamber type

Decoration panel

Fresh air intake kit1

Central remote controller4

Unified ON/OFF controller4

Schedule timer4

Adaptor for wiring5

Without the T-joint pipe and fanWith the T-joint pipe, without fan

Direct installation type

Sealing material of air discharge outletPanel spacer

Chamber connection kit2Insulation kit for high humidity

Wiring adaptor for electrical appendices5

Installation box for adaptor PCB

High-efficiency filter(including chamber)

Filter chamber Replacement long-life filterUltra long-life filterReplacement ultra long-life filter

(Colorimetric method 65%)(Colorimetric method 90%)

Replacement high-efficiency filter

(Colorimetric method 65%)(Colorimetric method 90%)

Remote controller

Navigation Remote Controller

Wireless type Cooling only

Wired type3Wired type3

Branch duct chamber

Remote sensor (for indoor temperature) KRCS01-4B

CEILING MOUNTED CASSETTE TYPE

27 28

FLOOR STANDING TYPE

SPECIFICATIONS

Power supply 1 Phase, 220–240 V, 50 Hz/220–230 V, 60 Hz

Note : 1Rated cooling capacities are based on the following conditions: Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

ModelName

Indoor unitOutdoor unitOutdoor unit

kW

°CDBCooling

°CWBCooling

Cooling

Cooling

Certified Operation range

Certified Operation range

Motor outputCompressor

Indoorunit

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R-410A)Sound level3

Cooling (H/M/L)Sound level3

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Machine weight kg

kg

Airflow rate(H/M/L)

Fan

Outdoorunit

Colour

Heat insulation

Max. interunit piping length mmMax. installation level difference

Type

Fresh white

Both liquid and gas piping

mmOutdoor unit

Ivory white

kWCoolingPower consumption

cfm

Night quiet mode dB(A)

Cooling capacity1,2

Rated (Min. - Max.)

30

21 to 46

14 to 25

m3/min

50 (Equivalent length 70)

VP20 (I.Do/ 20XO.Do/ 26)

o/ 9.5o/ 15.9

o/ 26.0 (Hole)

1,850X600X27039

595X845X30043

Hermetically sealed swing type

1.6 (Charged for 30 m)

635/565/49418/16/14

43/41/38

48

71FVQ71CVEBRZR71LVVM

60FVQ60CVE

RZR60LVVM

50FVQ50CVE

RZR50LVVM

7.1 (3.2-8.0)

1.761.351.12

2.58

3.1

140FVQ140CVEBRZR140LVVM

13.5(6.2-15.4)

5.40

45 4644

100FVQ100CVEBRZR100LVVM

990X940X320

10.0 (5.0-11.2)

78

2.032.7

(Charged for 30 m)

988/883/77728/25/22

988/918/84728/26/24

1,059/988/91830/28/26

3.28

50/47/44

49

125FVQ125CVEBRZR125LVVM

12.5 (5.7-14.0)

1,850X600X35047

2.43.15

(Charged for 30 m)

4.39

53/51/4851/48/46

1,170X900X32097

50

635/565/49418/16/14

45

125FVQ60CVEx2RZR125LVVM

12.5 (5.7-14.0)

97

2.4

4.39

43/41/381,850X600X270

39

140FVQ71CVEBx2RZR140LVVM

13.5(6.2-15.4)

5.40W/WCOP 2.75

6.0 (2.6-6.3)

1.843.26

5.0 (2.3-5,6)

1.273.94 2.503.05 2.85 2.85 2.50

3.1

46

Hermetically sealed scroll type

Indoor unitCEILING SUSPENDED TYPE

Kit nameName of option Remark

L-type piping kit (for upward direction)Drain pump kitFresh air intake kit

Remote controller Wireless type

Central remote controller2

Unified ON/OFF controller2

Schedule timer2

Adaptor for wiringWiring adaptor for electrical appendices3

Installation box for adaptor PCB

Note: 1Wiring for wired remote controller to be procured locally.2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB is necessary.

FHQ71CAVEB FHQ100CAVEB FHQ125CAVEB FHQ140CAVEB

Remote sensor (for indoor temperature)Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)

Wired type1 BRC1C61

KRP1BA54

DCS302CA61DCS301BA61DST301BA61

KRP4AA52

KDU50P140VEKDDQ50A140

Long-life filter KAFP501A160KAFP501A80

BRC7GA56

KRP1D93A

KHFP5N160

KRCS01-4BKJB311AAKJB212AA

Cooling only

Touch Controller2

Note: 1Wiring for wired remote controller to be procured locally.2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA93) is necessary.

WALL MOUNTED TYPEName of option Remark

Central remote controller2

Remote controller

Unified ON/OFF controller2

Schedule timer2

Wiring adaptor for electrical appendices3

Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)

Kit nameFAQ100CVEA

DCS302CA61DCS301BA61DST301BA61DCS601C51

DCS601C51

KRP4AA51

KJB311AAKJB212AA

Drain-up kit

Installation box for adaptor PCB

Noise filter ( For electromagnetic interface use only)

Remote sensor (for Indoor temperature) KRCS01-4B

FAQ71CVEAK-KDU572EVE

KRP4AA93

KEK26-1A

BRC7EB519BRC1C61

Wireless typeWired type1

BRC1E62Navigation Remote Controller Wired type1

BRC1E62Navigation Remote Controller Wired type1

Cooling only

Touch Controller2

Page 16: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

OPTIONS

Outdoor unitKit name

RZR71LVVM RZR100LVVMRZR50LVVM RZR60LVVM RZR125LVVM RZR140LVVMCentral drain plug

Central drain plugFixture for preventing overturning Base stationary type

Wire typeDemand adaptor

Wire fixture for preventing overturning

Name of option

Kit nameRZQ140KCTLT RZQ100LUYLTRZQ100KCTLT RZQ125KCTLT RZQ125LUYLT RZQ140LUYLTName of option

Fixture for preventing overturningDemand adaptorRefrigerant branch piping kit For twin multi

KKPJ5F180K-KYZP15C

KHRP58P216T

KPT-60B160

KKPJ5G280----------

KKTP5B112

KKPJ5F180KPT-60B160K-KYZP15CKRP58M51

KKP014A4------------------------------

----------KRP58M51

KDAJ25K71A

FBQ71DAVETFBQ60DAVETFBQ50DAVET FBQ100DAVET FBQ125DAVET FBQ140DAVET

Service panel

Air discharge adaptor

Adaptor for wiring (interlock for fresh air intake fan)

Remote controller Wireless type Cooling only

Name of option Remark

Filter chamberReplacement long life filterReplacement long life filter chamber kit

High-efficiency filter1 65%90%

BRC4C64

KTB25KA80WKTBJ25K80FKTBJ25K80T

KTB25KA160WKTBJ25K160FKTBJ25K160T

KAF372AA80KAF373AA80

KAF372AA160KAF373AA160

KDDF37AA80 KDDF37AA160KAF371AA80 KAF371AA160KAF375AA80 KAF375AA160

KDAJ25K140A

KRP1C64BRC1E62Navigation Remote Controller Wired type2BRC1C61Wired type2

Central remote controller3

Unified ON/OFF controller3

Schedule timer3

Wiring adaptor for electrical appendicesRemote sensorMounting plate for adaptor PCB.4

DCS301BA61DCS302CA61

DST301BA61

KRCS01-4BKRP4A96 5,6

KRP4AA51

Note: 1If installing a high efficiency filter on the unit, an assembly chamber for either bottom or rear suction is required. 2Wiring for wired remote controller to be procured locally. 3The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 4Mounting plate for adaptor PCB is necessary for each adaptor marked . 5Up to 2 adaptors can be fixed for each mounting plate.6Only one mounting plate can be installed for each indoor unit.

DCS601C51Touch Controller3

Kit name

29 30

Indoor unit

FLOOR STANDING TYPEKit nameName of option FVQ71CVEB FVQ100CVEBFVQ50CVE FVQ60CVE

DCS302CA61DCS301BA61DST301BA61

KAFJ95L160Remark

Touch Controller2

Replacement long-life filter

Navigation Remote ControllerCentral remote controller2

Unified ON/OFF controller2

Schedule timer2

Adaptor for wiring3

Wiring adaptor for electrical appendicesInstallation box for adaptor PCB

Note: 1Wiring for wired remote controller to be procured locally. 2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA95) is necessary.

FVQ125CVEB FVQ140CVEB

KRP1BA57DCS601C51

KRP4AA52KRP4AA95

BRC1E62Wired type1Remote controller BRC1C61Wired type1

DIMENSIONS (Unit: mm)

CEILING MOUNTED CASSETTE TYPE

Notes:1Sticking location for manufacture's label manufacture's label for indoor unit: Suction grille inner side's electric components box's lid surface manufacture's label for decoration panel : Decoration panel's corner decoration cover inner surface2In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

3When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

4Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the indoor unit and the ceiling opening so that

the panel overlap allowance can be ensured.5Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

950

8Piping ConnectionSide

6

A arrow view

Drain ConnectionSide

Note 2

7

9509

860~91

0(Ceilin

g open

ing sp

ace) (N

ote 4)

420

C

710(Hanging bolt pitch)420

B

300or less

780(

Hang

ing b

olt p

itch)

860~910(Ceiling opening space) (Note 4)

157

93

2x100=200 85

67

Connection positionof branch duct

C/L(round shape type)160

Connection positionof branch duct

16-M4 Hole

167

(square-shaped type)B arrow view

160

95

81

350

29213

29

350

80

160

ø100

Connection positionof fresh air intake kit

C/L 157

90

(direct installation type)

67

(knock hole)

Connection positionof branch duct

C arrow view

Connection positionof branch duct

2x100=

200

(round shape type)

(square-shaped type)

196

93

90

8025

95

160

20-M4Prepared hole

167

280

5028

8

80

167

95

157

340840

16510

4Hanging bolt 1

175

55

4-M8~M10Connection positionof branch duct(round shape type)

Connection positionof branch duct

2

40

80

160

2x100=200

125

(square-shaped type)

C/L

298

20

350

850

Adjust

able(0

~675) 55

29

330

160

16-M4 Prepared hole

160

1500 o

r more

81

93

157

130

Connection positionof branch duct

160

2x100=200

A

55

(square-shaped type)

From the

floor side

2500 or

more

(Note 4)

67

105

For he

ight in

stallat

ion

85

150

(require

d spac

e)

350

42

29

64

(round shape type)

27-M4 Prepared hole

60

35 or less (Note 4) 35 or less

3

Connection positionof branch duct

256

160 5

95

50

84055

167

The necessary space is 500mm or more when the air-outlet is blocked with the accessory.Moreover when the corner areas are blocked (both right and left of the blocked air outlet), the necessary space is 200mm or more.

1500mm or more200mm or more

1500mm or more

1500mm or more1500mm or more200mmor more

Required space

95

330

165

Connection positionof branch duct

160

20

16-M4 Prepared hole

50

350

12480

175

125

2

(square-shaped type)

4 1157

246

55

4-M8~M10

2x100=200 80

124

10

Hanging bolt

Connection positionof branch duct

C/L

110

(round shape type)

84055

280

256

40

Adjust

able(0

~675)

340

850

Connection positionof branch duct

1500 o

r more

Connection positionof branch duct

27-M4 Prepared hole

60

From the

floor side

2500 or

more

130

124

2x100=200

35 or less (Note 4)

55

A

150

84055

160

157256

105

(square-shaped type)

For he

ight in

stallat

ion

42

(require

d spac

e)

(Note 4)

95

3 85124

35 or less

5

(round shape type)

64

350

81

11050

124

81 2x100=200

350

Connection positionof branch duct

160

16-M4 Hole

B arrow view

(round shape type)

110

C/L124

85

157

(square-shaped type)

95

Connection positionof branch duct

80

157

213

95

160

Connection positionof fresh air intake kit

(square-shaped type)

C arrow view

(knock hole)90(round shape type)

124

183

109

25

C/L

124

802x1

00=200

(direct installation type)

ø100

20-M4Prepared hole

Connection positionof branch duct

Connection positionof branch duct

90

350

[FCQ50-140] [FCQ50-140] [FCQ100-140]

[FCQ50-71] [FCQ50-71]

[FCQ100-140] [FCQ100-140]

[FCQ50-71]

[FCQ50-71] [FCQ100-140]

Liquid piping connectionGas piping connectionDrain piping connectionTransmission wiring connectionRemote controller wiring connectionAir-outletSuction grilleCorner decoration coverDrain hose (accessory)

12345

6789

Page 17: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

131102

10260 116

20

210

19587

18 17

1230

100

5716

30

210

189

163

35

105

8

156

(Han

ging

bolt p

itch)

(Hanging bolt pitch)

1270

1

235

Hanging bolt4­ M8~M10

(Service space)30 or more 30 or more

(Service space)

519

7

13

690

57

ObstacleFloor side

300 o

r more

(Requir

ed spa

ce)

(Req

uired

spac

e)

For h

eight

instal

lation

From t

he floo

r side 2

500 or

more

221

83 4

268

268

5156

214

6

10576 23 7

The Front

Drain piping connection VP20(For left piping)

(Note.2)Brand name plate

4

57

131

19791

11

6 14

5

o/ 45

90

63

175

90

12

120

59

115

157

63

5140

13460

9

92

Connection position of fresh air intake kitφ100(Knock out hole)

Position slit hole for taking out in piping back(View from the front)

175

5

10319 15220

(Req

uired

spac

e)

Position : Hole of wall for taking out in piping back(View from the front)

235

Hanging bolt1

30 or more1590(Service space)

4­ M8~M10

(Service space)30 or more

11

131

197

6 57o/ 45

91

4 5

14

83

156

6

268

42

221

Drain piping connection VP20(For left piping)

76 3 5

(Note.2)Brand name plate

7

The Front

214268

105

195

156

189100

8

210

1550

260

57

210

163

2018

116

(Han

ging

bolt p

itch)

(Hanging bolt pitch)

17

30

10516

87

131 35

102

10

13

300 o

r more

197

690

57

ObstacleFloor side

(Req

uired

spac

e)

(Requir

ed spa

ce)

5Fo

r heig

ht ins

tallat

ionFro

m the

floor sid

e 2500

or mo

re

19 103

(Req

uired

spac

e)5

22015

175

Position : Hole of wall for taking out in piping back(View from the front)

40

59

115

63

Connection position of fresh air intake kit12090

51

90

φ100(Knock out hole) 9

1579217

5

1341263

60Position slit hole for taking out in piping back

(View from the front)

DIMENSIONS (Unit: mm)

31 32

CEILING SUSPENDED TYPE

Notes:12

3

Location of unit's Name Plate: Bottom of fan housing inside the suction grille.In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.Please do not place the thing been damp and troubled under an indoor unit.When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

CEILING SUSPENDED TYPE

[FHQ100-140CAVEB]

[FHQ71CAVEB]

Notes:12

3

Location of unit's Name Plate: Bottom of fan housing inside the suction grille.In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.Please do not place the thing been damp and troubled under an indoor unit.When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

1234567891011121314151617181920

Air discharge grilleAir suction grilleAir filterGas piping connectionLiquid piping connection Drain piping connectionEarth terminal (inside the control box) (M4)HangerRear piping penetration coverTop panel penetration coverRight side piping connection Left back drain piping connection Left side drain piping connection Right side drain piping connection Hole of wall for taking out in piping back Upward drain piping connection Upward gas piping connection Upward liquid piping connectionPower supply wiring and a unit wiring back connectionPower supply wiring and a unit wiring upper connection

1234567891011121314151617181920

Air discharge grilleAir suction grilleAir filterGas piping connectionLiquid piping connection Drain piping connectionEarth terminal (inside the control box) (M4)HangerRear piping penetration coverTop panel penetration coverRight side piping connection Left back drain piping connection Left side drain piping connection Right side drain piping connection Hole of wall for taking out in piping back Upward drain piping connection Upward gas piping connection Upward liquid piping connectionPower supply wiring and a unit wiring back connectionPower supply wiring and a unit wiring upper connection

6

φ80 hole

5

φ80 hole894

Approx.475

52

105

104

98

Piping and Wiring intakeOutside line

14.5

44

Mounting location 460

44

Approx.390Approx.345

8

120 or lessFor installation in high spaces

50 o

r mor

e

2500 or more

30 o

r mor

e(R

equir

ed sp

ace)

(Req

uired

spac

e)

Piping direction

2 19

238

Approx.400

290

240

Dimensions for full open front panel

3

50 or moreName plate Note)2

50 or morePiping directionPiping direction

1050

7

(Requred space) (Requred space)

WALL MOUNTED TYPE

[FAQ71CVEA]

Front panelFront grillAir outletGas pipingLiquid pipingDrain hoseEarth terminalRight side piping connection holeLeft side piping connection hole

123456789

Notes:123

Location of unit's of Name Plate:Right side surface of casingIn case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail.Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

Approx.4005

65

45

445

Piping and Wiring intake

79.5

Approx.465

6

Mounting location

φ80 hole

114

1085

14.5

φ80 hole

Outside line

Approx.46089

35.5

Piping direction

(Req

uired

spac

e)(R

equir

ed sp

ace)

120 or less

8

2500 or moreFor installation in high spaces

50 o

r mor

e30

or m

ore

(Requred space) (Requred space)1200

7

50 or more 50 or morePiping directionName plate Note)2Piping direction3

9

Approx.440

Dimensions for full open front panel

242

340

2 1

240

WALL MOUNTED TYPE

[FAQ100CVEA]

Front panelFront grillAir outletGas pipingLiquid pipingDrain hoseEarth terminalRight side piping connection holeLeft side piping connection hole

123456789

Notes:123

Location of unit's of Name Plate:Right side surface of casingIn case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail.Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

Page 18: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

This model to be fixed with fixture as shown below.

In case of fixing it at the bottomIn case vibration resistance is required, fix it at both the bottom and the rear.

50 or more

1500 or more

50 or more

Required space

AB

100

C

50

Detail

0.7

Suction grille stopper

(Two both sides)

18

2-7X15 oblong hole

184 184

(For wood screw)(Accessory)

330 30

Fixture

95

666

E G

68

Full open position of suction grille

H

Pull out direction of air-filter

F

D

75

KJ

L

740

or m

ore

(Pull o

ut dim

ensio

n of a

ir-filte

r)

5010

0

Approx.46

2

1

3

5

4

200

34 223

825

600

1850

314

253

95

598

677

616

541

8

9

10

130 215 126

PN

260

M

130

View

7

4- 14 Hole(For bolt)

(From the Air outlet)

View

150

760

150

785

245

215

5X150=750 43

435 16-8X12 oblong hole(All around)

3

3X65

=195

300

5

169

2X65

=130

290

26

300

or m

ore

(A c

ase

with

out

the

ceili

ng)

(Not

e.4)7

144

2500

or

mor

e

28

6

4

700

1 2

212

Air outlet

Ceilling

Air inlet(Note.2)

Floor surface

950

513

150 15

0(All around)

18-8X12 oblong hole

6X150=900

925

80

277

247

(From the Air inlet)

(All around)

1038

(S

uspe

ntio

n bo

lt po

sitio

n)

(Ser

vice

spa

ce)

11X6

5=71

5

9

450

or m

ore 65

13X6

5=84

5

1000

631

805

10

200

8

or le

ss

(All around)

700 or more(Service space)

(Suspention bolt position)

Inspection hatch 450 or more

Air inletAir outlet

30-φ4.7 hole 36-φ4.7 hole

B

Control box(450mmX450mm)Inspection hatch 1

View B-1

CASE 1)

Control box

or le

ss

Inspection hatch 1(450mmX450mm)

200

Ceiling

Control box

Inspection hatch

Fig.A

CASE2), 3)

or m

ore

or le

ss

or m

ore

200

1000

or more700

Inspection hatch 2

(same as the indoorunit size or more)

View B-2

Control box

Inspection hatch 3(Same as the indoorunit size + 300 or more)

or more700

1300

20

Inspection hatch

Control box

or m

ore

Ceiling

Airoutlet

Unit baseAir inlet

300

or m

ore

DIMENSIONS (Unit: mm)

33 34

[FBQ50/60/71DAVET]

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

According to any one of below 1) ~3), secure a space for service works, such as, checking and maintenance of control box, etc.

Notes)1 Location of MANUFACTURE'S LABEL: Control box surface2 Mount the air filter at the suction side. (Select its colorimethod (gravity method) 50% or more.)3 Do not locate things should not be wet under the indoor unit. Dews may drop when humidity reaches over 80%, or a drain gets stuck, or air filters are not clean.4 Space for Service Works

1) One inspection hatch (450X450) on the control box side and a space of 300mm or more under the unit. (Fig.A)2) One inspection hatch (450X450) on the control box side and 2 (two) inspection hatches under the unit. (Arrow View B-1)3) 3 (three) inspection hatches under the unit and the control box. (Arrow View B-2)

Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal (Terminal in Control box)Control box (Inside)Remote control wiring connectionPower-source wiring and a unit wiring connectionAir discharge flangeAir suction flangeHook

1234567

8910

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

(SAME AS THE INDOOR UNIT SIZE OR MORE)

Fig.AAir outlet

Inspection hatch 1(450mmX450mm)

Air inletUnit base

Control box

200

or le

ssCASE 1)

300

or m

ore

Inspection hatch

Control box

Ceiling

150

215

View

165 49

1160

245

(From the Air outlet)

7X150=1050

(All around)20-8X12 oblong hole635

1185

40

232

212

167

(467 or l

ess) 3

300

7169

1

(A ca

se wi

thout

the ce

iling)

6

2X65

=130

290

(Not

e.4)

300 o

r more4

2

28

144

70011

700

or le

ss 5

3X65

=195

2500

or m

ore

Air outlet

Floor surface

Air inlet (Note.2)

Ceiling

Adjus

table

80

20-8X12 oblong hole

8X150=1200

1350

150

713300 or less

150 27

7

1325

12(All around)

247

(From the Air inlet)

(Serv

ice sp

ace)

27 63140- 4.7 Hole(All around) 48- 4.7 Hole

1438

(Han

ging

bolt p

itch)

700 or more

(Hanging bolt pitch)

9

16X6

5=10

40

(All around)8

10

19X6

5=12

35

450

or m

ore

200

or le

ss14

00

(Service space)

1205

65

Air inlet

Inspection hatch 450 or more

Air outlet

200

or less

Control box

Inspection hatch 1(450mmX450mm)

700 or more

(SAME AS THE INDOOR UNIT SIZE OR MORE)

Inspection hatch 2

1400

or more 170

0 or m

ore

Control box

(SAME AS THE INDOOR UNIT SIZE +300 OR MORE)

Inspection hatch 3

700 or more

View B-2

CASE 2),3)

CeilingInspection hatch

B

20

or m

ore

Control box

View B-1

According to any one of below 1)~3),secure a space for service works,such as,checking and maintenance of control box,etc.

1)One inspection hatch (450X450) on the control box side and a space of 300mm or more under the unit.(Fig.A)2)One inspection hatch (450X450) on the control box side and 2 (two) inspection hatches under the unit.(Arrow View B-1)3)3 (three) inspection hatches under the unit and the control box.(Arrow View B-2)

Notes: 1Location of MANUFACTURE'S LABEL: Control box surface2Mount the air filter at the suction side.(Select its colorimethod (gravity method) 50% or more.3Do not locate things should not be wet under the indoor unit.Dews may drop when humidity reaches over 80%,or a drain gets stuck,or air filters are not clean.4Space for Service Works

[FBQ100/125/140DAVET]

Liquid piping connectionGas piping connectionDrain piping connectionEarth terminal(Terminal in Control box)Control box(Inside)Remote control wiring connectionPower supply wiring and a transmission wiringAir discharge flangeAir suction flangeHangerSocket (for maintenance)Drain hose(Accessory)

1234

56

7

89101112

FLOOR STANDING TYPE

Notes: 1Sticking location for manufacturer’s label: on the surface of cover of switch box inside the suction grille. 130

A

FVQ100/125/140CVEB50

190

B110

266

C186

350

D270

44

E45

49

F50

130

G50

190

H110

260

J180

266

K186

322

L242

79

M57

202

N144

229

P149FVQ50/60CVE, 71CVEB

Suction grilleAir filterThrough hole for side piping(70x90 oblong slit hole)Through hole for side piping( 80 slit hole)Through hole for side piping( 27 slit hole)Through hole for rear piping/wiring(80x130 oblong slit hole)Through hole for bottom piping/wiring(126x130 square hole)Liquid pipe connectionGas pipe connectionDrain pipe connection

123

4

5

6

7

8910

595

559

20094

449

509

419299

21Drain outlet

Drain outlet

163 112

272

479

269

Wiring inletName plate

20

573.5

845

342

7

78

2030

0

300131

326

Drain outletI.D. 18 hose for connection

Hole for anchor bolts (M8 or M10)

Liquid stop valve( 9.5CuT)

Earth terminal in switch box

Service port

Gas stop valve( 15.9CuT)

6010

5

Service port 144

OUTDOOR UNIT // RZR50/60/71LVVM

Page 19: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

OUTDOOR UNIT // RZR125/140LVVM, RZQ100/125/140KCTLT, RZQ100/125/140LUYLT

6

5

13

52

7

5553

95

67

223

30

53

567

95

80

145

19

5584

3038

350

(345

~355

)

320

91

37

620160

30

Hole for anchor bolt 4-M12

160

55

279

90

16

285

36

416

260

262

595

68

8 16

161

561

340

940

95

60

5

3

990

89

7 6 89 53

21

142

4

19

339

DIMENSIONS (Unit: mm)

30

223

5

52

13

76

67

5595

53

19137645

102

117

70

16

71 16

58

5

8

5

7

95

19

84

8054

145

55

6

142

2

3

6

89

7

19

5

423

1170

4

422

9554

900

1

60 89

94

6130

350

(345

~355

)

43

620

320

41

140

30

140

Hole for anchorbolt 4-M12

Gas piping connectionLiquid piping connectionService portEarth terminalRefrigerant piping intakePower supply wiring intakeTransmission wiring intakeDrain outlet

12345678

OUTDOOR UNIT // RZR100LVVM

Gas piping connectionLiquid piping connectionService portEarth terminalRefrigerant piping intakePower supply wiring intakeTransmission wiring intakeDrain piping connection

12345678

35 36

REMOTE CONTROLLER

Wired type

Staple

Remote controller

17

17

0~5

117

Remote controller

Remote controller

(Between remote controller and control box)

17

• Installation methodA Exposed body, exposed cord C Exposed body, embedded codeB Exposed body, embedded cord

Conduit

Control box

Through hole

Size

Specifications of cord

0.75~1.25 mm2

Total length 500 m

Type Shield wire (insulated thickness: 1 mm or more) Note) 1. Remote controller cord and staple are not

attached. They are field supplied parts.

120

120

17 18

42

84

38

Cord outlet hole2823

46

• Remote controller dimensions

Wireless typeCEILING MOUNTED CASSETTE TYPE <Round Flow>• Remote controller dimensions

• Remote controller holderinstallation procedure<installation to wall surface>

• Receiver installation procedure

• Receiver detail

Transmitting part

157

62 17.5

Liquid crystalremote controller(wireless)

Remote controllerholder

CEILING SUSPENDED TYPE

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

• Receiver installation procedure

120

72 83.5

106

(Ceil

ing op

ening

)

70 180.5

35 49

Service space for ceiling installation

• Receiver detail

Note :

Mor

e th

an 9

0(S

revic

e sp

ace)

(Ceiling opening)

2-5x9 Slot

Switch box(field Supplied parts)

Do not install more than 3 receivers in the vicinity of one another.With 4 or more units, there is always the possibility of malfunction

( 12- 16)

Receiver

Drain pipingside

Refrigerantpiping side

Decoration panel

WALL MOUNTED TYPE• Receiver installation procedure

BRC1C61

19

Upper case Lower case

40

2346

2848.5

4284

5X7 oblong hole

Code outlet hole5X15 oblong hole

Lower case portion

Lower case portion

Staple

19

A Exposed cord C Embedded cord(use switch box)

B Embedded cord

84

46Switch box for two switchex.) KJB211A(optional accessory)

Condit19

0~5

Switch box [field supplied part]

(Between remotecontroller and control box)

48.5

19

Note)2Through hole

40

( 8- 10)

84

28Switch box for one switchex.) KJB111A(optional accessory)

• Installation method

2.If the hole size is too large or the location is not proper, the hole may come out from the remote controller.

Note) 1. Remote controller cord and staple are not attached. They are field

supplied parts.

Size

Specifications of cord

0.75~1.25 mm2

Total length 500 m

Type Vinyl cord with sheath or cable (insulated thickness: 1mm or more)

BRC1E62

(Green)120

120

   Operationlamp

Top left outlet

Left outlet

Top centeroutlet

• Receiver detail

The Front

• Receiver detail

Receiver

Receiver

Page 20: floor-standing-type-fvqcveb-pdf - Daikin Home | Daikin ... · Use only those parts and accessories supplied or by Daikin. Ask a installer or contractor to install those parts and

Installation service space for outdoor unit

1000

or more

300 or more

L H

L H

H

L

500

or more100

or more

L H

For RZR50-140LVVM For RZQ100-140KCTLT, 100-140LUYLT

300

or more

1000 or more

200 or more

100

or more

100 or more 100 or more

100

or more

500 or more

When there are obstructions on the inlet side and both lateral sides

2. For series installation (more than two units)When there are obstructions on both sides

1. For single unit installation When there is an obstruction only on the inlet side

1. For single unit installation When there is an obstruction on the inlet side

2) When there is an obstruction in the overhead space

When there are obstructions on both sides

When there are obstructions on the inlet side and both lateral sides

2. For series installation (more than two units)

1. For single unit installation

2. For series installation (more than two units)

1. For single unit installation

2. For series installation (more than two units)

1. For single unit installation

2. For series installation (more than two units)

100

or more

500 or less

1000

or m

ore

An obstruction in the overhead space

500 or less

500 or more

1000

or m

ore

An obstruction in the overhead space

500 or less

1000 or more

1000

or m

ore

An obstruction in the overhead space

150

or more

150 or more 150 or more

500 or less

1000

or m

oreAn obstruction

in the overhead space

300

or more

1000 or more

200 or more

500 or less

1000

or m

ore

An obstruction in the overhead space

1.RZR50/60/71LVVM 2.RZR100-140LVVM

21

21

21

21

21

21

21

21

21

21

21

21

1000 or more

1) When the overhead space is open

2) When there is an obstruction in the overhead space

1) When the overhead space is openWhen there is an obstruction on the inlet side1 When there is an obstruction on the outlet side2

1000

or m

ore

500 or less

250 or more 150 or more150 or more

500 or less

200 or more

1000 or more 250 or more 250 or more

1000

or m

ore

250 or more200 or more250 or more

1000 or more

1000

or

mor

e

100 or more

500 or less

500 or more

50 or more

500 or more

50 or more

250 or more

1000

or m

ore

500 or less

1000 or more

1000 or more

250 or more

250 or more

1000

or more

200 or more

500 or more

500 or less

1000

or m

ore

100 or more

100 or more 250 or more

1) When the overhead space is open (There is no limit to the height of the obstruction on the outlet side.)

When there are obstructions on both the inlet and outlet sides(When the obstruction on the outlet side is higher than the unit itself)

3

Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.37 38

1000 or more

100 or more 100 or more

1000

or more

300

or more

L H

L H

100 or more 100 or more

300 or more

1000 or more

200 or more

100 or more 100 or more

500 or less

1000 or more

1000

or

mor

e

An obstruction in the overhead space

100 or more

100 or more

300

or more

1000 or more

200 or more

500 or less

1000

or

mor

e

An obstruction in the overhead space

100 or more

100 or more

When there is an obstruction on the inlet side

When there are obstructions on the inlet side and both sides

2. For multiple units installation (more than two units)

When there are obstructions on both sides

1) When the overhead space is open

1. For single unit installation

When there is an obstruction only on the inlet side

2) When there is an obstruction in the overhead space

1) When the overhead space is open

When there are obstructions on both sides

2) When there is an obstruction in the overhead space

When there is an obstruction on the inlet side

When there are obstructions on the inlet side and both sides

2. For multiple units installation (more than two units)

1. For single unit installation

1. For single unit installation

2. For multiple units installation (more than two units)

1. For single unit installation

2. For multiple units installation (more than two units)

1. For single unit installation

2. For multiple units installation (more than two units)

Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.

1 When there is an obstruction on the outlet side2

1) When the overhead space is open (There is no limit to the height of the obstruction on the outlet side.)

When there are obstructions on both the inlet and outlet sides(When the obstruction on the outlet side is higher than the unit itself)

3

H

L

500

or more

100

or more

L H

100 or more

100 or more100 or more

100 or more

500 or more

100 or more

500 or less

1000

or

mor

e

An obstruction in the overhead space

500 or less

500 or more

1000

or

mor

e

An obstruction in the overhead space

150 or more

150 or more150 or more

500 or less

1000

or

mor

e

An obstruction in the overhead space