flow measurement and control
TRANSCRIPT
-
8/10/2019 Flow Measurement and Control
1/43
S
N
Flow Measurement & ControlFlow metering, batching, controlling
You can build on our experience
We measure and control the resources of our world
-
8/10/2019 Flow Measurement and Control
2/43
2 3
The company Our productsNothing in the world is as powerful asan idea whose time has come.Victor Hugo
Quality is not a coincidence; it is theresult of our company philosophy.
Our products
Test stand and innovation center ofBadger Meter
Badger Meter, Inc., Milwaukee, USA
Badger Meter, Inc., Tulsa, USA
Badger Meter Europa GmbH in Neuffen,
Germany
Badger Meter Czech s.r.o. in Brno,Czech Republic
Badger Meter Slovakia s.r.o. in Bratislava,Slovakia
Badger Meter Asia in Singapore
Electromagnetic flow meters 4
Detector type II 6Sanitary detector for food 8Detector type III 9Amplifier type ModMAGM 2000 10Amplifier type B-MAG | M 5000 11
Amplifier type ModMAGM 1000 12Amplifier type ModMAGM 3000 / 4000 13
Turbine meters 14
Cx series and LoFlo series with single rotor 16Exact series with dual rotor 17Type 1100, QuikSertand Flow monitor B 2800/B 3000 18Type FloClean 3-A 19Turbine meter type VISION1000 20Turbine meter type VISION2000 21
Nutating disc meters 22
Recordallfluid meter 24Meters for AdBlueand aggressive media 26Batch systems 27
Impeller meters 28
Flow sensors 30Monitors and transmitters 31
Ultrasonic flow meters 32
Type DFX, TFX Ultra, TFXL and Fusion 34Type DXN and UFX 35Type MultySonic 8000 36Type iSonic 2000, DataControl 2500 and L2 xx 38
Heat meters and accessories 40
Type DXN, TFX Ultraand Btu 380 42GSM / GPRS 43
Oval gear meters 44
IOGseries 46Electronical meters 48Mechanical meters 49In-line meters 50Pulse transmitters 51
Variable area flow meters 52
Type EZ-View 54The H-Series 55MR series and Flow-Alert switch 56Type Vista-Gage, Vista-Gage Vacuum, Vista-Cator, Vista-Monitor 57
Vortex meters 58Type RWG & RWBG, RNG insertion and RNL in-line 60RVL series 61
Coriolis mass meters 62
Coriolis mass meter type MMC2 64Coriolis mass meter type MMC2 Hygiene and MME2 65
Differential pressure flow meters/Venturi tubes 66
Type Ellipse 68Venturi tubes 69Type Coin 69
Hydraulic testers 70
Type PFM, Flo-Check 70
Flow calibrators 71
Fluid manageme nt systems 72
LMS RF system 74MDS 2000 76FMS Compact 77
Small control valves 78
ReCovalves 80Process valves 81Sanitary valves 82
Positioners 83
We can measure the flow of allliquids in almost all branches ofthe industry, and in small and largeapplications including pressurepipes, semi-filled pipes and openchannels with a great variety ofmeasurement principles.A large product range provide a
solution for almost any of yourmeasurement applications in thewater and waste water industry,sewage plant, water conditioning,water supply, water discharge,chemical industry, process industry,heat transfer, pharmaceuticalindustry, concrete industry, foodand beverage industry, shipyardindustry, power plants, refineries,paper industry, metallurgical indus-try, automotive industry, photogra-phy industry, textile industry
A company which has successfullybeen providing the industry withflow meters for more than 108years is always aware of the impor-tance of quality in its products.However, quality is an on-goingprocess which we, as a company,
embrace every day.At Badger Meter Europa GmbH, weconsider quality as of t he whole.It is the quality of our work, whichyou, as a customer, are entitled toexpect from us.Quality begins with the individual,our employees, and requires a com-pany philosophy which fits accord-ingly. Our quality should accompanyyou throughout the process: fromthe inquiry, to the order and theproduct up to the service.No compromise in terms of quality.
Badger Meter Europa GmbH is awholly owned subsidiary ofBadger Meter, Inc., USA, based inMilwaukee, Wisconsin. With salesof more than 350 million Euro andthe dedication of more than 1300employees all around the world,
Badger Meter is a leading marketerand manufacturer of flow measure-ment and control devices since1905. Badger Meter was a pioneerin flow measurement and can lookback today at many patents in thatfield.
Badger Meter Europa GmbH isresponsible for the internationaloperations worldwide, except forthe United States, Mexico andCanada which are operated fromBadger Meter, Inc., USA.Highly qualified people as well asstate-of-the-art production andtest facilities ensure the best salessupport and service for our custom-ers. Badger Meter Europa GmbH isDIN ISO 9001:2008 certified and,since 1997, one of the test standsis officially PTB-approved andcertified from the Office of Weightand Measures as test equipmentaccording to the OIML R 117.
We help you in a timely manner tosolve your measurement problems,advise you and optimize yourmeasurement solution, technologyand site location before you makea decision. An extensive distributor
and service network assures thebest service all around the world.Local representatives are a bigadvantage for our customers. Theshort distance and the languagemake the assistance more eff icient.Our distributors are trained onBadger Meter products in their ownoffice or in our training center.
Our name assures you that ourproducts have been manufacturedwith the best care and in con-formity with all DIN ISO 9001:2008directives.
The company Long-term service andcompetence
You can compare we cant!
Flow measuring, batching,controlling
Quality is a tradition
-
8/10/2019 Flow Measurement and Control
3/43
S
N
4 5
Electromagnetic flow meters
Electromagnetic flow metersMeasuring principle
The meters for conductive
fluids
The electromagnetic flow meters are ideally suited for flow measurement of all liquids
with a minimum conductivity of 5 S/cm (20 S/cm for demineralized water).
These meters are very accurate and the flow measurement is independent of density,
temperature and pressure of the medium.
The operating principle of the electromagnetic flow meter is based onFaradays law of magnetic induction: The voltage induced across any con-ductor, as it moves at right angles through a magnetic field, is proportionalto the velocity of that conductor. The voltage induced within the fluid ismeasured by two diametrically opposed internally mounted electrodes.The induced signal voltage is proportional to the product of the magneticflux density, the distance between the electrodes and the average flowvelocity of the fluid.
-
8/10/2019 Flow Measurement and Control
4/43
6 7
Electromagnetic flow meters
Flange process connection
Detector type II
Size DN 6 2000
Nominal pressure upto PN 1 00
Flange process connection
Wall mounted
Flange process connection
Meter mounted
A
122 80
B1
120
K
D
d2x
n
DN
99180
180
M20(x3)
281
60 5.
2
65
A
B2
K
D
d2xn
DN
180
180
M20(x3)
83
The electromagnetic detector typeII is not only available in a numberof different flange process connec-tions (DIN, ANSI, JIS, AWWA, etc.)but also in a number of liners likehard rubber, soft rubber, PTFE, PFAor Halar.The detector can be configuredwith up to four electrodes for meas-uring, empty pipe and grounding
electrodes.
Available in sizes from DN 6 to DN2000 and nominal pressures up toPN 100, the detector type II is bestsuited for a variety of applicationsin the industry and the water/wastewater industry.
Lined measuring pipes with materi-als approved for drinking water:KTW/DVGW, NSF-61, WRAS, ACS.
Technical data
Size DN 6 2000 (1/4...80)Process connections Flange: DIN, ANSI, JIS, AWWA, etc.N om in al pr es su re U p t o P N 1 00P ro te ct io n c la ss I P 6 7, op ti on al IP 68M in . c on du ct iv it y 5 S/ cm
(20 S/cm for demineralized water)Liner material s Hard / soft rubber from DN 25 0 up to +80 C
PTFE DN 6 600 -40 up to +150 C
Hala r ( ECTFE ) f rom DN 300 - 40 up t o +150 CElectrodes materials Hastelloy C (standard)
TantalPlatinum / Gold platedPlatinum / Rhodium
Hous ing C arbon steel / Optio nal stainl ess steelLay length DN 6 20 170 mm
DN 25 50 225 mmDN 65 100 280 mmDN 125 200 400 mmDN 250 350 500 mmDN 400 700 600 mmD N 7 50 1 00 0 8 00 mmDN 1200 1400 1000 mmDN 1600 1600 mmDN 1800 1800 mmDN 2000 2000 mm
Dimensions (mm)
DN A Std* A ISO** B 1 B 2
wi th AN SI fla nge s w ith DIN fla ng es
D K d2 x n D K d2 x n
6 1/4 170 228 305 88,9 60,3 15,9 x 4 90 60 14 x 48 3/10 170 228 305 88,9 60,3 15,9 x 4 90 60 14 x 410 3/8 170 228 305 88,9 60,3 15,9 x 4 90 60 14 x 415 1/2 170 200 238 315 88,9 60,3 15,9 x 4 95 65 14 x 420 3/4 170 200 238 315 98,4 69,8 15,9 x 4 105 75 14 x 425 1 225 200 238 315 107,9 79,4 15,9 x 4 115 85 14 x 432 1 1/4 225 200 253 330 117,5 88,9 15,9 x 4 140 100 18 x 440 1 1/2 225 200 253 330 127 98,4 15,9 x 4 150 110 18 x 450 2 225 200 253 330 152,4 120,6 19 x 4 165 125 18 x 465 2 1/2 280 200 271 348 177,8 139,7 19 x 4 185 145 18 x 480 3 280 200 271 348 190,5 152,4 19 x 4 200 160 18 x 8100 4 280 250 278 355 228,6 190,5 19 x 8 220 180 18 x 8125 5 400 250 298 375 254 215,9 22,2 x 8 250 210 18 x 8150 6 400 300 310 387 279,4 241,3 22,2 x 8 285 240 22 x 8200 8 400 350 338 415 342,9 298,4 22,2 x 8 340 295 22 x 12
250 10 500 450 362 439 406,4 361,9 25,4 x 12 395 350 22 x 12300 12 500 500 425 502 482,6 431,8 25,4 x 12 445 400 22 x 12350 14 500 550 450 527 533,4 476,2 28,6 x 12 505 460 22 x 16400 16 600 600 475 552 596,9 539,7 28,6 x 16 565 515 26 x 16450 18 600 500 577 635,0 577,8 31,7 x 16 615 565 26 x 20500 20 600 525 602 698,5 635,0 31,7 x 20 670 620 26 x 20550 22 600 550 627 749,3 692,1 34,9 x 20 600 24 600 588 665 812,8 749,3 34,9 x 20 780 725 30 x 20650 26 600 613 690 869,9 806,4 34,9 x 24
700 28 600 625 702 927,1 863,6 35,1 x 28 895 840 30 x 24750 30 800 650 727 984,2 914,4 34,9 x 28 800 32 800 683 760 1060,5 977,9 41,3 x 28 1015 950 33 x 24850 34 800 708 785 1111,2 1028,7 41,3 x 32 900 36 800 725 802 1168,4 1085,8 41,3 x 32 1115 1050 33 x 28950 38 800 750 827 1238,3 1149,4 41,3 x 32 1000 40 800 790 867 1346,2 1257,3 41,3 x 36 1230 1160 36 x 281200 48 1000 900 977 1511,5 1422,4 41,3 x 44 1455 1380 39 x 321350 54 1000 975 1052 1682,8 1593,9 47,8 x 44 1400 5 6 1000 1000 1077 1675 1590 42 x 36
Standardwi th A NSI fl anges from D N 6 to 1400 Lbs 150with DIN flanges from DN 6 to 200 PN 16
f ro m D N 2 50 to 14 00 P N 1 0*Standard **ISO 13359Sizes DN 1600 2000 upon request.
-
8/10/2019 Flow Measurement and Control
5/43
-
8/10/2019 Flow Measurement and Control
6/43
10 11
Electromagnetic flow meters
Amplifier type ModMAGM 2000for all detectors
Amplifier type B-MAG | M 5000for flanged process connections
Dimensions Dimensions
Accuracy 0,2 % ofactual flow
Flow range 0,03 12 m/s
DN 6 DN 2000
IP 67 housing
Interfaces ModBus, HART,M-Bus, Profibus DP
99180
180
M20(x3)
281
60
5.2
65
99180
180
M20(x4)
281
60 5.
2
65
Verification Device
Up to 20 years battery life span
Accuracy better than 0,4 % of actual flow
Measuring range of 0,03 to 12 m/s
Sizes from DN 15 to DN 600
LCD display
IP 67 / IP 68 protection class
IrDA, ModBusRTU, M-Bus interfacesThe amplifier type ModMAGM 2000 is best suited for bidirec-tional flow measurement of fluidswith a conductivity > 5 S/cm (> 20S/cm for demineralized water).ModMAGM 2000 shows a highaccuracy, is easy to use and canbe chosen for a large and flexibleapplications spectrum.The backlight, four-line displayshows all actual flow measuringdata, daily and complete informa-tion, including alarm messages.
The standard amplifier has 4programmable digital outputs, onedigital input, analog output anddifferent interfaces.Integrated system self check-upmakes the putting into operationand the service easier.
The verification device enables theelectromagnetic flow meters typesModMAGM 2000 and B-MAG |M 5000 to be checked on site inregular time intervals at a low costand without interruption of theprocess.All important parameters of theflow meter are measured, proto-coled and evaluated.
Technical data
P ow er su pp ly 8 5 26 5 VA C, 45 6 5 H z,
-
8/10/2019 Flow Measurement and Control
7/43
12 13
Electromagnetic flow meters
Amplifier type ModMAGM 1000for all detectors
The low cost alternative
Accuracy 0,3 % ofactual flow
Flow range 0,03 12 m/s
DN 6 DN 200
Amplifier type ModMAGM 3000 / 4000for all detectors
Ex-proof
Protection class IP 67
Accuracy 0,2 % ofactual flow
Flow range 0,03 12 m/s
~188
~ 98 ~ 140
139
234
90
108
95 132
191
183
Dimensions
Junction box
Dimensions
ModMAGM 3000 / 4000
Dimensions
ModMAGM 1000
164
249
148
60
M20(x2)
65
5.2
80
The amplifier type ModMAGM 1000 is suited forbidirectional flow measurement of liquids >5 S/cm(>20 S/cm for demineralized water). It combines allthe opportunities of price with high level performance.Information such as flow rate, total flow rates, dailyflow rate or even an alert and can easily be read fromthe LCD display. Various inputs, outputs and interfacesallow a wide range of different applications with theM 1000.Thanks to the IP 67 aluminium housing the ModMAG
M 1000 is ideal for outdoor applications in ruggedenvironmental conditions.
Technical data
P ow er su pp ly 9 2 27 5 VA C (5 0/ 60 Hz ),
-
8/10/2019 Flow Measurement and Control
8/43
Measuring principle
The meters for fluids with
low viscosity
Turbine meters are only meant for applications with low viscosity fluids and gases.
Turbine meters are volumetric meters. When the fluid passes through, arotor is activated and the movement is either electronically or mechanicallytransmitted outside.
Turbine meters
14 15
Turbine meters
-
8/10/2019 Flow Measurement and Control
9/43
16 17
Cx series and LoFlo series with single rotorfor standard and low flow applications
Ceramic ball bearings
Large flow range
High repeatability
Long lifetime
Turbine meters
Exact series with dual rotorfor highly-precise flow measurement
No need for flowstraighteners
Enhanced performance dueto helical rotors
Superior absolute accuracy
Excellent repeatability
Wide opera ting flow range
Extended UVC* flow range
Integral pickoff imperviousto vibratio n
NVLAP calibration
The standard turbine meters of the Cx series are moreused in applications like coolant for cutting and form-ing operations, process control flow measurement,component test stands for the military, batch flowmetering, fuel consumption measurement in machines,motors and actuator aggregates, as well as for a greatnumber of R&D applications.
Coupled with an advanced EC 80 flow computer, thesemeter systems provide fully compensated precisionflow measurements. The EC 80 flow computer will lin-earize the meter within 0,1 % linearity over the entirerepeatable range.
Technical data: Cx series
Cal ibr at or unce rt ain ty < 0 ,05 % of r ead ingAccuracy 0,25 % of readingRepeatability 0,02 % of readingLinearitywith electronic linearizer
0,5 % of reading0,1 % of reading
Max. f requency out put 500 to 1500 Hz s tandar dOutput signal 0 10 V (square wave pulse)Response time 2 3 mS or better
The robust axial meters of the LoFlo series provide anexceptional repeatability of 0,25 % of reading. Whenpaired with the EC 80 flow computer, the calibrationdata is linearized to within 0,1 % of reading, allowingfor precision flow measurement over the entire usablerange of the meter. The series is not position-sensitiveand can be mounted in any piping orientation.
The custom long-life, ceramic low-friction ball bearingsystem used in the LoFlo series meets the demandsof water, hydrocarbons and cryogenic fluids. Capable ofmeasuring flows as low as 0,024 l/min, this meter is anideal solution for a multitude of applications.Typical uses include fuel injection production systems,blending of costly chemical additives, onboard fuel
consumption, refrigerants, dye injections, and more.
Cox is a division of Badger Meter, Inc.
Technical data: LoFlo series
Accuracy 0,25 % of readingRepeatability 0,25 %Frequency output 1500 1800 HzPressure rating 40 barResponse time 20 30 mSB od y c on st ru ct io n 3 16 SS T, fi tt in gs -6 AN (M S)
The Exact series is the worlds most precise meterof its kind, providing extended range performance notobtainable with traditional single rotor designs. It isused for aerospace, automotive, industrial and OEMapplications.
The Exact series provides an extended flow rangecapability, which often eliminates the need for mani-fold systems and thus simplifies installation and lowerscosts. The meters exceptional performance, enabledby the innovative dual rotor configuration. UVC* curvesimprove the accuracy and extend the usable measure-ment flow range.
With the Exact series (standard model CDX/CDL),
flow straighteners are not required to control proc-ess fluid swirl, as the dual rotor system cancels outthe rotor acceleration effect. With flow straighteners,bearing diagnostics can be determined by monitoringthe ratio of the rotors t o detect wear or cleanliness.The Exact series meters also utilize a unique pickoffsystem, which is impervious to vibration and minimizesspace. This allows for direct coupling of electronics ona robust mount having a lower profile. Both integraland remote electronics are available to process thesignal output.
The dual rotor technology is ideal for a wide range ofapplications. The meter is designed for bi-directionalflow and high shock environments. It utilizes a robustbearing system having dual ceramic bearings on eachrotor with the internals securely locked in place, result-ing in excellent repeatability. The dual rotor meter
Technical data
Ca lib ra tion uncer ta int y < 0 ,05 % o f r eadingAccuracy 0,1 % of readingRepeatability 0,02 % of readingLinearity (with linearizer) 0,01 % of readingP ro ce ss t em pe ra tu re - 27 0 C to + 15 0 C st an da rdO pe ra ti ng pr es su re U p t o 2 06 5 b ar de pe nd in g o n
size and end-fittingsPressure drop 0,9 bar at max. flow rate
@1,2 cStBearing Ceramic std.
(water and hydrocarbons)
allows for installation in applications that do not havespace for flow straighteners without loss of measure-ment accuracy. Pressures of up to 2065 bar can becontained, while compensating for viscosity changesusing integrated pressure sensors.
Cox is a division of Badger Meter, Inc.
*UVC = Universal viscosity curve
-
8/10/2019 Flow Measurement and Control
10/43
18 19
Type 1100, QuikSertandFlow monitor B 2800/B 3000for harsh applications
Robust meter for rigorousapplications
Meets highest demands
Simple installation
Low costs for maintenance
Turbine meters
Type FloClean 3-Afor sanitary applications
Long lifetime
Easy installation
Low maintenance costs
This rugged line of turbine metersis ideal for harsh industrial applica-tions. Stainless steel and tungstencarbide components ensure longlife. These products are also well-suited for industrial applicationswith high temperature and high
Technical data 1100
Material Body 316 SSRotor Stainless steelRotor support Stainless steelRotor shaft Tungsten carbide
Measu re r ange 0 ,03 0,1 l/s to 30 315 l/sP ip e s iz e I ns ta ll at io n i n p ip es fr om t o 1 0F low accur acy 1 % o f read ing f or 7 /8 and la rger
meters1 % of reading over the upper 70 % ofthe measuring range for 3/8, 1/2 and3/4 meters
Repeatability 0,1 %Cal i lb ra t ion W at er (N IST t r aceable cal ibr at ion )P ressu re ra tings 340 ba r max.Turbine temperature Up to 180 CEnd connections NPT, BSP, Victaulic, Flange, Hose
Barbed or Grayloc
A pp ro va ls C SA Cl as s I Di v 1 , G ro up s C & D ;Class II Div 1, Groups E, F & G:intrinsically safeCSA Class l Div 1 Groups C, D; com-plies to UL 1203 and CSA 22.2 No. 30Met Labs File No. E112860(For explosion proof models only)
Technical data QuikSert
for fluids for gases
Material Body Stainless steel Stainless steelRotor Stainless steel Stainless steelRotor support/shaft
Tungs ten c arbide Tungs ten c arbide
Measuring range 10:1 Accuracy 1 % of reading for 7/8 and
larger meters
1 % of reading over the upper70 % of the measuring rangefor 3/8, 1/2 and 3/4 meters
Repeatability 0,1 % 0,5 %Calibration Water
(NIST traceable calibration)Pressure rating 10 to 100 bar Vacuum 15.3 mPa max.Operating temperature Up to 180 C -40 C to +165 CE nd c on ne ct io ns W af er -s ty le A SM E/ AN SI
B16.5 1996Approvals For explosion proof models
only:Class l Div 1 Groups C, D;Complies to UL 1203 andCSA 22.2 No. 30Met Labs File No. E112860
Technical data B 2800 / B 3000
Power supplyBatteryLoop powered
1,5 VDC alkaline battery4 20mA, loop powered25 mA energy consumption max.
Pulse output signal One pulse for each increment of theleast significant digit of totalizer
P ul se t yp e O pt o- is ol at ed o pe n c ol le ct ortransistors
Max. voltage 30 VDCMax. pulse wid th (On st at e) 20 ms/max . pulse ra te
20 HzCurrent (On state) 0.9 V drop at 5.0 mA or
0.7 V drop at 0.1 mAInputs Magnetic pickupF re qu en cy ra ng e 1 to 35 00 HzTr ig ge r s en si ti vy 3 0 m V p -pOver voltage protection 30 VDCAccuracy 0,1 %Analog output 4 20 mAOperating temperature -30 C to +70 CUnits of measure(Rate/total)
l/min, m/d, m/h, gal/min, b/d
Units of measure(Total rate)
Liter, m, Kg, gallons, oil barrels,MGal, Cubic Ft, liquid barrels, Lbs
Time intervals (rate) Day, hour, minute, secondApprovals
Meter, remote andswivel mount
CSA Class I, Div.1, Groups C & Dintrinsically safeClass II, Division 1, Groups E, F & Gintrinsically safeCE: IEC 61326-1
Explosion-proof modelonly
CSA Class I, Div 1, Groups B, C & DCSA Class II, Groups E, F & GCSA Class III, Type 4, T6 @ 70 C
The FloClean 3-A sanitary turbine flow meter meetsthe requirements of 3-A sanitary standard and isrecommended for use in clean out-of place (COP) andsanitize out-of place (SOP) applications. The meter isperfectly adapted for use in the food, beverage andpharmaceutical industries.FloClean provides a local flow rate and volumetotalization when used with the BlancettB 2800 orB 3000 displays, as well as the ability to interface witha variety of PLCs and computers.
Technical data FloClean
Material ofconstruction
Bo dy 316 L stainles s steelTur bine 316 L st ainless s teel ,
Nickel platedBearingsstandard
Nickel bindery,tungsten carbide
Sh aft Nic kel binder y,tungsten carbide
M ea su re ra ng e 0 ,0 3 0, 1 t o 2 ,5 2 5 l /sAccuracy 1 % of readingR ep ea ta bi li ty 0, 1 % o f r ea di ngC al ib ra ti on W at er ( NI ST t ra ce ab le c al ib ra ti on )Operating pressure 65 bar (Tr i-Clamp)Operating temperature Up to 150 CE nd c on ne ct io ns S an it ar y cl am p en dM ag . p ic k- up N EM A 6 ; - 10 0 C t o + 15 0 C
pressure applications, for examplein secondary oil recovery, semicon-ductor and chemical processing.Electronic options enable the meterto interface with most computersand PLCs.
-
8/10/2019 Flow Measurement and Control
11/43
20 21
Turbine meter type VISION1000 Turbine meter type VISION2000for low viscosity, non-aggressive liquids, for very low flows for low viscosity, non-aggressive liquids, for very low flows
Good price/performanceratio
Compact construction
Easy installation
No maintenanceHigh operating pressure
Operates in any mountingposition
Good price/performanceratio
Compact construction
Easy installation
No maintenanceHigh operating pressure
Operates in any mountingposition
Turbine meters
Dimensions DimensionsThe turbine meters of the VISIONseries are for the exact metering ofsmall quantities of liquids.The actual flow as well as the flowalready flowed through can bemeasured.The VISION1000 series is bestsuited for small flow rates up to2,5 l/min.
The turbine meters of the VISIONseries are for the exact metering ofsmall quantities of liquids.The actual flow as well as the flowalready flowed through can bemeasured.The VISION2000 series is used forflow rates up to 35 l/min.
45
27.2
17
ca.
46.6
The meters are best suited for flowmeasurement of demineralizedwater, alkaline solutions, oils/salad oil, fuel oil, beverage, watersolutions or for fuel and fuel con-sumption. They are especially idealfor washing maschines and dishwashers, coffee machines, lasercooling plants, solar plants, backeryand steam cooking machines inlarge kitchen plants or CD cleaning.
The meters are best suited for flowmeasurement of demineralizedwater, alkaline solutions, oils/salad oil, fuel oil, beverage, watersolutions or for fuel and fuel con-sumption. They are especially idealfor washing maschines and dishwashers, coffee machines, lasercooling plants, solar plants, backeryand steam cooking machines inlarge kitchen plants or CD cleaning.
55
17
32.1
ca.
51.5
Specifications
Type 1000 2F 66
Measuring range l/min 0,1 2,5
K factor PPL* 18.500Size DN (mm) 5* PPL = pulses / liter
Pressure drop in bars for water
Type 1000 2F 66
0,5 l/min 0,021 l/min 0,051,5 l/min 0,152,5 l/min 0,25
Technical data
Material Trogamid (PA 12)Viscosity range 0,8 16 mm2/sec
Accuracy 3 % of valueRepeatability < 0,50 %Te mp er at ur e ra ng e - 20 C u p to + 10 0 CO pe ra ti ng pr es su re M ax . 2 5 b ar sBurst pressure 200 barsElectrical connection Electr ical connector EN 60529Power supply 5 24 VDCC ur re nt co ns um pt io n C a. 8 mAO ut pu t s ig na l O pe n c ol le ct or N PN p ul seP ul l- do wn re si st or 1 2, 2 k Oh msProcess connections G 1/4, NPT 1 /4
Technical data
Material Grilamid TR 55 (PA 12)Viscosity range 0,8 16 mm2/sec
Accuracy 3 % of valueRepeatability < 0,50 %Te mp er at ur e ra ng e - 20 C u p to + 10 0 CO pe ra ti ng pr es su re M ax . 2 5 b ar sBurst pressure 200 barsElectr ical connection Electr ical connector EN 60529
or cable connectionPower supply 5 24 VDCC ur re nt co ns um pt io n C a. 8 mAO ut pu t s ig na l O pe n c ol le ct or N PN p ul seP ul l- do wn re si st or 1 2, 2 k Oh msProcess connections G 3 /8 , NPT 3 /8 , O-r ing
Specifications
Type 2006 4F 44 2006 2F 66 2008 4F 16,5 2008 4F 23 2008 4F 44 2008 2F 66
Measuring range l/min 1 10 0,5 5 2 35 1,5 25 1 15 0,5 7,5
K factor PPL* 3300 6900 700 1000 2200 4600Size DN (mm) 6 6 8 8 8 8* PPL = puls es / liter
Pressure drop in bars for water
Type 2006 4F 44 2006 2F 66 2008 4F 16,5 2008 4F 23 2008 4F 44 2008 2F 66
0,5 l/min 1 l/min ~ 0 ~ 0 ~ 0 ~ 0 ~ 0 ~ 01,5 l/min 2 l/min 0,06 ~ 0 ~ 0 ~ 0 0,05 ~ 05 l/min 0,2 0,12 ~ 0 0,05 0,2 0,0510 l/min 0,7 0,4 ~ 0,12 0,17 0,4 0,215 l/min 0,9 ~ 0,25 0,27 0,420 l/min 1,3 ~ 0,45 0,48 0,725 l/min ~ 0,60 0,65 30 l/min ~ 0,92 0,97
-
8/10/2019 Flow Measurement and Control
12/43
The meters for a great variety
ofindustrial fluids
22 23
Nutating disc meters
Nutating disc metersNutating disc meters are best suited to measure flow and volume of low and
medium viscosity fluids.
Measuring principle
Nutating disc meters are positive displacement meters. The top and lower part of the meterchamber are cone shaped. A ball bearing centralizes the disc between the two cones.A nutating motion of the disc is generated when flow enters the meter chamber. Completeseparation between inlet and outlet chamber volumes is always achieved by one dedicateddisc diameter line. The inlet and outlet parts of the meter chamber are separated by a partitionplate. The positioning bar forces the disc to nutate around the center axis of the chamber,driving the transmission magnet.
-
8/10/2019 Flow Measurement and Control
13/43
24 25
The Recordallseries is a positivedisplacement meter. The series isbest suited for metering fluids up toa viscosity of 700 mPas and at anoperating temperature of 50 C upto 120 C.
Typical applications are: Clean andmoderately dirty liquids, hard andsoft water, oils, fuel, solvents, etc.
Recordallfluid meterfor clean and moderately dirty fluids
Magnetic coupling
Compatible with manyliquids
Wide flow range
Low pressure loss
Light weight
Nutating disc meters
The metering chamber includesdisc, positioning bar and trans-mission magnet. The chamber isinserted into the meter body.A screen in the inlet side of thebody protects the chamber againstpenetration of larger solid particles.
The meter system is modularand enables the combination ofmechanical or electronic displayswith any meter size.
Dimensions
Plastic modelDimensions
Bronze model
RCDL M 25 for AdBlue
see page 26
L
A
B
H2
A
L
H1
B
Technical data
Type M 25 M 35 M 40 M 70 M 120 M 170
Plastic Bronze Stainlesssteel
Bronze Plastic Stainlesssteel
Bronze Bronze Bronze
Nickel coated Nickel coated Nickel coated Nickel coated Nickel coated
Size DN 15, 20 15, 20 20 20 25 25 25 40 50
Nominal pressure PN 16 16 16 16 16 16 16 16 16Max. temperature (PPO) 50 C 50 C 50 C 50 C 50 C 50 C 50 C 50 C 50 CMax. temperature (Vectra) 120 C 120 C 120 C 120 C Flow range l/min (PPO) 1 100 1 100 1 100 2 132 2 160 2 160 4 265 8 454 8 643Flow range l/min (Vectra) 3 100 3 100 19 265 18 454 Accuracy (1:10) 0,5 % 0,5 % 0,5 % 0,5 % 0,5 % 0,5 % 0,5 % 0,5 % 0,5 %Accuracy (total range) 1,5 % 1,5 % 1,5 % 1,5 % 1,5 % 1,5 % 1,5 % 1,5 % 1,5 %Weight 1,2 kg 1,8 kg 5,8 kg 2,7 kg 1,8 kg 7 kg 5,5 kg 10,5 kg 13,6 kg
Materials
Type M 25 M 35 M 40 M 70 M 120 M 170Housing Nylon Bronze Stainl. steel
1.4571Bronze Polycarbo-
nateStainl. steel1.4571
Bronze Bronze Bronze
Nickel coated Nickel coated Nickel coated Nickel coated Nickel coated
Measuring chamber PPO / Vectra PPO / Vectra PPO / Vectra PPO PPO PPO PPO / Vectra PPO / Vectra PPOO-rings Buna / Viton Buna / Viton Buna / Viton Buna Buna Buna Buna / Viton Buna / Viton BunaRetainer strap (PPO) NylonRetainer strap (Vectra) Stainless steel 316 / 316 S/SScreen PPOBottom (PPO) Nylon Cast iron Stainl. steel Cast iron Polycarbonate Stainl. steel Cast iron Cast iron Cast iron
C Nickel coat. C Nickel coat. C Nickel coat. C Nickel coat. C Nickel coat.Bottom (Vectra) Bronze Stainl. steel Stainl. steel Bronze Bronze
B Nickel coat. B Nickel coat. B Nickel coat. B Nickel coat. B Nickel coat.Retainer ring Nylon Polycarbonate Magnet Barium/FerriteCrossbar NylonThrust roller NylonRoller insert Stainless steel 316 / 316 S/S
Dimensions (mm)
Type M 25 M 35 M 40 M 70 M 120 M 170
Plastic Bronze Stainlesssteel
Bronze Plastic Stainlesssteel
Bronze Bronze BronzeNickel coated Nickel coated Nickel coated Nickel coated Nickel coated
Connection A R 3/4, 1 R 3/4, 1 R 1 R 1 R 1 1/4 R 1 1/4 R 1 1/4 1 1/2 NPT 2 NPTLay length L 190 190 190 230 270 230 270 321 387Width B 122 122 110 133 151 135 184 223 240Height register H 1 125 125 130 132 150 130 165 178 204Height transmitter H 2 128 128 155 168 180 160 200 213 239
-
8/10/2019 Flow Measurement and Control
14/43
26 27
Nutating disc meters / Oval gear meters
Meters for AdBlueand aggressive media Batch systems
PC 100
High quality batch system for allbatch applications
ER-10
Totalizer, reversible t o flow
display with pulse output
CUB 5
Multifunction register with
two counters and flow displays
F 110
Totalizer, from easy display up tobatch controller
The ultra pure 32,5 % urea solution, also known underthe name of AdBlue, is the basis for the reduction oftoxic nitric oxides in exhaust gases from diesel oper-ated goods vehicles.AdBlueis made synthetically. The high purity andquality are DIN V 70070 certified.AdBluecan be metered with a plastic Recordall RCDL M 25 or M 40. All Badger Meter registers can be
mounted on the meters.
Magnetic coupling
Rugged construction
Light weight
Modular series
RCDL M 25, in-line meter LM OG-I-PVC, pulse transmitter LM OG-TI-PVC
Technical data
Type RCDL M25 LM OG-I-PVC LM OG-TI-PVC
Connection R 3/4, R1 1/2 BSPP 1/2 BSPPMax. operating pressure 16 bars 10 bars 10 barsFlow range 1 100 l/min 0,5 35 l/min 0,5 35 l/minTemperature range 50 C -10 C to +50 C -10 C to +50 CAccuracy 1,5 % 0,5 % 0,5 %Viscosity range 1 2000 mPas up to 2000 mPasPulse per liter 100 ppl 100 pplLay length 190 mm 82 mm 82 mm
-
8/10/2019 Flow Measurement and Control
15/43
Measuring principle
28 29
The meters forirrigation systems, building management
and the general industry
Impeller meters
Impeller meters
The series feature a six-bladed impeller design with a proprietary,non-magnetic sensing mechanism. The impeller shape coupled with theabsence of magnetic drag provides accuracy and repeatability throughoutthe flow range of the sensors. As the liquid flow turns the impeller,a low impedance square wave signal is transmitted with a frequencyproportional to the flow rate.
Impeller meters are a low cost alternative in irrigation systems (sprinklers, chemical injection
processes in water treatment, water management, etc.), in municipalities (fluoridation, pump
control, etc.) in the energy management (HVAC, building management, energy consumption
monitoring, etc.) and in the general industry (batch processes for bakeries, adding color dye to
water for textile, food processing, inks, and other color additive mixtures, adding liquid vitamins
and nutrients to feed water for livestock, automatisation in the film industry, etc.).
-
8/10/2019 Flow Measurement and Control
16/43
30 31
Impeller meters
Flow sensorsa great versality
2 up to 48
Special models up to 120
Large temperature range and pressure rates
Bidirectional measurements possible
Very good price / performance ratio
Monitors and transmittersfor all flow sensor series
Universal
Energy monitoring systems
Batch controllers
Various output options
The series 2100 and 3000 areversatile flow monitors with alpha-numeric LC display. They can beconfigured by the user to displayactual flow, total flow or otherparameters like optional relaystatus.
The batch controller type 2200 ena-bles a large variety of flow batchprocesses which require volumetricor time based measurements.
Models 2300 and 3050 togetherwith flow sensors of series 200 orSDI series offer an excellent unitfor energy consumption monitoringin many buildings which are cen-trally controlled. HVAC processesin residential or large complexes aswell as big industrial processes canbe monitored.
All flow sensors can be combinedwith transmitters of the series 300and 500 thus enabling the connec-tion to overriding plotting systemslike SPS or simple monitors.
The series 200 flow sensor is an insertion style flowsensor constructed of metallic and non-metallicmaterials. These sensors are designed for service incorrosive and non-corrosive liquids. The series can beinstalled in pipe sizes of 3 up to 40 (special modelsup to 120) and includes a special potted version(IR models) for irrigation applications (enabling directmounting in the earth).
T-type sensors offer another model variation. Thesemodels have been designed for indoor or protectedarea applications such as HVAC, heat / energymonitoring, water cooling systems, pump control andindustrial process monitoring.
The 4000 series flow sensor is an inline, flow-throughdesign using a tangential six-bladed impeller. Theseries is available in 1/2, 3/4, 1 pipe sizes and ismolded of PVC or PVDF materials. The compact designallows the 4000 series be used in a wide range ofindustrial applications, among them the flow measure-ment of ultra pure water in the semiconductor industry.
The SDI series flow sensor offers unparalleled perfor-mance for liquid flow measurement in closed pipesystems. The impeller sensor is well suited for flowcontrol, flow monitoring and batch type applications.The flow meter can be mounted in pipe sizes of 1,5 upto 48. This sensor can be used for water applicationsor as stainless steel version for corrosive fluids at hightemperatures and pressure rates. Bidirectional flowmeasurement or battery driven systems are availableas option.
Technical data I: Flow sensors
Type 200 225 226 2 50 228 4000 SDI
Material
Brass X X X X XBronze XStainless steel X X X X XPVC X X XPVDF XPVCS XCarbon steel XMax. temperature in C 105 150 60 105 150 105 105 150 105 60 60 104 135 150Potted version(up to 66 C)
X X X X X X X X X
Max. pressure in bar
60 C / 3 bar X X7 bar / 20 C X7 bar / 25 C X7 bar / 38 C X9,5 bar / 150 C X11 bar / 150 C X12 bar / 38 C X14 bar / 38 C X17 bar / 150 C X X20 bar / 38 C X14 bar / 150 C X X22 bar / 150 C X X X24 bar / 22 C X19 bar / 18 C X27 bar / 38 C X X X X X41 bar / 60 C X68 bar / 150 C X
Technical data II: Flow sensors
Type 200 225 / 226 250 228 380 4000 SDI
PVC
Mounting in pipe sizes DN 80 1000 80 1200* 6 32 50 65 32 100 20 50 6 25 32 900**3 40 3 48 0,5 1,5 2 2,5 1,5 4 3/4 2 0,5 1 1,5 36
Flow range in m/s (standard) 0,15 9 0,15 9 0,1 4,5 0,15 9 0,1 4,5 0,6 6 0,1 6Flow range in m/s (low flow) 0,09 2,5Accuracy (full scale / Qmax.) 1 % 1 % 1 % v. M. 1 % 3 % < 1 % 1 %Accuracy (of reading) 4 % 4 %Repeatability (full scale / Qmax.) 0,3 % 0,3 % 0,7 % 0,3 % 0,5 % 0,5 % 0,5 %*Special models up to DN 3000 / 120 **or larger upon request
Technical data: Monitors
T yp e 2 10 0 Wall mounted / Control panel mounted
2200 Batch controller2300 BTU3000 Wall mounted / Control panel mounted3050 BTU
Can be extended with signal outputs.
Technical data: Transmitters
Ty pe 3 10 Analog output, programmable320 Pulse output, programmable330 Relay output, programmable340 BTU340 LW-LonWorks BTU340 N2 BTU340 BN BTU380 BTU
-
8/10/2019 Flow Measurement and Control
17/43
Ultrasonic flow metersMeasuring principle (transit time)
t 1/2 t 2/1
32 33
The meters for water andwastewater
and other fluids
Ultrasonic flow meters are best suited for flow measurement of fluids in pressure pipes as well
as in channels and semi-filled pipes.
Ultrasonic signals are alternately sent in and against the flow direction.Ultrasonic energy bursts are transmitted and received via well-definedpaths across the flow stream. The velocity of the flow is accuratelymeasured by the difference in the arrival times of signals from theupstream and downstream transducers.The transit time difference (t = t 2/1 t 1/2) determines the averageflow velocity.
Ultrasonic flow meters
-
8/10/2019 Flow Measurement and Control
18/43
34 35
Ultrasonic flow meters
Type DFX, TFX Ultra, TFXL and Fusion Type DXN and UFXStationary devices for flow metering in full pipes Portable units for flow measurement in full pipes
Flexible to use
Non-intrusive metering
Long lifetime
Quick and easy installation
Non-contact measurement
Battery powered
Clamp-on sensors
Technical dataModel DFX (Doppler) TFX Ultra TFXL Fusion (Doppler/transit time)
L iqu id t ypes F luids wit h a min imum o f 100 ppm*useful suspended sound reflectorsgreater than 35 microns, and atleast 25 % of the total particlevolume is greater than 100 microns
Most clean liquids or liquids withsmall amounts of suspended solids
Most clean liquids or liquids withsmall amounts of suspended solids
Clear, solids-bearing or gaseousliquids
Pipe sizes DN 6 and higher DN 15 to DN 3000 DN 15 to DN 3000 DN 15 to DN 50Accuracy 2 % full scale 1 % of reading resp. 0.003 m/s 1 % 1 %Power supp ly 115/100/230 VAC 50/60 Hz 15 %
@ 17 VA max.;12 28 VDC @ 7 VA max.
AC: 95 264 VAC 47 63 Hz @17 VA max. resp. 20 28 VAC47 63 Hz @ 0,35 A max.DC: 10 28 VDC @ 5 W max.
11 28 VDC @ 0.25 A 12 30 VDC @ 0.1 A max.
Ambientconditions
-40 C to +85 C, 0 to 95 % rel.humidity (non-condensing)
-40 C to +85 C -40 C to +85 C -29 C to +85 C aluminium-29 C to +204 C stainless steel
Velocity range 0,05 to 9 m/s Bi directional 0,03 bis 12 m/s 0,03 to 12 m/s Bi directional 0,03 to 12 m/sDisplay Two line LCD, LED backlit Two line LCD, LED backlit Two line LCD, LED backlit Two line LCD, LED backlit*ppm = Particel per million
Type DXN is a fully portable flow and energy hybridmeter with clamp-on sensors, touch screen interfaceenabling quick and easy operation switching auto-matically between the most appropriate measuringprinciple (Hybrid, transit time and Doppler operation).The DXN benefits from an integrated data logger and isideal for the non invasive flow measurement of clean,solids bearing or gaseous liquids in closed pipes.
Technical data
Model DXN (hybrid) UFX (handheld)
Li quid types Liqu id dom inant flu ids 100 ppm * of 100 mi cron siz e s uspende dsolids or entraind gases
Accuracy 1 % of reading 2 % of full scale
R ep ea ta bi li ty 0, 1 % of re ad in gPower supp ly Int er na l 11,1 V l i th ium-Ion ba tt er y,
69 hrs of continous operation withbattery and indefinitely on externalpower.
Battery powered; non-rechargeablealkaline cells (four AAA cells), providinggreater than 30 hours of continuousoperation.
Ambient conditions -20 C to +45 C-30 C to +60 C
-20 C to +60 C
Sensor type Clamp-on Clamp-onVelocity Bi directional 0.0312 m/s 0,1 to 9 m/sDisplay Touch screen One line LCDUnits Engineering units:
meter, m, liter, million-liter, kg, feet,gallons, ft, million-gal, barrels (Liquids& oil), acre-feet, lbs,Flow units: second, minute, hour, day
l/min, m/h, gal/min, barrel per day
E nc lo su re Wa te r- /d us t r es is ta nt ( IP 6 4) N EM A 4 ( IP 6 5) A BS p la st ic ; 0 ,7 k gDimens ions 240 mm W x 197,6 mm H x 95 ,7 mm D 101 ,6 mm W x 195,6 mm H x 43 ,2 mm D* ppm = Particels per million
Sensoren DXN
Pipe size DN 15 DN 3000Enclosure
DTTSU CPVC, Ultemand anodizedaluminum track system
Connection Nickel-plated brass withTeflon insulation
DTTN / DTTL / DT94 Doppler CPVC, Ultem
Connection Nickel-plated brass withTeflon insulation
Pipe surface termperature
DTTSU / DTTN / DTTL -40 C to +120 CDT94 Doppler -40 C to +120 CSensor frequency
DTTSU 2 MHzDTTN 1 MHzDTTL 500 kHzDT94 Doppler 625 kHz
The ultrasonic flow meter series Dynasonicsdepending on the model uses the Doppler or transittime method. Applications can be found in waterand wastewater treatment, oil and gas applications,methane extraction and underground coal gasification,power generation, cooling in semiconductor processesand in HVAC cooling and heating systems. The ruggedconstruction ensures long life, even under extremeambient conditions.Type DFX is a Doppler fluid f low meter with clamp-onultrasonic sensors for use in fixed installations.
Type TFX Ultra is a liquid flow and energy meter foruse on many liquids and HVAC applications includinghot and cold water.Type TFXL is a low cost fixed liquid flow meter solutionthat can be clamped-on the outside of a pipe and doesnot need any maintenance.Type Fusion is a hybrid device which automaticallyswitches between Doppler and transit time methodsto adapt the measurement to the liquid compositionfrom clean to inpure/aerated. The device is ideal foruse in fixed installations with clean, solids-bearing orgaseous liquids.
Type UFX, a small, lightweight, battery powerd unit,used for checking the flow in metal or synthetic pipes.
TFX Ultra UFX
DFX
DXN
TFXL
Fusion
-
8/10/2019 Flow Measurement and Control
19/43
36 37
Ultrasonic flow meters
Type MultySonic 8000for flow measurement in open channels, fullfilled or partially filled pipes and channels,rivers up to 50 m width
Maintainance-free
Recording backflow and back up
No culverts required
Ex-approved
High accuracy
For channels from 0,2 to 50 m wide
For different channel profiles
Easy software updates via USB
Remote control via internet
The ultrasonic flow meter MultySonic 8000 has beenespecially designed for flow measurement of fluids inpipes (semi- or fullfilled pipes), rivers and streams witha width of 0.2 m 50 m.Measurements can take place in pressure pipes up to100 bars and under highly variable levels. A varietyof sensor forms and materials permit use under heavy
mechanical load and in aggressive media with pHvalues from 3.5 to 10.
Accuracy
Accuracies
Inflow path >10 D
-
8/10/2019 Flow Measurement and Control
20/43
38 39
Ultrasonic flow meters
Type iSonic 2000, DataControl 2500 and L2 xxfor flow and level measurement in open channels, semi-filled pipes, tanks/reservoirsand stormwater overflow basins
Flow / Quantity
Level and volumemeasurement
Differential measurement
Pump monitoring
Data collection
High accuracy
Manhole flume
Weirs an d flumes
The iSonic 2000 is a versatile ultrasonic flow meter.The microprocessor-based meter was designed tomeasure levels/volumes in tanks or flows in open chan-nels in combination with venturi channels, manholeflumes or effluent weirs.
The meter works according t o the Echolot principle,which means that a free outlet in the channel/pipeis required for this measuring principle. Some Q/Hrelations are already stored in the memory. A 35 point
graph can be programmed for unknown Q/H conver-sions.
When 2 sensors are in operation, the meter can beused for 2 channel measurements with separated total-izers or for differential measurement. The configurationof the flow meter is done via the front keypad or a PC.A data logger is integrated for recording measuringdata. The memory has a capacity of approx. 44 000records.
The DataControl 2500 is an evaluation device whichcan be connected to further equipments with analogor digital outputs. It is used for applications as alreadydescribed for iSonic 2000. The features and functionsare also similar to the iSonic 2000.
The L2 xx series is a 2-wire ultrasonic level sensordesigned for continuous level measurement of liquidsor viscous fluids. The maximum flow ranges are 6, 8, 10and 15 meters depending on type at a bloc distance of250 mm.
Technical data: Sensors L2 xx
Type L2 08 L2 10 L2 15
Range 0,3 8,00 m 0,4 10,00 m 0,5 15,00 mCurrent output 4 20 mAAccuracy 0,25 % of maximum spanResolution 3 mmPoint setting With magnetic keyBeam angle 11Operating temperature -20 C bis 60 C
The sensor has internal temperature compensationEnclosure rating IP 68Housing ABS / Tefzel,
UV resistantABS / PVC,
UV resistantABS / PVC,
UV resistantSupp ly vo lt age 17 V to 30 VDC (max. ) , 24 VDC t ypical ope ra ting vol tageApprovals EEx ia II C T6
V-Weir
The weirs are calculated by us.Various shapes possible.
Parshall flume
available from DN 75 (Qmax54 l/s) toDN 915 (Qmax1577 l/s).
Manhole flume
available from DN 100 (Qmax5,7 l/s) toDN 300 (Qmax94,4 l/s).
Technical data: Type iSonic 2000 (2-channel measurement)
H ou si ng m at er ia l P la st ic , U V- re si st an tD im en si on s H x L x W 2 40 x 2 70 x 7 6 m mProtection class IP 65Operating temperature range -20 C to +60 COutputs 2 analog outputs 4 20 mA or 0 5 V, isolated
5 relays, max. 250 VAC / 6 A2 digital outputs max. 80 VDC / 30 mARS 232 or RS 485Voltage output 24 VDC / 50 mA and 12 VDC
Inputs 2 analog inputs 4 20 mA, isolated4 digital inputs 1,3 VDC / 2 mA, optically separated
Disp lay f unction 8 -l ines f or l eve l, fl ow r at e, to ta l, vo lume anddistance
D is pl ay la ng ua ge E ng li sh , G er ma n, Sp an is h, Fr en chS upply vol tage 90 230 VAC or 12 14 V DCP ro gr am mi ng V ia f ro nt k ey pa d o r P C w it h s of tw ar e ( pa ss wo rd
protected)Measuring accuracy BAT 78 L 1,2 mm
BAT 52 L 4 mmBAT 35 L 24 mmBAT 85 2 mm
D at a l og ge r 2 M B f la sh , p ro gr am ma bl e t im e i nt er va ls ,Capacity for approx. 44 000 records,Records available as table or graphics
Technical data: Type DataControl 2500 (4-channel measurement)
H ou si ng m at er ia l P la st ic , U V- re si st an tD im en si on s H x L x W 2 40 x 2 70 x 7 6 m mProtection class IP 65Operating temperature range -20 C to +60 COutputs 2 analog outputs 4 20 mA or 0 5 V, isolated
2 digital outputs max. 80 VDC / 30 mA6 relays, max. 250 VAC / 6 ARS 232 or RS 485Voltage output 24 VDC / 50 mA and 12 VDC
Inputs 4 analog inputs 4 20 mA, isolated4 digital inputs 1,3 VDC / 2 mA, optically separated
Disp lay f unct ion 8 -l ines fo r l eve l , f l ow r at e, t ot al , vo lume , d i st ance,temperature, pH or pressure
D is pl ay la ng ua ge E ng li sh , G er ma n, Sp an is h, Fr en chSupply voltage 90 230 VAC / 10 WP ro gr am mi ng V ia f ro nt k ey pa d o r P C w it h s of tw ar e
(password protected)Data logger
2 MB flash, programmable time intervals,Capacity for approx. 44 000 records,Table and graphics
Technical data: Sensors for iSonic 2000
Type BAT 78 L BAT 52 L BAT 35 L BAT 85
Measuring range 4 m 8 m 16 m 3 mOffset 0,15 m 0,2 m 0,2 m 0,15 mBeam angle 7 8 9 3Temperature compensation IntegratedCable lengths Max. 1000 mProtection class IP 68
-
8/10/2019 Flow Measurement and Control
21/43
Measuring principle
40 41
Heat meters
Heat metersand accessories
The meters for
heat energy
Heat meters are used in building management, the chemical and petrochemical industry and in
the food and beverage industry to measure the h eat/cold quantity.
Vt1 t2
Ultrasonicsensor
Signal cable Converter 4 to 20 mA/pulse
USB interface
The heat meters use the highly precise ultrasonictransit-time measuring principle, for which twoultrasonic sensors are externally mounted on thepipeline and connected to the electronic. The ultrasonicsensors work alternately as transmitter and receiver,and mutually send ultrasonic signals. During thesetransmissions, the respective signal transit times of theto-and-from signals (t1, t2) are measured.
The electronic measures the difference of the transittime of the ultrasonic signals going with and againstthe flow direction t1and t2. These signals are eitherdecelerated or accelerated by the medium flow.The difference produced in both signal transit times isproportional to the flow rate and is used together withthe pipeline geometry for a precise flow calculation.
-
8/10/2019 Flow Measurement and Control
22/43
42 43
Heat meters
Type DXN, TFX Ultraand Btu 380Stationary and mobile devices
Ultrasonic or impellertechnology
Accessories
GSM / GPRSfor wireless data recording
Wireless m easuring sites
Access via internetindependently from location
Ideal for measuring sites indifficult areas
Technical data
Model DXN TFX Ultra Btu 380
Pipe size DN 50 DN 3000 DN 50 DN 3000 DN 20 DN 50Accuracy 1 % of reading 1 % 3 % of full scaleRepeatability 0,1 % of reading 0,5 % of reading 5 %Vo lt ag e i np ut 1 5- pi n h ig h d en si ty D SU B
0 5 V or 0 10 V, 1 % accuracy2x RTDs PT1000 tab type;-85 C to +300 C measurement range420 mA active/passive 1 % accuracyRate pulse: 0 to 1000Hz
USB 2.0RS 485 ModBusRTU, BACnetMS/TP(optional)10/100 Base-T: RJ 45, Communicationvia ModBusTCP/IP, EtherNet/IP orBACnet/IP
ModBusRTUBACnetMSTP
Voltage output 0 5 V or 0 10 V output voltage,1 % accuracy
Total pulse option:Opto isolated open collector transistor
Scaled pulses
E ne rg y s up pl y I nt er na l 1 1, 1 V li th iu m- Io n b at te ry ,6 9 hrs of continous operation withbattery and indefinitely on externalpower
AC: 95264 VAC 4763 Hz @ 17 VA max.bzw. 2028 VAC 4763 Hz @ 0,35 A max.DC: 1028 VDC @ 5 W max.
1235 VDC1228 VAC
Temperature
Unit
SensorsDTTSU / DTTN / DTTLDT94 Doppler
-20 C to +45 C-30 C to +60 C
-40 C to +120 C
-40 C to +85 C -20 C to +60 C (cold water modelBTU 380 CS)+4 C to +125 C (warm watermodel BTU 380 HS)
S en so r t yp e R TD ; 2 x p la ti n 3 85 , 1 00 0 o hm s, 3- wi rePVC cable jacket
RTD; platin 385, 1000 ohms, 3-wirePVC cable jacket
RTD
Velocity 0,03 to 12 m/s, bi directional > 12 m/s, bi directional 0,3 to 4,5 m/sDisplay Touch screen Two line LCD, LED backlitUnits BT U, wa tt, j oule, kil ow att B TU, MB TU, MMB TU , to ns, kJ, kW, MW kB TU /m in , k BTU /h, k W, M W, H P,
tons, customer definedEnclos ure Water/ dust resi stent (IP 64) Typ e 4 (IP 65 ): powd er coa ted alum inium ,
polycarbonate, stainless steell,polyurethane, nickle plated steelmounted brackets
Polycarbonate
DXN TFX Ultra Btu 380
For measurement of energy different measurementprinciples can be used.
The impeller model Btu 380 is used for simple in-lineoperations. Type Btu 380 provides BACnet MSTP andModBusRTU protocols as standard. The chosen pro-tocol can be user defined. Data about flow rates, totalrange, energy, total flow, temperature 1, temperature 2and t can be transmitted with the RS 485.
The ultrasonic energy meters type DXN and TFX Ultracan be clamped-on outside of the pipe and do notcontact the liquid. The energy flow meter measuresenergy usage in BTU, MBTU, MMBTU, tonns, kJ, kW,kWh, MW and is ideal for retrofit liquid and HVACapplications.
For consumption monitoring and leckage reduction inwater supply systems, precise flow measurement inlarge channels and rivers for the monitoring of naviga-bility and issue of f looding forecasts, or monitoring andalarm of overflow basins for rainwater, sewage plants,storm water overflow plants as well as for the controlof irrigation plants or level monitoring, alarm for auto-matical filling and connection to the supplying system,Badger Meter offers the possibility to record wirelessthe measuring data coming from flow meters.
Those data are transmitted to and filed on a centralserver via a GPRS module. The information can beretrieved, visualised, evaluated and downloaded via apassword protected access; the password is set by thecustomer.
The module is compatible with the following Badger
Meter series: MAG meters, RCDL , turbine meters,oval gear meters, impeller meters, ultrasonic flowmeters and Coriolis mass meters.
-
8/10/2019 Flow Measurement and Control
23/43
Measuring principle
The meters for liquids
with middle and high viscosity
As fluid passes through the metering chamber by entering the inlet port,it forces the internal gears to rotate and exits through the outlet port.Each rotation of the gear displaces a given volume of fluid. Controlledclearances between the gears and chamber wall insure minimum leakage.As the gears rotate, a magnet on each end of the gear activates thereedswitch and forward the pulses to the display or to the pulse output.
Oval gear meters
44 45
Oval gear meters
Oval gear meters are volumetric meters and are best suited for liquids with a viscosity
up to 5.000 mPas. (special models up to 1.000.000 mPas.). Typical applications are mineral
oils, hydraulic oils, solvents, brake fluids, coolants, transmission oils, etc.
Eichdirektion Stuttgart des Landes-gewerbeamts Baden-Wrttemberg
Physikalisch-Technische Bundes-anstalt Braunschweig und Berlin
TV Cert-Zertifizierungstelle derTV Management Service GmbH
National Weights andMeasures Laboratory
International Organizationof Legal Metrology
Asanet Cesky Metrologicky Institut
Bundesamt fr Eich- und Ver-messungswesen sterreich
-
8/10/2019 Flow Measurement and Control
24/43
46 47
IOGseries IOGseriesfor industrial applications for industrial applications
Combinable with allelectronics and displaysof the F-series
ATEX model
Various materialcombinations
High pressure andtemperatur e rates
Leakproof, magnetic drive
Only two moving parts toreduce maintenance costs
Oval gear meters
The IOGseries is made of modular meters witheconomical yet highly accurate and rugged design. Dueto the rugged nature of this particular flow measure-ment technology, the meters can be used in a numberof applications where conventional meters are notacceptable.
High accuracy andrepeatability
Flow ranges from 168 l/m
Vertical or horizontalinstallation
Low pressure drop
Minimum of wearable partsfor long product life
Optional adjustment of laylengthes
ATEX approval
Technical data
1 /4 ( l/ h) 1 /2 ( l/ mi n) 3 /4 ( l/ mi n) 1 ( l/ mi n) 1 H F ( l/ mi n) 1 ( l/ mi n) 2 ( l/ mi n) 3 ( l/ mi n)
Flow range 2,8-100 5,7-100 15-500 26,5-500 1-30 2-25 2-60 4,5-53 2,3-68 5,3-60 5,7-170 9,5-150 9,5-246 9,5-227 15-360 15-303 19-738 45-700V is co si ty ( cP ) > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0 > 5 ,0 < 5 ,0
Max. 1000 mPas. Consult factory for applications where a higher viscosity is required.A cc ur ac y ( %) 1, 0 2, 5 1, 0 2 ,5 0 ,5 2, 0 0, 5 2, 0 0, 5 2, 0 0, 5 1, 0 0, 5 1, 0 0, 5 1, 0 0, 5 1, 0Repeatability 0,03 %Pulses per liter 2170 390 100 66 43 17 9 3Operating temperature
Stainless steel -30 C up to +120 CAluminium/PPS/LCP
-30 C up to +80 C
Presure ratingNPT/BSP 10/55 bar 55 bar (800 psi) 200 bar (SS)
135 bar (Alu)135 bar (SS)100 bar (Alu)
100 bar (SS)68 bar (Alu)
68 bar (SS)50 bar (Alu)
Flanged model 150 lbs 285 psi (Alu, SS) 300 lbs 740 psi (SS) DIN PN 16, 16 bar
Please consult factory for higher pressure rates.Housing/connections
Aluminium NPT, BSP NPT, BSP, 150#, 300#, PN 16Stainless steel NPT, BSP NPT, BSP, 150#, 300#, PN 16Materials
Housing Stainless steel / AluminiumCover Stainless steel / AluminiumRotors Stainless steel Stainless steel or LCP (plastic) Stainless steelO-ring Buna-N/Viton/EPDM/A flas Standard: Stainless steel, Aflas,
Aluminium, VitonOptional: Buna, EPDM, Aflas, Viton
Aflas/Viton
The meters handle very viscous or highly corrosivefluids. They have been designed for a variety of chemi-cal applications including petroleum based fluids,water solutions, and any other liquid compatible withthe materials of construction.
Technical data type LM OG-I / LM OG-I PVC / LM OG-I stainless steel
Coolant /windshield liquid*
Brake fluid /waste oil**
LM OG-I HF 3 /4 LM OG-I HF 1
Flow range* 0,5 35 l/min 0,5 35 l/min 3 60 l/min 3 115 l/minOperating pressure 10/100 bars 100 bars up to 100 bars up to 100 barsOperating temperature -10 to +60 C -20 to +45 C -10 to +60/120 C -10 to +60/120 C
Accuracy (non-approved version) 1,0 % 0,5 % 0,5 % 0,5 %Weight without handle 1,0 kg / 1,4 kg 1,0 kg / 1,4 kg 0,8 kg 0,8 kg5-digit LCD display,5/16 high (8 mm)
Liters / Pints /Quarts / Gallons
Liters / Pints /Quarts / Gallons
Liters / Pints /Quarts / Gallons
Liters / Pints /Quarts / Gallons
Inlet and outlet connections 1/2 BSPP 1/2 BSPP 3/4 BSP 1 BSPHousing Alu / PVC / St. steel Alu / PVC / St. steel Alu / Stainless steel Alu / Stainless steelOval gears Delrin / Vectra /
Stainless steelDelrin / Vectra /Stainless steel
Vect ra / St . s teel Vect ra / St . s teel
*Tested with water at ambient temperature.**Tested with Mobil DTE-25 motor oil at ambient temperature. Min./max. flow rates will vary with fluid viscosity.
Technical data
Type LM OG-TI 100 LM OG-TI 100 PVC LM OG-TI HF 3/4 LM OG-TI HF 1
Flow range 0,5 35 l/min 0,5 35 l/min 3 60 l/min 3 115 l/minOperating pressure 0,35 100 bars 0,30 10 bars up to 100 bars up to 100 barsOperating temperature -10 to +60 C -10 to +45 C -10 to +60 C -10 to +60 CAccuracy 0,75 % 0,5 % 0,75 % 0,75 %Pulse rate 100 pulses/liter 100 pulses/liter 66,75 pulses/liter 66,75 pulses/literMax. reedswi tch r es i st ance 150 VAC @ 10 Watt 150 VAC @ 10 W at t 150 VAC @ 10 Watt 150 VAC @ 10 WattWeight 0,9 kg 0,9 kg 0,7 kg 0,7 kgInlet and outlet connections 1/2 BSPP 1/2 BSPP 3/4 BSP 1 BSP
The LM OG-I meters of the IOGseries are coated meters and havebeen designed to measure flows upto 115 l/m.
They can dispense fuels, hydrocar-bons, water based fluids, motoroils, gear oils, coolants and othersimilar liquids, as well as specialand aggressive fluids.
-
8/10/2019 Flow Measurement and Control
25/43
Electronical metersfor high flow
48 49
Oval gear meters
Electronical metersfor lubricants, approved and non-approved
Rugged construction
Easy battery exchange
User friendly
Mechanical metersfor high viscous lubricants
Rugged construction
Reliable
Very large viscosity rangeLM OG-PND(A)
LM OG-CNDA LM OG-CND
LM OG-HF CND
LM OG-PNDK
LM 1800 PG-E
LM 1800 PG-B
LM 1800 PG-M
Outlet PG-1011
Metallic outlet 30 bent, antidrop,with adjusting nut
Low pressure loss
Rugged construction
Large flow range
High pressure rates up to100 bars
No wearing parts
Pistol grip PG-121
with 1/2 swivelSwivel PG-107
1/2 BSP inside, 1/2 BSP outsideSight glass PG-113 Outlet PG-114
Outlet 1/2, BSP, 90 flexible withswivel
LM OG-CNDA
MID approved
The electronical meters are ofmodular design. The electronicregister is controlled by wettedmagnets.Robustness, easy handling andmaintenance are features of themeter series.
Technical data
Type LM OG-CND(A) LM OG-PND(A)* LM OG-PNDK LM 1800 PG-E LM OG-CND LM OG-HF CND
Connection 1/2 BSP 1/2 BSP 1/2 BSP 1/2 BSP 1/2 BSP 3/4 BSPMax. operating pressure 100 bars 100 bars 100 bars 70 bars 100 bars 100 barsFlow range 1 35 l/min (1 10)* 1 30 l/min (1 10)* 1 30 l/min 1 15 l/min 1 35 l/min 3 60 l/minTemperature range -10 C to +50 C -5 C to +50 C -5 C to +50 C -5 C to +50 C -10 C to +50 C -10 C to +50 CAccuracy 0,5 % (0,3 )* 0,5 % (0,3 )* 0,5 % 0,5 % 0,5 % 0,5 %Viscosity range 20 2000 mPas up to 2000 mPas up to 2000 mPas up to 50.000 mPas up to 5000 mPas up to 5000 mPas
D is pl ay 5 -d ig it L CD di sp la y 5 -d ig it LC D d is pl ay ** 6 -d ig it LC D d is pl ay 6 -d ig it L CD d is pl ay 6 -d ig it L CD di sp la y 6 -d ig it L CD di sp la yC alibr ation can be cal ibrated can be cal ibrated c an be cal ibrated c an be cali brated ca n be c ali brated can be c alibra ted* Data in brackets are for approved versions.** Measuring units, free programmable: Liters, quarts, pints, gallons
Easy menu driven electronic, freelyprogrammable dispense quanti-ties, integrated memories, displayof flow and large grafic displaydefine the electronic preset metersof the LM OG-P series. The batterycan be exchanged very easily from
outside while saved data remainuntouched.This series is available as eitherapproved version or non approvedversion.
The hose end meters are used incombination with overhead hosereels in the automotive servicingindustry to dispense motor andautomatic transmission oils.The meters are best suited forthe measurement of high viscousmineral oils in non-custody transferapplications.
The High Flow meter seriesLM OG-HF has been designed tomeasure flows up to 115 l/min.The meters are modular, of ruggedconstruction and shockproof.
The electronic register is micro-processed and powered by aLithium battery. Measuring unitslike liters, pints, quarts or gallonscan be entered.
The meters are used to dispenselubricants in non-custody transfersin repair and service workshops.
Typical fluids metered are motoroils and automatic transmission oilsup to 5.000 mPas.
Technical data
Type LM OG-HF 1 LM OG-HF 3/4 LM OG-HF CND 3/4
Accuracy 0,5 % of flow 0,5 % of flow 0,5 % of flow
Flow range 3 115 l/min 3 60 l/min 3 60 l/minMax. operatingpressure
100 bars 100 bars 100 bars
Operating temperature -10 C to +60 C -10 C to +60 C -10 C to +60 C
Technical data
Type LM 1800 PG-B LM 1800 PG-M
Connection 1/2 BSP 1/2 BSPMax. operating pressure 70 bars 70 bars
Flow range 1 15 l/min 1 15 l/minTemperature range -10 C to +70 C -10 C to +70 CAccuracy 0,75 % 0,75 %Viscosity range 50 50.000 mPas 50 50.000 mPas
-
8/10/2019 Flow Measurement and Control
26/43
50 51
Oval gear meters
In-line metersApproved and non approved
High accuracy
Rugged construction
Pulse transmittersApproved and non approved
Rugged construction
LM OG-A LM OG-T 100
UH-M LM OG-TK 100
LM OG LM OG-TAER 200
LM OG-K LM OG-HFT
Technical data
Type LM OG-A LM OG LM OG-K UH-M
Connection 1/2 BSP 1/2 BSP 1/2 BSP 1/2 BSPMax. operating pressure 100 bars 100 bars 100 bars 70 barsFlow range 1 10 l/min 1 35 l/min 1 35 l/min 1 15 l/minTemperature range -10 C to +50 C -10 C to +50 C -10 C to +50 C -10 C to +70 CAccuracy 0,3 % 0,5 % 0,5 % 0,5 %Viscosity range 20 2000 mPas up to 5000 mPas up to 5000 mPas 50 50.000 mPasCalibration can be calibrated can be calibrated can be calibrated
The meters are of modular designand have been designed as inlinemeters and hose end meters forwall-mounting in oil lines.They are best suited for approvedand/or non-approved consumptionmeasurements of lubricants inrepair centers.Typical liquids measured are motoroil and automatic transmission oilup to 5.000 mPas.
The electronic register is controlledby wetted magnets. Robustness,easy handling and maintenance arefeatures of the meter series.The electronic unit is shockproofand insulated against oil.
The mechanical inline metertype UH-M is ideal for the use inextreme temperature conditions.This meter has a resettable total-izer 110 l and a non-resettabletotalizer, 5 digit register.
Technical data
Type LM OG-T 100 LM OG-TAER 200 LM OG-TK 100 LM OG-HFT 3/4 LM OG-HFT 1
Connection 1/2 BSP 1/2 BSP 1/2 BSP 3/4 BSP 1 BSPMax. operating pressure 100 bars 100 bars 100 bars 100 bars 100 barsFlow range 1 35 l/min 1 35 l/min (1 10)* 1 35 l/min 3 60 l/min 3 115 l/minTemperature range -10 C to +50 C -10 C to +50 C -10 C to +50 C -10 C to +60 C -10 C to +60 CAccuracy 0,5 % 0,3 % 0,5 % 0,5 % 0,5 %Viscosity range up to 5000 mPas 20 2000 mPas up to 5000 mPas up to 5000 mPas up to 5000 mPasPulses per liter 100 ppl 100 ppl per channel 100 ppl 66,75 ppl 66,75 pplCalibration can be calibrated * Data in brackets are for approved versions.
Type LM OG-TAER 200 is an in-linemeter for custody transfers withPTB approval for installation intoany management system.This meter can be calibrated andhas a two channels output (100 pplper channel, 90 offset).
Type LM OG-TK is best suited forfluids like brake fluids and othermedia.
Type LM OG-T 100 is an in-linemeter with pulse output.Registers are available with eitherone channel pulse output (100 ppl)or two channels pulse output(100 ppl per channel, 90 offset).
-
8/10/2019 Flow Measurement and Control
27/43
52 53
Variable area flow meters
Measuring principle
Variable area
flow measurement
The variable area flow measurement method allows fluids (liquids and gases) volume streamsto be determined. A moving sharp-edged orifice is located within the piston assembly, formingan annular opening with the contoured metering cone. The piston assembly carries a cylindri-cal PPS/ceramic magnet that is magnetically coupled to an eternal indicating magnet, whichmoves precisely in direct response to movement of the piston therefore providing a visualdisplay of the flow rate.
Variable area flow metersHedlandvariable area flow meters are the industry benchmark. This product line has grown to
over 15.000 flow meters constructed of aluminium, brass or stainless steel with variable meas-
uring area for liquids, oil, water, compressed air and many other fluids and gases.
Hedlandmeters are recommanded for use in machine cooling and lubrication, packaging,
semiconductor production, high pressure and hose applications, automotive and aviation
industry as well as in the mining industry.
-
8/10/2019 Flow Measurement and Control
28/43
54 55
Variable area flow meters
Type EZ-ViewLow cost meter for oil, water and other liquids
Rugged construction
Installation in any position
Shock and vibrationinsensitive
Instantaneous directreading
Technical data
Fluid Flow range
Water b ased fl uids 2 to 100 l/ minWater 2 to 380 l/minOil 10 to 380 l/min
The H-SeriesVariable area in-line flow meters
Rugged, durable construc-tion in a luminium, brass orstainless steel
Installation in any position
Available from to 2and 3
Direct reading
360 rotable guard scale
Technical data
Meter for fluids
Version 240/410 bar(3500/6000 psi)
Basicmodel
Test k it H ightemperature
Petroleum-based x x xPhosphat ester based x x xWater-based, water/oil x x xWater and other fluids x xOil, caustic and corrosivefluids
x
Meter for pneumatic applications
Version 70/100 bar(1000/1500 psi)
x
Version 41 bar (600 psi) x
Water Oil, petroleum
For high
temperature
Test kit oilTest kit water Test kit air and
compressed gases
Waterbased fluids Air and
compressed gases
Air, caustic and
corrosive gases
Air
The EZ-Viewvariable area flow meters are rugged,low-cost direct reading meters.They are simple toinstall in any orientation from vertical t o horizontal,upside down etc. without sacrificing measurementperformance. Flow straighteners, located in the inletand outlet, allow the flow meter to be less sensitivto turbulent flow conditions. Further straighteners orother special installation is not required.
Constructed of high impact PPSU, the EZ-Viewproductline offers excellent structural integrity and chemicalcompatibility with a wide range of industrial chemicals.
EZ-Viewflow meters provide instantaneous, direct-reading flow rate measurement of liquids in closedpiping systems. The transparent PPSU body allowsvisual inspection of the fluid condition as well asviewing of the internal flow indicator r elative to al cali-brated flow scale. EZ-Viewdoes not require electricalconnections.
The unique spring loaded design of this variable areaflow meter for common fluids reduces viscosity sensi-tivity. Variable area meters are in-line meters.
The Hedlandvariable area flow meters are the mostreadable products in their class to monitor a widerange of liquids, petroleum-based fluids, phosphateester liquids, water, water-based fluids or water/oil
emulsions. A pneumatic series is also available formetering air and compressed gases.All meters are available as basic flow meters, test kitsor for high temperatures, corrosive liquids and gases.
-
8/10/2019 Flow Measurement and Control
29/43
56 57
Flow transmitter Pressure meters / Pressure indicators
MR series and Flow-Alert switchFor fluids, air and compressed gases
Type Vista-Gage, Vista-Gage Vacuum,Vista-Cator, Vista-Monitor
High pressure, low pressure and vacuum pressure indicators, accumulator monitor
Mounting in any position
Automatically signalalarms
Rugged brass construction
Pressure range from0.8 to 345 bar
Temperature range from-40 C to +116 C
Mounting in any position
Vista-Monitor
accumulator monitor
Vista-Gage
Hi-Pressure Gage
Vista-Gage
Lo-Pressure Gage
Vista-Gage
Vacuum Gage
Vista-Cator
pressure indicator
The HedlandMR series can operate as part of atotally integrated electronic process control/dataacquisition system with digital flow rate and total flowindication and non-contact sensor electronic integra-tion. In-field compensation for specific gravity, viscos-ity, pressure and temperature of pneumatic system isalso available.
The Flow-Alert switch flow meters are rugged, long-term variable area flow meters for measurment of flowvolumes. This product provides a local flow indicationand automatically signals the operator or PLC if flow istoo high or too low.Special scales are available according to customersrequest. Flow-Alert flow meters are available insingle switch, double switch, reed switch and microswitch versions.There is no need for flow straighteners or special
piping requirements.
The Vista-Gage Hi-Pressure is a unique piston-typepressure indicator, specifically designed to withstandmachine vibration, shock, pulsation, pressure surgesand other rigorous conditions that create problems forconventional pressure gauges with fragile bourdontube mechanisms.The Vista-Gage is ideal for heavy duty constructionvehicles and other off-the-road-mobile equipment,as well as hazardous industrial applications, such asinjection molding or die casting operations.
Vista-Gage is easy and less costly to install. It canoperate in any position, from vertical to horizontal.The cylindrical pressure indicator scale provides full360 readability. There is no need for snubbers, needlevalves, isolator valves or other costly components toprotect the gage.
Vista-Gage Lo-pressure offers the same ruggedfeatures and operation reliability of the high pressureVista-Gage, with the added safeguard of a built-inBuna-N diaphragm seal to eliminate even the smallestpossibility of a leak. The low pressure gage is availablewith pressure range from 0.83 to 6.9 bar.
VistaGage Vacuum ist designed to monitor vacuumpumps and other process system components invacuum ranges. This unique gage is able to withstandpulsations and surges well beyond its rated capac-ity, without damage. The built-in EPMdiaphragmseal eliminates the risk of leaks, making it ideal forindustrial-class vacuum system applications.
Vista-Cator is a simple GO/NO-GO pressure indicator,with a broadband tri-color scale, designed to function
as an emergency warning device in applications that donot require a precise indication of minor fluctuation inoperating pressure.
Vista-Monitor is a permanent accumulator monitor,operating with liquids or gases in a pressure range of1.4 to 207 bar and temperature range of -40 C to+116 C. Vista-Monitor is designed with a ruggedconstruction. It withstands shock, vibration and over-pressurization. Easy to install and maintaining.
-
8/10/2019 Flow Measurement and Control
30/43
58 59
Vortex meters
Measuring principle
Highly precise meters for gas, digester gas, liquids and air
in Wafer-,insertion- and in-line style
Vortex metersRacinevortex flow meters utilize ultrasonic sensing technology, allowing the meters to
perform with an extremely small bluff body. As a result, system pressure drop and meter turn-
down ratio are greatly improved. The meters benefit from a wide measuring range (up to 70:1)
and high accuracy (1 % of reading). By using intelligent electronic and HARTcommunications
Racinevortex meters are ideal for process engineering systems and refinery. The unit does not
use moving parts and requires little or no maintenance.
Flow Transmitting transducer
Receiving transducerShed vorticesSmall strut
Within the flow meter as flowing media moves across the strut or bluffbar vortices are also shed, but on a smaller scale. The meter transmitsan ultrasonic beam through the vortex pattern downstream of the strut.As vortices are shed, the carrier wave of the ultrasonic signal modulates.The modulation of the carrier wave is measurable and proportional to thenumber of vortices shed. Digital processing enables the vortices to becounted, and this value is converted into a velocity.
-
8/10/2019 Flow Measurement and Control
31/43
60 61
Vortex meters
Type RWG & RWBG, RNG insertion and RNL in-lineWafer gas meters, insertion meters, in-line meters in stainless steel
High accuracy
Low pressure drop
HARTcommunicationprotocol
For corrosive fluids
High accuracy
No moving parts
RVL seriesIn-line and wafer liquid meters / thermoplastic
Technical data
Model RWG / RWBG RNG Insertion RNL Insertion
Medium Gas/air Gas/air FluidsFlow range 0,1 7,5 to 9,5 280 l/s 0,6 43 m/s 0,6 5,5 m/sA cc ur ac y 1 % of re ad in g o ve r t he up pe r
90 % of the flow range1 % of reading over the upper90 % of the flow range
2 % of reading
Repeatability 0,5 % of reading 0,5 % of reading 0,5 % of readingOutput signal 2-wire, 4 20 mA loop 2-wire, 4 20 mA loop 2-wire, 4 20 mA loop
3-wire, 4 20 mA and/or pulseInput power 24 VDC 24 VDC 13 to 32 VDCC er ti fi ca ti on C E: E N6 13 26 -1 :2 00 2
Optional: ATEX II 2G Ex ib IIB T4Zone 1 Group IIB T4 and AEx ibIIB T4
CE: EN61326-1:2002Optional: ATEX II 2G Ex ib IIB T4Zone 1 Group IIB T4 and AEx ibIIB T4
CE
Technical data
Model RVL-Inline RVL-Inline flare end RVL Wafer
Connections Butt or NPT-thread Pipe (flare-end) WaferPipe si ze DN 15 DN 50 ( 1/ 2 to 2) DN 15 DN 25 ( 1/ 2 to 1) DN 15 DN 75 (1/ 2 to 3)Fl ow ranges 2 18 l/ min to
60 750 l/min2,3 18,9 l/min to7,9 94,6 l/min
4,7 56,8 l/min to94,6 1135,5 l/min
Accuracy 1 % of full scale, 4 20 mA and 0 5 VDC2 % of full scale, frequency pulse
Repeatability 0,25 % actual flowOutput signal 4 20 mA, 0 5 VDC or frequency pulse
(source/sink-driver; 1A source / 1.5A sink; typical output resistance 10 ohms)Input power 13 to 30 VDCCertification CSA standard C22.2 no. O-M and no. 142-M, CEMaterial options PVC, CPVC, PVDF PVDF PVC, CPVC, PP, PVDF
The models RWG and RWGB are designed for highaccuracy and extremly low pressure drop. There are nomoving parts necessary and after installation there isnearly no need of maintenance. The models RWG areusable for most of gases.
Type RWBG has a similar construction and is ideal foruse with digester gas applications as p. e. CH
4+ CO
2
mixtures. Meters of this series are built with two-wiretechnology with standard HARTcommunication foreasier programming and system integration.
Type RNG insertion gives highly precise measure-ments for liquids and the RNG is used in applicationsof metering gases (flare gas, stack gas, natural gas,biogas) and air.
The insertion-style meter Type RNL is characeterized byvery low pressure drop and is used in cooling towers,pools and waterparks. It also is used in the municipalwater treatment, ground water monitoring or inirrigation systems.
The RVL series meter utilizes vortex-shedding tech-nology to provide a repeatable flow measurementaccurate to 1 percent of f ull scale. The meter has nomoving parts, and any potential for fluid contamina-tion is eliminated by the meters corrosion-resistantall plastic construction. The meter includes a compacttwo-wire (4 20 mA) or three-wire (0...5 Volt DC orpulse) transmitter, contained within a convenientlyreplaceable plug-in electronic module. All electronicsare housed in a corrosion-resistant enclosure.
Unlike meters containing metal or moving parts, theRVL is perfect for aggressive or easily contaminatedfluids. Applications range from ultra-pure water tohighly corrosive chemicals and slurries. Units may bere-calibrated and the meter output span reprogrammedin the field. RVL meters are available in the follow-ing materials of construction: CPVC, PVC, PVDF andPolypropylene (PP).
-
8/10/2019 Flow Measurement and Control
32/43
62 63
Mass meters
The meters for mass measurement
of fluids
Coriolis mass metersMeasuring principle
Coriolis mass flow metering is based on the physical principle that a force, the so-calledCoriolis force, acts on a mass that is moving towards or away from the point of rotation withina rotating system.
The symmetrical arranged measuring tubes 1 and 2 are vibrated against each other in the Xand Y axis. The limbs RS 1 and RS 2 of the measuring tube 1 and the limbs RS 1 and RS 2 ofthe measuring tube 2 oscillate on a circular segment in case of zero flow.
A Cross section of pipeM Massw Angular velocityv Flow velocityQ FlowKc Coriolis force1 and 2 Measuring tubes
Coriolis mass meters are recommended for the direct, continuous measurement of the mass of
flowing liquids independently of their conductivity, density, temperature, pressure and viscosity
in the food, chemical and petrochemical industries. They are best suited to measure chemicals,
liquid food, suspensions, molasses, inks, lacquers, pastes, etc.
Q
Kc
Kc
1 2
y
x
w
w w
Q
Av =
-
8/10/2019 Flow Measurement and Control
33/43
64 65
Mass meters
Coriolis mass meter type MMC2 Coriolis mass meter type MMC2 Hygiene and MME2for the water industry, chemistry / petrochemistry, paper industry for food or as remote version
Accuracy of 0,1 % of range
Sturdy design
Virtually wear-free
Heatable up to 200 C
Insensitive to noise for example fromexternal vibrations or from gas andsolid content in the fluid
Ex-proof
Accuracy of 0,1 % of range
Excellent cleanability, EHEDG certified
CIP and SIP suitable up to 200 C
Polished fluid wetted parts
Insensitive to noise for example fromexternal vibrations or from gas andsolid content in the fluid
The Coriolis MultyMass MMC2 enables the measure-ment of mass and volume flow, density, concentrationand temperature with a single measuring instrument. Itis also well-proven for lime milk density measurement.Other typical applications are the dosing of expensivebiocides and high-precision fuel supply to burners inpower plants where an important increase in efficiencyis achieved through direct fuel mass flow measure-ment.
In the chemistry and petrochemistry it is ideal for fillingor dosing of oils, solvents and chemicals.It measures online the mass and volume flow, density,concentration and temperature of different fluids.
In the pulp and paper industry the Coriolis sets thestandards in color and coating kitchens. It is perfect forthe measurement of expensive chemicals, for air con-tent measurement around the head box and especially
for precise measurement of high viscosity fluids whilstmaintaining a huge turndown ratio.
Approvals
Explosion protection conforming toATEX, IEC(KEM 08 ATEX 0150X / 0151X),(IECEx KEM08 00.0034X)
Zone 0 / 1 / 2Dust-ignition-proof
FM explosion protection(PID: 3015261)
Class I Div. 1Class I Div. 2
Other approvals for potentiallyexplosive areas
On request
Hyg ien ic and s te ri l e r equi r ement s FDA
Flow meter sensor
Model number MMC2F la ng e D IN 25 01 / E N 1 09 2- 1 D N 1 5 DN 15 0 P N 4 0 PN 10 0Flange ASME B16.5 1/2 6 CL 150 CL 600Threaded pipe connection DIN 11851 DN 15 DN 100 (1/2 4)Tri-Clamp DIN 32676 (ISO 2852)
DN 15 DN 100 (1/2 4)Asept i c f lange DIN 11864- 2 DN 15 DN 100 (1/2 4 ) G t hr ea de d pi pe c on ne ct io n N PT t hr ea ds pi pe c on ne ct io n A cc ur ac y of m as s fl ow r at e 0 ,1 % / 0 ,1 5 % / 0, 25 % / 0 ,4 Accuracy of density 0,005 kg/l, 0,001 kg/lAccuracy of temperature 1 KMaterials in contact with f luid Stainless steel, Hastelloy C-4Protection class acc. to EN 60529 IP 67Fluid temperature -50 C to +200 C
Transmitter
Model number MME2 / MMC23, MMC27
Housing Separate, field-mount housing/compact housingCable length Up to 50 m; 300 m on requestSupply power 100 230 V AC, 24 V AC/DCCurren t output 1 A ctiv e: 0,4 20 m A o r pass iv e: 4 20 m ACurrent output 2 Passive: 4 20 mAPulse output Active (non-ignition-proof) or passiveExt. output switch-off YesExt. totalizer reset YesFor war d / rever se f low mete ring YesCommunication HART protocol, PROFIBUSPA,
FOUNDATION, Fieldbus
P ip e e mp ty de te ct io n Y es , b as ed on pr ec on fi gu re d d en si ty al ar m< 0,5 kg/l
Self-monitoring, diagnostics YesO n- si te d es pl ay / t ot al iz at io n Y esF ie ld op ti mi ze d f lo w / d en si ty Y esProtection class acc. to EN 60529 MME2: IP 65 / 67, NEMA 4X
MMC: IP 67, NEMA 4X
Approvals
Explosion protection conforming toATEX, IEC(KEM 08 ATEX 0150X / 0151X),(IECEx KEM08 00.0034X)
Zone 0 / 1 / 2Dust-ignition-proof
FM explosion protection(PID: 3015261)
Class I Div. 1Class I Div. 2
Other approvals for potentiallyexplosive areas
On request
Hygien ic and s te ri l e requ i