INSPECTION REPORT
For the Property at:
1243 SE 54TH ST. BOCA RATON, FL
Prepared for: BEN and BONNIE S.
Inspection Date: Tuesday, March 28, 2018
Prepared by: Bruce Berman
Bruce Berman,Mgr. 5197 Palazzo Place
Boynton Beach, FL 33437-2073 215-605-4380
March 31, 2017
Dear Ben and Bonnie S
Report No. 1633
1243 SE 54th St.
Boca Raton, FL 33496
Dear Ben and Bonnie,
At your request, an inspection of the above property was performed on March 28, 2018. I am pleased to submit the
enclosed report. This report is a professional opinion based on a visual inspection of the accessible components of the
home. This report is not an exhaustive technical evaluation. An evaluation of this nature would cost many times more.
Please understand that there are limitations to this inspection. Many components of the home are not visible during the
inspection and very little historical information is provided in advance of the inspection. While I can reduce your risk of
purchasing a home, I cannot eliminate it, nor can I assume it. Even the most comprehensive inspection cannot be
expected to reveal every condition you may consider significant to ownership. In addition to those improvements
recommended in my report, I recommend that you budget for unexpected repairs. On average, its been have found that
setting aside roughly one percent of the value of the home on an annual basis is sufficient to cover unexpected repairs. It
is the goal of the inspection to put you in a better position to make a buying decision. Not all improvements will be
identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered
a guarantee or warranty of any kind. The parties agree and understand the Inspector is not an insurer or guarantor
against defects in the structure, items, components or systems inspected. THE INSPECTOR MAKES NO WARRANTY,
EXPRESS OR IMPLIED, AS TO THE FITNESS FOR USE, CONDITION, PERFORMANCE OR ADEQUACY OF ANY
INSPECTED STRUCTURE, ITEM, AND COMPONENT, OR SYSTEM.
Your attention is directed to your copy of the Inspection Agreement. It more specifically explains the scope of the
inspection and the limit of my liability in performing this inspection. The Standards of Practice prohibits me from making
any repairs. I am not associated with any other party to the transaction of this property, except as may be disclosed to
you. The information provided in this report is solely for your use. I will not release a copy of this report without your
written consent.
Thank you for selecting my company. I appreciate the opportunity to be of service. Please feel free to call me with any
questions you may have about your home, or if I can be of any further assistance. There is no fee for this telephone
consulting. My fees are based on a single visit to the property. If additional visits are required for any reason, additional
fees may be assessed.
Sincerely,
Bruce
INVOICE
March 28, 2018
Client: Ben and Bonnie S.
Report No. 1633
For inspection at:
1243 SE 54th St.
Boca Raton, FL
Tuesday, March 28, 2018
Home Inspection $___.00 4 Point Inspection ___.00
Wind Mitigation Inspection ___.00
Total $___.00
PAID IN FULL - THANK YOU!
Bruce Berman
5197 Palazzo Place Boynton Beach, FL 33437-2073
215-605-4380
Report No. 1633 REPORT SUMMARY 1243 NE 54th St., Boca Raton, FL March 28, 2018
This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as a
courtesy and cannot be considered a substitute for reading the entire report. Please read the complete document.
Electrical
SERVICE BOX, GROUNDING AND PANEL \ Service box
Condition: Panel on right is missing latch. Photo 2
Location: Garage
Task: Replace
Condition: Cover missing A/C disconnect. Photo 3
Location: West side of house
DISTRIBUTION SYSTEM \ Switches
Condition: Damage
Two damaged switches. Kitchen counter top left of sink (Photo 4), master bedroom hall closet (Photo 5)
Implication(s): Electric shock | Fire hazard
Cooling & Heat Pump
General
I recommend further evaluation of the entire HVAC system by a licensed HVAC contractor and acquiring a service
contract.
Plumbing
FIXTURES AND FAUCETS \ Basin, sink and laundry tub
Condition: Slow drains
The sink in the "bamboo" bathroom drained slowly at the beginning if the inspection. After running it several times it
drained normally. Probably from not being used for some time.
Implication(s): Chance of water damage to contents, finishes and/or structure
Interior
CEILINGS \ General
Condition: Typical flaws
Appears to be a open seam in the ceiling at the front foyer. I was unable to determine the cause- No access was found to
the area above this ceiling
This concludes the Summary section.
The remainder of the report describes each of the home's systems and also details any recommendations we have for
improvements. Limitations that restricted our inspection are included as well.
The suggested time frames for completing recommendations are based on the limited information available during a
Page 1 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 REPORT SUMMARY 1243 NE 54th St., Boca Raton, FL March 28, 2018
pre-purchase home inspection. These may have to be adjusted based on the findings of specialists.
Page 2 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 ROOFING 1243 SE 54th St., Boca Raton, FL March 28, 2018
Description
General: Flashings-aluminum
General: The roof coverings appear to be in generally good condition and should have several years of service
remaining.
The home is considered to face : South
Sloped roofing material: Concrete tile
Sloped roof flashing material: Aluminum
Probability of leakage: Unable to predict
Recommendations
General
1. While no apparent signs of roof leaks were observed, I recommend annual inspection
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
General: Unable to determine age
Note: The roof is most likely to be original to house and should have a good number of years of service remaining.
Inspection performed: On ladder from edge of roof From ground With telephoto lens
Page 3 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 STRUCTURE 1243 SE 45th St., Boca Raton, FL March 28, 2018
Description
General: The structure, where visible, appeared to be in good condition. No major defects were observed in the
accessible structural components of the building, nor was there any evidence of substantial structural movement.
Configuration: Slab-on-grade
Foundation material: Not visible
Exterior wall construction: Concrete block
Roof and ceiling framing: Trusses Plywood sheathing
Recommendations
General
2. The structure, where visible, appeared to be in good condition.No major defects were observed in the accessible
structural components of the house nor was any evidence of substantial structural movement observed.
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
General: Inspection for Wood Destroying Organisms is not within the scope of this inspection. See report furnished by
others
Percent of foundation not visible: Foundation not visible
Page 4 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 ELECTRICAL 1243 NW 54th St., Boca Raton, FL March 28, 2018
Description
General: Inspection of the electrical system revealed the need for typical, minor repairs. Although these are not costly to
repair, they should be high priority for safety reasons. Unsafe electrical conditions represent a shock hazard. A licensed
electrician should be consulted to undertake the repairs recommended below.
Service entrance cable and location: Underground copper
Service size: 200 amp service consisting of two 100 amp service panels locatd in garage.
Main disconnect/service box rating: 200 Amps
Main disconnect/service box type and location: 200 amp disconnect is located at the east side of the house below
the electrec meter. Photo 1
1.
System grounding material and type: Ground rod-material undetermined
Distribution panel rating: Unable to determine
Note: Two 100 amp service panels
Auxiliary panel (subpanel) type and location: Breakers, located inguest house.
Auxiliary panel (subpanel) rating: 100 Amps
Distribution wire material and type: Copper - non-metallic sheathed
Type and number of outlets (receptacles): Grounded
Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): Exterior GFCI- Bathrooms Kitchen
Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): GFCI - garage
Page 5 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 ELECTRICAL 1243 NW 54th St., Boca Raton, FL March 28, 2018
Recommendations
SERVICE BOX, GROUNDING AND PANEL \ Service box
3. Condition: Panel on right is missing latch. Photo 2
Location: Garage
Task: Replace
2.
4. Condition: Cover missing A/C disconnect. Photo 3
Location: West side of house
3.
DISTRIBUTION SYSTEM \ Switches
5. Condition: Damage
Two damaged switches. Kitchen counter top left of sink (Photo 4), master bedroom hall closet (Photo 5)
Implication(s): Electric shock | Fire hazard
Page 6 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 ELECTRICAL 1243 NW 54th St., Boca Raton, FL March 28, 2018
4. 5.
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
System ground: Continuity of ground not verified nor quality determined
Circuit labels: The accuracy of the circuit index (labels) was not verified.
Page 7 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 HEATING 1243 SE 54th St., Boca Raton, FL March 28, 2018
Description
General: See cooling section
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
Page 8 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 COOLING & HEAT PUMP 1243 SE 45th St., Boca Raton, FL March 28, 2018
201820178
Description
General: The HVAC systems in this home consists of several zones including the main house, master
bedroom/bathroom suite, guest house. The ages of the various systems range from 2010 thru 2015. I found no
evidence/tags indicating the systems have been serviced within the past 12 months.
All of the systems were working at the time of the inspection.
Recommendations
General
6. I recommend further evaluation of the entire HVAC system by a licensed HVAC contractor and acquiring a service
contract.
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
Heat gain/loss calculations: Not done as part of a building inspection
Page 9 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 INSULATION AND VENTILATION 1243 SE 54th St., Boca Raton, FL March 28, 2018
Description
General: Insulation levels are typical for a home of this age and construction
Attic/roof insulation amount/value: 3-1/2" (+/-) fiberglass bats
Attic/roof ventilation: Soffit vent
Attic/roof air/vapor barrier: Not visible
Wall insulation material: Not visible
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
Page 10 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 PLUMBING 1243 SE 54th St., Boca Raton, FL March 28, 2018
Description
Water supply source: Public
Service piping into building: Copper
Supply piping in building: Copper Copper
Main water shut off valve at the: Located at southeast (front) exterior. Photo 6
6.
Water flow and pressure: Average
Water heater type: Conventional
Water heater fuel/energy source: Electric
Water heater manufacturer: Rudd
Mfg. Date: 01/99
Tank capacity: 80 gallons
Typical life expectancy: 10-12 years
Note: While this unit has exceeded it's normal life expectancy, it still produces hot water. Replacement may be required
at any time.
Page 11 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 PLUMBING 1243 SE 54th St., Boca Raton, FL March 28, 2018
7.
Recommendations
FIXTURES AND FAUCETS \ Basin, sink and laundry tub
7. Condition: Slow drains
The sink in the "bamboo" bathroom drained slowly at the beginning if the inspection. After running it several times it
drained normally. Probably from not being used for some time.
Implication(s): Chance of water damage to contents, finishes and/or structure
FIXTURES AND FAUCETS \ Toilet
8. Condition: The toilet "gray" bathroom ran continuously after first flushing it. After flushing several times
it worked properly. However I recommend replacing the "flapper" valve.
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
General: The water heater temperature should be set such that accidental scalding is minimized. Families with small
children should be especially aware of this.
Items excluded from a building inspection: Lawn sprinklers
Items excluded from a building inspection: Water quality Isolating/relief valves & main shut-off valve Concealed
plumbing Water heater relief valves are not tested
Page 12 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633 INTERIOR 1243 SE 54th St., Boca Raton, FL March 28, 2018
Description
General: On the whole, the interior finishes of the home are in above average condition.
Note: Please note that the whole house appears to have been painted.
Major floor finishes: Tile
Major wall finishes: Plaster/drywall Paneling
Major ceiling finishes: Plaster/drywall
Windows:
Vinyl
Vinyl sliding and casement windows
Exterior doors - type/material: Sliding glass Solid wood
Kitchen ventilation: Range hood
Recommendations
CEILINGS \ General
9. Condition: Typical flaws
Appears to be a open seam in the ceiling at the front foyer. I was unable to determine the cause- No access was found to
the area above this ceiling
Limitations
General: Common cracks are often caused by settlement, shrinkage of framing materials, temperature changes and
many other reasons. The cause of these cracks is normally hard (if not impossible) to determine. Often these cracks are
considered cosmetic. They can be repaired, but often will return at a later time.
Inspection limited/prevented by: New finishes/paint
Cosmetics: No comment offered on cosmetic finishes
Page 13 of 14
REPORT SUM ROOFING STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR APPLIANCES
Report No. 1633
Description
General: All appliances appeared to be new or almost new and were in working order
Cooktop: Electric
Exhaust fan: Discharge to exterior
Oven: Wall mounted electric, conventional/convection
Refrigerator: Wine refrigerator
Refrigerator: Side-by-side
Dishwasher: Built-in
Microwave oven: Built-in
Waste disposal: Two 1hp waste disposers
Washer and dryer: Dryer vented to garage 220 volt circut for dryer
Washer and dryer: Front-loading washer Laundry tub Dryer vented to exterior
Kitchen counter material: Wood cabinets
Kitchen counter material: Engineered stone
Limitations
General: All work (repairs, recommendations, etc.) called for, whether written or verbal, is to be performed by licensed
qualified contractors. Work should be completed before settlement/closing. Each individual contractor is responsible to
evaluate the entire system in question (examples: electrical, roofing, structural, etc.).
General: Be sure to run ALL appliances through their FULL cycles at the walk through before settlement/closing
General: The inspection of appliances are not within the scope/standards of practice of a home inspection. Any
comments regarding appliances are a courtesy to our clients, but are not officially part of this inspection
General: Appliances are tested for basic operation only. Accuracy of oven temperature was not tested. Self-cleaning
features of oven not tested. Central vacuum system was not tested.
END OF REPORT