Fluke-1625

GEO Earth Ground Testers

Page 2: Fluke 1625 user training final

Description of the Operating Elements

Page 3: Fluke 1625 user training final

Detail of Panel

66

Page 4: Fluke 1625 user training final

Panel Description

Page 5: Fluke 1625 user training final

Panel Description

Page 6: Fluke 1625 user training final

LCD Display

1. Digital display of measured value2. Measuring function field to display measuring

function3. Unit field: V, Ω, kΩ, Hz4. Special characters for operator guidance

Page 7: Fluke 1625 user training final

RA 2-pole, 3-pole MeasurementsTo make 2-pole or dead-earth measurements, connect a jumper between terminals H/C2 and S/P2 with the supplied connector cable. Refer to Figure. Then follow steps 1 thru 4 except use only earth electrode and the auxiliary earth electrode with minimum distance between them of 20 m.

A Select function RA 3-pole. Display is as shown below.

Page 8: Fluke 1625 user training final
Page 9: Fluke 1625 user training final
Page 10: Fluke 1625 user training final

RA 4-pole Measurements

Page 11: Fluke 1625 user training final
Page 12: Fluke 1625 user training final

RA 3-pole Selective Earth Resistance Measurement withCurrent Clamp

Page 13: Fluke 1625 user training final
Page 14: Fluke 1625 user training final

RA 4-pole Selective Earth Resistance Measurement withCurrent Clamp

Page 15: Fluke 1625 user training final
Page 16: Fluke 1625 user training final

Measurement of Resistances• Resistance Measurement (R~)

This measuring function determines the ohmic resistance between 0.001 Ω and

300 kΩ. The measurement is done with AC voltage. For measurements of very low resistances a compensation of the connecting leads is suggested (see “Compensation of Measuring Lead Resistance”).

Page 17: Fluke 1625 user training final
Page 18: Fluke 1625 user training final

• Resistance measurement (RF)

In this measuring mode all resistances from 0.001 Ω to 3 kΩ can be measured with

DC voltage and automatic polarity reversal as per EN61557-5. To achieve highest accuracy 4 pole measurements are possible. To balance the extension lead, a compensation has to be done.

Page 19: Fluke 1625 user training final